Heatcraft Refrigeration Products Condensing Units H-IM-CU manual
- Consulta online o descarga el manual de instrucciones
- 24 páginas
- 0.84 mb
Ir a la página of
manuales de instrucciones parecidos
-
Refrigerator
Heatcraft Refrigeration Products HYPERCORE H-HTSSB-1208
6 páginas 1.04 mb -
Fan
Heatcraft Refrigeration Products Air Defrost RLC
20 páginas 2.43 mb -
Fan
Heatcraft Refrigeration Products Air Defrost TLH
8 páginas 1.81 mb -
Clothes Dryer
Heatcraft Refrigeration Products REMOTE AIR-COOLEDCONDENSER 2500018
16 páginas 1.14 mb -
Humidifier
Heatcraft Refrigeration Products Unit Coolers H-IM-UC
8 páginas 0.44 mb -
Refrigerator
Heatcraft Refrigeration Products Refrigeration System H-IM-82B
20 páginas 1.57 mb -
Refrigerator
Heatcraft Refrigeration Products CHANDLER PST
12 páginas 2.51 mb -
Humidifier
Heatcraft Refrigeration Products Condensing Units H-IM-CU
24 páginas 0.84 mb
Buen manual de instrucciones
Las leyes obligan al vendedor a entregarle al comprador, junto con el producto, el manual de instrucciones Heatcraft Refrigeration Products Condensing Units H-IM-CU. La falta del manual o facilitar información incorrecta al consumidor constituyen una base de reclamación por no estar de acuerdo el producto con el contrato. Según la ley, está permitido adjuntar un manual de otra forma que no sea en papel, lo cual últimamente es bastante común y los fabricantes nos facilitan un manual gráfico, su versión electrónica Heatcraft Refrigeration Products Condensing Units H-IM-CU o vídeos de instrucciones para usuarios. La condición es que tenga una forma legible y entendible.
¿Qué es un manual de instrucciones?
El nombre proviene de la palabra latina “instructio”, es decir, ordenar. Por lo tanto, en un manual Heatcraft Refrigeration Products Condensing Units H-IM-CU se puede encontrar la descripción de las etapas de actuación. El propósito de un manual es enseñar, facilitar el encendido o el uso de un dispositivo o la realización de acciones concretas. Un manual de instrucciones también es una fuente de información acerca de un objeto o un servicio, es una pista.
Desafortunadamente pocos usuarios destinan su tiempo a leer manuales Heatcraft Refrigeration Products Condensing Units H-IM-CU, sin embargo, un buen manual nos permite, no solo conocer una cantidad de funcionalidades adicionales del dispositivo comprado, sino también evitar la mayoría de fallos.
Entonces, ¿qué debe contener el manual de instrucciones perfecto?
Sobre todo, un manual de instrucciones Heatcraft Refrigeration Products Condensing Units H-IM-CU debe contener:
- información acerca de las especificaciones técnicas del dispositivo Heatcraft Refrigeration Products Condensing Units H-IM-CU
- nombre de fabricante y año de fabricación del dispositivo Heatcraft Refrigeration Products Condensing Units H-IM-CU
- condiciones de uso, configuración y mantenimiento del dispositivo Heatcraft Refrigeration Products Condensing Units H-IM-CU
- marcas de seguridad y certificados que confirmen su concordancia con determinadas normativas
¿Por qué no leemos los manuales de instrucciones?
Normalmente es por la falta de tiempo y seguridad acerca de las funcionalidades determinadas de los dispositivos comprados. Desafortunadamente la conexión y el encendido de Heatcraft Refrigeration Products Condensing Units H-IM-CU no es suficiente. El manual de instrucciones siempre contiene una serie de indicaciones acerca de determinadas funcionalidades, normas de seguridad, consejos de mantenimiento (incluso qué productos usar), fallos eventuales de Heatcraft Refrigeration Products Condensing Units H-IM-CU y maneras de solucionar los problemas que puedan ocurrir durante su uso. Al final, en un manual se pueden encontrar los detalles de servicio técnico Heatcraft Refrigeration Produc en caso de que las soluciones propuestas no hayan funcionado. Actualmente gozan de éxito manuales de instrucciones en forma de animaciones interesantes o vídeo manuales que llegan al usuario mucho mejor que en forma de un folleto. Este tipo de manual ayuda a que el usuario vea el vídeo entero sin saltarse las especificaciones y las descripciones técnicas complicadas de Heatcraft Refrigeration Products Condensing Units H-IM-CU, como se suele hacer teniendo una versión en papel.
¿Por qué vale la pena leer los manuales de instrucciones?
Sobre todo es en ellos donde encontraremos las respuestas acerca de la construcción, las posibilidades del dispositivo Heatcraft Refrigeration Products Condensing Units H-IM-CU, el uso de determinados accesorios y una serie de informaciones que permiten aprovechar completamente sus funciones y comodidades.
Tras una compra exitosa de un equipo o un dispositivo, vale la pena dedicar un momento para familiarizarse con cada parte del manual Heatcraft Refrigeration Products Condensing Units H-IM-CU. Actualmente se preparan y traducen con dedicación, para que no solo sean comprensibles para los usuarios, sino que también cumplan su función básica de información y ayuda.
Índice de manuales de instrucciones
-
Página 1
H-IM-CU August 2008 P ar t No . 25008101 H-IM-CU-0808 | V ersion 000 C ondensing Units Installation and Opera tions Manual T able of C ontents General Safety Information...............................................................................2 Inspection .........................................................................................[...]
-
Página 2
2 General Safety Information Installation and maintenance to be performed only by qualied personnel who are familiar with this type of equipment. Some units are pressurized with dry air or iner t gas. All units must be evacuated befor e charging the system with r efrigerant. 1. 2. W ARNING: Refr igerant can be harmful if it is inhaled. Refrigera[...]
-
Página 3
3 © 2008 Heatcraft Refrigeration Products LL C The most important consideration which must be taken into account when deciding upon the location of air-cooled equipment is the provision for a supply of ambient air to the condenser , and removal of heated air fr om the condensing unit or remote c ondenser area. Where this essential requirement is n[...]
-
Página 4
4 Requirements for Remot e and Wa ter Cooled Condensing Units General Installation The indoor compressor units ar e designed to be used with a remote condenser . T he water cooled units are similar , except that they have an integral wat er cooled condenser . Inlet and outlet water connections are to be made in the eld. On units having a compr e[...]
-
Página 5
5 Figur e 3. Spring Mount Figur e 5. Spring Mount Figur e 4. Solid Mount for Mobile or Deep Sump Application Condensing Unit Rigging and Mounting Rigging holes are provided on all units . Caution should be exer cised when moving these units. T o prevent damage to the unit housing during rigging, cables or chains used must be held apart by spacer ba[...]
-
Página 6
6 CAUTION: Under no circumstance should all condenser motors be allo wed to cycle o on one control . At least one motor shall be wired t o operate at all times. Under most circumstances, the c ondenser motor nearest the inlet header should remain on whenev er the compressor is operating . CAUTION: F ans closest to the headers should not be c ycl[...]
-
Página 7
7 Refrigeration Oils* With the changes that hav e taken place in our industry due to the CFC issue, we hav e reevaluated our lubricants t o ensure compatibility with the new HFC refrigerants and HCFC interim blends o ered by several chemical producers. A s a secondary criteria, it is also desirable that any new lubricant be compatible with the t[...]
-
Página 8
8 Figur e 9. Example of Pipe Support Figur e 10. Condensing Unit / C ompressor to W all Suppor t Suction Lines Horizontal suction lines should slope away from the evapor ator towar d the compressor at the rat e of 1/4 inch per 10 feet for good oil r eturn. W hen multiple evaporators are c onnected in series using a common suction line, the branch s[...]
-
Página 9
9 Liquid Lines Liquid lines should be sized for a minimum pressur e drop to prev ent “ashing” . Flashing in the liquid lines would creat e additional pressure drop and poor expansion valve operation. If a system r equires long liquid lines from the receiv er to the evaporator or if the liquid has to rise v ertically upward an y distance, the[...]
-
Página 10
10 Pipe size example: Given: -10°F Fr eezer with one system having (2) ev aporators • One condensing unit rated at 24,000 B TUH’ s @ -20°F SST R404A refrigerant. • T wo evaporators each rated at 12,000 BTUH ’ s @ 10°F TD . • 100 feet of actual line run between condensing unit to rst evaporat or and 20 feet of actual line run between[...]
-
Página 11
11 T able 4. Pressure L oss of Liquid Refrigerants in Liquid Line Risers (Expressed in Pr essure Drop , PSIG, and Subcooling Loss, ˚F) Refrigerant Liquid Line Rise in Feet 10' 15' 20' 25' 30' 40' 50' 75' 100' PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F R22 4.8 1.6 7.[...]
-
Página 12
12 T able 7. Recommended Line Sizes for R-22 * Capacity BTUH Suction Line Size Liquid Line Size Suction T emperature Receiver to Expansion V alve Equivalent Lengths +40˚F Equivalent Lengths +20˚F Equivalent Lengths +10˚F Equivalent Lengths 0˚F Equivalent Lengths -10˚F Equivalent Lengths -20˚F Equivalent Lengths 25' 50' 100' 150[...]
-
Página 13
13 T able 8. Recommended Line Sizes f or R-404A and R507* Capacity BTUH Suction Line Size Liquid Line Size Suction T emperature Receiver to Expansion V alve Equivalent Lengths +20˚F Equivalent L engths +10˚F Equivalent L engths -10˚F Equivalent L engths -20˚F Equivalent L engths -30˚F Equivalent L engths -40˚F Equivalent L engths 25' 50&[...]
-
Página 14
14 Evacua tion and Leak Detection Due to the smaller molecule size of HFC’ s, they will tend to leak more r eadily than CFC’ s. Consequently , it is of the utmost impor tance that proper system evacuation and leak detection procedures be emplo yed. Copeland recommends a minimum evacua tion to 500 microns. In addition, a vacuum decay test is str[...]
-
Página 15
15 Check Out and Start Up After the installation has been completed, the f ollowing points should be cover ed before the syst em is placed in operation: Check all electrical and refrigerant connections. Be sure they are all tight. Observe compressor oil level befor e start-up. The oil level should be at or slightly abov e the 1/4 level of the sight[...]
-
Página 16
16 Sy stem Balancing - Compr essor Superheat IMPORT ANT: In order to obtain the maximum capacity from a system, and to ensur e trouble-free operation, it is necessary to balance each and every system. This is extremely important with any refrigeration system. The critical value which must be checked is suction superheat. Suction superheat should be[...]
-
Página 17
17 Electric Defrost T roubleshooting The electric defrost units are relativ ely simple and trouble-free in operation: Timer If the system does not go through its proper sequence , check timer operation through a defrost cycle . Check for loose wires or terminals . Before replacing timer , check other components. Operation of P aragon T imer T o set[...]
-
Página 18
18 T able 10. System T roubleshooting Chart PROBLEM POSSIBLE CA USES POSSIBLE C ORREC TIVE STEPS Compressor will not run 1. Main switch open. 2. F use blown. 3. Thermal ov erloads tripped. 4. Defective con tactor or coil. 5. Sy stem shut down by safety devices . 6. No cooling r equired. 7. Liquid line solenoid will not open. 8. Motor electrical tro[...]
-
Página 19
19 Air-Cooled C ondensing Units Quarterly 1) Visually inspect unit • Look for sig ns of oil stains on interconnection piping and condenser coil. P ay close attention t o areas around solder joints , building penetrations and pipe clamps. Check an y suspect areas with an electronic leak detector . Repair any leaks found and add refrigerant as need[...]
-
Página 20
20 Diagram 3. T ypical W iring Diagram for Single Evapora tor with and without Defrost Timer Diagram 4. T ypical W iring Diagram for Single Evapora tor with Defrost Timer Only[...]
-
Página 21
21 Diagram 5. T ypical W iring Diagram for Multiple Evapora tors with Defrost Timer Only Diagram 6. T ypical W iring Diagram for Single Evapora tor / Single Phase Defrost and E vaporat or F an Contactors[...]
-
Página 22
22 Diagram 7. T ypical W iring Diagram for Single Evapora tor Defrost and E vaporat or F an Contactors Diagram 8. T ypical W iring Diagram for Multiple Evapora tors with Ev aporator F an Contactors/without Heat er Limit Defrost[...]
-
Página 23
23 Diagram 10. T ypical W iring Diagram for Multiple Evapora tors Defrost and E vaporat or F an Contactors with Unit Cooler Holdout Rela y Diagram 9. T ypical W iring Diagram for Multiple Evapora tors with Heater Limit Defr ost and Evapor ator F an Contactors[...]
-
Página 24
Since product improv ement is a continuing eort, we reserve the right to make changes in specications without notice. C L I M A T E C O N T R O L Commercial Refrigeration Parts The name behind the brands you trust. ™ H-IM-CU-0808 Commercial Refrigeration Parts Replacement P arts by InterLink™ Comercial Refrigeration Parts is your link t o[...]