A.O. Smith 402 manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 48 pages
- 1.01 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Water Heater
A.O. Smith ADM - 115
74 pages 3.01 mb -
Water Heater
A.O. Smith TWI 35-130
62 pages 2.45 mb -
Water Heater
A.O. Smith SERIES 100
40 pages 0.73 mb -
Water Heater
A.O. Smith KEN/SE-66
2 pages 1.46 mb -
Water Heater
A.O. Smith ECT-66
28 pages 0.47 mb -
Water Heater
A.O. Smith BTI - 100
2 pages 0.1 mb -
Water Heater
A.O. Smith 201 Series
3 pages 1.25 mb -
Water Heater
A.O. Smith BTI - 65
6 pages 0.49 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation A.O. Smith 402. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel A.O. Smith 402 ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation A.O. Smith 402 décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation A.O. Smith 402 devrait contenir:
- informations sur les caractéristiques techniques du dispositif A.O. Smith 402
- nom du fabricant et année de fabrication A.O. Smith 402
- instructions d'utilisation, de réglage et d’entretien de l'équipement A.O. Smith 402
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage A.O. Smith 402 ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles A.O. Smith 402 et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service A.O. Smith en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées A.O. Smith 402, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif A.O. Smith 402, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation A.O. Smith 402. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
1 PRINTED IN U.S.A. 0906 COPPER BOILERS FOR HYDRONIC HEA TING AND HOT W A TER SUPPL Y CAUTION TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE INST ALLING AND USING THIS APPLIANCE. 21251 1-000 MC BEE, SC., RENTON, W A., STRA TFORD-ONT ARIO, VELDHOVEN-THE NETHERLANDS, NANJING , CHINA w [...]
-
Page 2
2 DIMENSIONS/CAP ACITIES DA T A Figure 1. IMPORT ANT! Refer to "Installation Clearances" section of manual (page 7) for recommended service clearances prior to boiler placement. TOP VIEW LEFT SIDE T ABLE 2. DIMENSIONAL DA T A AB CD E F Model Inches c m Inches c m Inches c m Inches c m Inches c m Inches c m GW/GB-1000 14.1 35.8 12.2 31.0 4[...]
-
Page 3
3 DIMENSIONS DA T A FOR OUTDOOR CONFIGURA TION Figure 2. T ABLE 3. DIMENSIONAL DA T A AB C D E F G H J Model Inches cm Inches cm Inches cm Inches cm Inches cm Inches cm Inches cm Inches cm Inches c m GBO/GWO-1000 14 35.5 31.6 80.3 71.8 182.4 15.5 39.4 39.75 101 58.25 148 15.9 40.83 16 40.64 46.8 1 18.9 GBO/GWO -1300 24.75 62.9 31.6 80.3 82 208.3 15[...]
-
Page 4
4 TABLE 5: PUMPING PERFORMANCE GUIDE TABLE 4: RECOVER Y CAP ACITIES TEMPERA TURE RISE - DEGREES °F (°C) Input Rating Water 40°F 50°F 60°F 70°F 80°F 90°F 100°F 1 10°F 120°F 130°F MODEL BTU/Hr . (kW) Flow (22.2°) (27.7°) (33.3°) (38.8°) (44.4°) (50°) (55.5°) (61.1°) (66.7°) (72.2°) GW - 1000 990,000 (290.1) G P H 2520 2016 1680 [...]
-
Page 5
5 At times you may not be able to smell an LP gas leak. One cause is odor fade, which is a loss of the chemical odorant that gives LP gas its distinctive smell. Another cause can be your physical condition, such as having a cold or diminishing sense of smell with age. For these reasons, the use of a propane gas detector is recommended. IF YOU EXPER[...]
-
Page 6
6 DIFFERENTIAL PRESSURE SWITCH The differential pressure switch ensures that a suf ficient differential exists between the air pressure in the pre-mix chamber and the inlet of the burner for safe, combustion and proper low NO x emission. The switch has two pressure tap s marked "+" (positive) and "-" (negative). Silicone tubing [...]
-
Page 7
7 DRAIN V AL VE (Not Supplied) Additional drain valves must be obtained and inst alled on each boiler and tank for draining purposes. SAFETY RELIEF V AL VES Y our local code authority may have other specific relief valve requirements not covered below . W ARNING THE PURPOSE OF A SAFETY RELIEF V AL VE IS TO A VOID EXCESSIVE PRESSURE WHICH MA Y CAUSE[...]
-
Page 8
8 the authority having jurisdiction, must be provided with a low water cutoff device either as a part of the boiler or at the time of boiler installation. W ARNING UNDER NO CIRCUMST ANCES SHOULD THE EQUIPMENT ROOM WHERE THE BOILER IS INST ALLED EVER BE UNDER NEGA TIVE PRESSURE. P ARTICULAR CARE MUST BE T AKEN WHEN EXHAUST F ANS, COMPRESSORS, AIR HA[...]
-
Page 9
9 SEE FIGURE 6). A T LEAST TYPE B VENTING MUST BE USED WITH THE ST ANDARD VENTING OPTION (thru-the-roof) USING THE NA TIONAL FUEL GAS CODE VENT T ABLES. TYPE B VENT PIPE CANNOT BE USED IF THE BOILER IS VENTED HORIZONT ALL Y OR AS A DIRECT VENT (SEE P AGES 12 THROUGH 15). ALL LOCAL UTILITY , ST A TE/ PROVINCIAL, REGULA TIONS ON VENTING MUST BE FOLLO[...]
-
Page 10
10 POWER VENT (OPTIONAL) The length of vent used in horizontally vented installations can be extended beyond the lengths shown in T ables 1 1 and 13 by implementing the kits listed below: TABLE 9: POWER VENT KITS. CONNECTING BOILER TO A COMMON VENT Do not connect the boiler to a common vent or chimney with solid fuel burning equipment. This practic[...]
-
Page 11
11 Figure 5. V ent T ermination Installation Clearances CAUTION DIRECT VENTING INTO DEAD AIR SP ACES SUCH AS ALLEYS, ATRIUMS AND INSIDE CORNERS CAN CAUSE RECIRCULA TION OF FLUE GASES. RECIRCULA TION OF FLUE GASES WILL CAUSE SOOTING , PREMA TURE F AILURE OF THE HEA T EXCHANGER AND ICING OF THE COMBUSTION AIR INT AKE DURING SEVERE COLD WEA THER. TO P[...]
-
Page 12
12 ST ANDARD VENT - VERTICAL (CA TEGOR Y I) IMPORT ANT! VENT PRESSURE MUST BE MAINT AINED BETWEEN -0.02" W .C. AND -0.04" W .C. A T 24" (61.0 cm) ABOVE BOILER COLLAR. • Connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length for Category I appliances shall be determin[...]
-
Page 13
13 T ABLE 1 1. ST ANDARD HORIZONT AL VENTING (CA TEGOR Y III) ST ANDARD VENT - HORIZONT AL (CA TEGOR Y III) W ARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants. • A maximum of two elbows can be used on inlet and outlet vent piping respectively . Each el[...]
-
Page 14
14 DIRECT VENT - VERTICAL (CA TEGOR Y I) T ABLE 12. DIRECT VENT (VERTICAL EXHAUST CONFIGURA TIONS) • Connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length for Category I appliances shall be determined per the latest edition of the National Fuel Code (U.S.) and CAN/CSA-B149.1 Insta[...]
-
Page 15
15 DIRECT VENT - HORIZONT AL (CA TEGOR Y III) W ARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeop ardize the safety and health of inhabitants. • A maximum of two elbows can be used on inlet and outlet vent piping respectively . Each elbow is equal to 10 feet (3 m) of straight pipe. • Use only [...]
-
Page 16
16 HYDRONIC INST ALLA TION The following is a brief description of the equipment required for installations noted in Figure 10. All installations must comply with local codes. T ABLE 14: INST ALLA TION ITEMS NO . SUGGESTED ITEMS FOR INST ALLA TION 1. P AIR OF SHORT PIPE NIPPLES, P AIR OF BOILER LOOP TEES AND BALL V AL VE BETWEEN SYSTEM SUPPL Y AND [...]
-
Page 17
17 Large systems with multiple boilers should include main water temperature controls (with or without outdoor reset) to sequence the boiler on and off, in relation to the load on the system. 24 V AC System Controller (Optional) GB models require a field supplied 24V AC operating control to be installed in the system such as: loop thermost at, indo[...]
-
Page 18
18 related to approximate water volume of the system. The system should be turned on to circulate water mix for about one hour and then flush clean with fresh water . Before operating the boiler , the entire system must be filled with water , purged of air and checked for leaks. Do not use S top Leak or other boiler compounds. THE W A TER HEA TER S[...]
-
Page 19
19 ONE GENESIS (MODEL GW) HOT W A TER SUPPL Y BOILER WITH HORIZONT AL T ANK Figure 12. T ank probe installation. PRESSURE RELIEF V AL VE RA TING SHOULD NOT EXCEED PRESSURE CAP ACITY OF ANY COMPONENT IN THE SYSTEM. PIPING SHOULD CONFORM TO LOCAL CODES. BALL V AL VES ARE SHOWN FOR SERVICING BOILER. HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE. DANGE[...]
-
Page 20
20 ONE GENESIS (MODEL GW) HOT W A TER SUPPL Y BOILER WITH VERTICAL T ANK Figure 13. Single boiler with vertical t ank. PRESSURE RELIEF V AL VE RA TING SHOULD NOT EXCEED PRESSURE CAP ACITY OF ANY COMPONENT IN THE SYSTEM. PIPING SHOULD CONFORM TO LOCAL CODES. BALL V AL VES ARE SHOWN FOR SER VICING BOILER. HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE[...]
-
Page 21
21 T ABLE 15. Suggested Pipe Size For Multiple Gas Appliances (Natural) T ABLE 16. Suggested Pipe Size For Multiple Gas Appliances (Prop ane Gas) Length of Pipe in Feet (Metres) Maximum Capacity of Pipe in BTU/hr and kW for Gas Pressures of 14 in. W .C. (0.5 psi) or Less and a Pressure Drop of 0.5 in. W .C . (based on 0.60 Specific Gravity Gas w/He[...]
-
Page 22
22 Where it is necessary to use more than the average number of pipe fittings i.e. elbows, tees, and valves in gas supply line, use a pipe larger than specified to compensate for increased pressure drop. Gas control trains are unique for each Genesis II unit. S tages one, two and three run sequentially left to right on the smaller units (GB/ GW 100[...]
-
Page 23
23 GB/GW 2100 GB/GW 2500 GB/GW 1000 - 1500 GAS MANIFOLD ASSEMBL Y GB/GW 1850 Figure 14. GB/GW 1000 - 2500 Gas Manifold Assembly Diagrams.[...]
-
Page 24
24 GENESIS GB/GW 1000-2500 SERIES 400 WIRING DIAGRAM FIGURE 15.[...]
-
Page 25
25[...]
-
Page 26
26 GENESIS GB/GW 1000-2500 SERIES 400 SCHEMA TIC DIAGRAM FIGURE 16.[...]
-
Page 27
27[...]
-
Page 28
28 Figure 17. CCB CENTRAL CONTROL BOARD[...]
-
Page 29
29 Figure 18. FCB FLAME CONTROL BOARD Diagram[...]
-
Page 30
30 Figure 19. PDB POWER DISTRIBUTION BOARD Diagram[...]
-
Page 31
31 Fuse Protection The 24V AC circuitry is protected with a 3 amp fuse on the Flame Control Boards (FCB) and a 7.5 amp fuse on the Central Control Board. If the fuse opens, a red LED located near the fuse will light. See Figures 17 and 18. If the red LED is illuminated, replace the fuse. Repeated failure of the fuse is an indication of possible dam[...]
-
Page 32
32 Lighting Instructions for the G(B/W) 1000 through 2500 models A . THIS APPLIANCE DOES NOT HA VE A PILOT . IT IS EQUIPPED WITH AN IGNITION DEVICE WHICH AUTOMA TICALL Y LIGHTS THE BURNER. DO NOT TR Y TO LIGHT THE BURNER BY HAND. B . BEFORE OPERA TING: SMELL ALL AROUND THE APPLI- ANCE AREA FOR GAS. BE SURE TO SMELL NEXT TO THE FLOOR BECAUSE SOME GA[...]
-
Page 33
33 Lighting Instructions for the G(B/W) 1000 through 2500 models FOR YOUR SAFETY READ BEFORE OPERA TING OPERA TING INSTRUCTIONS T O TURN OFF GAS TO APPLIANCE W ARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTL Y , A FIRE OR EXPLOSION MA Y RESUL T CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. A . THIS APPLIANCE DOES NOT HA VE A PILO[...]
-
Page 34
34 T ABLE 20. RISK OF SCALDS. TEMPERA TURE TIME TO PRODUCE 2nd & 3rd SETTING DEGREE BURNS ON ADUL T SKIN OVER 170°F (77°C) NEARL Y INST ANT ANEOUS 160°F (71°C) ABOUT 1/2 SECOND 150°F (66°C) ABOUT 1-1/2 SECONDS 140°F (60°C) LESS THAN 5 SECONDS 130°F (54°C) ABOUT 30 SECONDS 120°F (49°C) OR LESS MORE THAN 5 MINUTES USE ANTI-SCALD V AL [...]
-
Page 35
35 required): The CCB accepts analog temperature input s from up to three sensors (inlet, outlet and tank). • ECO input (CCB - required): The ECO (energy cut off) is a hi-limit switch, which is located inside the outlet probe. It is a normally closed switch that opens if the probe is exposed to a temperature higher than the trip point. Once tripp[...]
-
Page 36
36 CCB - Three position Dipswitch (Flame Control Section) SW2: This dipswitch is similar to the FCB dipswitches described below , but with only three switches being used: the number of blower speeds (switch #3), Hi Gas option (switch #2) and a spare (switch #1). Only the blower speed and Hi Gas options are the required selection, within the CCB . T[...]
-
Page 37
37 Operating Sequence NOTE: The following sequence is based on a three-stage system. 1. The EMC 5000 controller has four modes of operation: Initialization, S tandby , Running, and Service. The internal CCB and FCB micros control these modes through a sequence of steps (or S tates) which are further described in the "UIM Operating Procedures&q[...]
-
Page 38
38 followed by 15-second inter-purge period, then the system returns to step 7, if the "T rial for Ignition" dipswitch is set for three (3) tries. If the dipswitch is set for one (1) trial, the system will declare an error and boiler will require resetting the control. 10. If a flame is detected, stage two will be activated and start its [...]
-
Page 39
39 • Menu Screen: Displayed when the user presses the "Menu" key . This screen is the selection point for the other 9 screens. • T emperature Screen: Displays the sensed temperatures of the Outlet, Inlet, and T ank probes. Also displayed is the calculated Delta T (Outlet minus Inlet) for the system. Shorted ("Short") and dis[...]
-
Page 40
40 • Soft Fault S t ate: (See "Fault Description" section for list of soft and Auto Reset faults.) The CCB turns off the Powered V ent and the IRI Gas. The pump remains on for the selected post-circulate time to cycle the hot water out of the boiler . The FCB's are commanded to shut down and the Alarm output is turned on. The green[...]
-
Page 41
41 6. Use the UP or DOWN key to select the value you wish to enter . 7. T ouch the SELECT key to accept and store the new value. • Operating Dif ferential Setpoints: Each of the two stages has an independent Operating Differential setpoint. OPERA TING DIFFERENTIAL SETPOINT ADJUSTMENT PROCEDURE Each of the two stages has an independent Operating D[...]
-
Page 42
42 when an error is detected. It will also go to this screen upon power-up if an error was still valid when power was turned off. NOTE: Errors are cleared from this screen by pressing the "select" key . • Error History Screen: This screen displays a list of the last 9 errors (with time stamps) that have occurred. The last error to occur[...]
-
Page 43
43 “Low 24V AC” V olt age from transformer less than 18 vac Continuous Auto Reset Check transformer output. Should be over 24vac. May be caused by excessive current drain or a faulty transformer “Brown Out Reset” Indicates a brown out reset occurred - - - - None Caused by a momentary dip in voltage on the CCB +5vdc power bus. Cont act facto[...]
-
Page 44
44 PREVENT A TIVE MAINTENANCE This is an induced burner and the flame is not supposed to be directly on the burner . The flame should be just above the burner deck approximately 1/8” and blue in color . See Figure 22. Visually check flame characteristics through the view port located under the left-hand header on the boiler . Figure 22 shows the [...]
-
Page 45
45 After placing the boiler in operation, check the ignition system safety shut-off devices for proper operation. T o accomplish this with the main burners operating, close the valve on the manifold. Within four seconds the main burners should extinguish. If this does not occur immediately , discontinue gas supply by closing main manual shut-off an[...]
-
Page 46
46 all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained. The time between cleaning will vary from two to six months depending upon water conditions and usage. A change of approximately 5 o F (3°C) in the normal temperature rise through the boiler is usually an indication that scale should[...]
-
Page 47
47 NEW BOILER LIMITED W ARRANTY A. O. Smith Corporation, the warrant or , extends the following LIMITED W ARRANTY to the owner of this hydronic boiler: 1. If within TEN years after initial installation of the boiler , the heat exchanger shall prove upon examination by the warranto r to be defective in material or workmanship, the warrantor , at his[...]
-
Page 48
48 500 T ennessee Waltz Parkway , Ashland City , TN 37015 Phone: 800-433-2545 w w w.hotwater .com E-Mail: part s@hotwater .com[...]