Carrier 39LA manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 40 pages
- 2 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Air Conditioner
Carrier AIR CONDITIONING UNIT 38TRA
6 pages 0.12 mb -
Air Conditioner
Carrier 38CKG
2 pages 0.02 mb -
Air Conditioner
Carrier 38APS025-065
4 pages 2.76 mb -
Air Conditioner
Carrier 38HD
12 pages 0.69 mb -
Air Conditioner
Carrier Y
15 pages 1.22 mb -
Air Conditioner
Carrier OMNIZONE 50XJ064-104
64 pages 2.05 mb -
Air Conditioner
Carrier INFINITIR 15 SEER 48XT-A
10 pages 0.25 mb -
Air Conditioner
Carrier HOME STANDBY ASPAS1CCA007
4 pages 0.25 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation Carrier 39LA. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel Carrier 39LA ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation Carrier 39LA décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation Carrier 39LA devrait contenir:
- informations sur les caractéristiques techniques du dispositif Carrier 39LA
- nom du fabricant et année de fabrication Carrier 39LA
- instructions d'utilisation, de réglage et d’entretien de l'équipement Carrier 39LA
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage Carrier 39LA ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles Carrier 39LA et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service Carrier en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées Carrier 39LA, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif Carrier 39LA, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation Carrier 39LA. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without not ice and without inc urring obligations. Catalog No . 533-932 Printed in U .S.A. F orm 39L-6SI Pg 1 1110 2-04 Replaces: 39L-5SI Installation, Star t-Up and Ser v ice Instr uctions CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . . . . .[...]
-
Page 2
2 INTR ODUCTION Unit Identification — The 39L units are identified by the 18-digit part number listed on the serial plate. The part number describes all component, coil, motor , drive, and control selections. See Fig. 1-3 for unit identification. Fig. 1 — Unit Identif ication LEGEND Fig. 2 — 39L Model Number CV — Constant V olume DX — Dir[...]
-
Page 3
3 LEGEND Fig. 3 — Position 4, Unit Configuration Model (Component Sequence Als o Shown) COMB. — Combination PH — Preheat POS. — Po s i t i o n F actor y-installed option compo nents[...]
-
Page 4
4 PREINST ALLA TION 1. Check items received against packing list. Notify Carrier of any discrepancy . 2. Refer to Fig. 4 for service area requirements. 3. T o transfer unit from truck to storage site, refer to rigging details in Fig. 5 and section on unit rigging for proper handling. See T able 1 for component weights. 4. Do not stack unit componen[...]
-
Page 5
5 NO TE: D imensions in ( ) are in mm. DIMENSIONS (ft-in.) SIZE A B C D E 39LA 39LB 39LC 03 3-1 7 / 8 3-1 3 / 4 1-9 1 / 4 1- 7 11 / 16 0-7 7 / 8 1-3 3 / 4 2- 3 9 / 16 06 3-9 3 / 4 3-9 5 / 8 2-1 3 / 16 1-11 5 / 8 0-7 7 / 8 1-3 3 / 4 2- 3 9 / 16 08 4-1 11 / 16 4-1 9 / 16 2-5 1 / 8 2- 3 9 / 16 0-7 7 / 8 1-3 3 / 4 2- 3 9 / 16 10 4-9 9 / 16 4-9 7 / 16 2[...]
-
Page 6
6 Table 1 — Physical Data L EGEND *Less coil. †Coils ha ve 14 alumin um fins per in ch on copper tu bes. UNIT SIZE 03 06 08 10 12 15 18 21 25 UNIT WEIGHTS (lb)* 39LA 200 280 411 470 540 6 20 695 740 820 39LB 150 210 308 352 405 465 521 555 615 39LC 170 238 349 400 459 527 590 629 697 39LD 230 322 472 540 621 713 799 851 943 39LF 230 322 472 540[...]
-
Page 7
7 F AN OFF TRAP CONDITION WHEN F AN ST ARTS F AN RUNNING AND CONDENSA TE DRAINING DIFFERENTIAL 1 DRAIN NIPPLE DIFFERENTIAL 2 COOLING COIL DRAIN P AN H NO TE: Lift in one piece. Use slings and spreader bars at each lifting brack et. Fig. 5 — Unit Rigging Deta ils Fig. 7 — Condensat e Drain Fig. 6 — Unit Support Deta ils[...]
-
Page 8
8 INST ALLA TION Mixing Bo x DA MP E R ACT UA TO RS — The 39L mixing boxes are sup- plied with low leak dampers and blade and edge seals. Damper operating torques are shown in T able 2. The actuator and mounting brackets are field supplied and may be mounted inside or outside the unit. A typical inside mounting bracket is shown in Fig. 8. For ext[...]
-
Page 9
9 Table 3 — Recommended Actuators *Actuator is spring-retur n type. NO TES: 1. All actuators are direct coupled type, designed to be directly mounted into jackshaft assemb ly . 2. All actuators are equipped with a plen um rated cab l e, f actor y- terminate d to the actuator . Part No. HF27BB035 and 034 are 16 ft, HF27BB033 is 9.5 ft. 3. Damper a[...]
-
Page 10
10 Inlet Guide V ane (IGV) Actu ators — The control board positions the unit IGVs in order to maintain the duct stat- ic pressure, as measured by the static pressure transducer , at the required set point. The IGV actuato r is electrically connected to the control board and receives a signal whenever the guide vane position needs to be adjusted. [...]
-
Page 11
11 Install Fan Motor — For field installation of motors, be sur e electrical junction box is toward the center of the unit. This is necessary for drive and belts to be properly tightened. Use smallest slots in motor mounting base that will accommo- date motor and allow minimum overhang (Fig. 13). Be sure that motor holddown bolts are tight on fie[...]
-
Page 12
12 When field installing or replacing sheaves, install sheaves on fan shaft and motor shaft for minimum overhang. (See Fig. 13.) Use care when mounting sheave on fan shaft; too much force may damage bearing. Remove rust-preventative coating or oil from shaft. Make sure shaft is clean and free of burrs. Add grease or lubrican t to bore of sheave bef[...]
-
Page 13
13 6. T o determine corr ect belt tension, use the deflection formula given below and the tension data from Fig. 15 as follows: EXAMPLE: Given Belt Span 16 in. Belt Cross-Section A, Super Belt Small Sheave PD 5 in. Solution 1. From Fig. 15 find that deflection force for type A, super belt with 5-in. small sheave PD is 4 to 5 1 / 2 lb. 2. 3. Increas[...]
-
Page 14
14 W ater and Ste am Coil Piping Recommendations GE NE R AL — Use straps around the coil casing or the lifting holes (see Fig. 17) to lift and place the coil. Piping practices are outlined in the Carrier System Design Manual, Part 3, Piping Design. See T a bles 4-6 for circuiting data. W A TE R CO IL S — T ypically , coils are piped by connecti[...]
-
Page 15
15 When a water coil is applied downstream of a direct- expansion (DX) coil, a freeze-up thermostat must be installed between the DX and water coil and electrically interlocked to turn off the cooling to prevent freeze-up of the water coil. For outdoor-air application where intermittent chilled water coil operation is possible, one of the following[...]
-
Page 16
16 NO TES: 1. A b ypass is necessar y around trap and v alves when continu- ous operation is necessar y . 2. Bypass to be the same size as trap orif ice but ne ver less than 1 / 2 inch. Fig. 19 — Dripping Steam Supply to Condensate Return NO TES: 1. Flange or union is located to facilitate coil remov al. 2. When a b y pass with control is require[...]
-
Page 17
17 Refrigerant Piping, Direct-Expansion (DX) Coils (Fig. 23) — Direct-expansion coils are divided into 2 or 4 splits depending upon the unit size and coil circuiting. See T able 7 for coil circuiting data. Each split requires its own distributor nozzle, expansion valve, and suction piping. Suction connections are on the air entering side when the[...]
-
Page 18
18 Table 5 — Chilled Water Coil Circuiti ng Data (cont) LEGEND *Not av ailable on 39LB un its. NO TE : Connection sizes are MPT - inches. Table 6 — Steam Coil Connection Sizes LEGEND NO TE : Connection sizes are MPT - inches. SMALL F ACE AREA (39LB, 39LC, 39LF) COIL TYPE CIRCUITING UNIT SIZE 03 06 08 10 12 Face Area (sq ft) 2.72 4.72 6.58 7.95 [...]
-
Page 19
19 SU CT I ON PIP I NG — Connect suction piping as shown in Fig. 24 for face split coil or Fig. 25 for row split coil. Suction line from coil connection to end of the 15-diameter- long riser should be same tube size as coil connection to ensure proper refrigerant velocity . Refer to Carrier System Design Manual, Part 3, and size re- maining sucti[...]
-
Page 20
20 Table 7 — Direct Expan s ion Coil Circuiting Data LEGEND *May be field manif olded for ei ther face split or ro w split. †Where each TXV has the same number of circuits, that number is shown once. When coil has an unev en numbe r of circuits per TXV , both values are shown. **F actor y-supplied distributors hav e factory-selected nozzle size[...]
-
Page 21
21 Table 7 — Direct Expansion Coil Circuiting Data (cont) LEGEND *May b e field manif olded for ei ther face split or ro w split. †Where each TXV has the same number of circuits, that number is shown once. When coil has an unev en number of circuits per TXV , both values are sho w n. **F actor y-supplied distributors hav e factory-selected nozz[...]
-
Page 22
22 Table 8 — Distribut or Part Numbers Table 9 — Side Connector (Hot Gas Bypass) Data DIMENSIONS (in.) LEGEND PA R T N O . NO. OF TUBES CONNECTI ON OD (in.) SPORLAN NOZZLE Sporlan Carrier T yp e Size 1112-2- 1 / 4 EA07NC261 2 0.88 G 3 / 4 to 12 1112-3- 1 / 4 EA07FC027 3 1112-4- 1 / 4 EA07NC262 4 1112-5- 1 / 4 EA07NC263 5 1112-6- 1 / 4 EA07NC264[...]
-
Page 23
23 UNLOADING CONSIDERA TIONS — Direct expan sion coils can have two intertwined refrigerant circuits. In addition, quar- ter , half, full and double circuiting configurations are offered to allow optimum system performance and oil return at full and part-load operation. Circuiting selection should result in a circuit loading of 0.8 to 2.0 tons pe[...]
-
Page 24
24 TXV — Thermo static Expansion V alve Fig. 29 — Face Split Coil Manifolding (Typical ) TXV — Ther mostatic Expansion V alve Fig. 30 — Row Split Coi l Manifolding (Typical)[...]
-
Page 25
25 Electric Heater s — Electric heaters may be factory in- stalled or drop shipped to the jobsite and field installed. The heater can only be installed in the preheat-electric section. T o install electric heater , refer to Fig. 31 and proceed as follows: 1. Locate preheat-electric section already mounted on unit and remove protective shipping co[...]
-
Page 26
26 NO TE: All wir ing must be copper and must conf or m to the NEC (National Electrical Code). Fig. 32 — Typical Electric Heater Wiring Schematic[...]
-
Page 27
27 Table 10 — Electric Heat er Data LEGEND *Standard cont rol steps are listed under the Control St ep heading. “F ree” additional steps of c ontrol are op tionally available when the number of subcircuits excee ds the standard number of control steps . †MCA = 1.25 x FLA; for proper wire si zing, refer to T able 310- 16 of the NEC. **2 cont[...]
-
Page 28
28 Table 11 — Field Wiring for Incoming Conductors Sized for 125% of Heat er Load LEGEND *V alues are based on T able 310-16 of the NEC (Na tional Electrical Code) for 75 C insulated copper wire. Not more than 3 conductors in a racew ay . NO TES: 1. Be sure to consider length of wir ing run and possible v oltage drops when sizing wires. 2. Field [...]
-
Page 29
29 ST ART -UP Check L ist — Make a walkway inside unit components to protect insulation. Remove a ll construction debris from unit interior . Remove walkway before starting unit. FI L T ER S — Install unit filters in all filter sections. FA N S 1. Check lubrication of fan, motor bearings, and linkages. a. Note that bearings are ship ped complet[...]
-
Page 30
30 6. Check fan speed with a strobe -type tachometer or use the following formula: Obtain the motor rpm from the fan motor nameplate and read sheave pitch diameters marked on the fan and motor pulleys, or estimate the pitch diame- ters by using the pulley outside diameters. Then: Example: Actual Approximate Nameplate Motor Rpm = 1760 1760 Mtr Sheav[...]
-
Page 31
31 6. If solution is too weak, add more antifreeze until desired strength is reached, then circulate solution through coil for 15 minutes or until concentration is satisfactory . 7. Remove upper line from reservoir to reversible pum p. Drain coil to reservoir and then close service valve. 8. Break union and remove reservoir and its lines. 9. Leave [...]
-
Page 32
32 VER T ICAL UNIT SLANT CO IL REMOV AL (39LD Units) NOTE: Item numbers are in Fig. 39. 1. Refer to Fig. 4 for service area clearance. 2. Disconnect piping (Item 6). 3. Through fan access door (Item 2), remove screws (Item 3), while holding angle (Item 4) to top of coil side panels (Item 7). On opposite e nd of unit, gain access to similar screws b[...]
-
Page 33
33 HORIZONT AL OR VER T ICAL UNIT — DUAL COIL REMOV AL (39LA,39LD units — size 25) — (NO TE: Ite m numbers are in Fig. 40 unless otherwise indicated.) 1. Refer to Fig. 4 for se rvice area requirements. 2. Disconnect piping (Item 5). 3. Horizontal Unit, 39LA — On top panel (Item 3) remove screws located directly above side panels (Items 2 an[...]
-
Page 34
34 HORIZONT AL OR VER TICAL UNIT — VER TICAL COIL REMOV AL (39LB,LC,LF ,LH Units) — Item number s are in Fig. 41 unless otherwise indicated. 1. Refer to Fig. 4 for service area requirements. 2. Disconnect piping (Item 6). 3. Horizontal Unit, 39LB and 39LC — On top panel (Item 4) remove screws located directly above side panels (Items 2 and 7)[...]
-
Page 35
35 Changing Coil Hand NOTE: Electric heat coil hand cannot be changed. NOTE: The coil cover panel is not part of the coil. Remove cover panel from end of unit. New holes must be cut in coil cover panel. Original holes must be plugged and insulated. New side panels may be nece ssary when changing coil hand. NU -F I N CO IL S — The NuFin coil is ai[...]
-
Page 36
36 STEAM INNER DISTRIBUTING TUBE COILS — Ro tate in horizontal plane and reinstall. See Fig. 42. PI PI NG — Direct expansion, chilled water , and hot water coils should always be piped for counterflow . (Fluid should enter the coil at the leaving-air side.) Steam coils must have the condensate connection at bottom of coil. T o determine interva[...]
-
Page 37
37 Table 12 — F ilter Data *Only 2-in. filters are av ailable on size 03. 39L UNIT SIZE 03 06 08 10 12 15 18 21 25 Angle Filter Section Filter Qty…Size (in.) 2…16x25 4…16 x20 2…16x20 2…16x25 4…16x25 6…16x20 9…16x20 12…16x20 4…16x 20 8…16x25 4…16x20 8…16x25 Nominal Face Area (sq ft) 5.56 8.89 10.00 11.11 13.33 20.00 26.67[...]
-
Page 38
38 10. Check fan shaft diameter at bearing mount. If worn by more than .001 in. below nominal, shaft should be re- placed. 1 1. Install new bearing, tighten holddown bolts and then tighten bearing locking collar and setscrews. 12. Make certain fan wheel does not rub sides of fan housing after installing new bearings. 13. Recoat fan shaft with a rus[...]
-
Page 39
39 METRIC CONVERSION CHART[...]
-
Page 40
Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 533-932 Printed in U .S.A. Form 39L-6SI Pg 40 1110 2-04 Replaces: 39L-5SI Copy right 2004 Carrier Cor poration[...]