Generac Power Systems 05176-0 manual
- Consulta online o descarga el manual de instrucciones
- 52 páginas
- 3.68 mb
Ir a la página of
manuales de instrucciones parecidos
-
Portable Generator
Generac Power Systems UL 2200
4 páginas 0.39 mb -
Portable Generator
Generac Power Systems SG020
4 páginas 0.23 mb -
Portable Generator
Generac Power Systems 0043733
64 páginas 4.31 mb -
Portable Generator
Generac Power Systems 004992-0, 004992-1
48 páginas 5 mb -
Portable Generator
Generac Power Systems 04673-2
56 páginas 5.14 mb -
Portable Generator
Generac Power Systems SG025
4 páginas 0.23 mb -
Portable Generator
Generac Power Systems 005262-1
64 páginas 5 mb -
Portable Generator
Generac Power Systems 75
92 páginas 8.4 mb
Buen manual de instrucciones
Las leyes obligan al vendedor a entregarle al comprador, junto con el producto, el manual de instrucciones Generac Power Systems 05176-0. La falta del manual o facilitar información incorrecta al consumidor constituyen una base de reclamación por no estar de acuerdo el producto con el contrato. Según la ley, está permitido adjuntar un manual de otra forma que no sea en papel, lo cual últimamente es bastante común y los fabricantes nos facilitan un manual gráfico, su versión electrónica Generac Power Systems 05176-0 o vídeos de instrucciones para usuarios. La condición es que tenga una forma legible y entendible.
¿Qué es un manual de instrucciones?
El nombre proviene de la palabra latina “instructio”, es decir, ordenar. Por lo tanto, en un manual Generac Power Systems 05176-0 se puede encontrar la descripción de las etapas de actuación. El propósito de un manual es enseñar, facilitar el encendido o el uso de un dispositivo o la realización de acciones concretas. Un manual de instrucciones también es una fuente de información acerca de un objeto o un servicio, es una pista.
Desafortunadamente pocos usuarios destinan su tiempo a leer manuales Generac Power Systems 05176-0, sin embargo, un buen manual nos permite, no solo conocer una cantidad de funcionalidades adicionales del dispositivo comprado, sino también evitar la mayoría de fallos.
Entonces, ¿qué debe contener el manual de instrucciones perfecto?
Sobre todo, un manual de instrucciones Generac Power Systems 05176-0 debe contener:
- información acerca de las especificaciones técnicas del dispositivo Generac Power Systems 05176-0
- nombre de fabricante y año de fabricación del dispositivo Generac Power Systems 05176-0
- condiciones de uso, configuración y mantenimiento del dispositivo Generac Power Systems 05176-0
- marcas de seguridad y certificados que confirmen su concordancia con determinadas normativas
¿Por qué no leemos los manuales de instrucciones?
Normalmente es por la falta de tiempo y seguridad acerca de las funcionalidades determinadas de los dispositivos comprados. Desafortunadamente la conexión y el encendido de Generac Power Systems 05176-0 no es suficiente. El manual de instrucciones siempre contiene una serie de indicaciones acerca de determinadas funcionalidades, normas de seguridad, consejos de mantenimiento (incluso qué productos usar), fallos eventuales de Generac Power Systems 05176-0 y maneras de solucionar los problemas que puedan ocurrir durante su uso. Al final, en un manual se pueden encontrar los detalles de servicio técnico Generac Power Systems en caso de que las soluciones propuestas no hayan funcionado. Actualmente gozan de éxito manuales de instrucciones en forma de animaciones interesantes o vídeo manuales que llegan al usuario mucho mejor que en forma de un folleto. Este tipo de manual ayuda a que el usuario vea el vídeo entero sin saltarse las especificaciones y las descripciones técnicas complicadas de Generac Power Systems 05176-0, como se suele hacer teniendo una versión en papel.
¿Por qué vale la pena leer los manuales de instrucciones?
Sobre todo es en ellos donde encontraremos las respuestas acerca de la construcción, las posibilidades del dispositivo Generac Power Systems 05176-0, el uso de determinados accesorios y una serie de informaciones que permiten aprovechar completamente sus funciones y comodidades.
Tras una compra exitosa de un equipo o un dispositivo, vale la pena dedicar un momento para familiarizarse con cada parte del manual Generac Power Systems 05176-0. Actualmente se preparan y traducen con dedicación, para que no solo sean comprensibles para los usuarios, sino que también cumplan su función básica de información y ayuda.
Índice de manuales de instrucciones
-
Página 1
PO WER SY STEMS, INC. ® Installation and Owner’ s Man ual Air -cooled A utomatic Standb y Generators Model: 05176-0 (13 kW NG, 15 kW LP) D ANGER DEADL Y EXHAUST FUMES. OUTDOOR INST ALLA TION ONL Y!! Not intended f or use as Primary P ower in place of utility or in life-support applications. GENERA C POWER SYSTEMS, INC. R R *This manual shoul[...]
-
Página 2
I NTRODUCTION Thank you for purchasing this model by Generac P ower Systems Inc.. This model is a compact, high performance, air - cooled, engine - driven generator designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather , metal enclosure that is in[...]
-
Página 3
T able of Cont ents Air-cooled 1 5 kW Generators 1 Introduction ........................ Inside F ront Cover Read This Manual Thoroughly ........................ IFC Contents .......................................................... IFC Operation and Maintenance ............................ IFC How to Obtain Service ...............................[...]
-
Página 4
2 Study these SAFETY RULES carefully before install- ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely , efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental ru[...]
-
Página 5
3 ELE CTR ICAL HA Z AR DS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion. A void contact with bare wires, terminals, connections, e[...]
-
Página 6
D ANGER Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. 1.1 U N P ACKING/I NSP ECTION After unpacking, carefully inspect the contents for damage. • This standby generator set has been factory sup - plied with a weather protective enclosu[...]
-
Página 7
Section 1 — General Information Air-cooled 1 5 kW Generators 5 1.4 TH E GEN ER A T OR Exh aust En c lo su r e O il Filte r Batter y Com p artmen t F uel Inl et C ontro l P a n el D a t a D ecal O i l Di p stic k F uel Re g ulato r Com p osite Bas e Figure 1.1 – 15 kW , V -twin GT -990 Engine A U T O MATI C TRAN S FE R S WIT CH Figure 1.2 – 15[...]
-
Página 8
6 Section 1 — General Information Air-cooled 1 5 kW Generators 1.5 SP E CI F ICA TIONS 1.5.1 GEN ERA T OR Rated Max. Continuous P ower Capacity (W atts*) .......................... 13,000 NG/15,000 LP Rated V oltage........................................................ 120/240 Rated Max. Continuous Load Current (Amps) 120 V olts + .............[...]
-
Página 9
7 4. Remove the engine air in baffle located on the left - hand side of the battery compartment. T wo M6 screws are located on top of the baffle and two M6 screws are located on the inside of the baffle towards the back. 5. Remove the small hose clamp and hose from the fuel regulator . It may be necessary to pry the hose off of the brass fitting us[...]
-
Página 10
Remote monitoring functions are only available with the A UTO/OFF/MANU AL switch in the Auto or Manual position. Since the contacts are SPDT , it is possible to monitor either state of each alarm function. Relay 1: Engine running, normally closed. Engine not running, normally open Relay 2: T ransfer Switch in Emergency , normally closed Transfer Sw[...]
-
Página 11
9 Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol- lows 1. Connect UTILITY (NORMAL) power source cables to switch terminals N1, N2. 2. Connect customer LOAD leads to switch termi- nals T1, T2. Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of[...]
-
Página 12
10 Figure 2.4 – Battery Cable Connections NOTE: The generator is equipped with a battery trickle charger that is active when the unit is set up for automatic operation. W ith the battery installed and utility power source voltage available to the transfer switch, the battery receives a trickle charge while the engine is not running , to prevent s[...]
-
Página 13
11 3. Check utility power source voltage across termi- nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line -to - neutral voltage should be 120 volts AC. 4. When certain that utility supply voltage is compat- ible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transf[...]
-
Página 14
12 3.5 CH E CKI NG AUT OMA TIC OP ER A TION T o check the system for proper automatic operation, proceed as follows: 1. Set the generator’s main circuit breaker to it ’s OFF (or open) position. 2. Check that the AUTO/OFF/MANU AL switch is set to OFF . 3. Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to[...]
-
Página 15
13 Section 3 — Post Installation Start-up and Adjustments Air-cooled 1 5 kW Generators 7. T urn utility power to the main distribution panel back on. This can be done by switching the ser - vice main breaker to the on or closed position. Allow the generator to shut down. Do not make any unnecessary adjustments. Factory settings are corr ect f[...]
-
Página 16
14 Section 4 — Operation Air-cooled 1 5 kW Generators 4.1 USI NG TH E AUT O/OF F/MAN UAL SWIT CH (F IGU R E 4.1) 4.1.1 “ AUT O” POSITION Selecting this switch position activates fully automatic system operation. It also permits starting and exercising of the engine every seven days with the exercise timer (see "Generator T est Under Load[...]
-
Página 17
15 • Retransfer to utility power source then occurs. F . Engine Cool- down Timer • When the load is transferred back to utility power source, the engine cool- down timer starts tim- ing . • The timer will run for about one minute, and the generator will then shut down. 4.4 MAN U AL OP ER A TION D ANGER Do NOT manually transfer under load.[...]
-
Página 18
16 4.4.2 CL OSE T O EM ERGENCY SOURCE SI DE Before proceeding, verify the position of the switch by observing the position of the manual operation handle in Figure 4.2. If the handle is DOWN , the contacts are closed in the EMERGENCY (ST ANDBY) position. No further action is required. If the handle is UP , proceed with Step 1. Step 1: With the hand[...]
-
Página 19
17 7. Move the switch's main contacts back to their UTILITY position. F or example, load connected to UTILITY power supply . Refer to "Manual Operation". Handle and operating lever of trans- fer switch should be in UP position. 8. T urn on the UTILITY power supply to transfer switch, using whatever means provided (such as a UTILITY m[...]
-
Página 20
18 4.8.3.1 Approximat e Crank Cycle Times • 15 seconds ON • 7 seconds OFF • 7 seconds ON • 7 seconds OFF • Repeat for 45 seconds Approximately 90 seconds total 4.8.4 OVERSPEED This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gen- erator[...]
-
Página 21
19 Figure 5.3 – Oil Drain Hose and Filter Oil Filter Oil Drain Ho s e L o o s e n 3. After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip. 4. Refill with the proper recommended oil (see "Changing the Engine Oil"). See the "Specifications" section for oil capacities. 5.4 CHA[...]
-
Página 22
20 5.7 B A T TER Y MAI NTENANCE The battery should be inspected per the “Service Schedule”. The following procedure should be fol- lowed for inspection: 1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary . 2. Check the battery fluid level of unsealed batteries and, if necessary , fill with DISTIL[...]
-
Página 23
21 When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change. Figure 5.6 - V alve Clearance Adjustment Jam Nut Pivot Ball Stud Rock er Arm V alve Stem • [...]
-
Página 24
22 5.1 2.2 R ETUR N T O SERVICE T o return the unit to service after storage, proceed as follows: 1. Set the generator’s main circuit breaker to its OFF (or OPEN) position. 2. V erify that utility power is turned off and that the A UTO/OFF/MANU AL switch is set to OFF . 3. Check the tag on the engine for oil viscosity and classification. V erify [...]
-
Página 25
23 Section 5 — Maintenance Air-cooled 1 5 kW Generators 7 KW - 40 KW SMALL ST ANDBY GENER A T OR SET S F ollowing is a recommended maintenance schedule for small standby and residential generator sets from 7 kW to 40 kW in size, and applies to gas engine driven units. The established intervals in the schedule are the maximum recommended when the [...]
-
Página 26
24 Maintenance Level 1 Level 2 Level 3 Level 4 Level5 T asks Recom- T ask T ask Required T ask T ask Required T ask mended Comp. Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- Required (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) to be done Initials) annually/ Initials) Annually/ Initials) annually/ [...]
-
Página 27
25 Maintenance Level 1 Level 2 Level 3 Level 4 Level5 T asks Recom- T ask T ask Required T ask T ask Required T ask mended Comp. Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- Required (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) to be done Initials) annually/ Initials) Annually/ Initials) annually/ [...]
-
Página 28
26 Maintenance Level 1 Level 2 Level 3 Level 4 Level5 T asks Recom- T ask T ask Required T ask T ask Required T ask mended Comp. Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- Required (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) to be done Initials) annually/ Initials) Annually/ Initials) annually/ [...]
-
Página 29
27 Section 6 — T roubleshooting Air-cooled 1 5 kW Generators 6.1 TROU B LE SHOO TI NG GU I DE Problem Cause Correction The engine will not crank. 1. F use blown 1. Replace 15A fuse on generator control panel. 2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary . 3. Defective starter motor 3. * 4. Dead Battery [...]
-
Página 30
28 Section 7 — Mounting Dimensions Air-cooled 1 5 kW Generators Drawing No. 0F592 7[...]
-
Página 31
29 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Wiring Diagram – Drawing No. 0F5 643-B Part 1 TR - RELAY , TRANSFE R CUS T O MER SU PPLIE D BLA CK BATTERY 12V 0 HT O S P 2 S P 1 L OP 0 86 85 IM2 85 IM1 D D BA - BR US H A SS EMBL Y DIA G RAM KE Y CB2 - CIRCUIT BREAKER , ALTERNATOR EXCITATIO N C B1 - MAIN OU TP U T BREAKE R B C R - BA[...]
-
Página 32
G R D G R D 22 5 22 5 224 224 1 5 224 225 0 2 39 1 5A 66A 2 3 1 94 4 14 0 22 5B 224B 1 3A 0 1 1 C L OS E S T T O BEARIN G 0 66 77 4 4 0 F2 1 5 1 3 RE GU LAT OR V O LTA GE 1 94 2 3 N1 N1 4 66A N2 351 N2 N1 162 6 0 0 0 66A 6 1 62 0 MAN U A L S W 2 A U T O S W 1 1 b 1 1 a 0 351 C B 1 0 0 0 0 55 0 0 11 44 55 C2 3 2 1 66 1 3A 22 5B 224B TX 224 22 5 224A[...]
-
Página 33
31 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Wiring Diagram – Drawing No. 0F5 643-B Part 3 G R D CO M + RY5- RY1+ RY 3+ RY4- COM - RELAY B O AR D S I G NAL S REM O T E N1 N2 F4 1 94 T S N1A N1A N2A N1A N1 A N2A 1 94 2 3 N1A TR N2A N1 A E2 1 94 N1A 2 05 E2 2 3 12 6 1 2 05 N1A N2A N2 N1 194 2 3 N1 N2 1 94 1 5B A2 1 5A A2 22 9 147 1[...]
-
Página 34
32 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Electrical Schematic – Drawing No. 0F5844-B C HAR G E R BATTERY 1 62 22 V O LTA GE RE GU LAT OR ELE C TR O NI C 6 4 0 11 ( STATOR ) DPE WINDIN G C 2- 8 2 C 2- 7 C B 2 4 0 6 BA FIELD 1 3A 1 1 0 77 C 2- 1 3 1 2 C 1- 3 4 14 11 1 6 17 12 1 3 1 5 14 C 2- 3 PRINTED C IR CU I T 0 C 1- 6 C 2- [...]
-
Página 35
33 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Electrical Schematic – Drawing No. 0F5844-B SM C 1- 1 C 1- 5 SCR 0 0 0 1 6 0 1 8 D D IM2 IM1 S P 2 S P 1 1 6 0 SC 0 S W 1 1 5A 1 5 1 94 F S 0 14 WINDIN G ( STATOR ) P O WE R 22 44 11 C B 1 33 C 2- 5 C 2- 6 CUS T O ME R SU PPLIE D BATTERY 12 V BLA CK RED SC N1 TR N O XA 1 A COM CO I L B[...]
-
Página 36
34 47 54 7 2 2 2 0 49 4 9 4 3 43 36 4 37 2 5 35 32 34 35 2 6 53 74 4 6 51 8 7 8 80 39 81 1 8 52 44 63 1 5 51 2 1 71 69 42 1 0 41 7 3 49 9 51 4 9 11 0 72 7 9 5 2 7 35 4 9 44 5 56 1 57 1 9 52 47 4 0 69 50 22 65 1 2 68 1 4 7 5 4 9 71 55 17 30 68 67 3 35 25 2 8 1 2 9 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators Enclosure ?[...]
-
Página 37
35 ITEM P ART NO . QTY . DESCRIPTION 1 0C6140 1 A SS EMBL Y , ENCLO S URE BA S E 2 0C67 3 5 2 S UPPORT , ROOF FOLDING 3 0F006 3 1 ENCLO S URE, FRONT 4 0C7062 1 ENCLO S URE, EXHA U S T S IDE 5 0F562 9 1 ENCLO S URE, S IDE & BACK 6 0E 98 7 3 1 ENCLO S URE, ROOF 7 0C7065 1 P ANEL, AL TERNA TOR DIVIDER 8 0C 8 101A 1 P ANEL, MUFFLER BO X S IDE 9 0C [...]
-
Página 38
36 3 1 19 3 7 38 22 8, 9 27 45 46 44 28 47 10 25 3 2 5 14 13 17 23 34 15 21 35 20 4 15 29 5 13 38 6 7 23 25 12 27 40 41 36 39 45 44 43 1 30 15 11 47 45 24 45 47 50 49 48 5 1 53 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators Control Panel – Drawing No. 0F5 846[...]
-
Página 39
37 ITEM P ART NO . QTY . DESCRIPTION 1 0E7 88 6G 1 CIRCUIT BREAKER 70A X 2P 240V (15KW) 2 0A1 8 01 1 A SS EMBL Y , BA TTER Y CHARGER ENGINE 3 0 83 04 9 1 A SS EMBL Y , POTTED REGULA TOR 4 0C2174 1 RELA Y , 12V 25A S P S T 5 075210A 2 BLOCK 1 PO S ITION 6 0D 3 062 4 HEX S T AND-OFF #6- 3 2 x 3 / 8 " 7 0D 8 615 1 A SS EMBL Y , HOME S T ANDBY CON[...]
-
Página 40
38 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators GT -990 Eng ine – Drawing No. 0E8 7 7 4-Q Part 1[...]
-
Página 41
39 ITEM P ART NO. QTY . DESCRIPTION 1 0C572 9 1 A SS EMBL Y , CRANKCA S E HOU S ING WITH S LEEVE 2 0E 98 4 3 1 S EAL, 38 I.D . CRANK S HAFT 3 0 9 0 388 3 S CREW , T APTITE M6-1.0 X 12 YC 4 0C5 3 72 1 A SS EMBL Y , BREA THER 5 0C 3 005 1 GA S KET , BREA THER CO VER 6 0E 33 72B 1 S EP ARA TOR, OIL BREA THER 7 0D 8 067A 1 A SS EMBL Y , HEAD #1 G& [...]
-
Página 42
40 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators GT -990 Eng ine – Drawing No. 0E8 7 7 4-Q Part 2[...]
-
Página 43
41 ITEM P ART NO. QTY . DESCRIPTION 74 0C51 3 6A 2 KNOB, AIR CLEANER 75 0C 3 024 1 CO VER, AIRBO X NG/LP 76 0C 3 040 1 PRE-CLEANER, 77 0C 8 127 1 ELEMENT , AIR CLEANER 7 8 0D 8 564A 1 A SS EMBL Y , MIXER/AIRBOX 99 0 0D 8 564B 1 A SS EMBL Y , MIXER/AIRBO X 760 7 9 0D25 9 5 4 S CREW S HOULDER ( 8 MM) M6-1.0 X 1 8 8 0 0D4417 4 W A S HER,R UBBER 1/4&qu[...]
-
Página 44
42 2 9 3 6 3 4 11 2 3 5 24 4 3 21 7 1 3 33 12 38 17 3 2 3 1 2 8 3 1 20 1 9 10 17 15 3 2 16 22 39 4 9 8 6 3 7 14 3 2 40 1 3 2 24 25 10 3 0 1 9 26 2 8 27 2 8 3 2 3 1 41 10 1 8 3 6 2 8 3 5 41 2 9 42 3 6 3 6 3 5 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators 1 5 kW Generator – Drawing No. 0D34 1 7 -L[...]
-
Página 45
43 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators 1 5 kW Generator – Drawing No. 0D34 1 7 -L ITEM P ART NO . QTY . DESCRIPTION 1 0C6 93 4 1 AD APT OR, ENGINE 2 0C7 93 0 1 S T A T OR 12KW 0D2 3 5 9 S TAT O R 1 3 KW / 15KW 3 0C7 9 44 1 RO T OR 12KW 0D2 3 56 RO T OR 1 3 KW / 15KW 4 0C604 3 1 CARRIER, REAR BEARING 5 0D2 33[...]
-
Página 46
44 7KW 17 12 2 8 11 20 10 25 21 24 1 9 2 3 22 22 15 26 14 1 3 16 2 9 1 8 8 2 8 12 3 2 10 11 27 3 1 4 5 3 2 10 17 1 26 15 14 16 1 3 3 7 1 9 9 3 0 21 25 20 24 2 9 1 8 2 3 11 12 2 8 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators Gas Regulator – Drawing No. 0D8 7 20-H[...]
-
Página 47
45 ITEM P ART NO . QTY . DESCRIPTION 1 0D56 9 4 1 CA S TING, TWIN REGULA T OR HOU S ING 2 0F5022 1 S OLENOID COIL, 12VDC 3 0C4647 1 GA S KET , S OLENOID 4 0D4166 1 PLUNGER, LP REGULA TOR A SS EMBL Y 5 0C6070 1 S PRING- S OLENOID , PLUNGER 8 0F47 9 5 4 S CREW PPHM S EM S M4-0.7 X 10 9 0C5760J 1 JET , GN 410 ENGINE LP (7KW) 10 0C6606 2* BARBED S TRAI[...]
-
Página 48
46 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators T ransfer Switch – Drawing No. 0F563 3$-A[...]
-
Página 49
47 ITEM P ART NO . QTY . DESCRIPTION 1 0D 9 61 8 1 TR S W- H S B 200A 2P 250V 2 0E 33 75 6 LUG S LDL SS 250-#6 AL/CU 3 0F1252 6 S CREW BH S C 1/4-20 X 3 / 8 4 0220 9 7 6 W A S HER LOCK M6-1/4 5 074 9 0 8 5 S CREW HHTT M5-0. 8 X 16 BP 6 045771 1 NUT HEX M 8 -1.25 G 8 YEL CHR 7 057 3 2 9 1 LUG S LDL SS 3 50-#6 X 1 3 / 3 2 AL/CU 8 0274 8 2 1 W A S HER[...]
-
Página 50
48 CALI FOR N IA EM IS SION CONTROL W ARR ANT Y ST A TEM ENT Y OUR W AR R ANTY R IGHTS AND OB LIGA TIONS The California Air Resources Board (CARB) and Generac P ower Systems, Inc. (Generac) are pleased to explain the Emission Control System W arranty on your new engine. * In California, new utility , and lawn and garden equipment engines must be de[...]
-
Página 51
49 EM IS SION CONTROL S Y STEM W AR RANT Y Emission Control System W arranty (ECS W arranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS W arranty P eriod shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purcha[...]
-
Página 52
Part No. 0F5631 Revision C (12/07/06) Printed in U.S.A. Section 1 0 – W arranty Air-cooled 1 5 kW Generators GENERA C PO WER SYSTEMS ST ANDARD LIMITED W ARRANTY FOR HOME ST ANDBY/LIGHT COMMERCIAL PRODUCT 45kW AND BELO W For a period of two (2) y ears from the date of sale, or start-up by Authorized/Certified Generac P ower Systems Dealer , or bra[...]