Anderson Manufacturing AV-9000 инструкция обслуживания

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321

Идти на страницу of

Хорошее руководство по эксплуатации

Законодательство обязывает продавца передать покупателю, вместе с товаром, руководство по эксплуатации Anderson Manufacturing AV-9000. Отсутствие инструкции либо неправильная информация, переданная потребителю, составляют основание для рекламации в связи с несоответствием устройства с договором. В законодательстве допускается предоставлении руководства в другой, чем бумажная форме, что, в последнее время, часто используется, предоставляя графическую или электронную форму инструкции Anderson Manufacturing AV-9000 или обучающее видео для пользователей. Условием остается четкая и понятная форма.

Что такое руководство?

Слово происходит от латинского "instructio", тоесть привести в порядок. Следовательно в инструкции Anderson Manufacturing AV-9000 можно найти описание этапов поведения. Цель инструкции заключается в облегчении запуска, использования оборудования либо выполнения определенной деятельности. Инструкция является набором информации о предмете/услуге, подсказкой.

К сожалению немного пользователей находит время для чтения инструкций Anderson Manufacturing AV-9000, и хорошая инструкция позволяет не только узнать ряд дополнительных функций приобретенного устройства, но и позволяет избежать возникновения большинства поломок.

Из чего должно состоять идеальное руководство по эксплуатации?

Прежде всего в инструкции Anderson Manufacturing AV-9000 должна находится:
- информация относительно технических данных устройства Anderson Manufacturing AV-9000
- название производителя и год производства оборудования Anderson Manufacturing AV-9000
- правила обслуживания, настройки и ухода за оборудованием Anderson Manufacturing AV-9000
- знаки безопасности и сертификаты, подтверждающие соответствие стандартам

Почему мы не читаем инструкций?

Как правило из-за нехватки времени и уверенности в отдельных функциональностях приобретенных устройств. К сожалению само подсоединение и запуск Anderson Manufacturing AV-9000 это слишком мало. Инструкция заключает ряд отдельных указаний, касающихся функциональности, принципов безопасности, способов ухода (даже то, какие средства стоит использовать), возможных поломок Anderson Manufacturing AV-9000 и способов решения проблем, возникающих во время использования. И наконец то, в инструкции можно найти адресные данные сайта Anderson Manufacturing, в случае отсутствия эффективности предлагаемых решений. Сейчас очень большой популярностью пользуются инструкции в форме интересных анимаций или видео материалов, которое лучше, чем брошюра воспринимаются пользователем. Такой вид инструкции позволяет пользователю просмотреть весь фильм, не пропуская спецификацию и сложные технические описания Anderson Manufacturing AV-9000, как это часто бывает в случае бумажной версии.

Почему стоит читать инструкции?

Прежде всего здесь мы найдем ответы касательно конструкции, возможностей устройства Anderson Manufacturing AV-9000, использования отдельных аксессуаров и ряд информации, позволяющей вполне использовать все функции и упрощения.

После удачной покупки оборудования/устройства стоит посвятить несколько минут для ознакомления с каждой частью инструкции Anderson Manufacturing AV-9000. Сейчас их старательно готовят или переводят, чтобы они были не только понятными для пользователя, но и чтобы выполняли свою основную информационно-поддерживающую функцию.

Содержание руководства

  • Страница 1

    Anderson Instrument Co., Inc. 156 Auriesville Rd. Fultonville, NY 12072 Phone: 518-922-5315 800-833-0081 Fax: 518-922-8997 Instruction Manual Rev . G Doc. AIC-3677 A V -9000 Recorder/ Recording Controller ANDERSON[...]

  • Страница 2

    [...]

  • Страница 3

    AV-9000 Manual Revision Log Revision Revision Revision Revision Revision Date Date Date Date Date Description Description Description Description Description Edition 1 Edition 1 Rev A 6/16/95 7/14/95 Released Revised Pages: 4,5, 1-1 thru 1-5, 2-8, 4-3, 4-5, 4-6, 4-9 thru 4-11, 4-17, 4-37, 4-39, 4-40, 4-42, 4-48, 4-50, 4-57, 4-100, 4-101, 7-1 thru 7[...]

  • Страница 4

    [...]

  • Страница 5

    Prefix & T able of Contents 2 Edition 3 Rev G AV-9000 Manual Prefix MANUAL ORGANIZA TION This manual is organized in twelve major sections: Section 1 Introduction and General Information Section 2 Installation and Wiring Section 3 The Basics of Recorder Operation Section 4 Configuration Section 5 Display Programming Section 6 Chart Prompts Sect[...]

  • Страница 6

    Table of Contents PAGE SECTION 1 - INTRODUCTION AND GENERAL INFORMATION 1-1 1.1 Unpacking 1-1 1.2 Installation of Pen Cartridge Assembly 1-2 1.3 Order Matrix/Model Number 1-3 1.4 Specifications 1-4 1.5 Warranty Statement 1-7 SECTION 2 - INSTALLATION AND WIRING 2-1 2.1 Mounting 2-1 2.2 Preparation for Wiring 2-3 2.3 Wiring Connections - Inputs 2-6 2[...]

  • Страница 7

    Prefix & T able of Contents 4 Edition 3 Rev G PAGE 3.8.1 Chart Printing Interruptions 3-8 3.8.2 New Chart Printing Requirements 3-9 3.8.3 Example Chart 3-9 3.8.4 Sequence of Events 3-12 3.9 Getting Started 3-13 3.10 Quick Start Procedure 3-14 SECTION 4 - CONFIGURATION 4-1 4.1 Entering Configuration 4-1 4.1.1 Inputs 4-1 4.1.2 Constants 4-14 4.1.[...]

  • Страница 8

    Prefix & T able of Contents 5 Edition 3 Rev G PAGE SECTION 13 - CONTROLLERS 13-1 13.1 Entering Controllers 13-3 13.2 Control Setpoints 13-18 13.3 Control State Access 13-22 13.4 Tuning Parameters 13-31 SECTION 14 - PROFILERS 14-1 14.1 Profile Entry 14-1 14.2 Profile Settings 14-4 14.3 Profile Control 14-7 Figures and Tables Figure 1-1 Pen Cartr[...]

  • Страница 9

    Section 1 1-1 Edition 3 Rev G Section 1 - Introduction and General Information This instrument is a microprocessor based circular chart recorder capable of measuring, displaying, and recording from a variety of inputs. Applications include temperature, level, pressure, flow , and others. The instrument can be specified as either a one, two, three, [...]

  • Страница 10

    Section 1 1-2 Edition 3 Rev G 1.2 INST ALLA TION OF PEN CARTRIDGE ASSEMBL Y Remove the pen cartridge assembly from its shipping container . With mounting tab on the bottom, slide the pen cartridge assembly (item 2 on Figure 1-1) into the print actuator (item 1 on Figure 1-1). FIGURE 1-1 1 2 3 4 5 6 7 8 INSTALL PEN CARTRIDGE (2) PRINT ACTUATOR (1) P[...]

  • Страница 11

    Section 1 1-3 Edition 2 Rev F 1.3 ORDER MATRIX / MODEL NUMBER TYPE 1 Recorder Only 2 Recorder/Controller PENS/COLORS 2 Two Trend, Two Colors** 4 Four Trend Pens, Four Colors UNIVERSAL INPUTS 1 One Input 2 Two Inputs 3 Three Inputs 4 Four Inputs 6 Six Inputs 8 Eight Inputs 0 FIXED CHARACTER RELAY OUTPUTS 0 None 2 Two Relays 4 Four Relays 6 Six Relay[...]

  • Страница 12

    Section 1 1-4 Edition 2 Rev F 1.4 SPECIFICATIONS DESCRIPTION The instrument is the first circular chart recorder with the ability to record trend data and print alphanu- meric in four colors. It uses unique “ring only” charts and has the ability to zone and scale trend data. These capabilities not only provide the best trend data readability, b[...]

  • Страница 13

    Section 1 1-5 Edition 3 Rev G OPERA TOR INTERF A CE Beyond the configuration capability , the display , keypad, and prompting system provide superior real time data presentation. The display of each instrument value is configurable and three display formats are available, providing a range from fully detailed displays with 20 character tags, alarm [...]

  • Страница 14

    Section 1 1-6 Edition 3 Rev G INPUTS Input T ypes Thermocouple T ypes J, K, T , R, S, E, B, N, G, D, C, Ni/Ni-Moly , and Platinel II. RTD Platinum 100, 2 or 3 wire .00385 coefficient DIN 43760/IEC 751 .00392 coefficient USA .00392 coefficient SAMA Nickel 100, 2 or 3 wire Voltage DC 0 to 25mV , 0 to 100 mVDC, 0 to 1 VDC, 0 to 10 VDC Current DC 0 to [...]

  • Страница 15

    Section 1 1-7 Edition 3 Rev G 4 REF+LIN +CAL ° C 0.95 1.28 0.50 0.80 1.28 2.13 0.62 1.35 0.80 1.71 0.57 1.21 1.32 2.97 0.73 1.32 3.68 2.92 2.30 2.33 2.91 5.84 3.68 2.85 2.29 2.43 3.26 2.40 2.86 1.10 1.06 1.44 1.17 1.12 TC TYPE J WIDE J NARROW K WIDE K NARROW E WIDE E NARROW N WIDE N NARROW G C D NNM Platinel II See Note: RANGE ° C 0/1200 -200/0 0[...]

  • Страница 16

    Section 1 1-8 Edition 3 Rev G T o achieve stated results, the follo wing thermocouples must be used with the INPUT TYPE/RANGE set to TC NARRO W 4 REF+LIN +CAL ° C 0.55 1.12 2.98 1.45 1.90 1.87 2.39 TC TYPE T R S B See Note: RANGE ° C 0/400 -200/0 -250/-220 800/1700 200/800 250/1750 200/1800 1 REF ACC'Y ° C 0.12 0.23 0.73 0.43 0.58 0.56 0.74[...]

  • Страница 17

    Section 1 1-9 Edition 3 Rev G A CCURA CY T ABLES CONT . NOTES: The table attempts to show the ef fect of each significant factor which contributes to the overall measurement error . See the enumerated items below for more specific explanations of each column of data. 1. Reference Acc'y based on 0.025% (250ppm) of input voltage span. 2. Lineari[...]

  • Страница 18

    Section 1 1-10 Edition 3 Rev G O THER INPUT SPECIFICA TIONS Processing Square root and exponential functions for linear inputs Value Cutoff None, at value, to zero below value, to zero near zero Sensor Fault Detection Sensor break on all TCs, RTDs, 1 volt, 1 to 5 volt, 4-20mA, and millivolt inputs Sensor high and low on all inputs, 5% above or belo[...]

  • Страница 19

    Section 1 1-11 Edition 3 Rev G CURRENT OUTPUTS Drivers Any of over 20 values can be used to drive analog outputs (e.g. inputs, derived variables, etc.) Output Span 0 to 20mA or 4 to 20mA, nominal Resolution 12 bits based on a 0 to 25.6mA span Accuracy ± 0.1% of 20mA span reference accuracy Compliance 650 ohm load T O T ALIZERS Number Four are incl[...]

  • Страница 20

    Section 1 1-12 Edition 3 Rev G CONSTR UCTION (cont.) Panel Cutout 12.7 inches wide x 12.7 inches high (322.58mm wide x 322.58mm high) Panel Depth 5.25 inches (133.35 mm) Panel Protrusion 2.5 inches (63.5mm) Weight 25 lbs maximum ENVIR ONMENT AL AND OPERA TING CONDITIONS Operating T emperature 0 to 50 ° C (32 to 122 ° F) Storage T emperature -40 t[...]

  • Страница 21

    1.5 WARRANTY AND RETURN STATEMENT The products are sold by the factory under the warranties set forth in the following paragraphs. Such warranties are extended only with respect to a purchase of these products, as new merchandise, directly from the factory or from a factory distributor, representative or reseller, and are extended only to the first[...]

  • Страница 22

    [...]

  • Страница 23

    Section 2 2-1 Edition 3 Rev G Section 2 - Installation and Wiring Read these instructions carefully before proceeding with installation and operation. Electrical code requirements and safety standards should be observed. Installation should be performed by qualified personnel. 2.1 MOUNTING (Panel and Surface described below , pipe - to be determine[...]

  • Страница 24

    Section 2 2-2 Edition 3 Rev G FIGURE 2-1B 5.24" (133.10mm) 17.04" (432.82mm) EC1 EC5 EC2 EC3 EC6 EC4 14.12" (358.65mm) 12.600" (320.04mm) 7.747" (196.77mm) g 2.12" (53.85mm) 12.60" (320.04mm) 2.044" (58.93mm)[...]

  • Страница 25

    Section 2 2-3 Edition 3 Rev G 2.2 PREP ARA TION FOR WIRING This product is in conformity with the protection requirements of EU Council Directive 89/336EEC on the approxi- mation of the laws of the Member States relating to electromagnetic compatibility . The factory cannot accept responsibility for any failure to satisfy the protection requirement[...]

  • Страница 26

    Section 2 2-4 Edition 3 Rev G Use of Shielded Cable Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end only . The preferred [...]

  • Страница 27

    Section 2 2-5 Edition 3 Rev G Sensor Placement (Thermocouple or RTD) Thermocouple lead resistance should not exceed 300 ohms. If this is exceeded, instrument accuracy could be affected. T wo wire RTD's should be used only with lead lengths less than 10 feet. If the temperature probe is to be subjected to corrosive or abrasive conditions, it sh[...]

  • Страница 28

    Section 2 2-6 Edition 3 Rev G 2.3 WIRING CONNECTIONS - INPUTS All wiring connections are typically made to the instrument at the time of installation. Connections should be made at the terminal blocks, one 14 gauge wire maximum, using copper conductors except for thermocouple inputs. See Figure 2-4 (below) for the terminal block locations. The reco[...]

  • Страница 29

    Section 2 2-7 Edition 3 Rev G 2.3.1 SHIPPED CONFIGURA TION/JUMPER POSITIONING Each instrument is factory shipped with all parameters set to default values. These defaults are shown in the "display" box for each parameter in Section 4. Jumpers are used to condition the sensor inputs. All jumpers are located on the Input Board(s). The instr[...]

  • Страница 30

    Section 2 2-8 Edition 3 Rev G 2.3.3 A C PO WER CONNECTIONS W ARNING: UNIT SHOULD HA VE A POWER SWITCH OR CIRCUIT BREAKER IN CLOSE PROXIMITY OF EQUIPMENT AND WITHIN EASY REACH OF THE OPERA TOR. THE SWITCH SHALL BE MARKED AS THE DISCONNECTING DEVICE FOR THE UNIT . FIGURE 2-6 Connect the line voltage, hot and neutral, to L and N respectively . Connect[...]

  • Страница 31

    Section 2 2-9 Edition 3 Rev G 2.3.4 THERMOCOUPLE CONNECTIONS NOTE: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. T wo versions of Input Board s may be found, see Figure 2-7 and Figure 2-7A. Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if equi[...]

  • Страница 32

    Section 2 2-10 Edition 3 Rev G 2.3.5 R TD CONNECTIONS Note: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. T wo versions of Input Board s may be found, see Figure 2-8 and Figure 2-8A. Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if equipped. I[...]

  • Страница 33

    Section 2 2-11 Edition 3 Rev G 2.3.6 V OL T A GE CONNECTIONS Note: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. T wo versions of Input Board s may be found, see Figure 2-9 and Figure 2-9A. Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if equi[...]

  • Страница 34

    Section 2 2-12 Edition 3 Rev G 2.3.7 CURRENT CONNECTIONS Note: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. T wo versions of Input Board s may be found, see Figure 2-10 and Figure 2-10A. Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if equipp[...]

  • Страница 35

    Section 2 2-13 Edition 3 Rev G 2.3.8 SWITCH INPUT CONNECTIONS Note: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. T wo versions of Input Board s may be found, see Figure 2-10 and Figure 2-10A. Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if e[...]

  • Страница 36

    Section 2 2-14 Edition 3 Rev G 1 TB1 TB2 TB3 TB4 SSR + - +- N O TB1 TB2 TB3 TB4 P O W E R N C C LOAD 2.4 WIRING CONNECTIONS - OUTPUTS Relay output(s), if provided, may be assigned to any actuator , which includes alarms and/or optional control capability . Current output(s), if provided, may be assigned to any analog value, which includes derived a[...]

  • Страница 37

    Section 2 2-15 Edition 3 Rev G 2.4.3 CURRENT OUTPUT Note: Up to two boards may be present, stacked 2 high. Board 1 is the bottom board. Non-isolated and isolated outputs are available. Non-isolated Non-isolated current outputs are designated as current output 1 through current output 2. Current output 1 is located on Board 1 and Current Output 2 is[...]

  • Страница 38

    Section 2 2-16 Edition 3 Rev G 2.4.4 24VDC TRANSMITTER PO WER SUPPL Y Note: Up to four transmitter power supplies may be present. One transmitter can provide up to 25mA of current at 24 VDC. T ransmitter outputs are designated as T ransmitter Output 1 through T ransmitter Output 4. T ransmitter Output 1 is at TB1, T ransmitter Output 2 is at TB2, T[...]

  • Страница 39

    Section 2 2-17 Edition 3 Rev G FIGURE 2-15C RS-485 TB3 JP3 JP1 B A Network Continuation (If Applicable) T owards Computer[...]

  • Страница 40

    Edition 3 Rev G Section 3 3-1 Section 3 - The Basics of Recorder Operation 3.1 POWER-UP After proper installation, the following will occur when power is applied: • All segments in the vacuum fluorescent display will light, then • All the display LEDs will light, then • The instrument tag and the current time and date will appear . When compl[...]

  • Страница 41

    Section 3 Edition 3 Rev G 3-2 3.3 KEYP AD FUNCTION FIGURE 3-1 3.3.1 DISPLA Y KEY (DISP) While in Normal Display , the Display key initiates the Display Prompts and is used to step through the Display Prompts. 3.3.2 CHART KEY (CHART) While in Normal Display , the Chart key initiates the Chart Prompts and is used to step through the Chart Prompts. 3.[...]

  • Страница 42

    Edition 3 Rev G Section 3 3-3 3.4 CHANGING P ARAMETER SETTINGS - MODIFY There are three types of parameters in the instrument: values (numbers), text strings (groups of characters), and choices (selections made by picking one of a group of displayed descriptions). With a modifiable parameter description and its setting displayed, pressing the MOD k[...]

  • Страница 43

    Section 3 Edition 3 Rev G 3-4 • If the setting is one of a list of choices, the choice line containing the current choice will be displayed and the current choice will blink. If multiple choices are displayed, the LEFT ARROW or SCROLL keys will move the selection to the left or right. If all choices are not displayed at once, due to multiple choi[...]

  • Страница 44

    Edition 3 Rev G Section 3 3-5 ACTION TIME Selections made in action time settings are used to generate actuators that are true/false SETTINGS based on times and/or dates. ALARM SETTING Selections made in alarm settings determine the setpoint of each alarm configured. ENABLES/ Selections made in enables/passwords provide means of enabling or disabli[...]

  • Страница 45

    Section 3 Edition 3 Rev G 3-6 The following is the "1 V AL" at a time display format for process variables: display tag aaaannnnnn uuuuuu aaaa - individual alarm indicators: H = High Process Alarm L = Low Process Alarm R = Rate Alarm nnnnnn - represents a number , with up to as many digits as n's shown uuuuuu - represents the corresp[...]

  • Страница 46

    Edition 3 Rev G Section 3 3-7 Whenever the display format is other than "1 V AL" at a time, the different types are not intermixed in any given display step, consequently the second line may be blank. SEQUENTIAL DISPLA Y With Sequential Display active, the instrument provides a sequential display of all input, simulated, derived, and proc[...]

  • Страница 47

    Section 3 Edition 3 Rev G 3-8 T rends can be zoned into two different areas to allow for higher resolution on one end of the recorded span. The recorded area used on the chart for a trend may not necessarily use the entire area available for recording. Engineering unit values are printed next to the corresponding scale lines. The ZONE 1 LOW DIVISIO[...]

  • Страница 48

    Edition 3 Rev G Section 3 3-9 3.8.2 NEW CHAR T PRINTING REQUIREMENTS The following ACTION ON NEW CHAR T options are provided: NONE - JUST CONTINUE PRINT RANGE LIST PRINT SCALES The following example illustrates the format used if PRINT RANGE LIST has been configured. This method would be selected to reduce the time between chart installation and in[...]

  • Страница 49

    Section 3 Edition 3 Rev G 3-10 The value recorded on Pen 2 is the temperature, zoned to record 20 to 120 on the lower 10% of the chart, and 120 to 210 on the upper 90% of the chart. The value recorded on Pen 3 is the pH, input 4 zoned to record 0 to 14 on the upper 70% of the chart. The value recorded on Pen 4 is the status of alarm A1 1, zoned to [...]

  • Страница 50

    Edition 3 Rev G Section 3 3-11 T ABLE 3-2 Recorder Parameters (Not all parameters are shown) RECORDER NUMBER 1 2 3 4 Rs RECORDER T AG t t t t t t t t t t t t t t t t t t t t FLOW #1 TEMP #1 PH #1 ALARM #1 Rs V ALUE T O RECORD (V ALUE) DV1 IV2 IV4 DV2 Rs PEN/COLOR (PEN/COLOR) BLUE GREEN BLACK RED RS CHART DIVISIONS n n n 100 100 100 100 Rs ZONE 1 LO[...]

  • Страница 51

    Section 3 Edition 3 Rev G 3-12 3.8.4 SEQUENCE OF EVENTS 1 1:27 PM Chart installed 1 1:30 PM Instrument began printing with the Chart T ag, (UNIT #1) and the trend data collected and saved between 1 1:27 and 1 1:30, while continuing to save scanned data. Note the " ¨ " on the outer ring to indicate where trending began 1 1:31 PM Instrumen[...]

  • Страница 52

    Edition 3 Rev G Section 3 3-13 MAIN PROMPTS CONFIGURA TION CHART PROMPTS CHANGE CHART ST ART CHART CHAR T R O TAT E TREND COLLECT CHART SPEED CHART CONFIG YES NO DISP PROMPTS DISP P ASSWORD SYSTEM PROMPTS SYSTEM P ASSWORD ACT/TIME SETTINGS ALARM SETTINGS ENABLES P ASSWORDS CONFIG. TEST CAL MODEL REV TUNING P ARAMETERS* * CONTROLLER ONL Y DISP MODE [...]

  • Страница 53

    Section 3 Edition 3 Rev G 3-14 3.10 QUICK ST ART PROCEDURE This procedure can be used for starting up the recorder at the very basic level of recording inputs or to quickly familiarize yourself with the basic configuration process. A large number of default parameters are utilized and the default conditions are assumed. Please refer to the balance [...]

  • Страница 54

    Edition 3 Rev G Section 3 3-15 Step 8 Next, the display will show IVx DECIMAL POSITION, IVx RANGE LIMIT LOW , and IVx RANGE LIMIT HIGH. These will be used to calculate the engineering units range for volt/milliamp inputs for the Input being configured. For Thermocouple/R TD inputs, their values establish the expected range outside of which the inst[...]

  • Страница 55

    Section 3 Edition 3 Rev G 3-16 Software Reference/Record Sheet Configuration INPUT Parameter Input 1 Input 2 Input 3 Input 4 DISPLA Y T AG INPUT TYPE/RANGE T/C TYPE RTD TYPE DEG C/F SENSOR BREAK INPUT RANGE LOW INPUT RANGE HIGH PULSE RA TE HIGH COMMS ADDRESS COMMS REGISTER REGISTER TYPE V/MA CONVERSION DISPLA Y UNITS OTHER UNITS DECIMAL POSITION RA[...]

  • Страница 56

    Edition 3 Rev G Section 3 3-17 Software Reference/Record Sheet Configuration INPUT Parameter Input 5 Input 6 Input 7 Input 8 DISPLA Y T AG INPUT TYPE/RANGE T/C TYPE T/C INPUT SP AN RTD TYPE DEG C/F V/MA INPUT TYPE SENSOR BREAK INPUT RANGE LOW INPUT RANGE HIGH PULSE RA TE HIGH COMMS ADDRESS COMMS REGISTER REGISTER TYPE V/MA CONVERSION DISPLA Y UNITS[...]

  • Страница 57

    Section 3 Edition 3 Rev G 3-18 Software Reference/Record Sheet Configuration CONST ANTS Parameter CV -1 CV -2 CV -3 CV -4 V ALUE Parameter CV -7 CV -8 CV -9 CV -10 CV -1 1 CV -12 Parameter CV -5 CV -6 CV -7 CV -8 V ALUE Parameter CV -9 CV -10 CV -1 1 CV -12 V ALUE[...]

  • Страница 58

    Edition 3 Rev G Section 3 3-19 Software Reference/Record Sheet Configuration CUST OM CURVES Parameter CC-1 CC-2 DECIMAL POSITION OF INPUT DECIMAL POSITION OF OUTPUT NUMBER OF POINTS POINT P AIR 01 POINT P AIR 02 POINT P AIR 03 POINT P AIR 04 POINT P AIR 05 POINT P AIR 06 POINT P AIR 07 POINT P AIR 08 POINT P AIR 09 POINT P AIR 10 POINT P AIR 1 1 PO[...]

  • Страница 59

    Section 3 Edition 3 Rev G 3-20 Software Reference/Record Sheet Configuration CUST OM CURVES Parameter CC-3 CC-4 DECIMAL POSITION OF INPUT DECIMAL POSITION OF OUTPUT NUMBER OF POINTS POINT P AIR 01 POINT P AIR 02 POINT P AIR 03 POINT P AIR 04 POINT P AIR 05 POINT P AIR 06 POINT P AIR 07 POINT P AIR 08 POINT P AIR 09 POINT P AIR 10 POINT P AIR 1 1 PO[...]

  • Страница 60

    Edition 3 Rev G Section 3 3-21 Software Reference/Record Sheet Configuration DERIVED V ARIABLES Parameter DV -1 DV -2 DV -3 DV -4 DISPLA Y T AG FUNCTION INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT ACTUA TOR RESET ACTUA T OR DISPLA Y UNITS UNITS DESCRIPTION DECIMAL POSITION V ALUE FIL TER DISPLA Y OPTION DISPLA Y FIL TER seconds seconds seconds se[...]

  • Страница 61

    Section 3 Edition 3 Rev G 3-22 Parameter DV -9 DV -10 DV -1 1 DV -12 DISPLA Y T AG FUNCTION INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT ACTUA TOR RESET ACTUA TOR DISPLA Y UNITS UNITS DESCRIPTION DECIMAL POSITION V ALUE FIL TER DISPLA Y V ALUE DISPLA Y FIL TER seconds seconds seconds seconds seconds seconds seconds seconds Software Reference/Recor[...]

  • Страница 62

    Edition 3 Rev G Section 3 3-23 Software Reference/Record Sheet Configuration PROCESS V ARIABLES Parameter PV -1 PV -2 PV -3 PV -4 DISPLA Y T AG INPUT DISPLA Y UNITS OTHER UNITS DECIMAL POSITION V ALUE FIL TER DISPLA Y OPTION DISPLA Y FIL TER Ax1 ALARM TYPE Ax1 TIME BASE Ax1 SAMPLE PERIOD Ax1 HYSTERESIS Ax2 ALARM TYPE Ax2 TIME BASE Ax2 SAMPLE PERIOD[...]

  • Страница 63

    Section 3 Edition 3 Rev G 3-24 % % % % %/MIN OFF ON % % % % %MIN OFF ON % % % % %/MIN OFF ON % % % % %/MIN OFF ON CONTROL TYPE OUT 1 TYPE OUT 2 TYPE OUT 1 HYST OUT 2 HYST OUT 1 % LIMIT OUT 2 % LIMIT OUT 1 % ERROR OUT 2 % ERROR OUT SLEW RA TE MANUAL ACTUA TOR AUTO TRANSFER MAIN SP SOURCE REMOTE SP ACTUA T OR REMOTE SP SOURCE 2nd SP ACTUA TOR 2nd SP [...]

  • Страница 64

    Edition 3 Rev G Section 3 3-25 Software Reference/Record Sheet Configuration CONTROL SETPOINTS Parameter Setpoint 1 Setpoint 2 Setpoint 3 Setpoint 4 *PROMPT TEXT DISPLA Y UNITS OTHER UNITS DEC POSITION UPPER LIMIT LOWER LIMIT DISP OPTION Parameter Setpoint 1 Setpoint 2 Setpoint 3 Setpoint 4 *PROMPT TEXT DISPLA Y UNITS OTHER UNITS DEC POSITION UPPER[...]

  • Страница 65

    Section 3 Edition 3 Rev G 3-26 Software Reference/Record Sheet Configuration RECORDERS Parameter RCDR-1 RCDR-2 RCDR-3 RCDR-4 RECORDER T AG V ALUE TO RECORD PEN/COLOR RECORDING METHOD DECIMAL POSITION CHART DIVISIONS ZONE 1 LOW ZONE 1 HIGH SP AN 1 LOW SP AN 1 HIGH SCALE 1 INTER V AL ZONE 2 HIGH SP AN 2 HIGH SCALE 2 INTER V AL POSIT ON ERROR FIL TER [...]

  • Страница 66

    Edition 3 Rev G Section 3 3-27 Software Reference/Record Sheet Configuration TOT ALIZERS Parameter T OT AL-1 TOT AL-2 TOT AL-3 TOT AL-4 DISPLA Y T AG INPUT V ALUE TIME BASE TOT AL IS FLOW DISPLA Y UNITS DECIMAL POSITION DISPLA Y OPTION DISPLA Y FORMA T TOT ALIZER TYPE TOT ALIZER PRESET LOW FLOW CUT OFF RESET ACTUA TOR HOLD ACTUA T OR PULSED OUT PUL[...]

  • Страница 67

    Section 3 Edition 3 Rev G 3-28 Software Reference/Record Sheet Configuration TIMERS Parameter TIME-1 TIME-2 TIME-3 TIME-4 DISPLA Y T AG TIMER TYPE TIME FORMA T TIMER PERIOD RESET ACTUA TOR DISPLA Y OPTION Parameter LED-1 LED-2 LED-3 LED-4 ACTUA TOR Configuration LEDS Parameter LED-5 LED-6 LED-7 LED-8 ACTUA TOR[...]

  • Страница 68

    Edition 3 Rev G Section 3 3-29 Software Reference/Record Sheet Configuration RELA YS Parameter RL Y -1 RL Y -2 RL Y -3 RL Y -4 RELA Y USAGE ACTUA TOR T .P . V ALUE CYCLE TIME seconds seconds seconds seconds Parameter RL Y -5 RL Y -6 RL Y -7 RL Y -8 RELA Y USAGE ACTUA T OR T .P . V ALUE CYCLE TIME seconds seconds seconds seconds[...]

  • Страница 69

    Section 3 Edition 3 Rev G 3-30 Software Reference/Record Sheet Configuration CURRENT OUTPUTS Parameter CO-1 CO-2 CO-3 CO-4 SOURCE RANGE LOW RANGE HIGH OUTPUT RANGE OUTPUT ON ERROR mA mA mA mA mA mA mA mA[...]

  • Страница 70

    Edition 3 Rev G Section 3 3-31 Software Reference/Record Sheet Configuration INSTRUMENT SETTINGS Parameter INSTRUMENT T AG DISPLA Y OPTION INSTR. ON ACTUA TOR ALARMING ON ACTUA TOR CONTROL ON ACTUA TOR DA TE DISPLA Y FORMA T TIME DISPLA Y FORMA T CURRENT DA TE CURRENT DA Y CURRENT TIME TIME T O LOG DA T A COMMUNICA TIONS MODE COMMS ADDRESS COMMS BI[...]

  • Страница 71

    Section 3 Edition 3 Rev G 3-32 Software Reference/Record Sheet Configuration DERIVED ACTUA TORS Derived Actuator Equation DA-1 DA-2 DA-3 DA-4 DA-5 DA-6 DA-7 DA-8 DA-9 DA-10 DA-1 1 DA-12 DA-13 DA-14 DA-15 DA-16 DA-17 DA-18 DA-19 DA-20 DA-21 DA-22 DA-23 DA-24[...]

  • Страница 72

    Edition 3 Rev G Section 3 3-33 Software Reference/Record Sheet Configuration OPERA TOR INPUTS Parameter OI-01 OI-02 OI-03 PROMPT TEXT OFF/NO/0 CHOICE ON/YES/1 CHOICE ACTUA TION STYLE POWER UP ST A TE WHEN DISPLA YED Continuous Momentary Off On Same Always When Enabled Continuous Momentary Off On Same Always When Enabled Continuous Momentary Off On [...]

  • Страница 73

    Section 3 Edition 3 Rev G 3-34 Software Reference/Record Sheet Configuration OPERA T OR MESSAGES Parameter OM-01 OM-02 OM-03 ACTUA TOR LINE 1 TEXT LINE 2 TEXT DISPLA Y MODE Parameter OM-04 OM-05 OM-06 ACTUA TOR LINE 1 TEXT LINE 2 TEXT DISPLA Y MODE Parameter OM-07 OM-08 OM-09 ACTUA TOR LINE 1 TEXT LINE 2 TEXT DISPLA Y MODE Parameter OM-10 OM-1 1 OM[...]

  • Страница 74

    Edition 3 Rev G Section 3 3-35 No Y es No Y es No Y es No Y es No Y es No Y es Software Reference/Record Sheet Configuration CHART MESSAGES Parameter CM-01 CM-02 CM-03 CM-04 ACTUA TOR PEN/COLOR MESSAGE TEXT V ALUE 1 V ALUE 2 V ALUE 3 V ALUE 4 TIME/DA TE ST AMP ORIENT A TION No Y es No Y es Parameter CM-05 CM-06 CM-07 CM-08 ACTUA TOR PEN/COLOR MESSA[...]

  • Страница 75

    Section 3 Edition 3 Rev G 3-36 Software Reference/Record Sheet Configuration CONTROL ST A TE ACCESS Parameter T ext CA1 LINE 1 TEXT CA1 LINE 2 TEXT CA1 F1 KEY USAGE CA1 F1 LINE 1 TEXT CA1 F1 OFF ST A TE TEXT CA1 F1 ON ST A TE TEXT CA1 F2 KEY USAGE CA1 F2 LINE 1 TEXT CA1 F2 OFF ST A TE TEXT CA1 F2 ON ST A TE TEXT CA1 F3 KEY USAGE CA1 F3 LINE 1 TEXT [...]

  • Страница 76

    Edition 3 Rev G Section 3 3-37 Software Reference/Record Sheet Configuration CONTROL ST A TE ACCESS Parameter T ext CA2 LINE 1 TEXT CA2 LINE 2 TEXT CA2 F1 KEY USAGE CA2 F1 LINE 1 TEXT CA2 F1 OFF ST A TE TEXT CA2 F1 ON ST A TE TEXT CA2 F2 KEY USAGE CA2 F2 LINE 1 TEXT CA2 F2 OFF ST A TE TEXT CA2 F2 ON ST A TE TEXT CA2 F3 KEY USAGE CA2 F3 LINE 1 TEXT [...]

  • Страница 77

    Section 3 Edition 3 Rev G 3-38 Software Reference/Record Sheet Configuration CONTROL ST A TE ACCESS Parameter T ext CA3 LINE 1 TEXT CA3 LINE 2 TEXT CA3 F1 KEY USAGE CA3 F1 LINE 1 TEXT CA3 F1 OFF ST A TE TEXT CA3 F1 ON ST A TE TEXT CA3 F2 KEY USAGE CA3 F2 LINE 1 TEXT CA3 F2 OFF ST A TE TEXT CA3 F2 ON ST A TE TEXT CA3 F3 KEY USAGE CA3 F3 LINE 1 TEXT [...]

  • Страница 78

    Edition 3 Rev G Section 3 3-39 Software Reference/Record Sheet Configuration CONTROL ST A TE ACCESS Parameter T ext CA4 LINE 1 TEXT CA4 LINE 2 TEXT CA4 F1 KEY USAGE CA4 F1 LINE 1 TEXT CA4 F1 OFF ST A TE TEXT CA4 F1 ON ST A TE TEXT CA4 F2 KEY USAGE CA4 F2 LINE 1 TEXT CA4 F2 OFF ST A TE TEXT CA4 F2 ON ST A TE TEXT CA4 F3 KEY USAGE CA4 F3 LINE 1 TEXT [...]

  • Страница 79

    Section 3 Edition 3 Rev G 3-40 Software Reference/Record Sheet Configuration SIMULA TED V ARIABLES Parameter SV -1 SV -2 SV -3 SV -4 DISPLA Y T AG TYPE DISPLA Y UNITS OTHER UNITS DECIMAL POSITION RANGE LOW RANGE HIGH PERIOD (1/FREQ.) DISPLA Y OPTION C F Other minutes C F Other minutes C F Other minutes C F Other minutes[...]

  • Страница 80

    Edition 3 Rev G Section 3 3-41 Select Chart Configuration CHART SIZE CHART TYPE USED CHART T AG NORMAL SPEED MAJOR TIME PERIODS MINOR TIME PERIODS BLANK MAJOR PERIODS AL TERNA TE SPEED USED AL T SPEED ACTUA TOR AL TERNA TE SPEED MAJOR TIME PERIODS MINOR TIME PERIODS BLANK MAJOR PERIODS MAJOR LINE PEN/COLOR MA TCH SCALE COLOR SELECT A COLOR MAJOR LI[...]

  • Страница 81

    Section 3 Edition 3 Rev G 3-42 Software Reference/Record Sheet Configuration DISPLA Y PROGRAMMING Parameter SEQUENTIAL DISPLA Y DISPLA Y MODE DISPLA Y FORMA T DURA TION _______ SECONDS CONTINUOUS SEQUENCE 1 V AL 2 V ALS 4 V ALS[...]

  • Страница 82

    Edition 3 Rev G Section 3 3-43 Software Reference/Record Sheet Configuration ALARM SETTINGS PV 1 ALM 1 (A1 1) ALM 2 (A12) ALM 3 (A13) ALM 4 (A14) SETPOINT PV 2 ALM 1 ALM 2 ALM 3 ALM 4 PV 3 ALM 1 ALM 2 ALM 3 ALM 4 PV 4 ALM 1 ALM 2 ALM 3 ALM 4 PV 2 ALM 1 (A21) ALM 2 (A22) ALM 3 (A23) ALM 4 (A24) SETPOINT PV 3 ALM 1 (A31) ALM 2 (A32) ALM 3 (A33) ALM 4[...]

  • Страница 83

    Section 3 Edition 3 Rev G 3-44 Software Reference/Record Sheet Configuration ACTION TIME SETTINGS Parameter TIME 1 T AG TIME 1 DA TE 1 TIME 2 T AG TIME 2 DA TE 2 DA Y OF WEEK ACTUA T OR DA Y OF MONTH ACTUA T OR TIME DISPLA Y OPTION[...]

  • Страница 84

    Edition 3 Rev G Section 3 3-45 /HR R/M R/M MIN MIN /HR R/M R/M MIN MIN /HR R/M R/M MIN MIN /HR R/M R/M MIN MIN SP RAMP RA TE OUT 1 P . BAND OUT 2 P . BAND OUT 1 SHIFT OUT 2 SHIFT INTEGRA TION BAND INTEGRA TION SHIFT OUT 1 AUT O RESET OUT 2 AUT O RESET OUT 1 RA TE OUT 2 RA TE Software Reference/Record Sheet Configuration TUNING P ARAMETERS Parameter[...]

  • Страница 85

    Section 3 Edition 3 Rev G 3-46 Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enabled Disabled - Enab[...]

  • Страница 86

    Edition 3 Rev G Section 4 4-1 Section 4 - Configuration Selections made in Configuration set up the recorder for operation. Not all sections are applicable for every recorder . Before or during configuration of your recorder , it is recommended that the Software Reference/Record Sheet (found at end of Section 3) be completely filled in. 4.1 ENTERIN[...]

  • Страница 87

    Section 4 Edition 3 Rev G 4-2 Press the to change, then or to desired selection, then press . IVx COPY / INITIALIZE NO Selections YES or NO 2. Press the to advance to the next parameter , COPY/INITIALIZE . Choose YES if the parameters to be programmed are the same as another INPUT already programmed. If selection is NO, see Step 3. If selection is [...]

  • Страница 88

    Edition 3 Rev G Section 4 4-3 4. Press the to advance to the next parameter , INPUT TYPE/RANGE . 5. Press the to advance to the next parameter: OFF-NO INPUT selected, no other prompts for Input x will be seen, go to Step 1, Pg. 4-1. TC TYPE selected, go to Step 5A. RTD TYPE selected, go to Step 5B mV , mA, V olt, Switch Contact go to Step 6. COMMS [...]

  • Страница 89

    Section 4 Edition 3 Rev G 4-4 5B. Press the to advance to step 5C. 5C. If TC or RTD was selected , then press the to advance to the next parameter , DEGREES C/F . I N P U T S IVx DEGREES C / F ° F Selections ° C, ° F Press the to change, then or to desired choice, then the , or press the Special key directly below the desired choice. IVx RTD TY [...]

  • Страница 90

    Edition 3 Rev G Section 4 4-5 6. Press the to advance to the next parameter , SENSOR BREAK . Press the to advance through the next six prompts. They are six jumper position prompts, non-changeable, and are displayed for information /verification only . The jumper positions are based upon whether the input number is odd/even, input type, and span. R[...]

  • Страница 91

    Section 4 Edition 3 Rev G 4-6 8. If INPUT TYPE/RANGE selected was mA, mV , or VOL T , press the to advance to the next parameter , INPUT RANGE HIGH . 9. If INPUT TYPE/RANGE selected was PULSE , press the to advance to the next parameter , PULSE RA TE HIGH . (Not Y et Available) 10. If INPUT TYPE/RANGE selected was COMMS , press the to advance to th[...]

  • Страница 92

    Edition 3 Rev G Section 4 4-7 1 1. If INPUT TYPE/RANGE selected was COMMS , press the to advance to the next parameter , COMMS REGISTER . 12. If INPUT TYPE/RANGE selected was COMMS , press the to advance to the next parameter , REGIS- TER TYPE . 13. If INPUT TYPE/RANGE selected was mA, mV , or V olt , press the to advance to the next parameter , Vm[...]

  • Страница 93

    Section 4 Edition 3 Rev G 4-8 14. Press the to advance to the next parameter , DISPLA Y UNITS . 15. If DISPLA Y UNITS selected was OTHER , press the to advance to the next parameter , OTHER UNITS . 16. Press the to advance to the next parameter , DECIMAL POSITION . Press the t o change, then to desired choice, then , or press the key directly below[...]

  • Страница 94

    Edition 3 Rev G Section 4 4-9 17. If INPUT TYPE/RANGE selected was not SWITCH CONT ACT , press the to advance to the next parameter , RANGE LIMIT LOW . 18. If INPUT TYPE/RANGE selected was not SWITCH CONT ACT , press the to advance to the next parameter , RANGE LIMIT HIGH . Press the to change, then to desired value, or then , then press . Press th[...]

  • Страница 95

    Section 4 Edition 3 Rev G 4-10 19. If V/mA conversion selected was EXP , press the to advance to the next parameter , EXPONENT . 20. Press the to advance to the next parameter , CUTOFF TYPE . 21. If CUTOFF TYPE selected was other than NONE, press the to advance to the next parameter , CUTOFF V ALUE . Press the to change, then to desired value, then[...]

  • Страница 96

    Edition 3 Rev G Section 4 4-11 22. Press the to advance to the next parameter , INPUT CORRECT 1 (not seen if SWITCH CONT ACT or COM was selected). Press the t o change, to select digit to change, then to desired digit, then press t h e . This will change the correction (left number). Then change the value at which the correction will occur (right n[...]

  • Страница 97

    Section 4 Edition 3 Rev G 4-12 24. Press the to advance to the next parameter , V ALUE FIL TER . 25. Press the to advance to the next parameter , DISPLA Y OPTION . Press the t o change, then or , then to desired value, then press the . IVx DISPLA Y OPTION IN BOTH MODES Selections NOT DISPLA YED IN CONTINUOUS MODE IN SEQUENTIAL MODE IN BOTH MODES IV[...]

  • Страница 98

    Edition 3 Rev G Section 4 4-13 26. If INPUT TYPE/RANGE selected was SWITCH CONT ACT , press the to advance to the next param- eter , OPEN/1 DESCR.. 27. If INPUT TYPE/RANGE selected was SWITCH CONT ACT , press the to advance to the next param- eter , CLOSED/0 DESCR. . Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. Refer to Section[...]

  • Страница 99

    Section 4 Edition 3 Rev G 4-14 28. Press the to advance to the next parameter , DISPLA Y FIL TER . 29. Press the and the display advances to the next input to be programmed. Refer to the beginning of this section, page 4-1. 4.1.2 CONST ANTS Constants are available only when MA TH has been specified and present in the model number order matrix. From[...]

  • Страница 100

    Edition 3 Rev G Section 4 4-15 C O S T A N T S & C U S T O M C U R V E S 2. Press the to advance to the next parameter , V ALUE . 3. Press the and the display advances to the next constant to be programmed. Refer to the beginning of this section, page 4-14. 4.1.3 CUST OM CUR VES Custom Curves are available only when MA TH has been specified and[...]

  • Страница 101

    Section 4 Edition 3 Rev G 4-16 C U S T O M C U R V E S 1. Press the to display CUSTOM CURVE NUMBER . 2. Press the to advance to the next parameter , DECIMAL POSITION OF INPUT . 3. Press the to advance to the next parameter , DECIMAL POSITION OF OUTPUT . CUST OM CURVE NUMBER 1 Selections 1 to 4 Press the to change, then to desired number , then pres[...]

  • Страница 102

    Edition 3 Rev G Section 4 4-17 4. Press the to advance to the next parameter , NUMBER OF POINTS . 5. Press the to advance to the next parameter , POINT P AIR 01 . Press the to change, then to select digit to change, then to desired digit, then press the . This will change the "input" value (left number). Then change the "output"[...]

  • Страница 103

    Section 4 Edition 3 Rev G 4-18 D E R I V E D V A R I A B L E S Repeat this step for each POINT P AIR prompt for mm equal to 03 through 21 (or less). 7. Press the and the display advances to the next custom curve to be programmed. Refer to the begin- ning of this section, page 4-15. 4.1.4 DERIVED V ARIABLES Derived V ariables utilize math to DERIVE [...]

  • Страница 104

    Edition 3 Rev G Section 4 4-19 2. Press the to advance to the next parameter , DISPLA Y T AG . 3. Press the to advance to the next parameter , FUNCTION . For FUNCTION descriptions, refer to the end of this section, Page 4-27. Continue on to next page for additional steps unless NONE was selected, in which case, no other prompts for Derived V ariabl[...]

  • Страница 105

    Section 4 Edition 3 Rev G 4-20 4. Press the to advance to the next parameter , INPUT X . 5. Press the to advance to the next parameter , INPUT X, if it applies. Press the to change, then or as required to pick desired choice, then press the . Press the to change, then or as required to pick desired choice, then press the . D E R I V E D V A R I A B[...]

  • Страница 106

    Edition 3 Rev G Section 4 4-21 6. Press the to advance to the next parameter , INPUT X , if it applies. 7. Press the to advance to the next parameter , INPUT X , if it applies. Press the to change, then or as required to pick desired choice, then press the . Press the to change, then or as required to pick desired choice, then press the . D E R I V[...]

  • Страница 107

    Section 4 Edition 3 Rev G 4-22 8. Press the to advance to the next parameter , INPUT X , if it applies. Press the to change, then or as required to pick desired choice, then press the . D E R I V E D V A R I A B L E S DVxx INPUT X NONE USED Selections NONE USED IV1 IV2 IV3 IV4 IV5 IV6 IV7 IV8 PV1 PV2 PV3 PV4 DV1 DV2 DV3 DV4 DV5 DV6 DV7 DV8 DV9 DV10[...]

  • Страница 108

    Edition 3 Rev G Section 4 4-23 9. Press the to advance to the next parameter , INPUT ACTUA T OR (Only seen if an actuator is required per the FUNCTION specified). Press the to change, then or as required to pick desired choice, then press the . D E R I V E D V A R I A B L E S DVxx INPUT ACTUA T OR NONE / OFF Selections NONE / OFF ON / CONTINUOUS AN[...]

  • Страница 109

    Section 4 Edition 3 Rev G 4-24 10. Press the to advance to the next parameter , RESET ACTUA TOR , (Only seen if a reset actuator is required per the FUNCTION specified). Press the to change, then or as required to pick desired choice, then press the . D E R I V E D V A R I A B L E S DVxx RESET ACTUA T OR NONE / OFF Selections NONE / OFF ON / CONTIN[...]

  • Страница 110

    Edition 3 Rev G Section 4 4-25 Press the to change, then to desired choice, then press the . 1 1. Press the to advance to the next parameter , DISPLA Y UNITS . 12. Press the to advance to the next parameter , UNITS DESCRIP (only seen if OTHER was selected as DISPLA Y UNITS) 13. Press the to advance to the next parameter , DECIMAL POSITION . DVxx DI[...]

  • Страница 111

    Section 4 Edition 3 Rev G 4-26 14. Press the to advance to the next parameter , V ALUE FIL TER . 15. Press the to advance to the next parameter , DISPLA Y OPTION . 16. Press the to advance to the next parameter , DISPLA Y FIL TER . 17. Press the and the display advances to the next derived input to be programmed. Refer to the begin- ning of this se[...]

  • Страница 112

    Edition 3 Rev G Section 4 4-27 DERIVED V ARIABLE FUNCTION T o simplify formulas or make them easier to read, various letters or abbreviations are used for the inputs, such as A, B, X, or TEMP . During configuration, a descriptive prompt will appear on line 1, as specified by "PROMPT :" for each input, while the source of the input is sele[...]

  • Страница 113

    Section 4 Edition 3 Rev G 4-28 4. POL YNOMIAL INPUT 1: X PROMPT : DVxx INPUT X INPUT 2: A PROMPT : DVxx INPUT A INPUT 3: B PROMPT : DVxx INPUT B INPUT 4: C PROMPT : DVxx INPUT C INPUT 5: D PROMPT : DVxx INPUT D ACTUA TOR: n/a RESET : n/a OUTPUT : = A*X**3 + B*X**2 + C*X + D 5. LINEAR MASS FLOW - AGA 3 LINEAER GAS FLOW INPUT 1: F PROMPT : DVxx RAW F[...]

  • Страница 114

    Edition 3 Rev G Section 4 4-29 NOTES: DP - Dif ferential Pressure PRES - Static Pressure - must be ABSOLUTE TEMPF - Flow T emperature - must be degrees F COMP - Compressibility Correction C - Scaling Constant This function converts TEMP from degrees F to degrees R in the equation. 7. RELA TIVE HUMIDITY INPUT 1: DBT PROMPT : DVxx DRY BULB TEMP ° F [...]

  • Страница 115

    Section 4 Edition 3 Rev G 4-30 10. HIGH SELECT and LOW SELECT INPUT 1: A PROMPT : DVxx INPUT A INPUT 2: B PROMPT : DVxx INPUT B ACTUA TOR: n/a RESET : n/a OUTPUT : = HIGHER of A and B for HIGH SELECT = LOWER of A and B for LOW SELECT 1 1. HIGH PEAK INPUT 1: A PROMPT : DVXX INPUT ACTUA TOR: n/a RESET : YES PROMPT : DVxx RESET ACTUA TOR OUTPUT : = HI[...]

  • Страница 116

    Edition 3 Rev G Section 4 4-31 17. CONVERT C TO F INPUT 1: A PROMPT : DVxx INPUT ° C ACTUA TOR: n/a RESET : n/a OUTPUT : = (A * 9/5) +32 18. BTU INPUT 1: F PROMPT : DVxx FLOW INPUT 2: TEMPH PROMPT : DVxx HIGHER TEMP INPUT 3: TEMPL PROMPT : DVxx LOWER TEMP INPUT 4: C PROMPT : DVxx SCALING CONST . ACTUA TOR: n/a RESET : n/a OUTPUT : = C*F* (TEMPH-TE[...]

  • Страница 117

    Section 4 Edition 3 Rev G 4-32 4.1.5 PR OCESS V ARIABLES Process V ariables define variables for use with alarms and/or control outputs From the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASS- WORD appears in the lower display line, the correct "password" will need to be entered before access t[...]

  • Страница 118

    Edition 3 Rev G Section 4 4-33 If selection is NO, proceed to step 3 . If selection is YES: 3. Press the to advance to the next parameter , DISPLA Y T AG . Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. P R O C E S S V A R I A B L E S PVx DISPLA Y T AG PROCESS V AL X Selections T ext Press the to change to the process variable to[...]

  • Страница 119

    Section 4 Edition 3 Rev G 4-34 4. Press the to advance to the next parameter , INPUT TYPE . If NONE USED was selected, no other prompts for PROCESS V ALUE X will be seen. Refer back to step 1, page 4-32. 5. Press the to advance to the next parameter , DISPLA Y UNITS . PVx DISPLA Y UNITS ° F Selections ° C ° F OTHER Press the to change, then to d[...]

  • Страница 120

    Edition 3 Rev G Section 4 4-35 6. If OTHER was selected in DISPLA Y UNITS , press the to advance to the next parameter , OTHER UNITS . 7. Press the to advance to the next parameter , DECIMAL POSITION . 8. Press the to advance to the next parameter , V ALUE FIL TER . Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. Press the to chan[...]

  • Страница 121

    Section 4 Edition 3 Rev G 4-36 9. Press the to advance to the next parameter , DISPLA Y OPTION . 10. Press the to advance to the next parameter , DISPLA Y FIL TER . Press the to change, then to desired choice, then press the . Press the to change, then to desired value, then press the . PVx DISPLA Y FIL TER 0 SECONDS Selections 0 to 9999 seconds P [...]

  • Страница 122

    Edition 3 Rev G Section 4 4-37 1 1. Press the to advance to the next parameter , ALARM 1 TYPE . * When CONTROL LOOP OPEN is selected for ALARM TYPE and NON PID is selected for CONTROL TYPE (CONTROLLERS section of CONFIGURA TION), prompt LOOP ALARM TYPE will be displayed The CONTROL LOOP ALARM is a special alarm which detects faults in the control f[...]

  • Страница 123

    Section 4 Edition 3 Rev G 4-38 12. Press the to advance to the next parameter , ALARM 1 TIME BASE (only seen if Ax1 TYPE is RA TE). 13. Press the to advance to the next parameter , ALARM 1 SAMPLE PERIOD (only seen if Ax1 TYPE is RA TE). 14. Press the to advance to the next parameter , ALARM 1 HYSTERESIS. NOTE: If RA TE Alarm is selected, Hysteresis[...]

  • Страница 124

    Edition 3 Rev G Section 4 4-39 15. Press the to advance to the next parameter , ALARM 2 TYPE . * When CONTROL LOOP OPEN is selected for ALARM TYPE and NON PID is selected for CONTROL TYPE (CONTROLLERS section of CONFIGURA TION), prompt LOOP ALARM TYPE will be displayed 16. Press the to advance to the next parameter , ALARM 2 TIME BASE (only seen if[...]

  • Страница 125

    Section 4 Edition 3 Rev G 4-40 17. Press the to advance to the next parameter , ALARM 2 SAMPLE PERIOD (only seen if Ax2 TYPE is RA TE). 18. Press the to advance to the next parameter , ALARM 2 HYSTERESIS . NOTE: If RA TE Alarm is selected, Hysteresis equals RA TE in units/TIME BASE. 19. Press the to advance to the next parameter , ALARM 3 TYPE . * [...]

  • Страница 126

    Edition 3 Rev G Section 4 4-41 20. Press the to advance to the next parameter , ALARM 3 TIME BASE (only seen if Ax3 TYPE is RA TE). 21. Press the to advance to the next parameter , ALARM 3 SAMPLE PERIOD (only seen if Ax3 TYPE is RA TE). 22. Press the to advance to the next parameter , ALARM 3 HYSTERESIS . NOTE: If RA TE Alarm is selected, Hysteresi[...]

  • Страница 127

    Section 4 Edition 3 Rev G 4-42 23. Press the to advance to the next parameter , ALARM 4 TYPE . * When CONTROL LOOP OPEN is selected for ALARM TYPE and NON PID is selected for CONTROL TYPE (CONTROLLERS section of CONFIGURA TION), prompt LOOP ALARM TYPE will be displayed 24. Press the to advance to the next parameter , ALARM 4 TIME BASE (only seen if[...]

  • Страница 128

    Edition 3 Rev G Section 4 4-43 25. Press the to advance to the next parameter , ALARM 4 SAMPLE PERIOD (only seen if Ax4 TYPE is RA TE). 26. Press the to advance to the next parameter , ALARM 4 HYSTERESIS . NOTE: If RA TE Alarm is selected, Hysteresis equals RA TE in units/TIME BASE. Press the to change, then to desired value, then press the . Ax4 S[...]

  • Страница 129

    Section 4 Edition 3 Rev G 4-44 27. Press the to advance to the next parameter , LOOP ALARM TIME (only seen if CONTROL LOOP OPEN selected as ALARM TYPE and ON/OFF selected as CONTROL TYPE). 28. Press the to advance to the next parameter , ALARM INHIBIT (only seen if an Alarm has been configured). On power-up, an "alarm" condition may occur[...]

  • Страница 130

    Edition 3 Rev G Section 4 4-45 4.1.6 RECORDERS Recorders defines values being recorded, tags, method, source of data and chart divisions and zoning. In the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASSWORD appears in the lower display line, the correct "password" will need to be entered before[...]

  • Страница 131

    Section 4 Edition 3 Rev G 4-46 If selection was NO, proceed to step 3. If selection was YES: 3. Press the to advance to the next parameter , RECORDER T AG . Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. R E C O R D E R S Rx RECORDER T AG Selections T ext Rs COPY FROM RECRDER (0 = INITIAL IZ E) X Recorder to be copied from 0 = F [...]

  • Страница 132

    Edition 3 Rev G Section 4 4-47 4. Press the to advance to the next parameter , V ALUE TO RECORD . If NONE USED was selected, no other prompts for Recorder X will be seen. Refer back to step 1, page 4- 43. 5. Press the to advance to the next parameter , PEN/COLOR . NOTE: Default for Pen varies with Recorder Number: Pen 1 Red, Pen 2 Green, Pen 3 Blue[...]

  • Страница 133

    Section 4 Edition 3 Rev G 4-48 6. Press the to advance to the next parameter , RECORDING METHOD . 7. Press the to advance to the next parameter , DECIMAL POSITION . 8. Press the to advance to the next parameter , CHART DIVISIONS . R E C O R D E R S Rx RECORDING METHOD DRAG - MIN T O MAX Selections INST ANT ANEOUS V ALUES CONNECT THE V ALUES DRAG - [...]

  • Страница 134

    Edition 3 Rev G Section 4 4-49 9. Press the to advance to the next parameter , ZONE 1 LOW . 10. Press the to advance to the next parameter , ZONE 1 HIGH . R E C O R D E R S Rx ZONE 1 LOW DIVISION 0 Selections 0 to 200 Press the to change, then to desired value, then press the . Press the to change, then to desired digit, then to desired value, then[...]

  • Страница 135

    Section 4 Edition 3 Rev G 4-50 1 1. Press the to advance to the next parameter , SP AN 1 LOW . 12. Press the to advance to the next parameter , SP AN 1 HIGH . R E C O R D E R S Press the to change, then then to desired number , then press the . Press the to change, then then to desired number , then press the . Units correspond to Units configured [...]

  • Страница 136

    Edition 3 Rev G Section 4 4-51 13. Press the to advance to the next parameter , SCALE 1 INTER V AL . 14. Press the to advance to the next parameter , ZONE 2 HIGH . Rx SCAL E 1 INTERV AL 10 DIVISIONS Selections 0 to 200 0 = NO SCALES Rx ZONE 2 HIGH DIVISION 0 Selections 0 to 200 0 = SINGLE ZONE R E C O R D E R S Press the to change, then then to des[...]

  • Страница 137

    Section 4 Edition 3 Rev G 4-52 15. Press the to advance to the next parameter , SP AN 2 HIGH (Only if Zone 2 HIGH ≠ 0). 16. Press the to advance to the next parameter , SCALE 2 INTERV AL (Only if Zone 2 HIGH ≠ 0). Rx SCAL E 2 INTERV AL 10 DIVISIONS Selections 0 to 200 0 = NO SCALES Units correspond to Units configured in corresponding V alue to[...]

  • Страница 138

    Edition 3 Rev G Section 4 4-53 17. Press the to advance to the next parameter , POSITION ON ERROR (pen location in Chart Divisions on an ERROR condition). 18. Press the to advance to the next parameter , FIL TER . 19. Press the and the display advances to the next recorder variable to be programmed. Refer to the beginning of this section, page 4-43[...]

  • Страница 139

    Section 4 Edition 3 Rev G 4-54 4.1.7 T O T ALIZERS T otalizers are seen only if T OT ALIZA TION was specified and present in the model number order matrix. From the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASS- WORD appears in the lower display line, the correct "password" will need to be ent[...]

  • Страница 140

    Edition 3 Rev G Section 4 4-55 Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. T O T A L I Z E R S If selection was NO, proceed to step 3. If selection was YES: 3. Press the to advance to the next parameter , DISPLA Y T AG . Tx COPY FROM TOT AL (0 = INITIALIZE) X T otalizer to be copied from 0 = F ACTORY DEF AUL T Press the to cha[...]

  • Страница 141

    Section 4 Edition 3 Rev G 4-56 4. Press the to advance to the next parameter , INPUT V ALUE . If NONE USED was selected, no other prompts for T otalizer X will be seen. Refer back to step 1, page 4- 52. 5. Press the to advance to the next parameter , TIME BASE . Press the to change, then , , as required to desired choice, then press the . Press the[...]

  • Страница 142

    Edition 3 Rev G Section 4 4-57 6. Press the to advance to the next parameter , T OT AL IS FLOW . 7. Press the to advance to the next parameter , DISPLA Y OPTION . 8. Press the to advance to the next parameter , DECIMAL POSITION . Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. T O T A L I Z E R S Tx DECIMAL POSITION 0 Selections 0[...]

  • Страница 143

    Section 4 Edition 3 Rev G 4-58 9. Press the to advance to the next parameter , DISPLA Y OPTION . 10. Press the to advance to the next parameter , DISPLA Y FORMA T . 11. Press the t o advance to the next parameter , TOT ALIZER TYPE . Press the to change, then to desired choice, then press the . Press the to change, then to desired choice, then press[...]

  • Страница 144

    Edition 3 Rev G Section 4 4-59 12. Press the to advance to the next parameter , TOT ALIZER PRESET . Note: Units are that of TOT AL. * T otal Decimal Position 13. Press the to advance to the next parameter , LOW FLOW CUTOFF . Note: Units are that of INPUT (RA TE). If no units were selected, the display will show - NONE -. *Input Decimal Position Pre[...]

  • Страница 145

    Section 4 Edition 3 Rev G 4-60 14. Press the to advance to the next parameter , RESET ACTUA T OR . Press the to change, then , , as required to desired choice, then press the . T O T A L I Z E R S Tx RESET ACTUA TOR NONE / OFF Selections NONE / OFF ON / CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 [...]

  • Страница 146

    Edition 3 Rev G Section 4 4-61 15. Press the to advance to the next parameter , HOLD ACTUA T OR . Press the to change, then , , as required to desired choice, then press the . T O T A L I Z E R S Tx HOLD ACTUA T OR NONE / OFF Selections NONE / OFF ON / CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A[...]

  • Страница 147

    Section 4 Edition 3 Rev G 4-62 16. Press the to advance to the next parameter , PULSED OUTPUT . 17. Press the to advance to the next parameter , PULSE EVER Y (only seen if PULSED OUTPUT select is YES). Note: Units are that of TOT AL. 18. Press the and the display advances to the next totalizer to be programmed. Refer to the beginning of this sectio[...]

  • Страница 148

    Edition 3 Rev G Section 4 4-63 4.1.8 TIMERS T imers are seen only if the MA TH option was specified and present in the model number order matrix. From the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASS- WORD appears in the lower display line, the correct "password" will need to be entered befor[...]

  • Страница 149

    Section 4 Edition 3 Rev G 4-64 Press the to change, then to desired choice, then press the . Press the to change, then to desired value, then press the . 3. Press the to advance to the next parameter , TIMER TYPE . If OFF was selected, no other prompts for TIMER X will be seen, refer back to step 1, page 4-61. 4. Press the to advance to the next pa[...]

  • Страница 150

    Edition 3 Rev G Section 4 4-65 Press the to change, then , , as required to desired choice, then press the . 6. Press the to advance to the next parameter , RESET ACTUA TOR . T I M E R S TMx RESET ACTUA T OR NONE / OFF Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INST[...]

  • Страница 151

    Section 4 Edition 3 Rev G 4-66 Press the to change, then to desired choice, then press the . 7. Press the to advance to the next parameter , DISPLA Y OPTION . 8. Press the and the display advances to the next timer to be programmed. Refer to the beginning of this section, page 4-61. 4.1.9 LEDS In this section, each of the available 8 individual LED[...]

  • Страница 152

    Edition 3 Rev G Section 4 4-67 Press the to change, then , , as required to desired choice, then press the . L E D S 2. Press the to advance to the next parameter , LED ACTUA T OR . 3. Press the and the display advances to the next LED to be programmed. Refer to the beginning of this section, page 4-64. LED x ACTUA TOR NONE / OFF Selections NONE/OF[...]

  • Страница 153

    Section 4 Edition 3 Rev G 4-68 L E D S & R E L A Y S 4.1.10 RELA YS Relays only available when specified and present in the model number order matrix. From the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASS- WORDS appears in the lower display line, the correct "password" will need to be ent[...]

  • Страница 154

    Edition 3 Rev G Section 4 4-69 Press the to change, then , , as required to desired choice, then press the . 3. Press the to advance to the next parameter , RELA Y ACTUA T OR (only available if RELA Y USAGE selected was ST A TE OR ON-OFF or PULSED OUTPUT). R E L A Y S RELA Y x ACTUA TOR NONE / OFF Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PRO[...]

  • Страница 155

    Section 4 Edition 3 Rev G 4-70 Press the to change, then , , as required to desired choice, then press the . 4. Press the to advance to the next parameter , RELA Y T .P . V ALUE (only seen if RELA Y USAGE selected was TIME PROPORTIONING). 5. Press the to advance to the next parameter , CYCLE TIME (only seen if RELA Y USAGE selected is TIME PROPORTI[...]

  • Страница 156

    Edition 3 Rev G Section 4 4-71 4.1.11 CURRENT OUTPUTS Only seen if current outputs has been specified and present in the model number order matrix. From the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASS- WORD appears in the lower display line, the correct "password" will need to be entered bef[...]

  • Страница 157

    Section 4 Edition 3 Rev G 4-72 Press the to change, then to desired choice, then press the . 3. Press the to advance to the next parameter , RANGE LOW . 4. Press the to advance to the next parameter, RANGE HIGH . 5. Press the to advance to the next parameter , OUTPUT RANGE . COx RANGE LOW 0 units Selections ± 999999 COx RANGE HIGH 100 units Select[...]

  • Страница 158

    Edition 3 Rev G Section 4 4-73 6. Press the to advance to the next parameter , OUTPUT ON ERROR . 7. Press the and the display advances to the next current output to be programmed. Refer to the begin- ning of this section, page 4-69. C U R R E N T O U T P U T S Press the t o change, then to desired value, then press the . COx OUTPUT ON ERROR 0 mA Se[...]

  • Страница 159

    Section 4 Edition 3 Rev G 4-74 4.1.12 INSTR UMENT SETTINGS Instrument Settings define instrument tag, display option and date/time format. From the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASS- WORD appears in the lower display line, the correct "password" will need to be entered before acces[...]

  • Страница 160

    Edition 3 Rev G Section 4 4-75 Press the to change, then , , as required to desired choice, then press the . 3. Press the to advance to the next parameter , INSTR. ON ACTUA TOR . I N S T R U M E N T S E T T I N G S INSTR. ON ACTUA TOR ON / CONTINUOUS Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 [...]

  • Страница 161

    Section 4 Edition 3 Rev G 4-76 4. Press the to advance to the next parameter , ALARMING ON ACTUA TOR . Press the to change, then , as required to desired choice, then press the . I N S T R U M E N T S E T T I N G S ALARMING ON ACTUA TOR ON / CONTINUOUS Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A3[...]

  • Страница 162

    Edition 3 Rev G Section 4 4-77 5. Press the key to advance to the next parameter , CONTROL ON ACTUA TOR (only seen on controller). CONTR OL ON ACTUA TOR ON / CONTINUOUS Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A11 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INSTR UMENT ALARM CHART FULL OP INP 1 OP INP 2 OP INP 3[...]

  • Страница 163

    Section 4 Edition 3 Rev G 4-78 6. Press the to advance to the next parameter , DA TE DISPLA Y FORMA T . 7. Press the to advance to the next parameter , TIME DISPLA Y FORMA T . 8. Press the to advance to the next parameter , CURRENT DA TE . Press the to change, then to desired choice, then press the . D A TE DISPLA Y FORMA T MM / DD / YY Selections [...]

  • Страница 164

    Edition 3 Rev G Section 4 4-79 9. Press the to advance to the next parameter , CURRENT DA Y . 10. Press the to advance to the next parameter , CURRENT TIME . 11. Press the to advance to the next parameter , TIME T O LOG DA T A (NOT A V AILABE A T THIS TIME). I N S T R U M E N T S E T T I N G S Press the to change, then , as required to desired choi[...]

  • Страница 165

    Section 4 Edition 3 Rev G 4-80 12. Press the to advance to the next parameter , COMMUNICA TIONS MODE (Only seen if the communi- cations option is present). 13. Press the to advance to the next parameter , COMMS ADDRESS 1 (only seen if SLA VE is selected in COMMUNICA TIONS MODE). 14. Press the to advance to the next parameter , COMM BIT RA TE . I N [...]

  • Страница 166

    Edition 3 Rev G Section 4 4-81 15. Press the to advance to the next parameter , COMMS P ARITY . 16. Press the to advance to the next parameter , INPUT SCAN SEQUENCE The input scan rate is programmable and dependant on the number of active inputs present. The total scans per second for the instrument is 16 scans/second, and the instrument can have u[...]

  • Страница 167

    Section 4 Edition 3 Rev G 4-82 DERIVED ACTUA TOR 1 Selections 1 to 24 Press the to change, then to desired number , then press the . 17. Press the and the display advances to INSTRUMENT T AG . T o exit, press the . Refer to the beginning of this section, page 4-72. 4.1.13 DERIVED A CTU A T ORS Derived Actuators are used when two or more actuators n[...]

  • Страница 168

    Edition 3 Rev G Section 4 4-83 2. Press the to advance to the next parameter , COPY/INITIALIZE . Choose YES if the parameters to be programmed are the same as another DERIVED ACTUA TOR already programmed. If selection was NO, proceed to step 3. If selection was YES: D E R I V E D A C T U A T O R S Press the to change, then to desired choice, then p[...]

  • Страница 169

    Section 4 Edition 3 Rev G 4-84 3. Press the to advance to the next parameter , ITEM 1 . Repeat the ITEM prompt as needed to configure the items necessary to form the desired logic equation. D E R I V E D A C T U A T O R S Press the to change, then , as required to desired choice, then press the . DAxx ITEM 1 Selections END OR AND NOT ( ) ANY ALARM [...]

  • Страница 170

    Edition 3 Rev G Section 4 4-85 4. Press the and the display advances to the next derived actuator to be programmed. Refer to the beginning of this section, page 4-80. 4.1.14 OPERA T OR INPUTS Operator Inputs are prompts programmed that allow these prompts to turn on or off actuators that control some other function within the instrument. From the N[...]

  • Страница 171

    Section 4 Edition 3 Rev G 4-86 Choose YES if the parameters to be programmed are the same as another OPERA TOR INPUT already pro- grammed. If selection was NO, proceed to step 3. If selection was YES: 3. Press the to advance to the next parameter , PROMPT TEXT . If TEXT not entered, no other prompt in OPERA TOR INPUTS will be seen. Refer back to st[...]

  • Страница 172

    Edition 3 Rev G Section 4 4-87 4. Press the to advance to the next parameter , OFF ST A TE TEXT . 5. Press the to advance to the next parameter , ON ST A TE TEXT . 6. Press the to advance to the next parameter , ACTUA TION STYLE . Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. Refer to Section 3.4.2 Changing T ext, page 3-3 for i[...]

  • Страница 173

    Section 4 Edition 3 Rev G 4-88 7. Press the to advance to the next parameter , POWER UP ST A TE . 8. Press the to advance to the next parameter , WHEN DISPLA YED . 9. Press the and the display advances to the next operator input to be programmed. Refer to the beginning of this section, page 4-81. Press the to change, then to desired choice, then pr[...]

  • Страница 174

    Edition 3 Rev G Section 4 4-89 4.1.15 OPERA T OR MESSA GES Operator Messages are user defined messages to advise or provide information, via the display , that selected actuators are active. From the Normal Display , press the until CONFIGURA TION is seen in the lower display line. If P ASS- WORD appears in the lower display line, the correct "[...]

  • Страница 175

    Section 4 Edition 3 Rev G 4-90 If selection was NO, proceed to step 3. If selection was YES: Press the to change to the desired operator message to be copied from. OMxx COPY FROM OM (0 = INITIALI ZE) 1 Operator Message to be copied from 0 = F ACTORY DEF AUL T O P E R A T O R M E S S A G E S[...]

  • Страница 176

    Edition 3 Rev G Section 4 4-91 Press the to change, then , as required to desired choice, then press the . 3. Press the to advance to the next parameter , ACTUA TOR . O P E R A T O R M E S S A G E S OMxx ACTUA T OR NONE / OFF Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A[...]

  • Страница 177

    Section 4 Edition 3 Rev G 4-92 Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. OMxx DISPLA Y MODE PREEMPT Selections PREEMPT PREEMPT T O CYCLIC PREEMPT T O OFF CYCLIC BACKGROUND Press the to change, then to desired choice, then press the . OMxx LINE 2 TEXT Selection[...]

  • Страница 178

    Edition 3 Rev G Section 4 4-93 Press the to change, then to desired number , then press the . CHAR T MESSAGE NUMBER 1 Selections 1 to 12 CMxx COPY / INITIALIZE NO Selections NO YES Press the to change, then to desired choice, then press the . 7. Press the and the display advances to the next operator message to be programmed. Refer to the beginning[...]

  • Страница 179

    Section 4 Edition 3 Rev G 4-94 Press the to change to the desired chart message to be copied from. CMxx COPY FROM CM (0 = INITIAL IZE) 1 Chart Message to be copied from 0 = F ACTORY DEF AUL T Choose YES if the parameters to be programmed are the same as another CHAR T MESSAGE already pro- grammed. If selection is NO, proceed to step 3. If selection[...]

  • Страница 180

    Edition 3 Rev G Section 4 4-95 Press the to change, then , as required to desired choice, then press the . 3. Press the to advance to the next parameter , ACTUA TOR . C H A R T M E S S A G E S CMxx ACTUA TOR NONE / OFF Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INST[...]

  • Страница 181

    Section 4 Edition 3 Rev G 4-96 Press the to change, then to desired choice, then press the . 4. Press the to advance to the next parameter , PEN/COLOR . 5. Press the to advance to the next parameter , MESSAGE TEXT . C H A R T M E S S A G E S CMxx PEN / COLOR RED Selections BLUE GREEN RED BLACK VIOLET Refer to Section 3.4.2 Changing T ext, page 3-3 [...]

  • Страница 182

    Edition 3 Rev G Section 4 4-97 6. Press the to advance to the next parameter , V ALUE 1 . 7. Press the to advance to the next parameter , V ALUE 2 . Press the to change, then , as required to desired choice, then press the . Press the to change, then , as required to desired choice, then press the . CMxx V ALUE 1 NONE USED Selections NONE USED IV1 [...]

  • Страница 183

    Section 4 Edition 3 Rev G 4-98 8. Press the to advance to the next parameter , V ALUE 3 . 9. Press the to advance to the next parameter , V ALUE 4 . Press the to change, then , as required to desired choice, then press the . Press the to change, then , as required to desired choice, then press the . CMxx V ALUE 3 NONE USED Selections NONE USED IV1 [...]

  • Страница 184

    Edition 3 Rev G Section 4 4-99 CMxx TIME / DA TE ST AMP NO Selections YES NO 10. Press the to advance to the next parameter , TIME/DA TE ST AMP . 11. Press the to advance to the next parameter , CMSS ORIENT A TION. 12. Press the and the display advances to the next chart message to be programmed. Refer to the beginning of this section, page 4-89. 4[...]

  • Страница 185

    Section 4 Edition 3 Rev G 4-100 Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. SVx TYPE OFF Selections OFF SIN W A VE SA WTOOTH SQUARE W A VE SPIKES 1. Press the to display SV NUMBER . 2. Press the to advance to the next parameter , DISPLA Y T AG . 3. Press the to advance to the next parameter , TYPE . S I M U L A T E D V A R I A[...]

  • Страница 186

    Edition 3 Rev G Section 4 4-101 If OFF was selected, no other prompts for SIMULA TED V ARIABLES X will be seen. Refer back to step 1, page 4-97. 4. Press the to advance to the next parameter , DISPLA Y UNITS . 5. If DISPLA Y UNITS selected was OTHER , press the to advance to the next parameter , OTHER UNITS . 6. Press the to advance to the next par[...]

  • Страница 187

    Section 4 Edition 3 Rev G 4-102 7. Press the to advance to the next parameter , RANGE LOW . 8. Press the to advance to the next parameter , RANGE HIGH. Units correspond to Units configured in Simulated V ariable S I M U L A T E D V A R I A B L E S SVx RANGE HIGH 100 units Selections ± 999999 (decimal position = 0) ± 9.9999 (decimal position = 4) [...]

  • Страница 188

    Edition 3 Rev G Section 4 4-103 SVx DISPLA Y OPTION IN BOTH MODES Selections NOT DISPLA YED IN CONTINUOUS MODE IN SEQUENTIAL MODE IN BOTH MODES S I M U L A T E D V A R I A B L E S SVx PERIOD (1 / FREQ.) 60 MINUTES Selections 1 to 1440 9. Press the to advance to the next parameter , PERIOD. 10. Press the to advance to the next parameter , DISPLA Y O[...]

  • Страница 189

    Edition 3 Rev G Section 5 5-1 Section 5 - Display Programming Selections made in the Display prompts section determine what is displayed and how it is displayed. From the Normal Display , press the . If the Display prompts are disabled, when the DISP key is pressed, DISPLA Y KEY DISABLED will appear in the lower display line. Refer to Section 9, En[...]

  • Страница 190

    Edition 3 Rev G 5-2 Section 5 3. When this prompt is displayed with the AUT OMA TIC/MANUAL choice, if the associated controller is configured for PID control and is in the manual mode, pressing the DOWN key will display the prompts below: Note: The controller may have its manual actuator set to something other than CAxFn, and in this case the promp[...]

  • Страница 191

    Edition 3 Rev G Section 5 5-3 T o change the setpoint, press the key , then keys to desired setpoint, then press the key . T o exit, press the key . 5. Following the top level Setpoint Prompt, if any controllers are configured for PID control and are in manual mode, the following prompt will appear: SELECT MANUAL V ALUES This prompt provides an alt[...]

  • Страница 192

    Edition 3 Rev G 5-4 Section 5 6. Following the top level Manual V alues prompts, the "Standard Display" prompts are displayed as follows: DISPLA Y MODE CONTINUOUS SEQUENCE AMM used, default CONTINUOUS DISPLA Y FORMA T 1 V AL 2 V ALS 4 V ALS AMM used, default 1 V AL SEQUENTIAL DISPLA Y DURA TION n SECONDS SEQUENCE, AMM used, default 1 7. I[...]

  • Страница 193

    Edition 3 Rev G Section 6 6-1 Section 6 - Chart Prompts From the Normal Display , press the . If the Chart Prompts are disabled, when the CHART key is pressed, CHART KEY DISABLED will appear in the lower display . Refer to Section 9, Enables & Passwords, for instruc- tions to enable Chart Prompts. If the Chart Prompts are not disabled BUT the p[...]

  • Страница 194

    Section 6 Edition 3 Rev G 6-2 6. Upon selection of YES , the chart is initialized and the unit exits to the NORMAL DISPLA Y if Chart Rotation and T rend Data Collect are ON. If either Chart Rotation or Trend Data Collect are OFF , after the initialization message, the unit will display CHART ROT A TION OFF and/or TREND DA T A COLLECT OFF , as appli[...]

  • Страница 195

    Edition 3 Rev G Section 6 6-3 3. Press the to advance to the next parameter , CHART T AG . 4. Press the to advance to the next parameter , NORMAL SPEED . 5. Press the to advance to the next parameter , NORMAL SPEED (only seen if NORMAL SPEED selected was OTHER). Refer to Section 3.4.2 Changing T ext, Page 3-3, for instructions. NORMAL SPEED 24 HOUR[...]

  • Страница 196

    Section 6 Edition 3 Rev G 6-4 6. Press the to advance to the next parameter , MAJOR TIME PERIODS . 7. Press the to advance to the next parameter , MINOR TIME PERIODS . 8. Press the to advance to the next parameter , BLANK MAJOR PERIODS . Press the to change, then to desired digit, then to desired value, then press the . MAJOR TIME PERIODS 24 Select[...]

  • Страница 197

    Edition 3 Rev G Section 6 6-5 9. Press the to advance to the next parameter , MAJOR LINE PEN/COLOR . 10. Press the to advance to the next parameter, MAJOR LINE PEN/COLOR (only seen if MAJOR LINE PEN/COLOR selected was SELECT A COLOR). MAJOR LINE PEN / COLOR MA TCH SCALE COLOR Selections MA TCH SCALE COLOR SELECT A COLOR Press the to change, then to[...]

  • Страница 198

    Section 6 Edition 3 Rev G 6-6 1 1. Press the to advance to the next parameter , MINOR LINE PEN/COLOR . 12. Press the to advance to the next parameter , MINOR LINE PEN/COLOR (only seen if MINOR LINE PEN/COLOR selected was SELECT A COLOR). MINOR LINE PEN / COLOR MA TCH SCALE COLOR Selections MA TCH SCALE COLOR SELECT A COLOR Press the to change, then[...]

  • Страница 199

    Edition 3 Rev G Section 6 6-7 13. Press the to advance to the next parameter , TIME PEN/COLOR . 14. Press the to advance to the next parameter , DA TE/PEN COLOR . Press the to change, then to desired choice, then press the . Press the to change, then to desired choice, then press the . TIME PEN / COLOR RED Selections BLUE GREEN RED BLACK VIOLET Not[...]

  • Страница 200

    Section 6 Edition 3 Rev G 6-8 15. Press the to advance to the next parameter , CHART T AG PEN/ COLOR. 16. Press the to advance to the next parameter , ACTION ON NEW CHART . 17. Press the to advance to the next parameter, ST OP AFTER 1 REV . ST OP AFTER 1 REV NO Selections NO YES Press the to change, then to desired choice, then press the . CHAR T T[...]

  • Страница 201

    Edition 3 Rev G Section 6 6-9 Press the to change, then , to desired choice, then press the . 18. Press the to advance to the next parameter , ROT A TE CHART ACTUA TR . ROT A TE CHART ACTUA TR CHART ROT A TION Selections NONE / OFF ON / CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INSTRUMEN[...]

  • Страница 202

    Section 6 Edition 3 Rev G 6-10 Press the to change, then , to desired choice, then press the . 19. Press the to advance to the next parameter , COLLECT DA T A ACTUA TR . COLLECT DA T A ACTUA TR CHART ROT A TION Selections NONE / OFF ON / CONTINUOUS ANY ALARM ANY PROCESS ALARM A1 1 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INSTRUME[...]

  • Страница 203

    Edition 3 Rev G Section 6 6-11 CHART ROT A TION PROMPT DISPLA YED Selections PROMPT NOT DISPLAYED PROMPT DISPLA YED TREND DA T A COLLECT PROMPT NOT DISPLA YED Selections PROMPT NOT DISPLAYED PROMPT DISPLA YED CHART SPEED PROMPT PROMPT NOT DISPLA YED Selections PROMPT NOT DISPLAYED PROMPT DISPLA YED Press the to change, then to desired choice, then [...]

  • Страница 204

    Edition 3 Rev G Section 7 7-1 Section 7 - Alarm Settings Selections made in Alarm Settings determine the setpoints (or RA TE if RA TE alarm selected) of each alarm configured in the Process V ariables section of the Configuration section in System Prompts. From the Normal Display , press the until ALARM SETTINGS appears in the lower display line. I[...]

  • Страница 205

    Section 7 Edition 3 Rev G 7-2 3. Press the to advance to the next parameter , ALARM 2 SETPOINT . If RA TE Alarm was selected, setpoint refers to RA TE. 4. Press the to advance to the next parameter , ALARM 3 SETPOINT . If RA TE Alarm was selected, setpoint refers to RA TE. Units correspond to Units configured in Process V ariables with per unit tim[...]

  • Страница 206

    Edition 3 Rev G Section 7 7-3 5. Press the to advance to the next parameter , ALARM 4 SETPOINT . If RA TE Alarm was selected, setpoint refers to RA TE. 6. Press the and the display advances to the next applicable ALARMS FOR PV NUMBER prompt. Refer to the beginning of this section, page 7-1. Units correspond to Units configured in Process V ariables[...]

  • Страница 207

    Edition 3 Rev G Section 8 8-1 Section 8 - Action Time Settings Action T ime Settings are simply TIME/DA TE settings that can be used to initiate a desired action. Selections made in Action T ime Settings are used to generate actuators TIME 1, TIME/DA TE 1, TIME 2, TIME/DA TE 2, TIME 1 T O TIME 2, and TIME/DA TE 1 TO 2. The TIME 1 and TIME 2 actuato[...]

  • Страница 208

    Section 8 Edition 3 Rev G 8-2 2. Press the to advance to the next parameter , TIME 1 . 3. Press the to advance to the next parameter , DA TE 1 . Press the to change, then , to desired value, then press t h e . Change and enter each portion of the time. Press the to change, then , to desired value, then press t h e . Change and enter each portion of[...]

  • Страница 209

    Edition 3 Rev G Section 8 8-3 4. Press the to advance to the next parameter , TIME 2 T AG . 5. Press the to advance to the next parameter , TIME 2 . Refer to Section 3.4.2 Changing T ext, page 3-3 for instructions. Press the to change, then , to desired value, then press t h e . Change and enter each portion of the time. TIME 2 T AG ST OP TIME Sele[...]

  • Страница 210

    Section 8 Edition 3 Rev G 8-4 6. Press the to advance to the next parameter , DA TE 2 . 7. Press the to advance to the next parameter , DA Y OF WEEK ACTUA TOR . Day of Week Actuator works in conjunction with the CURRENT DA Y entry under INSTRUMENT SETTINGS, page 4-76. The DA Y OF WEEK ACTUA T OR will be active if the day selected matches the curren[...]

  • Страница 211

    Edition 3 Rev G Section 8 8-5 Press the to change, then to desired choice, then press the . TIME DISPLA Y OPTION NOT DISPLA YED Selections NOT DISPLA YED IN CONTINUOUS MODE IN SEQUENTIAL MODE IN BOTH MODES 8. Press the to advance to the next parameter , DA Y OF OF MONTH ACTUA TOR . Day of Month Actuator works according to the days numerical date. F[...]

  • Страница 212

    Edition 3 Rev G Section 9 9-1 Section 9 - Enables & Passwords Enables and Passwords provides a means of enabling or disabling prompt sections and provides additional operational security with the use of 6 digit password. If the Display prompts or Chart prompts are disabled, those prompt sections will not be accessible and DISPLA Y KEY DISABLED [...]

  • Страница 213

    Section 9 Edition 3 Rev G 9-2 2. Press the to advance to the next parameter , ACTION TIME SETTINGS . 3. Press the to advance to the next parameter , PROFILE ENTR Y (Only on Profiles). 4. Press the to advance to the next parameter , PROFILE CONTROL (Only on Profiles) . ACTION TIME SETTINGS Selections DISABLED ENABLED Press the to change, then , to d[...]

  • Страница 214

    Edition 3 Rev G Section 9 9-3 A LARM SETTINGS Selections DISABLED ENABLED . 5. Press the to advance to the next parameter , ALARM SETTINGS . 6. Press the to advance to the next parameter , TUNING P ARAMETERS (only seen if CONTROLLER). 7. Press the to advance to the next parameter , SETPOINT CHANGES (only seen if CONTROLLER). TUNING P ARAMETERS Sele[...]

  • Страница 215

    Section 9 Edition 3 Rev G 9-4 8. Press the to advance to the next parameter , CONFIGURA TION . 9. Press the to advance to the next parameter , DERIVED ACTUA TORS . 10. Press the to advance to the next parameter , OPERA TOR INPUTS CONFIGURA TION . OPERA T OR INPUTS CONF Selections DISABLED ENABLED Press the to change, then , to desired choice, then [...]

  • Страница 216

    Edition 3 Rev G Section 9 9-5 1 1. Press the to advance to the next parameter , OPERA T OR MESSAGES . 12. Press the to advance to the next parameter , CHART MESSAGES . 13. Press the to advance to the next parameter , SIMULA TED V ARIABLES . Press the to change, then , to desired choice, then press the . OPERA T OR MESSA GES Selections DISABLED ENAB[...]

  • Страница 217

    Section 9 Edition 3 Rev G 9-6 14. Press the to advance to the next parameter , TEST . 15. Press the to advance to the next parameter , CALIBRA TION . 16. Press the to advance to the next parameter , CHART PROMPTS . CHAR T PROMPTS Selections DISABLED ENABLED Press the to change, then , to desired choice, then press the . TEST Selections DISABLED ENA[...]

  • Страница 218

    Edition 3 Rev G Section 9 9-7 17. Press the to advance to the next parameter , CHART CONFIGURA TION . 18. Press the to advance to the next parameter , DISPLA Y PROMPTS . 19. Press the to advance to the next parameter , OPERA TOR INPUTS . CHAR T CONFIGURA TION Selections DISABLED ENABLED Press the to change, then , to desired choice, then press the [...]

  • Страница 219

    Section 9 Edition 3 Rev G 9-8 20. Press the to advance to the next parameter , CONTROL ST A TE ACCESS (only seen if CONTROL- LER) 21. Press the to advance to the next parameter , SYSTEM PROMPTS P ASSWORD . 22. Press the to advance to the next parameter , ENABLES & P ASSWORDS P ASSWORD . Press the to change, then , to desired value, then press t[...]

  • Страница 220

    Edition 3 Rev G Section 9 9-9 Press the to change, then , to desired value, then press the . DISPLA Y PROMPTS P ASSWORD 0 Selections 0 to 999999 (0=No password protection) Press the to change, then , to desired value, then press the . CHART PROMPTS P ASSWORD 0 Selections 0 to 999999 (0=No password protection) 23.Press the to advance to the next par[...]

  • Страница 221

    Edition 3 Rev G Section 10 10-1 Section 10 - T est T est describes all possible diagnostic tests built into the recorder . From the Normal Display , depress the until TESTS appears in the lower display line. If P ASSWORD appears in the lower display line, the correct "password" will need to be entered before access to T est is allowed. If[...]

  • Страница 222

    Edition 3 Rev G 10-2 Section 10 10.1 RELA Y TEST Allows the operator to verify that the LEDs, Relay and/or SSRD output(s) is/are working. A V olt/Ohm meter will be required to test the output. Step 1 With RELA Y in the lower display line, depress the and INITIA TE RELA Y TEST appears in the upper display line and NO appears in the lower display lin[...]

  • Страница 223

    Edition 3 Rev G Section 10 10-3 10.3 KEYP AD TEST Allows the operator to verify that the keypad is functional. No test equipment is required to perform this test. Step 1 With KEYP AD in the lower display line, depress the and INITIA TE KEYP AD TEST appears in the upper display line and NO appears in the lower display line. Depress , select YES, the[...]

  • Страница 224

    Edition 3 Rev G 10-4 Section 10 10.5 CHART DEMONSTRA TION Allows the user to demonstrate the chart capabilites. CAUTION: When this "TEST" is intiated, any parameter values previously programmed will be replaced with the demonstration values. Step 1 With CHART DEMONSTRA TION in the lower display line, depress the , INITIA TE CHART DEMO app[...]

  • Страница 225

    Edition 3 Rev G Section 10 10-5 Step 4 The current output reading should be equal to the displayed value. Step 5 T o exit the test, depress the and the instrument will return to the normal display .[...]

  • Страница 226

    Edition 3 Rev G Section 1 1 11-1 Section 11 - Calibration Calibration describes all possible field calibration procedures for the recorder as well as methods of invoking default program and calibration values. The procedures described include the input and range calibration as well as chart calibration. From the Normal Display , press the until CAL[...]

  • Страница 227

    Edition 3 Rev G 11-2 Section 11 1 1.1 INPUT CALIBRA TION This routine allows for the calibration of all input channels and all input types. Important Notes: 1. The calibration information is stored on each input board for all input types in an Electrically Erasable Programmable Read Only Memory (EEPROM). The instrument and every input board supplie[...]

  • Страница 228

    Edition 3 Rev G Section 1 1 11-3 Step 4 Be sure that the jumpers on the Input Board for the Input being calibrated are positioned as shown in T able 1 1-3, and Figure 1 1-1 or T able 1 1-3A and Figure 1 1-1A, depending on which circuit board is fitted. T ABLE 1 1-3 INPUT BOARD JUMPER POSITIONS INPUT 1, 3, 5, 7 INPUT 2, 4, 6, 8 JU1 JU2 JU3 JU7 JU1 1[...]

  • Страница 229

    Edition 3 Rev G 11-4 Section 11 When installing an Input Board for any reason, check the location (where this board is mounted), then verify the position of JU13 and/or JU14. TC WIDE or TC NARROW were selected, go to Step 5, if not, go to Step 6. Step 5 Depress the and the upper display line will show IVx CAL CJC OR TC and the lower display line wi[...]

  • Страница 230

    Edition 3 Rev G Section 1 1 11-5 Step 8 Repeat steps 1 through 8 for each input to be calibrated. 1 1.2 COLD JUNCTION CALIBRA TION Step 1 With INPUT CALIBRA TION on the lower display line, press the to enter the Input Calibration. The upper display will display CALIBRA TE INPUT and the lower display line will display IV1 . If other than IV1 or IV2 [...]

  • Страница 231

    Edition 3 Rev G 11-6 Section 11 Step 7 Connect the proper TC type up to the input being calibrated. Place the thermometer next to the HOT Junction (sensor point) of the TC connected. Depress the and the upper display line will display IVx CAL CJC and lower display line will display CJC READS: 25.0 C . Depress the , then use the UP/DOWN to change th[...]

  • Страница 232

    Edition 3 Rev G Section 1 1 11-7 CHART Will place a dot on the inner or outer ring, whichever is selected for calibration SCROLL Will select either the inner or outer ring UP Will move the selected (inner or outer) ring position to the left and print a dot in the new position without moving the chart. DOWN Will move the selected (inner or outer) ri[...]

  • Страница 233

    Edition 3 Rev G 11-8 Section 11 Step 2 Connect the milliamp meter across the corresponding output terminals observing proper polarity , terminal 1 is positive. Step 3 Depress and INITIA TE mA CAL appears in the upper display line and NO appears in the lower display line. Depress select YES, then depress . Step 4 The display should be flashing the m[...]

  • Страница 234

    Edition 3 Rev G Section 1 1 11-9 Step 1 With CALIBRA TION DEF AUL TS in the lower display line, depress the . SET CAL DEF AUL TS appears in the upper display line and NO appears in the lower display line. Step 2 Depress and then select YES, then depress .[...]

  • Страница 235

    Edition 3 Rev G Section 13 13-1 SECTION 13 - CONTROLLERS When the instrument is specified with the Controller option, in addition to the normal configuring required for the Recorder functions, other parameters such as CONTROLLERS, SETPOINTS, and TUNING P ARAMETERS will need to be configured in order for the instrument to operate properly . Along wi[...]

  • Страница 236

    Section 13 Edition 3 Rev G 13-2 Up to 8 setpoints can be configured. Each has a variable text prompt, units, decimal position, limits, and “normal display” display option. Whenever the PROMPT TEXT , as configured in SETPOINTS, is not blank, the setpoint will be displayed in the key prompts. The setpoints are not inherently associated with a con[...]

  • Страница 237

    Edition 3 Rev G Section 13 13-3 T o utilize the CONTROL ST A TE ACCESS capability and select either AUTOMA TIC or MANUAL control, proceed as follows: From the “Normal Display”, depress the key , CONTROLLER 1 should be displayed on the upper display line (or what was configured for CA1 LINE 1 TEXT above) and A/M should be displayed on the lower [...]

  • Страница 238

    Section 13 Edition 3 Rev G 13-4 2. Press the to advance to the next parameter , COPY/INITIALIZE. Cx COPY/INITIALIZE NO Selections YES or NO If selection is NO, see Step 3. If selection is YES: Cx COPY FROM CONTRLR (0=INITIALIZE) X Input to be copied from 0=F ACT ORY DEF A UL T 3. Press the to advance to the next parameter , CONTROL TYPE. Cx CONTR O[...]

  • Страница 239

    Edition 3 Rev G Section 13 13-5 CASCADE control uses two “control blocks”. The output of one controller is the setpoint of a second controller . Ratio and bias (see Steps 20 & 21) need to be applied to the connecting setpoint. Because of the interaction between controllers, cascade control will only apply to controllers 1 and 2, or 3 and 4,[...]

  • Страница 240

    Section 13 Edition 3 Rev G 13-6 6. Press the to advance to the next parameter, OUTPUT 1 HYSTERESIS (only seen if OUT 1 TYPE is ON/OFF). NO TE: Units correspond to Units configured in Process V ariables Cx OUT 1 HYSTERESIS 3 UNITS Selections 0 to 999999 (decimal position = 0) 0 to 9.9999 (decimal position = 4) 7. Press the to advance to the next par[...]

  • Страница 241

    Edition 3 Rev G Section 13 13-7 9. Press the to advance to the next parameter , OUTPUT 2 PERCENT UPPER LIMIT (only seen if OUT 2 TYPE is PID). Cx OUT 2 PERCENT UPPER LIMIT 100% Selections 1 to100 10.Press the to advance to the next parameter , OUTPUT 1 PERCENT ON ERROR (only seen if OUT 1 TYPE is PID). Cx OUT 1 PERCENT ON E RROR 0% Selections 1 to1[...]

  • Страница 242

    Section 13 Edition 3 Rev G 13-8 12.Press the to advance to the next parameter , OUTPUT SLEW RA TE (only available with PID). Cx OUTPUT SLEW RA TE 0% / M IN Selections 0 to100% 0 = OFF SLEW RA TE allows the control to slowly ramp the output to avoid a rapid start up. Abrupt changes may set the outputs to 0%. If the slew rate is programmed to 60%/MIN[...]

  • Страница 243

    Edition 3 Rev G Section 13 13-9 13.Press the to advance to the next parameter , MANUAL ACTUA TOR (only if either output is proportional) Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A11 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INSTR UMENT ALARM CHART FULL OP INP 1 OP INP 2 OP INP 3 OP INP 4 OP INP 5 OP INP 6 OP I[...]

  • Страница 244

    Section 13 Edition 3 Rev G 13-10 14.Press the to advance to the next parameter , AUTO MANUAL AUT O TRANSFER (only if MANUAL ACTUA TOR is not NONE/OFF). Cx A UT O M/A TRANSFER OFF Selections OFF ON NO TE: If the pr ocess variable reaches setpoint while in manual mode, this parameter , when selected, allows the contr oller to revert to automatic mode[...]

  • Страница 245

    Edition 3 Rev G Section 13 13-11 16.Press the to advance to the next parameter , REMOTE SETPOINT ACTUA T OR. Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A11 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INSTR UMENT ALARM CHART FULL OP INP 1 OP INP 2 OP INP 3 OP INP 4 OP INP 5 OP INP 6 OP INP 7 OP INP 8 OP INP 9 OP IN[...]

  • Страница 246

    Section 13 Edition 3 Rev G 13-12 17.Press the to advance to the next parameter , REMOTE SETPOINT SOURCE (only if REMOTE SP ACTUA TOR is not NONE/OFF). Cx REMO TE SP SOURCE NONE USED Selections NONE USED IV1 IV2 IV3 IV4 IV5 IV6 IV7 IV8 PV1 PV2 PV3 PV4 D V1 D V2 D V3 D V4 D V5 D V6 D V7 D V8 D V9 D V10 D V11 D V12 CV1 CV2 CV3 CV4 CV5 CV6 CV7 CV8 CV9 [...]

  • Страница 247

    Edition 3 Rev G Section 13 13-13 18.Press the to advance to the next parameter , SECOND SETPOINT ACTUA T OR. Selections NONE/OFF ON/CONTINUOUS ANY ALARM ANY PROCESS ALARM A11 A12 A13 A14 A21 A22 A23 A24 A31 A32 A33 A34 A41 A42 A43 A44 INSTR UMENT ALARM CHART FULL OP INP 1 OP INP 2 OP INP 3 OP INP 4 OP INP 5 OP INP 6 OP INP 7 OP INP 8 OP INP 9 OP IN[...]

  • Страница 248

    Section 13 Edition 3 Rev G 13-14 19.Press the to advance to the next parameter , SECOND SETPOINT SOURCE (only if SECOND SP ACTUA TOR is not NONE/OFF). Cx SECOND SP SOURCE NONE USED Selections NONE USED IV1 IV2 IV3 IV4 IV5 IV6 IV7 IV8 PV1 PV2 PV3 PV4 D V1 D V2 D V3 D V4 D V5 D V6 D V7 D V8 D V9 D V10 D V11 D V12 CV1 CV2 CV3 CV4 CV5 CV6 CV7 CV8 CV9 C[...]

  • Страница 249

    Edition 3 Rev G Section 13 13-15 21.Press the to advance to the next parameter , REMOTE SETPOINT BIAS. Cx REMO TE SP BIAS 0 NO TE: Bias is applied to the remote setpoint before it is used, and to the output of the first contr oller in cascade mode, bef ore it is used as the setpoint of the second controller . Bias is an offset added to the output. [...]

  • Страница 250

    Section 13 Edition 3 Rev G 13-16 23.Press the to advance to the next parameter , FEEDFOR W ARD HIGH (only if FEEDFORW ARD was selected as CONTROL TYPE). Cx FEEDFOR W ARD HIGH 100 Selections ± 999999 (decimal position = 0) ± 9.9999 (decimal position = 4) 24.Press the to advance to the next parameter , FEEDFORW ARD LOW (only if FEEDFORW ARD was sel[...]

  • Страница 251

    Edition 3 Rev G Section 13 13-17 26.Press the to advance to the next parameter , DISPLA Y RAMPED SETPOINT . Cx DISPLA Y RAMPED SP NO T DISPLA YED Selections NO T DISPLA YED IN CONTINOUS MODE IN SEQUENTIAL MODE IN BO TH MODES 27.Press the to advance to the next parameter , DISPLA Y % OUTPUTS (only if either output is propor- tional). Cx DISPLA Y % O[...]

  • Страница 252

    Section 13 Edition 3 Rev G 13-18 13.2 CONTROL SETPOINTS There are 8 Control Setpoints that can be configured in the SETPOINTS section of CONFIGURA TION. This menu sets the text prompt for the setpoint, the unit type, decimal position, limits and the display option mode. Setting and/or changing the setpoints is accomplished via the prompt section. I[...]

  • Страница 253

    Edition 3 Rev G Section 13 13-19 2. Press the to advance to the next parameter , PROMPT TEXT . SPx PR OMPT TEXT SETPOINT 1 Selections TEXT Note: If PROMPT TEXT is blank, the corresponding setpoint will not be activated or appear in the prompts associ- ated with the key . Also, no other prompts are displayed for configuring the setpoint. 3. Press th[...]

  • Страница 254

    Section 13 Edition 3 Rev G 13-20 5. Press the to advance to the next parameter , DECIMAL POSITION. SPx DECIMAL POSITION 0 Selections 0 to 4 6. Press the to advance to the next parameter , UPPER LIMIT . SPx UPPER LIMIT 100 UNITS Units correspond to units configured in Steps 3 or 4 above. Selections ± -999999 (decimal position=0) ± -9.9999 (decimal[...]

  • Страница 255

    Edition 3 Rev G Section 13 13-21 8. Press the to advance to the next parameter , DISPLA Y OPTION. SPx DISPLA Y OPTION NO T DISPLA YED Selections NO T DISPLA YED IN CONTINUOUS MODE IN SEQUENTIAL MODE IN BO TH MODES 9. Press the and the display advances to the next setpoint to be programmed. Refer to the beginning of this section, page 13-18. Press t[...]

  • Страница 256

    Section 13 Edition 3 Rev G 13-22 13.3 CONTROL ST A TE ACCESS CONTROL ST A TE ACCESS provides a quick and convenient method for changing states, such as AUTO to MANUAL or LOCAL to REMOTE setpoint. If configured, when the key is pressed, a two line prompt is displayed and the Function Keys, as configured, perform these change state requirements. The [...]

  • Страница 257

    Edition 3 Rev G Section 13 13-23 2. Press the to advance to the next parameter , LINE 2 TEXT . CAx LINE 2 TEXT A/M SP1/SP2 L/R Selections TEXT NOTE: If the CONTROL ST A TE ACCESS is not being used for Controller 1, OR, if SP1/SP2 AND/OR LOCAL REMOTE (L/R), it is suggested that this prompt be blank. 3. Press the to advance to the next parameter , F1[...]

  • Страница 258

    Section 13 Edition 3 Rev G 13-24 4. Press the to advance to the next parameter , F1 LINE 1 TEXT . CAx F1 LINE 1 TEXT CONTR OLLER 1 Selections TEXT 5. Press the to advance to the next parameter , F1 OFF ST A TE TEXT (only seen if KEY USAGE selected was CUSTOM). CAx F1 OFF ST A TE TXT A UT OMA TIC Selections TEXT 6. Press the to advance to the next p[...]

  • Страница 259

    Edition 3 Rev G Section 13 13-25 7. Press the to advance to the next parameter , F2 KEY USAGE. CAx F2 KEY USA GE NO T USED Selections NO T USED C1 A UT O/MANU AL C2 A UT O/MANU AL C3 A UT O/MANU AL C4 A UT O/MANU AL LOCAL/REMO TE SP1/SP2 CUST OM 8. Press the to advance to the next parameter , F2 LINE 1 TEXT (only seen if F2 KEY USAGE selected is ot[...]

  • Страница 260

    Section 13 Edition 3 Rev G 13-26 10. Press the to advance to the next parameter , F2 ON ST A TE TEXT (only seen if KEY USAGE selected was CUSTOM). CAx F2 ON ST A TE TEXT Selections TEXT 1 1. Press the to advance to the next parameter , F3 KEY USAGE. CAx F3 KEY USA GE SP1/SP2 Selections NO T USED C1 A UT O/MANU AL C2 A UT O/MANU AL C3 A UT O/MANU AL[...]

  • Страница 261

    Edition 3 Rev G Section 13 13-27 13. Press the to advance to the next parameter , F3 OFF ST A TE TEXT (only seen if KEY USAGE selected was CUSTOM). CAx F3 OFF ST A TE TXT SP1 Selections TEXT 14. Press the to advance to the next parameter , F3 ON ST A TE TEXT (only seen if KEY USAGE selected was CUSTOM). CAx F3 ON ST A TE TEXT SP2 Selections TEXT 15[...]

  • Страница 262

    Section 13 Edition 3 Rev G 13-28 16. Press the to advance to the next parameter , F4 LINE 1 TEXT (only seen if F4 KEY USAGE selected is other than NOT USED). CAx F4 LINE 1 TEXT Selections TEXT 17. Press the to advance to the next parameter , F4 OFF ST A TE TEXT (only seen if KEY USAGE selected was CUSTOM). CAx F4 OFF ST A TE TXT Selections TEXT 18.[...]

  • Страница 263

    Edition 3 Rev G Section 13 13-29 19. Press the to advance to the next parameter , F5 KEY USAGE. CAx F5 KEY USA GE LOCAL/REMO TE Selections NO T USED C1 A UT O/MANU AL C2 A UT O/MANU AL C3 A UT O/MANU AL C4 A UT O/MANU AL LOCAL/REMO TE SP1/SP2 CUST OM 20. Press the to advance to the next parameter , F5 LINE 1 TEXT . CAx F5 LINE 1 TEXT CONTR OLLER 1 [...]

  • Страница 264

    Section 13 Edition 3 Rev G 13-30 22. Press the to advance to the next parameter , F5 ON ST A TE TEXT (only seen if KEY USAGE selected was CUSTOM). CAx F5 ON ST A TE TEXT REMO TE Selections TEXT 23.Press the and the display advances to the next Control State Access to be programmed. Refer to the beginning of this section, page 13-22 . Refer to Secti[...]

  • Страница 265

    Edition 3 Rev G Section 13 13-31 13.4 TUNING P ARAMETERS The T uning parameters section is where adjustments to the proportional band, automatic reset (integral), and other parameters for proper operation of proportional controls and/or first output/second output etc. for on/off controls are made. For illustration purposes, all available parameters[...]

  • Страница 266

    Section 13 Edition 3 Rev G 13-32 2. Press the to advance to the next parameter , COPY/INITIALIZE. Cx COPY/INITIALIZE NO Selections YES or NO If selection is NO, see Step 3. If selection is YES: Cx COPY FR OM CONTRLR (0=INITIALIZE) X Input to be copied from 0=F ACT OR Y DEF A UL T 3. Press the to advance to the next parameter , SETPOINT RAMP RA TE. [...]

  • Страница 267

    Edition 3 Rev G Section 13 13-33 4. Press the to advance to the next parameter , OUTPUT 1 PROPORTIONAL BAND (only if Output 1 T ype in CONTROLLERS was set to PID). Cx OUT 1 PR OP B AND 100 units Note: Units correspond to Units configured in Process V ariables. Selections 0 to 999999 (decimal position=0) 0 to 9.9999 (decimal position=4) NOTE: When t[...]

  • Страница 268

    Section 13 Edition 3 Rev G 13-34 6. Press the to advance to the next parameter , OUTPUT 1 SHIFT . Cx OUT 1 SHIFT 0 units Note: Units correspond to Units configured in Process V ariables. Selections 0 to 999999 (decimal position=0) 0 to 9.9999 (decimal position=4) 7. Press the to advance to the next parameter , OUTPUT 2 SHIFT (only if Output 2 is us[...]

  • Страница 269

    Edition 3 Rev G Section 13 13-35 8. Press the to advance to the next parameter , INTEGRA TION BAND (only if proportional output). Cx INTEGRA TION B AND 100 units Note: Units correspond to Units configured in Process V ariables. Selections 0 to 999999 (decimal position=0) 0 to 9.9999 (decimal position=4) INTEGRA TION BAND sets the range where integr[...]

  • Страница 270

    Section 13 Edition 3 Rev G 13-36 10.Press the to advance to the next parameter , OUTPUT 1 AUTO RESET (only if output 1 is proportional). Cx OUT 1 A UT O RESET 0.00 REPEA TS/MIN Selections 0 to 100.00 1 1.Press the to advance to the next parameter , OUTPUT 2 AUT O RESET (only if output 2 is proportional). Cx OUT 2 A UT O RESET 0.00 REPEA TS/MIN Sele[...]

  • Страница 271

    Edition 3 Rev G Section 13 13-37 12.Press the to advance to the next parameter , OUTPUT 1 RA TE (only if output 1 is proportional). Cx OUT 1 RA TE 0.00 MINUTES Selections 0 to 100.00 13.Press the to advance to the next parameter , OUTPUT 2 RA TE (only if output 2 is proportional). Cx OUT 2 RA TE 0.00 MINUTES Selections 0 to 100.00 RA TE attempts to[...]

  • Страница 272

    Edition 3 Rev G Section 14 14-1 SECTION 14 - PROFILERS The profiling capability basically consists of a functional block that modifies the setpoint(s) and event outputs over time. The setpoint profiling is linked to the first four setpoints and the four process values. Event outputs are merely actuators that can be used for any purpose, but typical[...]

  • Страница 273

    Section 14 Edition 3 Rev G 14-2 7. Press the SCROLL key to advance to the next parameter , PxxSy SETPOINT 2 (if setpoints > 1). Press the MOD key to change, then UP/DOWN to desired setpoint value, then press the ENTER key . 8. Press the SCROLL key to advance to the next parameter , PxxSy SETPOINT 3 (if setpoints = 3 or 4). Press the MOD key to c[...]

  • Страница 274

    Edition 3 Rev G Section 14 14-3 When Segs Done - Profiles may be joined together to increase the number of segments or to make use of common profiling sequences. When all segments in the initiated profile have been executed the specified number of loops, the WHEN SEGS DONE parameter can “join” another profile. The instrument retains which profi[...]

  • Страница 275

    Section 14 Edition 3 Rev G 14-4 14.2 PROFILE SETTINGS T o enter the Profile Settings section, from the Normal Display , press the SCROLL key until CONFIGURA TION appears in the lower display line. With CONFIGURA TION in the lower display line, press the DOWN key . Press the SCROLL key until PROFILE SETTINGS appears in the lower display line. 1. Wit[...]

  • Страница 276

    Edition 3 Rev G Section 14 14-5 7. Press the SCROLL key to advance to the next parameter , PROFILE DISPLA Y OPTION. Selections are: NOT DISPLA YED; IN CONTINUOUS MODE; IN SEQUENTIAL MODE; or IN BOTH MODES. Press the MOD key to change, then UP/DOWN to desired choice, then press the ENTER key . If one of the DISPLA Y option is selected, the parameter[...]

  • Страница 277

    Section 14 Edition 3 Rev G 14-6 DA4 DA5 DA6 DA7 DA8 DA9 DA10 DA11 DA12 DA13 DA14 DA15 DA16 DA17 DA18 DA19 DA20 DA21 DA22 DA23 DA24 OUTPUT_11 OUTPUT_12 OUTPUT_21 OUTPUT_22 OUTPUT_31 OUTPUT_32 OUTPUT_41 OUTPUT_42 EVENT 1 EVENT 2 EVENT 3 EVENT 4 EVENT 5 EVENT 6 EVENT 7 EVENT 8 PRESET_1 PRESET_2 PRESET_3 PRESET_4 TOT AL_PO1 TOT AL_PO2 TOT AL_PO3 TOT AL[...]

  • Страница 278

    Edition 3 Rev G Section 14 14-7 14.3 PROFILE CONTROL T o enter the Profile Control section, from the Normal Display , press the DISP key until SELECT appears in the upper display line and PROFILE CONTROL appears in the lower display line. If PROFILE CONTROL is not displayed, then Profile Control has been disabled. Refer to Section 9, Enables and Pa[...]

  • Страница 279

    Section 14 Edition 3 Rev G 14-8 7. Press the SCROLL key to advance to the next parameter , CURRENT SEGMENT . Selections are 1-8. Press the MOD key to change, then the UP/DOWN as required to the desired choice, then press the ENTER key . Only modifiable if profile is presently not running. Current Segment - This is the current active segment, which [...]

  • Страница 280

    Edition 3 Rev G Section 14 14-9 PROFILE NUMBER Parameter P 1 P 2 P 3 P 4 DESCRIPTION SETPOINTS TO PROFILE NUMBER OF SEGMENTS SEGMENT 1 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS -RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 2 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS [...]

  • Страница 281

    Section 14 Edition 3 Rev G 14-10 PROFILE NUMBER Parameter P 1 P 2 P 3 P 4 SEGMENT 6 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 7 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL [...]

  • Страница 282

    Edition 3 Rev G Section 14 14-11 PROFILE NUMBER Parameter P 5 P 6 P 7 P 8 DESCRIPTION SETPOINTS TO PROFILE NUMBER OF SEGMENTS SEGMENT 1 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS -RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 2 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS[...]

  • Страница 283

    Section 14 Edition 3 Rev G 14-12 PROFILE NUMBER Parameter P 5 P 6 P 7 P 8 SEGMENT 6 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 7 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL [...]

  • Страница 284

    Edition 3 Rev G Section 14 14-13 PROFILE NUMBER Parameter P 9 P 10 P 1 1 P 12 DESCRIPTION SETPOINTS TO PROFILE NUMBER OF SEGMENTS SEGMENT 1 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS -RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 2 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUT[...]

  • Страница 285

    Section 14 Edition 3 Rev G 14-14 PROFILE NUMBER Parameter P 9 P 10 P 1 1 P 12 SEGMENT 6 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 7 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DW[...]

  • Страница 286

    Edition 3 Rev G Section 14 14-15 PROFILE NUMBER Parameter P 13 P 14 P 15 P 16 DESCRIPTION SETPOINTS TO PROFILE NUMBER OF SEGMENTS SEGMENT 1 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS -RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 2 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUT[...]

  • Страница 287

    Section 14 Edition 3 Rev G 14-16 PROFILE NUMBER Parameter P 13 P 14 P 15 P 16 SEGMENT 6 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DWELL SEGMENT 7 RAMP TIME hhh:mm:ss SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4 EVENT OUTPUTS - RAMP DWELL TIME hhh:mm:ss EVENT OUTPUTS - DW[...]

  • Страница 288

    Edition 3 Rev G Section 14 14-17 Parameter PROFILE ENTR Y DISABLED DURING RUN ENABLED DURING RUN PROF ST ART ACTUA TOR PROFILE SELECTOR PROF ABORT ACTUA TOR PROF HOLD ACTUA TOR PROF ADV ANCE ACTUA TR PROF DISPLA Y OPTION[...]

  • Страница 289

    Edition 3 Rev G Appendix A A-1 Appendix A - Board Layouts FIGURE A-1 POWER SUPPL Y BOARD G P1 P2 N L P3[...]

  • Страница 290

    Appendix A Edition 3 Rev G A-2 FIGURE A-2 MOTHER BOARD J5 J6 J4 J7 J1 J3[...]

  • Страница 291

    Edition 3 Rev G Appendix A A-3 FIGURE A-3 RELA Y/SSR BOARD RELAY 4 TB1 TB2 J7B J7A TB3 TB4 RELAY 1 RELAY 2 RELAY 3 1 + 2 – 3 1 NO 2 C 3 NC[...]

  • Страница 292

    Appendix A Edition 3 Rev G A-4 FIGURE A-4 INPUT BOARD 1 JU11 JU2 JU5 JU12 JU15 JU3 JU16 JU6 JU8 JU7 U6 TB2 TB1 JU4 JU1 1 JU13 JU14[...]

  • Страница 293

    Edition 3 Rev G Appendix A A-5 FIGURE A-5 MOT OR DRIVER BOARD J4B J5 J6 J1 J7 J4A J3 J2[...]

  • Страница 294

    Appendix A Edition 3 Rev G A-6 FIGURE A-6 CURRENT OUTPUT BOARD TB1 J5B + - J5B TB2 + - TB1 + - NON-ISOLATED ISOLATED[...]

  • Страница 295

    Edition 3 Rev G Appendix A A-7 FIGURE A-7 TRANSMITTER POWER SUPPL Y BOARD J3 TB2 + - TB1 + - TB3 + - TB4 + -[...]

  • Страница 296

    Appendix A Edition 3 Rev G A-8 FIGURE A-8 COMMS BOARD TB1 TB2 TB4 TB3 TB1 - 232 Main TB3 - 485 Main TB2 - 232 Aux TB4 - 485 Aux J2 J1 U1[...]

  • Страница 297

    Edition 3 Rev G Appendix B B-1 Appendix B - Ranges THERMOCOUPLE JU7/JU8 POSITION TYPE OPERA TING RANGE Wide J -200 ° C to 760 ° C -328 ° F to 1400 ° F Narrow J -200 ° C to 450 ° C -328 ° F to 842 ° F Wide K -250 ° C to 1370 ° C -418 ° F to 2498 ° F Narrow K -250 ° C to 600 ° C 418 ° F to 1112 ° F Wide E -250 ° C to 1000 ° C -418 ?[...]

  • Страница 298

    Appendix B Edition 3 Rev G B-2 RTD JU7/JU8 POSITION TYPE OPERA TING RANGE Low Platinum 100 ohm -200 ° C to 480 ° C .00385 Din -328 ° F to 896 ° F Low Platinum 100 Ohm -100 ° C to 450 ° C .00392 USA -148 ° F to 842 ° F Low Platinum 100 Ohm -200 ° C to 560 ° C .00392 SAMA -328 ° F to 1040 ° F Low Nickel 100 Ohm -40 ° C to 200 ° C -40 °[...]

  • Страница 299

    Edition 3 Rev G Appendix C C-1 Appendix C - Reference Section Next to each term is the prompt section it appears in, as appropriate, and the applicable section or page of this manual. T erms that are printed in all upper case letters appear in the instruments display , or are keypad designa- tions . In some cases, additional words are inserted for [...]

  • Страница 300

    Appendix C Edition 3 Rev G C-2 A VERAGE V ALUES - System Prompts - Configuration - Recorders - Page 4-46 The choice for the parameter RECORDING METHOD that prints a single dot corresponding to the average of the trended value during the “print interval”. This method records a series of dots which may not form a continuous trend line. BACKGROUND[...]

  • Страница 301

    Edition 3 Rev G Appendix C C-3 CHART ROT A TION (Actuator) Actuator that is controlled by the selected state for the CHART ROT A TION prompt found in the Chart Prompts section. See ROT A TE CHART ACTUA TR. CHART ROT A TION (Prompt) - Chart Prompts - Page 6-2 Parameter that controls the CHART ROT A TION actuator . This parameter is like a special Op[...]

  • Страница 302

    Appendix C Edition 3 Rev G C-4 CONST ANTS - System Prompts - Configuration - Page 4-14 Prompt section containing parameters used as fixed values which are typically used for scaling constants in Derived V ariables. CONTINUOUS (ACTUA TION) - System Prompts - Configuration - Operator Inputs - Page 4-83 A choice for the parameter ACTUA TION STYLE whic[...]

  • Страница 303

    Edition 3 Rev G Appendix C C-5 DAxx ITEM xx - System Prompts - Configuration - Derived Actuators - Page 4-80 One of a list of choices that is used to configure a Derived Actuator . The list includes actuators and logical operators that are combined to form a logic equation. Data collection - See T rend data collection DA TE FORMA T - System Prompts[...]

  • Страница 304

    Appendix C Edition 3 Rev G C-6 DISPLA Y T AG - System Prompts - Configuration Parameter used to specify a description or designation that can be displayed with the Input V alue, Process V ariable, or Derived V ariable when they are included in the Display Sequence in the 1 V AL (1 value at a time) Display Mode. The tags do not appear in the other d[...]

  • Страница 305

    Edition 3 Rev G Appendix C C-7 INPUTS - System Prompts - Configuration - Page 4-1 Prompts section that configures how hardware inputs are processes to provide the desired engineering values, decimal position, and units, for the sensor type and range used. Other characteristics are also configured for out- of-range checking, cutof f, input correctio[...]

  • Страница 306

    Appendix C Edition 3 Rev G C-8 MA TCH SCALE COLOR - Chart Prompts - Chart Configuration - Page 6-8 A choice for MA TCH/SELECT prompts which specifies that the corresponding time line, time, or date and chart tag should be in the same color as the scale, as the chart is being printed. Minor time lines Minor time lines are printed as a series of dots[...]

  • Страница 307

    Edition 3 Rev G Appendix C C-9 OPERA TOR INPUTS - System Prompts - Configuration - Page 4-84 Prompts section that configures the text for the message and states and actuation type associated with each Operator Input. The corresponding actuators can then be changed in the Display Prompts. OPERA TOR MESSAGES - System Prompts - Configuration - Page 4-[...]

  • Страница 308

    Appendix C Edition 3 Rev G C-10 Prompt A message that is displayed in the upper line, while a prompt section name or parameter (value, choice, or text) is displayed in the lower line. During normal operation, the instrument is either displaying a value(s), a message, or a prompt. Prompt section A general term for a group of prompts, such as Display[...]

  • Страница 309

    Edition 3 Rev G Appendix C C-11 RELA YS - System Prompts - Configuration - Page 4-66 Prompts section that configures actuators and other parameters associated with relay and/or solid state relay driver outputs. RELA Y x USAGE - System Prompts - Configuration - Relays - Page 4-66 Parameter that specifies the type of output the relay is to provide, o[...]

  • Страница 310

    Appendix C Edition 3 Rev G C-12 Sensor break While there are sensor break jumpers, JU1 and JU4, sensor break and out-of-range conditions are actually determined and handled by the software. When either occurs, the software will drive the input value to +99999 or -99999 based upon whether SENSOR BREAK is software configured for UPSCALE or DOWN SCALE[...]

  • Страница 311

    Edition 3 Rev G Appendix C C-13 TEST - System Prompts - Section 10 Prompt section which provides access to various test routines. T ext A general term which refers to a parameter that is a series of characters, such as a display tag, units, or contents of a configurable message. TIME BASE - System Prompts - Configuration - T otalizers - Page 4-54 P[...]

  • Страница 312

    Appendix C Edition 3 Rev G C-14 TO ZERO BELOW V ALUE - System Prompts - Configuration - Inputs - Page 4-10 One of the choices for CUTOFF TYPE which specifies that the resultant IV (Input V alue) is set to zero whenever the input value is less than the CUTOFF V ALUE. Consequently negative values are set to zero. The CUTOFF V ALUE must be positive. T[...]

  • Страница 313

    Edition 3 Rev G Appendix C C-15 ZONE 1 LOW - System Prompts - Configuration - Recorders - Page 4-47 Parameter that specifies the DIVISION or ring corresponding to the “bottom” end of the zone. For reverse ranges (lower engineering value at the outer portion), either the two ZONE parameters or the two SP AN parameters can be reversed. ZONE 2 HIG[...]

  • Страница 314

    Edition 3 Rev G Appendix D D-1 Appendix D - Examples EXAMPLE 1 Application: Palmer-Bowlus Flume Height/Flow Given: T ransmitter output linear in distance (4mA=0.0", 20mA=2.85") Configuration: Inputs: As required Custom Curves: See below Derived V ariables: See below Process V ariables (if alarming required): As required Recorders: See bel[...]

  • Страница 315

    Appendix D Edition 3 Rev G D-2 EXAMPLE 2 Application: User would like to combine logically 3 alarms to create an AND situation. Configuration: Derived Actuators: Derived Actuator 1 DA1 Item 1 A1 1 (Alarm 1 Process V alue 1 Active) DA1 Item 2 AND DA1 Item 3 A12 (Alarm 2 Process V alue 1 Active) DA1 Item 4 AND DA1 Item 5 A13 (Alarm 3 Process V alue 1[...]

  • Страница 316

    Edition 3 Rev G Appendix D D-3 EXAMPLE 4 Operator Messages Operator Messages are user defined messages to advise, or provide information, via the display , that selected actuators are active. The messages are displayed as specified by the Operator Message Display Mode parameter setting. Application: A user would like a visual indication whenever th[...]

  • Страница 317

    Appendix D Edition 3 Rev G D-4 EXAMPLE 6 Latching Alarm Configuration: Process V ariables: Process V ariable 1 PV1 Display T ag users choice PV1 Input IV1 A1 1 Alarm T ype Process - High A11 Hysteresis 3 LEDs: LED Number 8 LED 8 Actuator DA 1 Relays: Relay Number 4 Relay 4 Usage State or On-Off Relay 4 Actuator DA 1 Derived Actuators: Derived Actua[...]

  • Страница 318

    Edition 3 Rev G Appendix D D-5 EXAMPLE 7 Latching High Alarm - Latched Open Configuration: Process V ariables: Process V ariable users choice PV1 Display T ag users choice PV1 Input users choice A1 1 Alarm T ype Process - High LEDs LED Number users choice LED # Actuator A11 Relay Relay Number users choice Relay # Usage State or On/Off Relay # Actua[...]

  • Страница 319

    Edition 3 Rev G Appendix E E-1 Appendix E - Accuracy T ables See Note: RANGE ° C 0/1200 -200/0 0/400 -200/0 0/1370 -250/0 0/500 -250/0 0/1000 -250/0 0/300 -250/0 0/1300 -250/0 0/600 -200/0 -250/-200 1800/2300 800/1800 500/800 300/500 0/300 1800/2300 1200/1800 300/1200 0/300 1800/2300 300/1800 0/300 450/1370 0/450 1000/1400 500/1000 0/500 1 REF ACC[...]

  • Страница 320

    Appendix E Edition 3 Rev G E-2 THE FOLLOWING THERMOCOUPLES ARE A V AILABLE AS NARROW ONL Y INPUT TYPE T T/C R T/C S T/C B T/C INPUT TYPE 385 RTD 392 RTD 392 SAMA 100 ohm Nickel See Note: RANGE ° C 0/400 -220/0 -250/-220 800/1700 200/800 250/1750 200/1800 See Note: RANGE ° C -160/480 -200/-160 -100/450 -200/560 -40/200 01 REF ACC'Y ° C 0.12 [...]

  • Страница 321

    Edition 3 Rev G Appendix E E-3 See Note: SP AN mV 0/10000 0/1000 0/100 0/25 See Note: SP AN mA 4/20 0/20 5 DEVIA TION ACC'Y uV/ ° C 1000 100.0 10.0 2.5 5 DEVIA TION ACC'Y uA/ ° C 2.0 2.0 6 RESOL uV/bit 381 38.1 3.81 0.954 6 RESOL. uA/bit 0.763 0.763 4 REF+LIN +CAL uV 3500 350 45 26 4 REF+CAL uA 7 7 3 F ACT ORY CAL uV 1000 100 20 20 3 F [...]