Carrier 50ZH024-060 manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 24 pages
- 1.46 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Air Conditioner
Carrier 48AK
118 pages 6.36 mb -
Air Conditioner
Carrier 30GT
4 pages 0.16 mb -
Air Conditioner
Carrier 25HCR
10 pages 0.43 mb -
Air Conditioner
Carrier 48DM
4 pages 0.23 mb -
Air Conditioner
Carrier 38GP
12 pages 1.16 mb -
Air Conditioner
Carrier 48XL-A
8 pages 0.98 mb -
Air Conditioner
Carrier ZONEKIT2ZCAR
16 pages 0.21 mb -
Air Conditioner
Carrier 50ES-A
6 pages 1.95 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation Carrier 50ZH024-060. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel Carrier 50ZH024-060 ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation Carrier 50ZH024-060 décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation Carrier 50ZH024-060 devrait contenir:
- informations sur les caractéristiques techniques du dispositif Carrier 50ZH024-060
- nom du fabricant et année de fabrication Carrier 50ZH024-060
- instructions d'utilisation, de réglage et d’entretien de l'équipement Carrier 50ZH024-060
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage Carrier 50ZH024-060 ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles Carrier 50ZH024-060 et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service Carrier en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées Carrier 50ZH024-060, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif Carrier 50ZH024-060, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation Carrier 50ZH024-060. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
50ZH024-060 Packaged Heat Pump Units Installation, Start-Up and Service Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 INTRODUCTION ..........................................................................2 RECEIV[...]
-
Page 2
equipment, pay attention to precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations. Before performing service or maintenan[...]
-
Page 3
Fig. 2—Unit Base Dimensions, 50ZH024-030 UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRAVITY IN. (MM) lb kg X Y Z 50ZH024 208/230-1-60 232 106 14.0 (356) 19.0 (483) 12.0 (305) 50ZH030 208/230-1-60, 208/230–3–60 254 116 14.0 (356) 19.0 (483) 12.0 (305) C00156 REQUIRED CLEARANCE FOR OPERA TION AND SERVICING INCHES [mm] CONDENSER . COI[...]
-
Page 4
Fig. 3—Unit Base Dimensions, 50ZH036–048 UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRAVITY IN. (MM) lb kg X Y Z 50ZH036 208/230-1-60, 208/230-3-60, 460–3–60 277 126 14.0 (356) 19.0 (483) 15.0 (381) 50ZH042 208/230-1-60, 208/230-3-60, 460–3–60 295 134 14.0 (356) 19.0 (483) 15.0 (381) 50ZH048 208/230-1-60, 208/230-3-60, 460–[...]
-
Page 5
Fig. 4—Unit Base Dimensions, 50ZH060 UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRAVITY IN. (MM) lb kg X Y Z 50ZH060 208/230-1-60, 208/230-3-60, 460-3-60 368 167 14.0 (356) 20.0 (508) 16.0 (406) C00158 REQUIRED CLEARANCE FOR OPERA TION AND SERVICING INCHES [mm] CONDENSER . COIL ACCESS SIDE..............................................3[...]
-
Page 6
INSTALL FLANGES FOR DUCTWORK CONNECTIONS (50ZH060 ONLY) The 50ZH060 units are shipped with flanges which must be field-installed on the unit. To install unit flanges: 1. Five pieces of flange are shipped on the return-air opening of the unit. Remove the flanges from the shipping position (See Fig. 5). Screws are field-supplied. 2. One piece of flan[...]
-
Page 7
Unit removes condensate through a 1 3/64-in. ID hole (using 3/4-in. OD piping or tubing) which is located at the end of the unit. See Fig. 2-4 for location of condensate connection. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground- level installations. Install a field[...]
-
Page 8
The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole. See Fig. 2-4. Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty. ROUTING POWER LEADS INTO UNIT Use only copper wire between disconnect and unit. The high- voltage leads should be in a conduit unt[...]
-
Page 9
4. Connect the RED lead to the BLK wire from which the ORG lead was disconnected. Insulate with wirenut from Step 1. 5. Using the wirenut removed from the RED lead, insulate the loose terminal on the ORG lead. 6. Wrap the wirenuts with electrical tape so that the metal terminals cannot be seen. Indoor blower-motor speeds may need to be changed for [...]
-
Page 10
Step 1—Check for Refrigerant Leaks LOCATE AND REPAIR REFRIGERANT LEAKS AND CHARGE THE UNIT AS FOLLOWS: 1. Using both high- and low-pressure ports, locate leaks and reclaim remaining refrigerant to relieve system pressure. 2. Repair leak following accepted practices. NOTE: Install a liquid-line filter drier whenever the system has been opened for [...]
-
Page 11
charts to determine what the suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted. Example: (See Fig. 16) Outdoor Temperature —85°F Suction Pressure—74 psig Suction Temperature should be—60°F Not[...]
-
Page 12
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly. Disconnect electrical power to the unit and install lockout tag before changing blower speed. Electrical shock can cause serious injury or death. Airflow can be changed by changing the lead connections of the blower motor. Units 50ZH024, 0[...]
-
Page 13
Table 3—Electrical Data—50ZH UNIT 50ZH SIZE (–SERIES, IF USED) V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal KW* FLA MCA FUSE OR CKT BKR MOCP 024–311 208/230–1–60 187 254 11.4 56.0 0.9 2.4 -/- 3.8/5.0 5.6/7.5 7.5/10.0 -/- 18.3/20.8 26.9/31.3 36.1/41.7 17.6/17.6 40.4/43.6[...]
-
Page 14
NOTE: Some units are equipped with a time-delay relay. On these units, the indoor fan remains on for 30 seconds after G or Y is deenergized. COOLING With the thermostat subbase in the cooling position, the thermostat makes circuit R-O. This energizes the reversing valve solenoid (RVS) and places the unit in standby condition for cooling. NOTE: The [...]
-
Page 15
supplemental electric heat. When thermostat is satisfied, contacts open, deenergizing contactor and relay; motors and heaters deen- ergize. The IFM may be controlled by a time-delay relay that keeps the fan on for 30 seconds. DEFROST Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks f[...]
-
Page 16
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract. The ability to properly perform maintenance on this equip- ment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures[...]
-
Page 17
mild detergent-and-water-solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring or air filter(s). For best results, spray outdoor- coil fins from inside to outside the unit. On units with an outer and inner outdoor coil, be sure to clean between the coils. Be sure to flush all dirt [...]
-
Page 18
Step 6—Electrical Controls and Wiring Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag. Remove the top panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or bur[...]
-
Page 19
Check valves are also located in the liquid lines near the strainers. The Strainers are the larger of the two components. Step 12—High Flow Valves Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves can not be accessed for se[...]
-
Page 20
Fig. 24–Typical Heat Pump Operation, Cooling Mode C95044 STRAINER ACCUMULA TOR COMPRESSOR STRAINER LCS OUTDOOR COIL INDOOR COIL A B D C Check V alves A Closed B Open C Closed D Open LEGEND LCS Loss of Charge Switch Acutrol Metering Device Check V alve (Arrow indicates direction of flow) COOLING CYCLE 1. Hot gas from compressor flows through the 4[...]
-
Page 21
Fig. 25–50ZH Balance Point Chart C01038 Balance Point Worksheet 0 10000 20000 30000 40000 50000 60000 70000 80000 - 1 0 0 1 02 0 3 04 05 0 6 0 Outdoor Air Temp (Deg F) 024 030 036 042 048 060 Building Heat Loss, BTUH Unit Integrated Heating Capacity (BTUH) 21[...]
-
Page 22
Table 8—Troubleshooting—Cooling and Heating SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start. Power Failure Call power company Loss of Charge Switch open Evaluate unit for possible refrigerant leak Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective thermostat, contractor, transformer, or control [...]
-
Page 23
START-UP CHECKLIST (REMOVE AND STORE IN JOB FILE) I. PRELIMINARY INFORMATION Model No ............................................................................................................................................................. Serial No ................................................................................................[...]
-
Page 24
Copyright 2003 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 50zh5si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Tab 6 8 PC 101 Catalog No. 535-00080 Printed in U.S.A. Form 50ZH-5SI Pg 24 7-03 Replaces: 50ZH-4SI[...]