Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE manuale d’uso
- Visualizza on-line o scarica il manuale
- 64 pagine
- 1.38 mb
Vai alla pagina of
Manuali d’uso simili
-
Electric Heater
Lennox International Inc. 090V60C
64 pagine 1.38 mb -
Electric Heater
Lennox International Inc. Lennox CompleteHeatTM COMBINATION HEATING SYSTEM
10 pagine 0.19 mb -
Electric Heater
Lennox International Inc. MERIT SERIES GAS FURNACE DOWNFLOW AIR DISCHARGE
52 pagine 1.34 mb -
Electric Heater
Lennox International Inc. ML193DF
52 pagine 1.34 mb -
Electric Heater
Lennox International Inc. 110V60C
64 pagine 1.38 mb -
Electric Heater
Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE
64 pagine 1.38 mb -
Electric Heater
Lennox International Inc. 090V36C
64 pagine 1.38 mb -
Electric Heater
Lennox International Inc. 070V36B
64 pagine 1.38 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE
- nome del fabbricante e anno di fabbricazione Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Lennox International Inc. in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Lennox International Inc. DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
Page 1 02/1 1 *2P0211* 50661 1−01 *P506611-01* 201 1 Lennox Industries Inc. Dallas, T exas, USA AIR FLOW DOWNFLOW W ARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, person- al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equiv[...]
-
Pagina 2
Page 2 Unit Dimensions − inches (mm) AIR EXHAUST AIR OUTLET COMBUSTION AIR INT AKE FLOW 2 − 1/16 (52) 090V48C A B C D SLP98DF Model No. in. mm in. mm in. mm in. mm 070V36B 17 − 1/2 446 16 − 3/8 416 16 406 7 − 5/8 194 090V36C 21 533 19 − 7/8 505 19 − 1/2 495 9 − 3/8 238 090V60C 1 10V60C GAS PIPING INLET (Either Side) ELECTRICAL INLET[...]
-
Pagina 3
Page 3 Part s Arrangement FIGURE 1 BURNER BOX ASSEMBL Y GAS V AL VE ACCESS P ANEL COMBUSTION AIR INDUCER BLOWER ACCESS P ANEL BLOWER ASSEMBL Y (V ariable S peed Blower Motor Is Hidden) BAG ASSEMBL Y CONTROL BOX (includes variable capacity integrated control, transformer , circuit breaker and door switch) PRIMARY LIMIT[...]
-
Pagina 4
Page 4 SLP98DFV Gas Furnace The S LP98DFV category IV g as furnace is equipped with a variable−capacity , variable−s peed integrated control. This control ensures compatibility with the Lennox icom- fort T ouch thermostat and Harmony III zone contr ol system, as well as a thermost at whi ch provides humidity control. The furnace is equi[...]
-
Pagina 5
Page 5 Installed in Combination with a Cooling Coil When this furnace is used wi th cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a p arallel flow a r rangement, a d amper (or other m eans to control the flow o f air) must a dequately prevent c[...]
-
Pagina 6
Page 6 General W ARNING Product contains fiberglass wool. Disturbing the insulation in this product during inst allation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer . (Fiberglass wool is known t o the St ate of Cal- ifornia to cause cancer .) Fiberglass wool may also cause respiratory , skin, and[...]
-
Pagina 7
Page 7 NOTE − The 1/2 hp blower motor used in some SLP98DFV unit is equipped with three flexible legs and one rigid leg. Th e rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer mus t be removed before the furnace is placed into[...]
-
Pagina 8
Page 8 T ABLE 1 NON−COMBUSTIBLE FLOOR OPENING SIZE Cabinet Wid th Front to Rear Side to Side in . mm in. mm B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422 C Cabinet (21") 19 − 3/4 502 20−1/8 51 1 NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2. FIGURE 8 SUPP[...]
-
Pagina 9
Page 9 FIGURE 10 COOLING COIL PLENUM PROPERL Y SIZED FLOOR OPENING SLP98DF UNIT Return Air Opening −− Downflow Unit s Return air may be brought in only through the top opening of a furnace installed in the downflow position. The follow- ing steps should be t aken when installing plenum: 1 − Bottom edge of plenum should be flanged with a hemme[...]
-
Pagina 10
Page 10 Pipe & Fittings Specifications All p ipe, fittings, primer a nd s olvent c ement m us t conform with A mer ican National S tandard Institute a nd the Ameri- can Soci ety f or T e sting and Ma terials (ANS I/ASTM ) s tan - dards. The solvent shall be free−flowing and contain no lumps, u ndissolved p articles or any foreign m atter that[...]
-
Pagina 11
Page 11 T ABLE 5 OUTDOOR TERMINA TION KITS USAGE SLP98DF UNIT VENT PIPE DIA. (in.) ST ANDARD CONCENTRIC Outdoor Exhaust Accelerator (Dia. X Length) Outdoor Exhaust Acceler ator (Dia. X Length) 2" Wall Plate Kit 3" W all Plate Kit 2" Wall Ring Kit Flush- Mount Kit 1−1/2" Concentric Kit 2" Concentric Kit 3" Concentric [...]
-
Pagina 12
Page 12 V enting Practices FIGURE 13 * See table 4 for allowable pipe. Piping Suspension Guidelines NOTE − Isolate piping at the point where it exits the out side wall or roof in order to prevent transmission of vibration to the structure. SCHEDULE 40 PVC −− Support every 5 feet. all other pipe* −− Support every 3 feet. W all inside outsi[...]
-
Pagina 13
Page 13 NOTE − The exhaust collar on all models is sized to ac - commodate 2" Schedule 40 vent pipe. Contact the Ap - plication Dep artment for more information concerning sizing o f v ent system s w hich inclu de multiple pipe s izes. NOTE − All horiz ontal runs of exhaust pipe must slope back toward unit. A minimum of 1/ 4" (6mm) dr[...]
-
Pagina 14
Page 14 T ABLE 7 Maximum Allowable Intake or Exhaust V ent Length in Feet *Siz e intake and exhaus t pipe length separately . Values in table are for Intake OR Ex haust, not com bined total. Both Intake an d Exhaus t must be same pipe size. St andard T ermination at Elevation 0 − 4500’ Number Of 90° Elbows Used 2" Pipe 2−1/2" Pipe [...]
-
Pagina 15
Page 15 T ABLE 7 Maximum Allowable Intake or Exhaust V ent Length in Feet *Siz e intake and exhaus t pipe length separately . Values in table are for Intake OR Ex haust, not com bined total. Both Intake an d Exhaus t must be same pipe size. Concentric T ermination at Elevation 0 − 4500’ Number Of 90° Elbows Used 2" Pipe 2−1/2" Pipe[...]
-
Pagina 16
Page 16 FIGURE 16 TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSA TE TRAP INST ALLA TION TRANSITION 2” 2” 2” 3” Use only the factory − supplied trap. Trap can be installed on either side of cabinet within 5 ft. of the furnace. TRAP TOP VIEW Exhaust Air Intake DO NOT transition from smaller to larger pipe size in horizontal runs of exhaust p[...]
-
Pagina 17
Page 17 FIGURE 18 VENT TERMINA TION CLEARANCES FOR DIRECT VENT INST ALLA TIONS IN THE USA AND CANADA K D E L B C F G A B J A M I H INSIDE CORNER DET AIL VENT TERMINAL AIR SUPPL Y INLET AREA WHERE TERMINAL IS NOT PERMITTED Fixed Closed Operable B Fixed Closed Operable B B A = B = C = D = E = F = G = H = I = J = K = L = M = US Installations 1 Canadia[...]
-
Pagina 18
Page 18 Det ails o f Int ake a nd Ex haust Piping T erminations f or Direct V ent Installations NOTE − In Direc t V ent i ns tallations, combustion a ir is tak- en from outdoors and flue ga ses are discharged to out - doors. NOTE − Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used [...]
-
Pagina 19
Page 19 C A E D B A B D D B C A C 12" 1 1 2 2 2" (51mm) V ent Pipe 3" (76mm) V ent Pipe A − Clearance above grade or average snow accumulation B −Horizontal separation between intake and exhaust C −Minimum from end of exhaust to inlet of intake D −Exhaust pipe length E −W all support distance from top of each pipe (intake/e[...]
-
Pagina 20
Page 20 FIGURE 22 FIELD−SUPPLIED W ALL TERMINA TION OR (15F74) W ALL RING TERMINA TION KIT With INT AKE ELBOW See venting table 7 for maximum venting lengths with this arrangement. * Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall su[...]
-
Pagina 21
Page 21 12" (305mm) Min. above grade or average snow accumulation. FIGURE 24 DIRECT VENT CONCENTRIC W ALL TERMINA TION 71M80, 69M29 or 60L46 (US) 44W92 or 44W93 (Canada) INT AKE AIR EXHAUST AIR INT AKE AIR INT AKE AIR EXHAUST AIR OUTSIDE WALL GRADE CLAMP (Not Furnished) FIELD−PROVIDED REDUCER MA Y BE RE- QUIRED TO ADAPT LARGER VENT PIPE SIZE[...]
-
Pagina 22
Page 22 FIGURE 30 12” (305 mm) Minimum Above Grade or Average Snow Accumulation 1/2” (13 mm) FOAM INSULA TION (Field − Furnished) 5” (127 mm) 5 − 1/2” (140 mm) EXHAUST AIR INT AKE AIR GRADE 12” (305 mm) INT AKE AIR EXHAUST AIR GRADE 12” (305 mm) max. for 2” (51 mm) dia. exhaust 20” (508 mm) max. for 3” (76 mm) dia. exhaust WAL[...]
-
Pagina 23
Page 23 Condensate Piping This unit is designed for either right- or lef t-side exit of con- densate piping. Refer to figure 3 2 for condensate trap loca- tions. NOTE − If necessary the condensate trap may be inst alled up to 5 feet away from the furnace. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap. NOTE − Vin[...]
-
Pagina 24
Page 24 FIGURE 34 Adapter 1/2 inch slip X 1/2 inch mpt (Not Furnished) Drain T rap Assembly (Furnished) V ent Drain T rap Clean Out 5 Feet Maximum Coupling 1/2 inch slip X slip (Not Furnished) 90 ° Elbow 1/2 inch PVC (Not Furnished) 1/2 inch PVC Pipe (Not Furnished) 1/2 inch PVC Pipe (Not Furnished) 1 (25) Minimum Above T op of Condensate Drain Co[...]
-
Pagina 25
Page 25 CAUTION A sep arate drain line must be run to the drain from the condensate trap to ensure proper drainage and pressure switch operation. DO NOT connect the con- densate trap drain into the drain line from the evapo- rator coil. FIGURE 35 SL98DFV with Evaporator Coil Drain Condensate trap and evaporator coil must drain separately as shown. [...]
-
Pagina 26
Page 26 GROUND JOINT UNION AUTOMA TIC GAS V AL VE (with manual shut−off valve) FIELD PROVIDED AND INST ALLED GROUND JOINT UNION Left Side Piping (St andard) Right Side Piping (Alternate) AUTOMA TIC GAS V AL VE (with manual shut−off valve) DRIP LEG DRIP LEG MANUAL MAIN SHUT−OFF VA LV E (1/8 in. NPT plugged tap shown) MANUAL MAIN SHUT−OFF VA [...]
-
Pagina 27
Page 27 1 − Seal any unused openings in the common venting sys- tem. 2 − Ins pect the venting system f or p roper si z e and h or izontal pitch. Determine that there is no blockage, restriction, leakage, corros ion, or other defic iencies whic h could cause an unsafe condition. 3 − Close all building doors and windows and all doors be- tween [...]
-
Pagina 28
Page 28 1 − The power supply wiring must meet Class I restric- tions. Protected by either a fuse or circuit breaker , se- lect circuit protection and wire size according to unit nameplate. NOTE − Unit nameplate states maximum current draw . See table for maximum over−current protection. T ABLE 1 1 SLP98DF Model Maximum Over−Current Protecti[...]
-
Pagina 29
Page 29 1 − When the thermostat is set to F AN ON," the indoor blower will run continuously at a percent a g e of the sec- ond−stage cooling speed when there is no cooling or heating demand. The percentage is set using DIP switches 6 and 7. 2 − When the SLP98DFV is running in the heating mode, the integrated control will automatically[...]
-
Pagina 30
Page 30 FIGURE 41 icomfort T ouch Thermostat with SLP98DFV and Non−Communicating Outdoor Unit icomfort − ENABLED SLP98DFV FURNACE icomfort T ouch THERMOST A T NON−COMMUNICA TING OUTDOOR AIR CONDITIONING UNIT − 1 OR 2 ST AGE icomfort T ouch Thermostat icomfort −Enabled SLP98DFV Indoor Furnace Non−Communicating Outdoor[...]
-
Pagina 31
Page 31 FIGURE 42 Optional Accessories for use with any icomfort T ouch System NOTE: 24V UV LIGHT APPLICA TIONS Furnace transformer will not have ad- equate va to power 24v UV light ap- plications. An additional transformer for UV light applications is required. icomfort T ouch THERMOST A T DISCHARGE AIR SENSOR NOTE: icomfort THERMOST A[...]
-
Pagina 32
Page 32 T ABLE 14 Field Wiring Connections for Non−Communicating Thermost at Applications Thermost at DIP Switch Settings and On−Board Links (figure 44) Wiring Connections DIP Switch 1 W915 (Y1 to Y2) T wo−Stage Cooling W914 (DS to R) Dehumidifi- cation or Harmony III W951 (O to R) Heat Pumps 1Heat / 1 Cool NOT E − Use DIP switch 3 to s[...]
-
Pagina 33
Page 33 T ABLE 14 Field Wiring for Non−Communicating Applications (Continued) Thermost at DIP Switch Settings and On−Board Links (figure 44) Wiring Connections DIP Switch 1 W915 (Y1 to Y2) T wo−Stage Cooling W914 (DS to R) Dehumidifi- cation or Harmony III W951 (O to R) Heat Pumps 2 Heat / 2 Cool OFF Cut Intact Intact S1 T’STAT CONTROL [...]
-
Pagina 34
Page 34 T ABLE 14 Field Wiring for Non−Communicating Applications (Continued) Thermost at DIP Switch Settings and On−Board Links (figure 44) Wiring Connections DIP Switch W915 (Y1 to Y2) T wo−Stage Cooling W914 (DS to R) Dehumidifi- cation or Harmony III W951 (O to R) Heat Pumps Dual Fuel Single−S tage Heat Pump ComfortSense ® 7000 L77[...]
-
Pagina 35
Page 35 FIGURE 43 TYPICAL SLP98DFV WIRING DIAGRAM[...]
-
Pagina 36
Page 36 Integrated Control INTEGRA TED CONTROL THERMOST A T CONNECTIONS (TB1) 1/4" QUICK CONNECT TERMINALS FIGURE 44 RS−BUS LINK (TB82, future use) I+ = DA T A HIGH CONNECTION I − = DA T A LOW CONNECTION RS−BUS OUTDOOR (TB83) R = 24V AC I + = DA T A HIGH CONNECTION I − = DA T A LOW CONNECTION C = 24V AXC COMMON RS−BUS INDOOR (TB84) R[...]
-
Pagina 37
Page 37 T ABLE 15 Non−Communicating Thermostat Selection Switch Settings Operation Thermost at Switch 1 Switch 2 Switch 3 V ariable Capacity Heat (35% to 100%) T wo−S tage Off On Off Three−S tage Heat (35%, 70%, 100%) Single−S tage On Off 2nd stage delay OFF = 7 minutes ON = 12 minutes 3rd stage delay 10 minutes fixed T wo−S tage Heat (W1[...]
-
Pagina 38
Page 38 Switches 8 and 9 −− Cooling Mode Blower Speed −− The unit i s shipped from the factory with the DIP switches posi- tioned for high speed (4) indoor blower motor operation during the cooling mode. The table below provides the cooling mode blower speeds that will result from dif ferent switch settings. Refer to tables beginning on pag[...]
-
Pagina 39
Page 39 Switches 1 4 th r ough 19 −− Heating Mode Blower S peed −− These switches are factory set at the OFF position which provides 100 % of normal speed during HIGH HEA T de- mand, 70% of normal speed during MID−RANGE HEA T deman d and 35% of normal speed during LOW HEA T de- mand. Switches 14, 15 and 16 are used to adjust the LOW HEA T[...]
-
Pagina 40
Page 40 BLOWER DA T A SLP98DF070V36B BLOWER PERFORMANCE (less lter) HEA TING BLOWER PERFORMANCE Heating Adjust CFM Selections Heating Input Range and Blower V olume - CFM 35% 40% 50% 60% 70% 80% 90% 100% Increase (+15%) Heat CFM 495 543 639 735 830 926 1022 111 8 Increase (+7.5%) Heat CFM 473 516 604 691 778 866 953 1041 Default Heat CFM 450 489[...]
-
Pagina 41
Page 41 BLOWER DA T A SLP98DF090V48C BLOWER PERFORMANCE (less lter) HEA TING BLOWER PERFORMANCE Heating Adjust CFM Selections Heating Input Range and Blower V olume - CFM 35% 40% 50% 60% 70% 80% 90% 100% Increase (+15%) Heat CFM 723 790 925 1060 1 195 1329 1464 1599 Increase (+7.5%) Heat CFM 690 752 878 1004 1 129 1255 1381 1507 Default Heat CFM[...]
-
Pagina 42
Page 42 BLOWER DA T A SLP98DF1 10V60C BLOWER PERFORMANCE (less lter) HEA TING BLOWER PERFORMANCE Heating Adjust CFM Selections Heating Input Range and Blower V olume - CFM 35% 40% 50% 60% 70% 80% 90% 100% Increase (+15%) Heat CFM 8 11 906 1096 1286 1475 1665 1855 2045 Increase (+7.5%) Heat CFM 744 835 1017 1 199 1380 1562 1744 1926 Default Heat [...]
-
Pagina 43
Page 43 T ABLE 24 COOLING OPERA TING SEQUENCE SLP98DFV and Single−St age Outdoor Unit OPERA TING SEQUENCE SYSTEM DEMAND SYSTEM RESPONSE System Condition S tep Demand Relative Humidity Compressor Blower CFM (COOL) Comments 1st stage O G S tatus D* NO CALL FOR DEHUMIDIFICA TION Normal Operation 1 On On On Accept able 24 VA C High 100% Compressor an[...]
-
Pagina 44
Page 44 T ABLE 25 COOLING OPERA TING SEQUENCE SLP98DFV and T wo−Stage Out door Unit OPERA TING SEQUENCE SYSTEM DEMAND SYSTEM RESPONSE System Condition S tep Demand Relative Humidity Compressor Blower CFM (COOL) Comments 1st stage 2nd stage O G S tatus D* NO CALL FOR DEHUMIDIFICA TION Normal Operation − Y1 1 On On On Acceptable 24 VA C Low 70% C[...]
-
Pagina 45
Page 45 Unit S t art−Up FOR YOUR SAFETY READ BEFORE OPERA TING W ARNING Do not use this furnace if any part has been under- water . A flood−damaged fu rnace is extremely dan- gerous. Attempt s to use the furnace can result in fire or explosion. Immedi ately call a qualified ser- vice t echnician to i nspect the f urnace a n d t o replace all g [...]
-
Pagina 46
Page 46 9 − Replace the access panel. 10− Turn on all electrical power to to the unit. 1 1− Set the thermostat to desired setting. NOTE − When unit is initially started, steps 1 through 1 1 may need to be repeated to purge air from gas line. 12− I f the appliance will not operate, follow the instructions T urning Off Gas to Unit" [...]
-
Pagina 47
Page 47 Proper Combustion Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com- bustion. T ake combustion sample beyond the flue outlet and comp are to the tables below . The maximum carbon monoxide reading should not exceed 50 ppm. T ABLE 28 High Fire SLP98DFV Unit CO 2 % For Nat CO 2 % For[...]
-
Pagina 48
Page 48 T emperature Rise Af te r the furnace has been started and supply and return air temperatures have been allowed to st abilize, check the temperature rise with the unit operating at 100 percent fir- ing rate. If necessary , adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blo[...]
-
Pagina 49
Page 49 closed contact s and pressure switches for normally open cont acts. The combustion air inducer is ener- gized at ignition speed, which is approximately the same as the inducer speed at 70 percent firing rate. 2 − Once the control receives a signal that the low−fire pressure switch has closed, the combustion air induc- er begins a 15−s[...]
-
Pagina 50
Page 50 Service W ARNING ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Failure t o follow safety warnings exactly could result in dangerous operation, serious injury , death or property damage. Improper servicing could result in dangerous opera- tion, serious injury , death, or property damage. Before servicing, disconnect all electrical power to fu[...]
-
Pagina 51
Page 51 19 − Thoroughly rinse and drain the heat exchanger . Soap solutions can be corrosive. T ake care to rinse entire assembly . 20 − Reinstall heat exchanger into cabinet making sure that the clamshells of the heat exchanger assembly are resting on the support located at the rear of the cabi- net. Remove the indoor blower to view this area [...]
-
Pagina 52
Page 52 Planned Service A service technician should check the following items dur- in g an annual inspection. Power to the unit must be shut off for the service technician’s safety . Burners − Must be inspected for rust, dirt, or s igns of water . V e nt pipe − Must be inspected for signs of water , cracked, damaged or sagging pipe, or discon[...]
-
Pagina 53
Page 53 Integrated Control Diagnostic Codes Press the diagnostic push button and hold it to cycle through a menu of options. Every five seconds a new menu item will be dis played. Release the button when the desired mode is displayed. When a solid "P" is displayed, the furnace capacity/ size is programmed. When the solid E" is dis[...]
-
Pagina 54
Page 54 Integrated Control Diagnostic Codes (continued) Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover E 223 Low pressure switch failed open − Refer to troubleshooting in installation instruction. Check inches of water column pressure during operation of low pressure switch on heat call, measure inches of water col[...]
-
Pagina 55
Page 55 Integrated Control Diagnostic Codes (continued) Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover E 295 Indoor blower motor temperature is too high. Indoor blower motor over temperature (motor tripped on internal protector), Check motor bear- ings, amperes. Replace if necessary . E 310 Discharge error sensor fai[...]
-
Pagina 56
Page 56 Configuring Unit Size Code Power−Up − Number displayed represent s by integrated control unit size code (furnace model and capacity). If three horizont al bars are displayed followed by continuous E203, furnace control does not recognize unit size code. Configure per the following: Furnace control in IDLE mode No heating, cooling or ind[...]
-
Pagina 57
Page 57 T roubleshooting: Heating Sequence of Operation IGNITION AND CALL FOR LOW FIRE WITH TWO−ST AGE THERMOST A T Call For 2nd St age Heat Call For Heat Satisfied Limit Switch Closed? Limit Closes Within 3 Minutes? NO Soft Lockout: Error Code Flashes flashes YES Rollout Circuit Closed? Low Pressure Switch Open? Low Pressure Switch Closed Within[...]
-
Pagina 58
Page 58 T roubleshooting: Heating Sequence of Operation (Continued) CALL FOR HIGH FIRE WITH TWO−ST AGE THERMOST A T 1st Call for High Fire? W ait for Call for Heat Satisfied 2 S tage Thermostat 2nd S tage Recognition Delay (30 Seconds) YES High Pressure Switch Closes Within 10 Seconds? NO Error Code Flashes NO YES Wait 5 Minutes 3A 2 1 2 1 System[...]
-
Pagina 59
Page 59 T roubleshooting: Heating Sequence of Operation (Continued) CALL FOR HEA T SA TISFIED 1st S tage Heat 2nd S tage Heat 2nd S tage Call for Heat satisfied? NO 1st S tage Call for Heat satisfied? Gas valve De−Energized YES NO 1 4 3A 3B YES OR Combustion Air Inducer switched to 70% rate speed Adjust Indoor Blower to appropiate speed Combustio[...]
-
Pagina 60
Page 60 T roubleshooting: Heating Sequence of Operation (Continued) IGNITION AND CALL FOR HEA T WI TH SINGLE−ST AGE THERMOST A T Call For Heat Satisfied Limit Switch Closed? Limit Closes Within 3 Minutes? NO Soft Lockout: Error Code Flashes flashes YES Rollout Circuit Closed? Low Pressure Switch Open? Low Pressure Switch Closed Within 150 Seconds[...]
-
Pagina 61
Page 61 T roubleshooting: Cooling Sequence of Operation CALL FOR COOLING 1st S tage Cooling Request Received Energize 1st S tage Cooling Contactor (Compressor & Fan) 2nd S tage Cooling Request? YES 2nd S tage Cooling Request S till Active? De−Energize 1st S tage Cooling Contactor (Compressor & Fan) YES 1st S tage Cooling Request S till Ac[...]
-
Pagina 62
Page 62 T roubleshooting: Continuous Fan Sequence of Operation CONTINUOUS LOW SPEED INDOOR BLOWER SEQUENCE OF OPERA TION (S peed Determined by Dip Switch settings) De−Energize Ramping Profile NO Request for Heat Received? Request for Cooling Received? NO YES Call for Fan Removed? YES NO YES Go to Call for Cooling 6 1 4 5 1 Call for Continuous Blo[...]
-
Pagina 63
Page 63 Rep air Parts List The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the nameplate −− Example: SLP98DF070V36B. All service must be performed by a licensed profes- sional installer (or equivalent), service agency , or gas supplier . Cabinet Parts Oute[...]
-
Pagina 64
Page 64 Requirement s for Commonwealth of Massachusetts Modifications to NFP A−54, Chapter 10 Revise N FP A− 54 section 10.8.3 to add the following re- quirement s: Fo r all side wall, horizontally vented, gas−fueled equipment installed in every dwelling, building or structure used in whole or in p art for residential purposes, including thos[...]