Goodman Mfg PG 15 manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 28 pages
- 1.73 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Heating System
Goodman Mfg CPG SERIES
32 pages 0.88 mb -
Heating System
Goodman Mfg GPH1424H41AB
12 pages 0.3 mb -
Heating System
Goodman Mfg PG 15
28 pages 1.73 mb -
Heating System
Goodman Mfg GPH1430H41AB
12 pages 0.3 mb -
Heating System
Goodman Mfg GPH1460H41AB
12 pages 0.3 mb -
Heating System
Goodman Mfg GPH1442H41AB
12 pages 0.3 mb -
Heating System
Goodman Mfg GPH1448H41AB
12 pages 0.3 mb -
Heating System
Goodman Mfg GSH13
8 pages 0.38 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation Goodman Mfg PG 15. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel Goodman Mfg PG 15 ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation Goodman Mfg PG 15 décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation Goodman Mfg PG 15 devrait contenir:
- informations sur les caractéristiques techniques du dispositif Goodman Mfg PG 15
- nom du fabricant et année de fabrication Goodman Mfg PG 15
- instructions d'utilisation, de réglage et d’entretien de l'équipement Goodman Mfg PG 15
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage Goodman Mfg PG 15 ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles Goodman Mfg PG 15 et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service Goodman Mfg en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées Goodman Mfg PG 15, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif Goodman Mfg PG 15, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation Goodman Mfg PG 15. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
Goodman Manufacturing Company , L.P . 5151 San Felipe, Suite 500, Houston, TX 77056 www .goodmanmfg.com © 2006 - 2009, 2012 Goodman Manufacturing Company , L.P . IO-324H 1 1/12 This Forced Air Central Unit Design Complies With Requirements Embodied in The American National S tandard / National S tandard of Canada Shown Below . ANSI Z21.47•CSA-2.[...]
-
Page 2
2 INDEX REPLACEMENT PARTS ............................................................................................................................... ........................ 4 O RDERING P ARTS .............................................................................................................................................. 4 SAFETY [...]
-
Page 3
3 MAINTENANCE .................................................................................................................................................................. 1 7 F IL TER R EPLACEMENT OR C LEANING .................................................................................................................... 17 C ABINET F INI[...]
-
Page 4
4 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate. Replacement parts for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the white b[...]
-
Page 5
5 CA RBON M ONOXIDE POISON ING HA ZA RD B10259-216 Carbo n monox ide produc ing devic es (suc h as an auto mobile, s pace heater , gas wat er heat er, etc.) should not be operat ed in encl osed are as such a s unventi lated garage s, utility rooms or parki ng areas be cause of the da nger of car bon monoxi de (CO) poisonin g result ing from th e ex[...]
-
Page 6
6 Rooftop Installation • The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material. • T o avoid possible personal injury , a safe, flat surface for service personnel should be provided. R OOF C URB I NSTALLATIONS O NLY : • Sufficient structural support must be determined prior to locating and [...]
-
Page 7
7 RIGGING DET AILS IMPORT ANT NOTE: If using bottom discharge with roof curb, ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the Nati[...]
-
Page 8
8 8. The unit must be connected to the building piping by one of the following methods: • Rigid metallic pipe and fittings • Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations) • Listed gas appliance connectors used in accordance with the terms of their listing that are completely in [...]
-
Page 9
9 cooling. Units which will have economizers may use thermostats with two or three stages of cooling. All units can use single stage or multi-stage thermostats. Refer to figures later in this section for wiring. The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is [...]
-
Page 10
10 U NIT V OLTAGE The unit transformer is factory connected for 230V operation. If the unit is to operate on 208V , reconnect the transformer primary lead as shown on the unit wiring diagram. The induced draft blower on some models is equipped with a low speed 230V lead (blue) and a low speed 208V lead (black). If equipped, connect the induced draf[...]
-
Page 11
11 All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation. A duct system should be inst alled in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, W arm Air Heating and V entilating Systems. Pamphlets No. 90A and 90B. The supply duct from the unit[...]
-
Page 12
12 NORMAL SEQUENCES OF OPERA TION H EATING This unit is equipped with an ignition control that automatically lights the main burner . DO NOT attempt to light the main burners by any other method. 1. Thermostat calls for low or high stage heating. 2. Induced draft blower energizes for 15-second pre-purge. 3. The spark igniter and low and high stage [...]
-
Page 13
13 If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower compartment temperature drops below the limit reset temperature, the limit will automatically reset. Secondary Contro l Limit Back of Unit Secondary Limit Control Pre-Operation Checks 1. Close the manual gas valve external [...]
-
Page 14
14 With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at rated input with the recommended blower speed. If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blo[...]
-
Page 15
15 space. It is the installing contractors responsibility to ensure the proper refrigerant sub-cooling at the condenser is adjusted for each application. As the outdoor ambient temperature rises the sub-cooling decreases and as the outdoor ambient temperature lowers, the sub-cooling increases. NOTE: Proper sub-cooling adjustment optimizes cooling p[...]
-
Page 16
16 A BNORMAL O PERATION - H EATING I NTERNAL C ONTROL F AILURE If the integrated ignition control in this unit encounters an internal fault, it will go into a “hard” lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring.[...]
-
Page 17
17 NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time. H IGH P R[...]
-
Page 18
18 M AIN B URNER F LAME (Q UALIFIED S ERVICER O NLY ) Flames should be stable, soft and blue (dust may cause orange tips but must not be yellow). The flames must extend directly outward from the burner without curling, floating or lifting off. Ch eck the bur ner flam es fo r: 1. Good adju stme nt 2. Sta ble, so ft and blue 3. Not curling, floating [...]
-
Page 19
19 APPENDIX[...]
-
Page 20
20 HEA TING TIMING CHART COOLING TIMING CHART Red Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual O ff Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch S tuck Open 3 Flashes Pressure Switch S tuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas V alve C[...]
-
Page 21
21 CO M BU STION AIR I N TAK E EXHAU ST FLU E HOOD CONTRO L WIR E E N T R AN CE POW E R WIRE ENTR ANC E 7 7/8 7 5/16 SUC TIO N/LI QU ID PRE SSURE PO RTS BEH I ND COMPRE SSOR A C CES S PANEL HEA T EX CHA N GE A CCE SS P ANEL GAS SU P PLY ENTRANCE CONDEN SATE DRA IN CONNEC TION 3/4" NP T FEMALE 16 1/8 19 1/8 EVA PORA TOR/ CO N T ROL PAN EL A CCE[...]
-
Page 22
22 *PG15*****41A* WIRI NG DIAGRAM HIGH VOL T AGE! D A LL . M. F . ISCONNECT P OWER BEFORE SERVICING UL TIPLE POWER SOURC ES MA Y BE P R ESENT AILURE TO DO SO MA Y CAUSE PR OPERTY DAMAGE , PERSONAL I NJ U R Y OR DE A TH Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. YL BL PU PU PU YL GR BL[...]
-
Page 23
23 *PG15*****41A* WIRING DIAGRAM HIGH VOL T AGE! D A LL . M. F . ISCONNECT P OWER BEFORE SERVICING UL TIPLE POWER SOURC ES MA Y BE P R ESENT AILURE TO DO SO MA Y CAUSE PR OPERTY DAMAGE , PERSONAL I NJ U R Y OR DE A TH EC ON ECON OMI ZER 8. FO R ECO NOMI ZER, RE MOVE P LUG FR OM E C O NO MIZER H ARNESS . CO NNE C T PLUG FR OM ECO NOM I Z ER T O HA R[...]
-
Page 24
24 HIGH VOL T AGE! D A LL . M. F . ISCONNECT P OWER BEFORE SERVICING UL TIPLE POWER SOURC ES MA Y BE P R ESENT AILURE TO DO SO MA Y CAUSE PR OPERTY DAMAGE , PERSONAL I NJ U R Y OR DE A TH Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. *PG15*****41B* WIRING DIAGRAM[...]
-
Page 25
25 HIGH VOL T AGE! D A LL . M. F . ISCONNECT P OWER BEFORE SERVICING UL TIPLE POWER SOURC ES MA Y BE P R ESENT AILURE TO DO SO MA Y CAUSE PR OPERTY DAMAGE , PERSONAL I NJ U R Y OR DE A TH Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. *PG15*****41B* WIRING DIAGRAM[...]
-
Page 26
26 - NOTE: Roof overhang should be no more than 36". 3" MI N 12" MIN 12" MIN 36" MIN (FOR SERVICE ) . 48" MIN MINIMUM CLEARANCES RECOMMENDED FIL TER SIZES UNI T 2 T on 2 1/2 T on 3 T on 3 1/2 / 4 T on 5 T on Min. Filt er Size (1)20 x 20 x 1 (1) 20 x 25 x 1 (1)25 x 25 x 1 (2) 20 x 2 0 x 1 (2)20 x 25 x 1[...]
-
Page 27
27 BLOWER PERFORMANCE DA T A X = Outside of T emperature Rise Range - Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c. CFM W ATTS RISE CFM W ATTS RISE CFM W ATTS CFM W ATTS CFM W ATTS 0.1[...]
-
Page 28
28 P ACKAGE UNITS - DUAL FUEL & GAS HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDA TIONS We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin. R EPLACE OR C LEAN F IL TER IMPORT ANT NOTE: Never operate unit without a filter installed as dust and lint will bui[...]