Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025 manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 32 pages
- 0.94 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Heating System
Carrier MPE62L-10R
64 pages 1.51 mb -
Heating System
Carrier 48MPD
64 pages 1.51 mb -
Heating System
Carrier 48HJ015-025
32 pages 0.66 mb -
Heating System
Carrier LJE
33 pages 2.76 mb -
Heating System
Carrier 48MA/50ME016-040
48 pages 0.86 mb -
Heating System
Carrier Z6
68 pages 2.89 mb -
Heating System
Carrier ZW
68 pages 2.89 mb -
Heating System
Carrier 48NVT
27 pages 2.12 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025 ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025 décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025 devrait contenir:
- informations sur les caractéristiques techniques du dispositif Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025
- nom du fabricant et année de fabrication Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025
- instructions d'utilisation, de réglage et d’entretien de l'équipement Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025 ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025 et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service Carrier en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
Installation Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ............................. 1-12 Step 1 — Provide Unit Support ...............1 • ROOF CURB • AL TERNA TE UNIT SUPPOR T Step 2 — Rig and Place Unit ..................3 • POSITIONING • ROOF MOUNT Step 3 — Field Fabricate Ductwork ......[...]
-
Page 2
ACCESSOR Y P ACKAGE NO. CURB HEIGHT DESCRIPTION ‘ ‘A ’’ ‘ ‘B’ ’ ‘ ‘C’’ 50PQ900221 1 8 -2 9 (305) Standard Curb — 14 9 High —— — 50PQ900141 2 8 -0 9 (610) Standard Curb for Units Requiring High Installation —— — 50PQ900151 2 8 -0 9 (610) Horizontal Supply and Return Curb 5 8 -6 9 (1676) 0 8 -2 1 ⁄ 2 9 (64) 1 8[...]
-
Page 3
AL TERNA TE UNIT SUPPOR T — When the curb cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side. Step 2 — Rig and Place Unit — Inspect unit for trans- portation[...]
-
Page 4
T able 1 — Physical Data UNIT SIZE 48 HJD015/HJE015 HJE017 HJD025 208/230, 460 V 575 V OPERA TING WT (lb) Al/Al* 1640/1660 2010 2235 Unit Al/Cu* 1770/1790 2160 2385 Cu/Cu* 1840/1860 2250 2515 Economizer 11 0 11 0 11 0 Roof Curb† 200 200 200 COMPRESSOR 06D Semi-Hermetic Number 12 2 Cylinders 64 6 REFRIGERANT TYPE R-22 Charge (lb) System 1 22.50 [...]
-
Page 5
UNIT 48HJ MAXIMUM SHIPPING WEIGHT Lb Kg D015 1920 871 E015 1940 880 E017 2310 1048 UNIT 48HJ DIMENSIONS XY Ft-in. mm Ft-in. mm D015 3-2 965 4-0 1219 E015 3-2 965 4-0 1219 E017 3-7 3 ⁄ 8 1 102 3-6 5 ⁄ 8 1083 UNIT 48HJ WEIGHT OF CORNER* ABCD Lb Kg Lb Kg Lb Kg Lb Kg D015 365 166 360 163 373 169 540 245 E015 372 169 363 165 377 171 547 248 E017 509[...]
-
Page 6
MAXIMUM SHIPPING WEIGHT Lb Kg 2535 1 150 NOTES: 1. Dimensions in ( ) are in millimeters. 2. Center of gravity . 3. Direction of airflow . 4. Ductwork to be attached to accessory roof curb only . 5. Minimum clearance: a. Rear: 7 8 0 9 (2134) for coil removal. This dimen- sion can be reduced to 4 8 0 9 (1219) if conditions permit coil removal from t[...]
-
Page 7
Step 3 — Field Fabricate Ductwork — Secure all ducts to building structure. Use flexible duct connectors be- tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be ins[...]
-
Page 8
S t e p6—T r a p Condensate Drain — See Fig. 1 1 for drain location. One 3 ⁄ 4 -in. half coupling is provided inside unit evaporator section for condensate drain connec- tion. An 8 1 ⁄ 2 in. x 3 ⁄ 4 -in. diameter and 2-in. x 3 ⁄ 4 -in. diameter pipe nipple, coupled to standard 3 ⁄ 4 -in. diameter elbows, pro- vides a straight path dow[...]
-
Page 9
Step 8 — Make Electrical Connections FIELD POWER SUPPL Y — Unit is factory wired for volt- age shown on unit nameplate. When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (T able 2). All field wiring must comply with NEC and local requirements. Route power and ground lines through control box end pa[...]
-
Page 10
Use the following formula to determine the percent volt- age imbalance. % V oltage Imbalance: = 100 x max voltage deviation from average voltage average voltage EXAMPLE: Supply voltage is 460-3-60. AB =452 v BC =464 v AC =455 v A verage V oltage = 452 +464 +455 3 = 1371 3 = 457 Determine maximum deviation from average voltage: (AB) 457 −452 =5 v [...]
-
Page 11
5. Loosen sheet metal screws for top cover of base unit located above outdoor-air inlet opening. 6. Match notches in hood top cover with unit top cover screws. Insert hood flange between top cover flange and unit. T ighten screws. 7. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support brack[...]
-
Page 12
ST ART -UP Use the following information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up. Unit Preparation — Check that unit has been installed in accordance with these installation instructions and appli- cable codes. Compressor Mounting — Loosen the compressor hold- down bolts until sidewise movement of the washer unde[...]
-
Page 13
T able 3A — Fan Performance Data, 48HJ015, 208/230, 460-V Units AIRFLOW (CFM) EXTERNAL ST A TIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm W atts Bhp Rpm Watts Bhp Rpm W atts Bhp Rpm W atts Bhp Rpm Watts Bhp 3750 741 510 0.58 854 715 0.82 952 921 1.05 1041 1 130 1.29 1 124 1344 1.53 4000 773 647 0.74 882 859 0.98 978 1071 1.22 1064 1285 1.46 1 145[...]
-
Page 14
T able 3B — Fan Performance Data, 48HJ015, 575-V Units AIRFLOW (CFM) EXTERNAL ST A TIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm W atts Bhp Rpm Watts Bhp Rpm W atts Bhp Rpm W atts Bhp Rpm Watts Bhp 3750 741 510 0.58 854 715 0.82 952 921 1.05 1041 1030 1.29 1 124 1344 1.53 4000 773 647 0.74 882 859 0.98 978 1071 1.22 1064 1285 1.46 1 145 1502 1.71[...]
-
Page 15
T able 4 — Fan Performance Data, 48HJ017 Units AIRFLOW (CFM) EXTERNAL ST A TIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm W atts Bhp Rpm Watts Bhp Rpm W atts Bhp Rpm W atts Bhp Rpm Watts Bhp 4500 630 805 0.9 741 1059 1.2 846 1341 1.5 945 1653 1.9 1039 1993 2.2 4800 659 943 1.1 765 1208 1.4 865 1497 1.7 961 1816 2.0 1052 2163 2.4 5100 688 1094 1.2 [...]
-
Page 16
T able 5 — Fan Performance Data, 48HJ025 Units AIRFLOW (CFM) EXTERNAL ST A TIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm W atts Bhp Rpm Watts Bhp Rpm W atts Bhp Rpm W atts Bhp Rpm Watts Bhp 6000 800 1732 1.88 891 2047 2.22 975 2376 2.58 1055 2728 2.96 1 133 3104 3.37 6500 853 2134 2.32 939 2471 2.68 1018 2819 3.06 1094 3185 3.46 1 167 3573 3.88 7[...]
-
Page 17
T able 7 — Accessory/FIOP Economizer Static Pressure (in. wg) UNIT 480HJ UNIT VOL T AGE CFM ECONOMIZER PRESSURE DROP 015, 017 All 3,750 .03 4,000 .03 5,000 .05 6,000 .07 7,500 .10 025 All 6,000 .07 7,200 .09 9,000 .1 1 10,000 .12 LEGEND BHP — Brake Horsepower FIOP — Factory-Installed Option NOTES: 1. The factory-assembled horizontal adapter s[...]
-
Page 18
SERVICE Before performing service or maintenance operations on unit, turn of f main power switch to unit. Electrical shock could cause personal injury. Cleaning — Inspect unit interior at beginning of each heat- ing and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior . MAIN [...]
-
Page 19
F AN SHAFT BEARINGS — For 015 units, the bearings are permanently lubricated. No field lubrication is required. For 017 and 025 units, the bearings are of the pillow block type and have grease fittings. The bearing opposite the motor end has an extended tube line so it can be lubricated from the motor side. Lubricate the bearings twice annually[...]
-
Page 20
SER VICE AND REPLACEMENT (See Fig. 30) — The 48HJ017,025 units use a fan motor mounting system that features a slide-out motor mounting plate. T o replace or serv- ice the motor , slide out the bracket. 1. Remove the evaporator-fan access panel and the heat- ing control access panel. 2. Remove the center post (located between the evaporator fan a[...]
-
Page 21
5. Set the outdoor -air thermostat (OA T), located in the econo- mizer section of the unit to 75 F . 6. If the outdoor temperature is below 75 F , the econo- mizer will control the mixed air with the mixed-air sen- sor . If the outdoor air is above 75 F , place a jumper around the contacts of the OA T . 7. Jumper terminal T to terminal T1 on the mo[...]
-
Page 22
Pilot Adjustment 1. Set system selector switch at OFF position to shut of f unit. T urn of f power to unit. 2. Remove screw cap cover on pilot gas valve to expose adjusting screw (See Fig. 36). 3. T urn valve knobs to pilot position. 4. T urn on power to unit. Set system selector switch to HEA T position and set thermostat to a setting that will ca[...]
-
Page 23
Main Burners — For most applications, main burners are factory set and should require no adjustment. However , if burner adjustment is necessary: 1. Perform pilot adjustment. 2. T urn gas valve to ON position. Allow unit to operate at least 15 minutes with burner access panel in place. 3. Remove access panel. 4. Loosen primary air shutter (Fig. 3[...]
-
Page 24
Fig. 38 — T ypical Wiring Schematic (48HJ025 Shown) 24[...]
-
Page 25
Fig. 38 — T ypical Wiring Schematic (48HJ025 Shown) (cont) 25[...]
-
Page 26
Fig. 39 — T ypical Component Arrangement (48HJ025 Shown) 26[...]
-
Page 27
LEGEND FOR FIG. 38 and 39 AHA — Adjustable Heat Anticipator BKR W/A T — Breaks with Amp T urns C— Contactor , Compressor CB — Circuit Breaker CC — Cooling Compensator CH — Crankcase Heater CLO — Compressor Lockout CLS — Compressor Lockout Switch COMP — Compressor Motor CR — Control Relay CT — Current T ransformer DM — Damper[...]
-
Page 28
[...]
-
Page 29
[...]
-
Page 30
P ACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Installation Overview • Maintenance • Operating Sequence A large selection of product, theory , and skills programs is available. Al[...]
-
Page 31
[...]
-
Page 32
ST ART -UP CHECKLIST MODEL NO.: DA TE: SERIAL NO.: TECHNICIAN: PRE-ST ART -UP: M VERIFY THA T ALL P ACKING MA TERIALS HA VE BEEN REMOVED FROM UNIT M REMOVE ALL SHIPPING HOLDDOWN BOL TS AND BRACKETS PER INSTRUCTIONS M VERIFY INST ALLA TION OF ECONOMIZER HOOD M VERIFY INST ALLA TION OF EXHAUST HOOD M VERIFY THA T CONDENSA TE CONNECTION IS INST ALLED [...]