American Power Conversion PD80KG6FK1-M manual
- Consulta online o descarga el manual de instrucciones
- 92 páginas
- 2.72 mb
Ir a la página of
manuales de instrucciones parecidos
-
Power Supply
American Power Conversion 480kW 400V
72 páginas 4.97 mb -
Power Supply
American Power Conversion SUA3000XL NETPKG
19 páginas 1.02 mb -
Power Supply
American Power Conversion 475I
2 páginas 0.19 mb -
Power Supply
American Power Conversion AP8841
24 páginas 0.72 mb -
Power Supply
American Power Conversion AP9825I
1 páginas 0.02 mb -
Power Supply
American Power Conversion AP9222EXP
43 páginas 0.59 mb -
Power Supply
American Power Conversion PD150L6F
84 páginas 1.97 mb -
Power Supply
American Power Conversion 5000RMB
23 páginas 0.76 mb
Buen manual de instrucciones
Las leyes obligan al vendedor a entregarle al comprador, junto con el producto, el manual de instrucciones American Power Conversion PD80KG6FK1-M. La falta del manual o facilitar información incorrecta al consumidor constituyen una base de reclamación por no estar de acuerdo el producto con el contrato. Según la ley, está permitido adjuntar un manual de otra forma que no sea en papel, lo cual últimamente es bastante común y los fabricantes nos facilitan un manual gráfico, su versión electrónica American Power Conversion PD80KG6FK1-M o vídeos de instrucciones para usuarios. La condición es que tenga una forma legible y entendible.
¿Qué es un manual de instrucciones?
El nombre proviene de la palabra latina “instructio”, es decir, ordenar. Por lo tanto, en un manual American Power Conversion PD80KG6FK1-M se puede encontrar la descripción de las etapas de actuación. El propósito de un manual es enseñar, facilitar el encendido o el uso de un dispositivo o la realización de acciones concretas. Un manual de instrucciones también es una fuente de información acerca de un objeto o un servicio, es una pista.
Desafortunadamente pocos usuarios destinan su tiempo a leer manuales American Power Conversion PD80KG6FK1-M, sin embargo, un buen manual nos permite, no solo conocer una cantidad de funcionalidades adicionales del dispositivo comprado, sino también evitar la mayoría de fallos.
Entonces, ¿qué debe contener el manual de instrucciones perfecto?
Sobre todo, un manual de instrucciones American Power Conversion PD80KG6FK1-M debe contener:
- información acerca de las especificaciones técnicas del dispositivo American Power Conversion PD80KG6FK1-M
- nombre de fabricante y año de fabricación del dispositivo American Power Conversion PD80KG6FK1-M
- condiciones de uso, configuración y mantenimiento del dispositivo American Power Conversion PD80KG6FK1-M
- marcas de seguridad y certificados que confirmen su concordancia con determinadas normativas
¿Por qué no leemos los manuales de instrucciones?
Normalmente es por la falta de tiempo y seguridad acerca de las funcionalidades determinadas de los dispositivos comprados. Desafortunadamente la conexión y el encendido de American Power Conversion PD80KG6FK1-M no es suficiente. El manual de instrucciones siempre contiene una serie de indicaciones acerca de determinadas funcionalidades, normas de seguridad, consejos de mantenimiento (incluso qué productos usar), fallos eventuales de American Power Conversion PD80KG6FK1-M y maneras de solucionar los problemas que puedan ocurrir durante su uso. Al final, en un manual se pueden encontrar los detalles de servicio técnico American Power Conversion en caso de que las soluciones propuestas no hayan funcionado. Actualmente gozan de éxito manuales de instrucciones en forma de animaciones interesantes o vídeo manuales que llegan al usuario mucho mejor que en forma de un folleto. Este tipo de manual ayuda a que el usuario vea el vídeo entero sin saltarse las especificaciones y las descripciones técnicas complicadas de American Power Conversion PD80KG6FK1-M, como se suele hacer teniendo una versión en papel.
¿Por qué vale la pena leer los manuales de instrucciones?
Sobre todo es en ellos donde encontraremos las respuestas acerca de la construcción, las posibilidades del dispositivo American Power Conversion PD80KG6FK1-M, el uso de determinados accesorios y una serie de informaciones que permiten aprovechar completamente sus funciones y comodidades.
Tras una compra exitosa de un equipo o un dispositivo, vale la pena dedicar un momento para familiarizarse con cada parte del manual American Power Conversion PD80KG6FK1-M. Actualmente se preparan y traducen con dedicación, para que no solo sean comprensibles para los usuarios, sino que también cumplan su función básica de información y ayuda.
Índice de manuales de instrucciones
-
Página 1
80 kW InfraStruXur e PDU PD80KF6FK1-M PD80KG6FK1-M PD80KL6FK1-M Operation and Configuration 208/480/600 V Input[...]
-
Página 2
[...]
-
Página 3
80kW InfraStruXure PDU—Op eration and Co nfiguration i About This Manual Audience This manual is intended for end-users of an 80 kW InfraStruXure PDU. It covers the operation, customization, and quick config uration of the InfraStruXure PDU. It also includes basic InfraStruXure system operation. Companion manuals For additional informatio n about[...]
-
Página 4
[...]
-
Página 5
Contents 80kW InfraStruXure PDU—Operation and Configuration iii Safety ............................. ........................ ................. 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety symbols used in this[...]
-
Página 6
iv 80kW InfraStruXure PDU—Operation and Configuration Contacts Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Breakers Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Alarms Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 View Active Alarms . . [...]
-
Página 7
80kW InfraStruXure P DU—Operation and Config uration v Configuring the Network Management Interface . . . . . . . . . . . 45 Connect the InfraStruXure PDU to your network . . . . . . . . . 45 Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 45 TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . 46 De[...]
-
Página 8
vi 80kW InfraStruXure PDU—Op eration and Configuration Product Information ........ ........................ .............. 71 InfraStruXure Standard Warranty . . . . . . . . . . . . . . . . . . . . . . . 71 Life-Support Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 How to Obtain Service . . . . . . . . . . . . . .[...]
-
Página 9
80kW InfraStruXure PDU—Op eration and Co nfiguration 1 Safety Over view Save these instru ctions This manual contains important instructions t hat must be followed during installation, operation, and maintenance of the PDU. Safety symbols used in this manual C ro s s - re f ere n c e s y m b o l s u s e d i n t h i s m a n u a l Ele c tr ical Ha [...]
-
Página 10
2 80kW InfraStruXure PDU—Op eration and Configuration Wa r n i n g s Installation/Maintenance Only a certified electrician can perform these tasks: • Connect the InfraStruXure PDU to utili ty power • Connect the cross tie output breaker to an other InfraS truXure PDU • Connect a switch to the EPO inte rface on the InfraS t ruXure PDU Only a[...]
-
Página 11
Safety 80kW InfraStruXure PDU—Op eration and Co nfiguration 3 T otal Power Off 1. Set the Symmetra PX UPS System Enable switch to Off. 2. Set the DC Disconnect breaker of each Battery Enclosure to Off. 3. Set the PDU Main Input ( A ) switch to Off. 4. If applicable, set the PDU Bypass Input ( B ) switch to Of f 5. If applicable, set the PDU Cro s[...]
-
Página 12
Safety 4 80kW InfraStruXure PDU—Op eration and Configuration EMI This equipment has been tested and found to comp ly with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These lim its are designed to prov ide reasonable protection against harmful interference when the equipment is operated in a commercial environmen[...]
-
Página 13
80kW InfraStruXure PDU—Op eration and Co nfiguration 5 Over view InfraStruXur e PDU Components The APC 80 kW InfraStruXure PDU provides distribution an d management of electrical powe r . The InfraStruXure PDU has the capacity of 80 kW , a ccepts 208, 480, or 600 V , 3-phase input, a nd distributes 208 V , 3-phase power to equipment rack s and Ra[...]
-
Página 14
Overview 6 80kW InfraStruXure PDU—Op eration and Configuration PDU fr ont view (exterior) PDU wide shielding troughs— The PDU shielding troughs accommodate the power cables exiting the roof of the PDU. Power Cables— These power cables feed equipment racks; they are fed th rough knockout panels on the top (or bottom) of the PDU. The po[...]
-
Página 15
Overview 80kW InfraStruXure PDU—Op eration and Co nfiguration 7 Fr ont view (interior) Ground lugs — G round lugs are provided for the Main Input switch, Bypass Input switch, and Cross Tie Output breaker . The main input lug has two holes: one for a main ground and one for the GE C. See the instruction sheet, Certified Electrician’ s Inst[...]
-
Página 16
Overview 8 80kW InfraStruXure PDU—Op eration and Configuration Fr ont view (door open) Wrapa roun d maintenance bypass panel — The maintenance bypass panel has three circuit breakers that allow the UPS to be electrically isolated from the main power source, while maintaining the power panels. The input circuit breaker is labeled Q1, the out[...]
-
Página 17
Overview 80kW InfraStruXure PDU—Op eration and Co nfiguration 9 Rear view (interior) 42-position circuit br eaker panel —Each PDU has a circuit breaker panel with 42 pole positions. Each pole provides power at 120 volts L-N or 208 volts L-L. The amperage each position provides depen ds on the size of the circuit b reaker used . Panel cu[...]
-
Página 18
Overview 10 80kW InfraStruXure PDU—Op eration and Configuration PDU monitoring unit This connection provides the input power for the PDU monitoring unit. The power is supplied by the monito ring unit circuit breaker on the front of t he PDU. If the pan el is on, and t he monitoring unit circuit breaker is closed, the monitoring unit is pow er[...]
-
Página 19
Overview 80kW InfraStruXure PDU—Oper ation and Conf iguration 11 User connection plate For a description and location of th e user connection plate, see ( ) on pa ge 8. For cl arity , the user connection plate is shown in the fo llowing illustration in greater detail. Connect the InfraStruXure PDU to the network of the InfraS truXure Ma[...]
-
Página 20
[...]
-
Página 21
80kW InfraStruXure PDU—Oper ation and Conf iguration 13 PDU Display Interface Over view Y ou can use the display interface to configure settin gs, set alarm t hresholds, and provide audible and visual alarms. ESC ? Loa d Powe red Chec k Log Byp ass Alarm Load On LED When green, all output phases are within th[...]
-
Página 22
PDU Display Interface 14 80kW InfraStruXure PDU—Op eration and Configuration T op-level status scr eens After system start-up, the display interface displays a brief start-up screen and then scrolls automatically and continuously through four screens of basic status information. Press the Up and Down arrow keys to interrupt the automatic scrollin[...]
-
Página 23
PDU Display Interface 80kW InfraStruXure PDU—Oper ation and Conf iguration 15 On some screens, continue arrows ( indicate that there are additional screens to view in the category . Press the Up or Down arrow key to vi ew the additio nal screens. P a s s w o rd - p ro t e c t e d s c re e n s When configuring or changing settings, you will[...]
-
Página 24
16 80kW InfraStruXure PDU—Op eration and Configuration Load-Meter Scr een From the Load-Meter screen, you can select the following items: T otal Load by Phase The load supported by each phase in kV A, in RMS current ( Irms ), and as a percentage of the maximum allowable load ( %LD ). T otal Load Summary For the total load supported: • kW : The [...]
-
Página 25
80kW InfraStruXure PDU—Oper ation and Conf iguration 17 V olt-Meter Scr een From the V olt-Meter screen, you can select the following items: Output V oltage Displays each phase-to-phase output voltage (e.g., L1-2 for phase L1 to phase L2) and each phase-to-neutral output voltage (e.g., L1 for phase L1 to neutral). Input V oltage Displays each pha[...]
-
Página 26
18 80kW InfraStruXure PDU—Op eration and Configuration Contacts Scr een Overview The PDU can monitor external contact closure even ts. Possible applications include the following: • Magnetic contact switches • W indow foil • T amper sw itches • Heat detectors • W ater sens ors • Pressure sensors • Building smoke and fire detection s[...]
-
Página 27
PDU Display Interface 80kW InfraStruXure PDU—Oper ation and Conf iguration 19 . Alarm Relay Map Configure the relay output s, using the Alarm Relay Map. Each Alarm Map corresponds to an output relay . For example, Alarm Map 01of04 corresponds to the first of four relay outputs. The second line, in brackets [ ], lists the items that you have selec[...]
-
Página 28
PDU Display Interface 20 80kW InfraStruXure PDU—Op eration and Configuration How to connect contacts to the PDU monito ring unit 1. Choose one or more contact number on the User/EPO contacts port on the user co nnection plate to which you will connect the contacts. The user connection plate is connected to the PDU monitoring unit. 2. From the PDU[...]
-
Página 29
80kW InfraStruXure PDU—Oper ation and Conf iguration 21 Br eakers Scr een Use the Breakers screen to view the status of the system and PDU circuit breakers. UPS & System Bypass Reports the operation mode of the UPS and the state of the Q1, Q2, and Q3 circuit breakers on the PDU. Main Input Reports status of PDU Main Input Circuit Breaker ( Op[...]
-
Página 30
22 80kW InfraStruXure PDU—Op eration and Configuration Alarms Scr een View Active Alarms Use this option of the Al arms screen to display active alarms (alarm s that have not been resolved). Scroll through the list to view each active alarm. Alarm/Event Log Use this selection of the Alarms screen to access the following options: New Logged Items [...]
-
Página 31
PDU Display Interface 80kW InfraStruXure PDU—Oper ation and Conf iguration 23 Alarm Setup Use this option of the Al arms screen to access the following options: Alarm Beeper Use this option of the Al arms screen to turn the alarm beeper ON or OFF . Loading Limits Configure the following in amps and as a percentage of full l oad: • Out High : Th[...]
-
Página 32
PDU Display Interface 24 80kW InfraStruXure PDU—Op eration and Configuration PDU Alarms This table lists all alarms that can be generate d by the InfraStruXure P DU, as displayed by the All Possible Alarms option, with numeric variables between the < > characters. Logged alarms will display specific numbers instead. Alarm Condition Explanat[...]
-
Página 33
80kW InfraStruXure PDU—Oper ation and Conf iguration 25 Panel Scr een Branch Ckt Loading Y ou can display Branch Ckt Loading (Branch Circuit Loading) stat us if the option to measure current at the distribution breakers is installed. Y ou can view data for each individual panel positio n on the distribut ion panel. T o view status of a panel posi[...]
-
Página 34
PDU Display Interface 26 80kW InfraStruXure PDU—Op eration and Configuration Panel Configuration Configure the branch metering settings for each breaker on the distribution panel. The panel p o sition numbers on the screen correspond to the numbers on the distribution panel. (Odd numbers are on the left; even numb ers are on the right.) Once you [...]
-
Página 35
PDU Display Interface 80kW InfraStruXure PDU—Oper ation and Conf iguration 27 Global Panel Config Configures the same number of poles or breaker ra tings for all circuit breakers simultaneously . For example, if your system uses onl y 3-pole, 20-amp br eakers, choose this optio n, scroll to the value 3 for Poles and 020 for Amp Rating, and then s[...]
-
Página 36
28 80kW InfraStruXure PDU—Op eration and Configuration Config Scr e en System/Network Use this option of the Co nfig screen to access these options: System Password • Password : Change the system password required to access protected screens and fields in the display interface. Enter a string of up to eight alphanumeric characters, followed by [...]
-
Página 37
PDU Display Interface 80kW InfraStruXure PDU—Oper ation and Conf iguration 29 Electrical Config This option of the Config scre en displays informat ion about the e lectrical serv ice that provides input to the InfraStruXure PDU. All of th e values displayed on this screen are set at the factory . Use this information when viewing and setting alar[...]
-
Página 38
PDU Display Interface 30 80kW InfraStruXure PDU—Op eration and Configuration Manufactur er Data Use this option of the Co nfig screen to display a scrollable lis t containing inf ormation about the InfraStruXure PDU. This information is useful when requestin g service or product updates. The following information is displayed: • Manufacturer Na[...]
-
Página 39
80kW InfraStruXure PDU—Oper ation and Conf iguration 31 System Operation How to T ransfer the UPS into Maintenance Bypass Operation When servicing the UPS, transfer the UPS into maintenance bypass operation. When the UPS is operating in maintenanc e bypass, input power fl ows directly to the PDU and out to the load equipment. Note Select Help fro[...]
-
Página 40
System Operation 32 80kW InfraStruXure PDU—Op eration and Configuration Note The H3 LED above the Q3 circuit breaker illuminates, in dicating that it is safe to operate the Q3 circuit breaker . 2. Close (turn ON) the Q3 circuit breaker on the PDU. If you have a dual-fed system , check to ensure that power is available be fore operating the Q3 cir[...]
-
Página 41
System Operation 80kW InfraStruXure PDU—Oper ation and Conf iguration 33 The UPS is now in main tenance bypass operation. 5. Open (turn OFF) the XR Batte ry Enclosure DC Disconnect circuit breaker . 6. Open (turn OFF) the Q1 circuit breaker on the PDU. 7. If applicable, open (turn OFF) the PDU Q10 Bypass Input ( B ) switch.[...]
-
Página 42
34 80kW InfraStruXure PDU—Op eration and Configuration How to Return fr om Maintenance Bypass Operation Note Select Help from the top-level menu screen on th e PDU display interface and select the second help topic, Returning fr om PDU Maintenance Bypass , or follow the procedure below: 1. Close (turn ON) the Q1 circuit breaker on the PDU. 2. If [...]
-
Página 43
System Operation 80kW InfraStruXure PDU—Oper ation and Conf iguration 35 4. Close (turn ON) the UPS System Enable switch. The UPS will show a For ced Bypass message on the display interface, and the Fault LED will be red. 5. Command the UPS to ap ply power to the load: a. Press the E SC key at the top-le vel status screen to open the top-level me[...]
-
Página 44
System Operation 36 80kW InfraStruXure PDU—Op eration and Configuration c. Select UPS Into Bypass on the Control menu, and press the E NTER key . Control Menu d. Confirm the selection on the next screen: select Y es, UPS into Bypass , and press the E NTER key . Confirmation Scr een Note The H2 LED above the Q2 circuit breaker illuminates, indicat[...]
-
Página 45
80kW InfraStruXure PDU—Oper ation and Conf iguration 37 How to Ensur e T otal Power Off 1. Command the UPS to turn off power to the load: a. Press the E SC key at the top-le vel status screen to open the top-level menu an d have access to eight submenus. b. Select Control , and press the E NTER key . T op-Level Menu c. Select Tu r n L o a d O f f[...]
-
Página 46
System Operation 38 80kW InfraStruXure PDU—Op eration and Configuration 3. Set the XR Battery Enclosure DC Disconnect circuit breaker to the OFF position. 4. Pull out all battery un its in the XR Battery Enclosures to the red battery disconnect line. 5. Set the Main Input switch ( A ), and, if applicable, the Q10 Bypass Input switch ( B ), and Cr[...]
-
Página 47
80kW InfraStruXure PDU—Oper ation and Conf iguration 39 How to Apply Power to the System This procedure instructs on how to apply power to a system that has already been inst alled. For initial start-up instructions, see the InfraStruX ur e 80 kW Installation and S tart-Up manual. 1. Set the upstream utility , and, if applicable, the bypass input[...]
-
Página 48
System Operation 40 80kW InfraStruXure PDU—Op eration and Configuration 4. Ensure that all battery units are pushed all th e way into the XR Battery Enclosures and locked into position. 5. Set the XR Battery Enclosure DC Disconnect circuit breaker to ON. 6. Set the UPS System Enable switch to ON When the System Enable switch is placed in the ON p[...]
-
Página 49
System Operation 80kW InfraStruXure PDU—Oper ation and Conf iguration 41 7. Read the messages displayed on the UPS display interface: a. Note any alarms, and verify tha t they are appropriate for start-up conditions. b. V erify that the UPS accepts the input. T op-Level S tatus Scr een 8. Command the UPS to ap ply power to the load: a. Press the [...]
-
Página 50
System Operation 42 80kW InfraStruXure PDU—Op eration and Configuration 9. T o apply power to the PDU distribution panel, close (turn ON) the Q2 circuit breaker on the PDU . 10. T o apply po wer to the PDU power cords and connected equipment, close (turn ON) the distribution panel breake rs. 1 1. If applicable, close (turn ON) the Cr oss Tie Outp[...]
-
Página 51
80kW InfraStruXure PDU—Oper ation and Conf iguration 43 Communication Configuration InfraStruXur e PDU Management Options Overview Y ou have two management options for the InfraS t ruXure PDU. Y ou can ma nage the InfraStruXure PDU along with the rest of your InfraS truXure equipment through the Infra S t ruXure Manager (APC LAN), or you can mana[...]
-
Página 52
44 80kW InfraStruXure PDU—Op eration and Configuration Configuring the InfraStruXur e Manager Connect the InfraStruXur e PDU to the InfraStruXur e Manager 1. Connect a Cat-5 netw ork cable to the surge-protected etherne t port on the PDU user c onnection plate. Y ou can make connections from inside the enclosure, or you can remove the user connec[...]
-
Página 53
80kW InfraStruXure PDU—Oper ation and Conf iguration 45 Configuring the Network Management Interface Connect the InfraStruXur e PDU to your network 1. Connect a Cat-5 netw ork cable to the surge-protected etherne t port on the PDU user c onnection plate. Y ou can make connections from inside the enclosure, or you can remove the user connection pl[...]
-
Página 54
Communication Configu ration 46 80kW InfraStruXure PDU—Op eration and Configuration TCP/IP configuration methods Use one of the following methods to define the TCP/I P settings needed by the InfraS truXure PDU: • Device IP Configuration W izard (See “Devi ce IP Configuration W iza rd” on this page .) • BOOTP or DHCP server (See “BOOTP &[...]
-
Página 55
Communication Configu ration 80kW InfraStruXure PDU—Oper ation and Conf iguration 47 BOOTP & DHCP configuration The Boot Mode Setting, a TCP/IP option in the InfraS truXure PDU’ s Network menu, identifies how the TCP/IP settings will be defi ned. The possible settings are Manual , DHCP on ly , BOOTP only , and DHCP & BOOTP (the default [...]
-
Página 56
Communication Configu ration 48 80kW InfraStruXure PDU—Op eration and Configuration 3. When the InfraS truXure PDU reboots, the BOOTP server provid es it with the TCP/IP settings. – If you specified a bootup file name, the InfraStru Xure PDU att empts to transfer that file from the BOOTP server using TFTP or FTP . The InfraStruXure PDU a ssumes[...]
-
Página 57
Communication Configu ration 80kW InfraStruXure PDU—Oper ation and Conf iguration 49 Local access to the control console Y ou can use a local computer that connects to the InfraS truXure PDU through the co nsole port o n the InfraStruXure PDU monitoring un it to access the control console. 1. Select a serial port at the local computer , and disa [...]
-
Página 58
Communication Configu ration 50 80kW InfraStruXure PDU—Op eration and Configuration 2. Use Ping with a size of 1 13 bytes to assign the IP address defined by th e ARP command. For the IP address defined in step 1, use one of the following Ping commands: – W indows command format: ping 156.205.14.141 -l 113 – LINUX command format: ping 156.205[...]
-
Página 59
80kW InfraStruXure PDU—Oper ation and Conf iguration 51 How to Access a Network Management Interface on a Configur ed InfraStruXur e PDU We b i n t e r f a c e As your browser, you can use Microsoft ® Intern et Explorer 5.0 (and hig her) or Netscape ® 4. 0.8 (and higher , except Netscape 6. x ) to access the InfraSt ruXure PDU through its W eb [...]
-
Página 60
Communication Configu ration 52 80kW InfraStruXure PDU—Op eration and Configuration T elnet for basic access. T elnet provides the ba sic security of authentication by user name and password, but not the high-security benefits of encr yption. T o use T elnet to ac cess an InfraStruXure PDU’ s control console from any co mputer on th e same subn[...]
-
Página 61
Communication Configu ration 80kW InfraStruXure PDU—Oper ation and Conf iguration 53 FT P a n d S C P Y ou can use FTP (enabled by default) or Secure CoPy (SCP) to transfer new firmware to the InfraStruXure PDU, or to access a copy of the In fraS truXure PDU’ s event logs. SCP provides the higher security of encrypted data transmission and is e[...]
-
Página 62
54 80kW InfraStruXure PDU—Op eration and Configuration How to Recover Fr om a Lost Network Management Interface Passwor d 1. Select a serial port at the local computer , and disa ble any service that uses that port. 2. Connect the serial cable (APC part number 940- 0103) to the selected po rt on the computer a nd to the console port on the InfraS[...]
-
Página 63
80kW InfraStruXure PDU—Oper ation and Conf iguration 55 Customizing and Updating the PDU Important Safety Instructions Ele c tr ical Ha zard APC does not r ecommend that you perform maintenance of the P DU while it is receiving input p ower . However , due to the cr itical nature of data center loads, this may occur . If you must perform maintena[...]
-
Página 64
56 80kW InfraStruXure PDU—Op eration and Configuration PDU Or derable Part List Circuit Br eake rs PD1P20ABBSD single-pole, 20-amp breaker PD3P20ABBSD three-pole, 20 -amp breaker PD1P50ABBSD single-pole, 50-amp breaker PD3P80ABBSD three-pole, 80 -amp breaker PD2P20ABBSD two-pole, 20-amp breaker PD3P100ABBSD three-pole, 100-amp breaker PD2P30ABBSD[...]
-
Página 65
Customizing and U pdating the PD U 80kW InfraStruXure PDU—Oper ation and Conf iguration 57 Power Cables 30 A, 3-wire power cables PDW7L6-30C 7-foot power cable PDW43L6-30C 43-foot power cable PDW9L6-30C 9-foot power cable PDW45L6-30C 45-foot power cable PDW1 1L6-30C 1 1-foo t power cable PDW47L6-30C 47-foot power cable PDW13L6-30C 13-foot power c[...]
-
Página 66
58 80kW InfraStruXure PDU—Op eration and Configuration How to Add Cir cuit Br eakers and Power Cables Add a cir cuit br eaker on the PDU 1. Snap and bolt the new circuit breake r into a position on the panel. 2. Remove the corresponding plastic blanking plate on the front panel of the PDU. Add a power ca ble to the PDU or RDP Before adding a powe[...]
-
Página 67
Customizing and U pdating the PD U 80kW InfraStruXure PDU—Oper ation and Conf iguration 59 4. At the front of the PDU, connect the power cord’ s individual wires: a. If you have branch current monitoring insta lle d, route the phase conductor through a cur rent sensor . If it is a three-phase cabl e , route the L1, L2, and L3 wi res through a c[...]
-
Página 68
60 80kW InfraStruXure PDU—Op eration and Configuration How to T est the EPO Switch Overview After a certified electrician has co nnected an EPO sw itch to the PDU monitoring unit by way o f the user connection plate, you can easily test the switch to make sure it is wired and working properly . The illustration below shows the EPO functio ns on t[...]
-
Página 69
Customizing and U pdating the PD U 80kW InfraStruXure PDU—Oper ation and Conf iguration 61 4. If the test was successful, place the Arm/T est rocker switch back to the Arm position. The PDU display interface will clear the EPO test mo de alarm. If the test was not successful, see the troubleshooting chart: 5. Repeat this test for each EPO switch [...]
-
Página 70
Customizing and Updating th e PDU 62 80kW InfraStruXure PDU—Op eration and Configuration If you choose to use a 24 V AC, 24 VDC, or co ntact closure connection to the EPO, us e one of the following UL-listed wire types: • CL2 Class 2 cable for genera l purpose use • CL2P Plenum cable for use in ducts, plenums, and other space used for environ[...]
-
Página 71
80kW InfraStruXure PDU—Oper ation and Conf iguration 63 How to Connect User Input Contacts and Relay Outputs to the PDU User Connection Plate Overview Make contact closure connections (NO or NC) at the us er connection plate to monito r dry contacts . Y ou can make eight co nnections—four inpu t contacts and four relay outputs. The figure at th[...]
-
Página 72
Customizing and Updating th e PDU 64 80kW InfraStruXure PDU—Op eration and Configuration How to connect contacts to the PDU monitoring unit. 1. Choose one or more contact numbers on the User/EPO contacts port on the user connection plate to w hich you will connect t he contacts . The user connection plate connects to the PDU monitoring unit. 2. F[...]
-
Página 73
80kW InfraStruXure PDU—Oper ation and Conf iguration 65 How to Download Firmwar e Upgrades Upgrading the PDU monitor pr ocessor Y ou can download available PDU monitor processo r upgrades through the PDU displa y interface. The most obvious indication that a firmware upgrade is necessary occurs when the Network Management Card and the monito r pr[...]
-
Página 74
Customizing and Updating th e PDU 66 80kW InfraStruXure PDU—Op eration and Configuration 5. Enter your User Name and Password (both apc , for administrators only) and press the E NTER key . 6. From the Control Console menu, select System , then To o l s , then File T ransfer , then XMODEM . 7. The system will then prompt you with Perform transfer[...]
-
Página 75
80kW InfraStruXure PDU—Oper ation and Conf iguration 67 Specifications 80 kW InfraStruXur e PDU Performance T ransformer Ef ficiency (if installed) 97% System Full Load Ou tput Rating 80kW System Monitoring Of Current Distribution branch monitoring (op tional), subfeed Of V oltage AC main input, bypass input, output at distribut ion panels, outpu[...]
-
Página 76
Specifications 68 80kW InfraStruXure PDU—Op eration and Configuration Power Cables to Encl osures/ Rack PDUs 4W + G 4W + G 4W + G Power Cable Connecti ons L21-20 L21-20 L21-20 Power Cable Lengths V arious V arious V arious Power Cable W iring (T op Exit) Accommodates 10 + cables Power Cable W iring (Bottom Exit) Accommodates 10 + cables Subfeed S[...]
-
Página 77
Specifications 80kW InfraStruXure PDU—Oper ation and Conf iguration 69 Shipping with a Transformer 2200 lb (1000 kg) Shipping wit hout a T ransformer 1384 lb (628 kg) Service Access Front and rear Clearance 208 V : Greater than or equal to 36 in (914 mm) 480 V : Greater than or equal to 42 in (1067 m m) T ransformer (if installed) T ype Isolation[...]
-
Página 78
[...]
-
Página 79
80kW InfraStruXure PDU—Oper ation and Conf iguration 71 Pr oduct Information InfraStruXur e Standar d W arranty APC warrants that all components of the InfraS truXure system will be free from defect in material and workmanship for a period of two years from th e date of start up when start up has been performed by APC authorized service personnel[...]
-
Página 80
Product Informati on 72 80kW InfraStruXure PDU—Op eration and Configuration THERE ARE NO W ARRANTIES, EXPRESS OR IMPLIED, BY OPERA T ION OF LA W OR OTHER WISE, OF PRODUCTS SOLD, SER VICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED W ARRANTIES OF MERCHANT ABILITY , SA TISF ACTION AND FITNESS FOR A P AR T[...]
-
Página 81
80kW InfraStruXure PDU—Oper ation and Conf iguration 73 Life-Support Policy APC Thr ee-Phase Systems As a general policy , American Po wer Conversion Corporation and its affiliates and subsidiaries worldwide (APC) do not recommend th e use of any of its products in life support applications where failure or malfunction of the APC product can be r[...]
-
Página 82
80kW InfraStruXure PDU—Oper ation and Conf iguration 74 How to Obtain Service How to contact APC Customer support for this or any other APC product is available at no charge in any of the following ways: • V isit the APC W eb site to access documents in the APC Knowledge Base and to submit any customer support requests. – www .apc.com (Corpor[...]
-
Página 83
InfraStruXure PDU—Operation and Maintenance 75 Appendix Changes in This Manual Overview The following list references the sp ecific changes made to this manual since its last release (990-1468B). General Changes Updated manual to reflect the InfraS truXu re PDU’ s network management capabilities. Changes by page number Page 1 1 Added section de[...]
-
Página 84
[...]
-
Página 85
Index 80kW InfraStruXure PDU—Operation and Configuration 77 A Access to the control console , 49 to the PDU through FTP , 53 to the PDU through SCP , 53 to the PDU through SNMP , 52 Access holes, for cables , 6 Active alarms , 22 Add circuit breakers and power cables, how to , 58 – 59 Agency approvals , 69 Alarm beeper , 23 Alarm LED , 13 Alarm[...]
-
Página 86
78 80kW InfraStruXure PDU—Operation and Configuration F Factory defa ults, resett ing the , 30 Firmware updates, how to download , 65 Front view door open , 8 exterior , 6 interior , 7 FTP access to the PDU , 53 Fuses , 7 G Global Panel Config , 27 Ground bar, location of , 59 Ground lugs , 7 Ground wire, location of , 59 I InfraStruXure Manager [...]
-
Página 87
80kW InfraStruXure PDU—Operation and Configuration 79 Specifications , 67 – 69 electrical , 67 performance , 67 voltage , 67 wiring , 68 SSH, for accessing a network management interface , 52 Switches arm/test rocker , 10 bypass input , 7 EPO DIP , 10 main input , 7 System ID , 30 T TCP/IP configuration methods , 46 Telnet, for accessing a netw[...]
-
Página 88
[...]
-
Página 89
[...]
-
Página 90
[...]
-
Página 91
[...]
-
Página 92
*990-1468C* APC W orldwide Customer Support Customer support for thi s or any other APC product is available at no char ge in any of the following ways: • V isit the APC W eb site to acce ss documents in the APC Knowledg e Base and to submit customer support requests. – www .apc.com (Corporate Headquarters) Connect to localized APC W eb sites f[...]