Bryant 683B manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 30 pages
- 0.79 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Heat Pump
Bryant 575C
28 pages 1.22 mb -
Heat Pump
Bryant 213A
32 pages 0.91 mb -
Heat Pump
Bryant PURONT 213A
44 pages 4.73 mb -
Heat Pump
Bryant 280ANV
18 pages 2.1 mb -
Heat Pump
Bryant LEGACY LINE 13 HEAT PUMP WITH PURONR REFRIGERANT 223A
58 pages 0.48 mb -
Heat Pump
Bryant 657A
4 pages 0.07 mb -
Heat Pump
Bryant 604D
4 pages 0.23 mb -
Heat Pump
Bryant Puron Refrigerant Two-Speed
8 pages 0.16 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation Bryant 683B. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel Bryant 683B ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation Bryant 683B décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation Bryant 683B devrait contenir:
- informations sur les caractéristiques techniques du dispositif Bryant 683B
- nom du fabricant et année de fabrication Bryant 683B
- instructions d'utilisation, de réglage et d’entretien de l'équipement Bryant 683B
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage Bryant 683B ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles Bryant 683B et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service Bryant en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées Bryant 683B, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif Bryant 683B, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation Bryant 683B. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 INTRODUCTION ..........................................................................2 RECEIVING AND INSTALLATION ..........................................2 ICM FIOP PRE-START-U[...]
-
Page 2
WARNING: Before performing service or maintenance operations on system, turn off main power to unit and install lock-out tag. Turn off accessory heater power switch if applicable. Electrical shock could cause severe injury or death. CAUTION: Puron® (R-410A) systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equ[...]
-
Page 3
pre-programmed table of airflows. The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used (See Fig. 8). a. GAS HEAT/CFM?[...]
-
Page 4
(3.) SYSTEM TYPE-Factory selected on 583B system AC- AIR CONDITIONER. (4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM for 036 & 060, and LO for 024 & 030.. (5.) ON/OFF DELAY-Factory selected 0/90 profile. (6.) CONTINUOUS FAN-Select desired fan speed when ther- mostat is set to continuous fan. i. COMFORT OPTIONS—SUPER DEHUMIDIFY ([...]
-
Page 5
(1.) If indoor temperature is above temperature set point and humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O—The unit delivers single speed cooling airflow. c. COOLING MODE-DEHUMIDIFICATION (1.) If indoor temperature is above temperature set point and humidity is above humidity set point, thermostat [...]
-
Page 6
(4.) ENH (enhanced) selection provides a 30 sec. cooling & heat pump on delay with no airflow, plus 150 seconds at 70 percent airflow and no off delay for added comfort. This will minimize cold blow in heat pump operation and could enhance system efficiency. f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED WHEN THERMOSTAT IS SET ON CONTINUOUS FAN ([...]
-
Page 7
to a level which causes the Thermidistat™ to close its contacts. When the contacts close, the airflow will return to 100 percent of selected cooling airflow. To activate this mode wire in Thermidistat™ see jumper in Fig. 10. e. DEHUMIDIFY AND SUPER DEHUMIDIFY CAPABILITIES This model unit is capable of responding to a signal from Thermidistat™[...]
-
Page 8
airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized, the ICM will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the[...]
-
Page 9
This configuration provides the following comfort enhance- ments: (a.) A 30 sec blower on delay with 150 sec at 70 percent airflow to allow the indoor coil to warm up or cool down before the blower is asked to deliver 100 percent airflow reducing the cold blow sensation at start up in heating and allowing the indoor coil to more quickly reach wet c[...]
-
Page 10
value. If circuit R to G is open (0–v.) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over cooling. e. ELECTRIC HEATING MODE (1.) Thermostat closes circuit R to W/W1, or W2—The unit delivers the selected electric heat airflow. There are no on or off delays. f. HEAT [...]
-
Page 11
remains on for 4 minutes. Observe that compressor, outdoor fan and indoor blower motors start after the call for Cooling. At the end of 4 minutes, the cooling cycle stops and the MODE reverts back to OFF . The Indoor Blower continues to run for the time selected on the Easy Select™ board after OFF icon is displayed. (3.) HEAT PUMP HEATING— Pres[...]
-
Page 12
blower motor stops. The unit is in a ‘‘standby’’ condition, waiting for the next ‘‘call for cooling’’ from the room thermostat. The 5 minute compressor delay also applies to heat pump heating mode. ELECTRICAL DATA & SCHEMATICS—ICM FIOP I. PHYSICAL DATA & ELECTRICAL SCHEMATICS Use the Physical Data and Electrical Tables on [...]
-
Page 13
f. Loosen set-screw that secures wheel to motor shaft, remove screws that secure motor mount brackets to blower housing, and slide motor and motor mount out of blower housing. 2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orientation. b. Lift wheel from housing. When handling and/or cleaning blower wheel,[...]
-
Page 14
Fig. 14—ICM FIOP Electric Schematic—Unit 583B C01035 —14—[...]
-
Page 15
TABLE 4—ICM FIOP PHYSICAL DATA—UNIT 683B THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 683B 024040 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb.) 310 324 324 321 321 380 380 COMPRESSORS Quantity Scroll 1 REFRIGERANT (R-410A) Quantity (lb.) 7.0 8.9 [...]
-
Page 16
TABLE 5—ICM FIOP PHYSICAL DATA—UNIT 683B (CONTINUED) THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 683B 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY (ton) 444555 OPERATING WEIGHT (lb.) 409 409 409 504 504 504 COMPRESSORS Quantity Scroll 1 REFRIGERANT (R-410A) Quantity (lb.) 10.6 10.6 10.6 12.4 12.4 12.4 [...]
-
Page 17
Fig. 15—ICM FIOP Electric Schematic—Unit 683B C01101 —17—[...]
-
Page 18
TABLE 7—ICM FIOP PHYSICAL DATA—UNIT 702B THIS DATA APPLIES TO 702B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 024 030 036 042 048 060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb) 270 291 299 321 326 399 COMPRESSOR Scroll REFRIGERANT (R-410A) Quantity (lb) 5.0 5.5 6.9 9.0 9.5 10.0 REFRIGERANT METERING DEVICE Orifice ID (i[...]
-
Page 19
TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA UNIT SIZE 702B V-PH-HZ VOLTAGE RANGE COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 -/- 3.8/5.0 5.4/7.2 7.5/10.0 -/- 18.1/20.8 25.9/30.0 36.1/41.7 2[...]
-
Page 20
Fig. 16—ICM FIOP Electrical Schematic—702B C01037 —20—[...]
-
Page 21
TABLE 9—ICM FIOP PHYSICAL DATA—UNIT 602B THIS DATA APPLIES TO 602B UNITS WITH THE ICM INDOOR MOTOR FIOP UNIT SIZE 602B024 602B030 602B036 602B042 602B048 602B060 NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 299 320 328 350 355 428 COMPRESSOR QUANTITY 1 TYPE SCROLL COMPRESSOR REFRIGERANT R-410A REFRIGERANT METERING DEVICE Ch[...]
-
Page 22
TABLE 10—602B WITH ICM FIOP ELECTRICAL DATA UNIT SIZE 602B V-PH-HZ VOLTAGE RANGE COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA FLA FLA Nominal kW* FLA MCA MAX FUSE OR CKT. BKR. MOCP 024 208/230–1–60 187 253 13.5 61.0 0.9 4.3 -/- 3.8/5.0 5.4/7.2 7.5/10.0 -/- 18.1/20.8 25.9/30.0 36.1/41.7 [...]
-
Page 23
Fig. 17—ICM FIOP Electrical Schematic—602B c01036 —23—[...]
-
Page 24
TABLE 11–583B & 683B COOLING (AND HEAT PUMP HEATING-683B ONLY) DRY COIL ICM AIRFLOW SMALL CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 0.0–0.4 0.4–0.7 0.7–1.0 024 COOLING † 745 675 – 835 750 690 940 880 815 COOLING DEHUMIDIFY [...]
-
Page 25
TABLE 14—583B & 683B GAS HEATING ICM AIRFLOW LARGE CABINET EASY SELECT™ BOARD SETTING (CFM) 1000 1250 1600 1750 1800 Unit Size External Static Pressure 0.0–1.0 0.0–1.0 0.0–1.0 0.0–1.0 0.0–1.0 Gas Heat Size 042 060 1000 –––– 090 – 1250 – – – 048 090 – 1250 – – – 115 – – 1600 – – 130 – – – 1750 [...]
-
Page 26
TABLE 17—702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.1–1.0 0.1–1.0 0.1–1.0 042 COOLING † 1100 1225 1410 COOLING DEHUMIDIFY 980 980 1125 HEAT PUMP COMFORT (602B Only) 990 1100 1265 048 COOLING † 1260 1400 1610 COOLING DEHUMIDIFY [...]
-
Page 27
TABLE 21—ICM FIOP WET COIL PRESSURE DROP (IN. WG) UNIT SIZE STANDARD CFM (SCFM) 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 024 0.005 0.007 0.010 0.012 0.015 ––––––––––– 030 – 0.007 0.010 0.012 0.015 0.018 0.021 0.024 –––––––– 036 – – – 0.019 0.023 0.027 0.032 0.037 0.0[...]
-
Page 28
ICM QUICK REFERENCE GUIDE c01034 EASY SELECT HEA TER/MOTOR AUX HEA T KW/CFM 0-30 1075 SEC1 SEC2 J1 AC/HP SIZE 036 030 024 018 AC HP-COMFORT HP-EFF NOM HI ENH LO SYSTEM TYPE AC/HP CFM ADJUST ON/OFF DELA Y CONTINUOUS F AN MED HI YEL LO AUX1 HUM1 AUX2 24V AC GRY HUM2 YEL WHT BLK ORN BLU VIO 0-20 875 0-10 725 0 90 30 90 0 0 0-5 625 TM J2 D H R W 1 W 2 [...]
-
Page 29
c01999 ST ART -UP CHECKLIST (Remove and Store in Job File) I. Preliminary Information MODEL NO .:_________________________________ SERIAL NO .:__________________________________ D A TE:_______________________________________ TECHNICIAN:_________________________________ II. PRE-ST ART -UP (Inser t checkmark in bo x as each item is completed) ( ) VER[...]
-
Page 30