Heatcraft Refrigeration Products 25000601 инструкция обслуживания
- Просмотреть online или скачать инструкцию
- 28 страниц
- 1 mb
Идти на страницу of
Похожие руководства по эксплуатации
-
Fan
Heatcraft Refrigeration Products BHL
24 страниц 2.69 mb -
Fan
Heatcraft Refrigeration Products ELC/EFC
20 страниц 2.32 mb -
Refrigerator
Heatcraft Refrigeration Products SWN0150H2B
12 страниц 1.8 mb -
Refrigerator
Heatcraft Refrigeration Products SWN0310M6D
12 страниц 1.8 mb -
Refrigerator
Heatcraft Refrigeration Products PST051L6B*
8 страниц 1.05 mb -
Blower
Heatcraft Refrigeration Products 4346B001
8 страниц 0.63 mb -
Fan
Heatcraft Refrigeration Products BMG
16 страниц 2.39 mb -
Refrigerator
Heatcraft Refrigeration Products PST086M6B*
8 страниц 1.05 mb
Хорошее руководство по эксплуатации
Законодательство обязывает продавца передать покупателю, вместе с товаром, руководство по эксплуатации Heatcraft Refrigeration Products 25000601. Отсутствие инструкции либо неправильная информация, переданная потребителю, составляют основание для рекламации в связи с несоответствием устройства с договором. В законодательстве допускается предоставлении руководства в другой, чем бумажная форме, что, в последнее время, часто используется, предоставляя графическую или электронную форму инструкции Heatcraft Refrigeration Products 25000601 или обучающее видео для пользователей. Условием остается четкая и понятная форма.
Что такое руководство?
Слово происходит от латинского "instructio", тоесть привести в порядок. Следовательно в инструкции Heatcraft Refrigeration Products 25000601 можно найти описание этапов поведения. Цель инструкции заключается в облегчении запуска, использования оборудования либо выполнения определенной деятельности. Инструкция является набором информации о предмете/услуге, подсказкой.
К сожалению немного пользователей находит время для чтения инструкций Heatcraft Refrigeration Products 25000601, и хорошая инструкция позволяет не только узнать ряд дополнительных функций приобретенного устройства, но и позволяет избежать возникновения большинства поломок.
Из чего должно состоять идеальное руководство по эксплуатации?
Прежде всего в инструкции Heatcraft Refrigeration Products 25000601 должна находится:
- информация относительно технических данных устройства Heatcraft Refrigeration Products 25000601
- название производителя и год производства оборудования Heatcraft Refrigeration Products 25000601
- правила обслуживания, настройки и ухода за оборудованием Heatcraft Refrigeration Products 25000601
- знаки безопасности и сертификаты, подтверждающие соответствие стандартам
Почему мы не читаем инструкций?
Как правило из-за нехватки времени и уверенности в отдельных функциональностях приобретенных устройств. К сожалению само подсоединение и запуск Heatcraft Refrigeration Products 25000601 это слишком мало. Инструкция заключает ряд отдельных указаний, касающихся функциональности, принципов безопасности, способов ухода (даже то, какие средства стоит использовать), возможных поломок Heatcraft Refrigeration Products 25000601 и способов решения проблем, возникающих во время использования. И наконец то, в инструкции можно найти адресные данные сайта Heatcraft Refrigeration Products, в случае отсутствия эффективности предлагаемых решений. Сейчас очень большой популярностью пользуются инструкции в форме интересных анимаций или видео материалов, которое лучше, чем брошюра воспринимаются пользователем. Такой вид инструкции позволяет пользователю просмотреть весь фильм, не пропуская спецификацию и сложные технические описания Heatcraft Refrigeration Products 25000601, как это часто бывает в случае бумажной версии.
Почему стоит читать инструкции?
Прежде всего здесь мы найдем ответы касательно конструкции, возможностей устройства Heatcraft Refrigeration Products 25000601, использования отдельных аксессуаров и ряд информации, позволяющей вполне использовать все функции и упрощения.
После удачной покупки оборудования/устройства стоит посвятить несколько минут для ознакомления с каждой частью инструкции Heatcraft Refrigeration Products 25000601. Сейчас их старательно готовят или переводят, чтобы они были не только понятными для пользователя, но и чтобы выполняли свою основную информационно-поддерживающую функцию.
Содержание руководства
-
Страница 1
Beacon II Smart Controller Installation & Operation Manual Part No. 25000601 Replaces H-IM-80C (12/03) Features ................................................................ 2-3 Installation ............................................................. 4 Wiring .................................................................... 5 Power Supp[...]
-
Страница 2
2 The Beacon II Smart Controller performs all the standard Beacon functions with the additional benefit of: a) Remote mounting for easy access b) Remote monitoring and programming c) Controlling four completely separate systems d) Logging data e) Smart Defrost f) Access via PC or modem g) Has buzzer to signal alarms h) Locking keypad Beacon II Smar[...]
-
Страница 3
3 Features of the Beacon II Smart Controller • Monitoring of the complete refrigeration system. • Programming of a variety of parameters for the optimum control of the refrigeration system. • The Beacon II Smart Controller has a Liquid Crystal Display (LCD) which shows: current time, actual box temperature, box temperature set-point and if th[...]
-
Страница 4
4 INST ALLA TION The Beacon II Smart Controller should be installed in a location where the large Liquid Crystal Display (LCD) can be viewed easily , yet is secure and vibration free. Because of the LCD screen, the Beacon II Smart Controller should not be mounted where it will experience temperatures below 40 ° F or above 100 ° F. A terminal stri[...]
-
Страница 5
5 WIRING All 24 volt wiring must be run separate from the line voltage wiring . All Low voltage wiring must be 18 gauge minimum and must be run separate from high voltage wiring. The maximum distance from the Beacon II Smart Controller t o the Master Evaporator is 1000 ft. The terminal strip in the Beacon II Smart Controller i s labeled similarly t[...]
-
Страница 6
6 For the second system, connect MUL TI OUT 2 from the Beacon II Smart Controller t o the MUL TI IN on the Beacon II board on the Evaporator in this second system. Then connect MUL TI IN 2 from the Beacon II Smart Controller t o t h e MUL TI OUT on the Beacon II board on the Evaporator on this second system. See typical wiring diagram at the back o[...]
-
Страница 7
7 will continue to operate and maintain the box temperature. This occurs only if an external power supply is used on the Beacon II Smart Controller . If the Beacon II Smart Controller LCD displays all 88888 this indicates that the power supply is below 18 V AC. When this occurs the system will power down and shut off. When the power supply is corre[...]
-
Страница 8
8 • COOLING: Depressing this button will start the system in the cooling cycle immediately (The 4 minutes “Hold Off” is bypassed). This button will illuminate to indicate that the Cooling function is “ON”. System operation will be as described under REFRIGERA TION MODE in the Beacon II installation manual. Pressing the COOLING button whil[...]
-
Страница 9
9 • SUPRHT – Superheat: 4 to 20 ° F . Use “SETPOINT” slide-bar to select desired superheat temp., then press “ENTER.” If multiple evaporators are connected, use the “+” button to set other evaporators on this system. • SMT DFT : Smart Defrost: On/Off. Use “SETPOINT” slide-bar to turn it ON or OFF , then press “ENTER” - (f[...]
-
Страница 10
10 • EXVSET - Expansion valve step setting (Stepper Motor setting 0 to 255 steps: use + button to check other evaporators if Master/slave) • SUCTMP – Evaporator Suction temperature (Measured by the Suction Sensor) • SSVTMP – Saturated Suction temperature at the Evaporator (Determined by Suction T ransducer) • SUCPRE – Evaporator Sucti[...]
-
Страница 11
11 • *SPSEN - Suction pressure transducer shorted, open or not installed • *ODSEN - Outdoor temperature sensor shorted • *SUPLO - Superheat too low • *SHTDN - Compressor shutdown (High or low refrigerant pressure or low oil pressure) The error code will flash alternately with the normal display information. When the error condition is corre[...]
-
Страница 12
12 The system will pumpdown, cycle off and try to restart for three consecutive times. Each try will be after the 4 minutes “Hold Off” period, for the following fault conditions. Oil pressure High pressure or low pressure cutout (or any other compressor safeties) After the fourth try , the Alarm contacts will be closed and an alarm message disp[...]
-
Страница 13
13 Real-time data can also be recorded and stored on a Desktop PC while the PC is connected to the Beacon II Smart Controller . The PC will continuously request information from the Beacon II Smart Controller regarding system operation and setup and record this data every minute, in an Excel spreadsheet. This information is stored to the PC hard dr[...]
-
Страница 14
14 PC & MODEM ACCESS For access to the system from a PC directly or via a modem, the SMAR T II Software must be purchased and installed on your PC. With PC access, ALL system settings can be monitored, changed or logged from a remote location. The stored data can be viewed in an Excel spreadsheet. Recommended Requirements PC with a 233 Mhz cloc[...]
-
Страница 15
15 SYSTEM DEF AUL TS Following are factory defaults for the parameters which can be programmed in the Beacon II Smart Controller . If the user does not select a setting for any of the following parameters, the default will be used. It is important the user set ALL parameters based of their needs. P ARAMETERS CODE AIR ELECTRIC Refrigerant REFTYP R22[...]
-
Страница 16
16 Parts Parts List HRP P ART P ART DESCRIPTION NUMBER Beacon II Control Board 28910101 T emperature Sensor kit – White Leads* 89904902 T ransformer 120/24 volt – 40 V A 22529601 T ransformer 240/24 volt - 40 V A 22529602 T ransformer 460/24 volt – 40 V A 22529603 T ransformer 575/24 volt – 40 V A 22529701 Pilot Relay 2251 1401 Contactor fo[...]
-
Страница 17
17 Beacon II T roubleshooting Guide PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check Primary Power Supply Disconnect 1. Check fuses and circuit breakers 2. Check V oltage to Evaporator Transformer Go to 2. Check field wiring for breaks LED is not lit. 3. Check T ransformer Secondary Output V olts next step 3. Replace if necessary 4. Check V oltage[...]
-
Страница 18
18 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check wiring connection to the board • Correct field wiring to the board 2. Low Pressure Safety (LPS) T ripped: • Check for correct refrigerant type • Change setpoint to match refrigerant • Check refrigerant charge • Add more refrigerant to proper charge • Check LPS setting • Correct LPS [...]
-
Страница 19
19 Beacon II T roubleshooting Guide (continued) PROBLEM Step ACTION ITEM IF OK IF NOT OK E9 Multi-out to Multi-in 1. Check for 24 volts power to the board 1. If no voltage, see “LED is not lit” above Communication Wiring for low voltage, see “88888 LED display” (only shows after initial 2. Check for crossed communication wiring Go to 2. Cor[...]
-
Страница 20
20 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check system operation: Is it running? 1. Check power to condensing unit Check position of Service Mode switches Check compressor overloads and contactor 2. Check system charge 2. Add or remove refrigerant to proper charge 3. Check for proper operating superheat 3. Check EEV operation Check control boa[...]
-
Страница 21
21 Wiring Diagrams[...]
-
Страница 22
22 Wiring Diagrams[...]
-
Страница 23
23 Wiring Diagrams[...]
-
Страница 24
24 Wiring Diagrams[...]
-
Страница 25
25 Notes[...]
-
Страница 26
26 Notes[...]
-
Страница 27
27 Notes[...]
-
Страница 28
Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd • Stone Mountain, GA 30087 (770) 465-5600 • Fax (770)465-5990 www .heatcraftrpd.com Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice.[...]