Lochinvar CG200 manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 28 pages
- 1 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Water Heater
Lochinvar 1002
16 pages 0.97 mb -
Water Heater
Lochinvar COPPER-FIN II 402 - 2072
80 pages 7.97 mb -
Water Heater
Lochinvar CW-0986
1 pages 0.12 mb -
Water Heater
Lochinvar LS
2 pages 0.08 mb -
Water Heater
Lochinvar SF
2 pages 0.08 mb -
Water Heater
Lochinvar CH/CF/CP 300-750
4 pages 0.42 mb -
Water Heater
Lochinvar 2001
16 pages 0.97 mb -
Water Heater
Lochinvar AW 150 thru 500
4 pages 0.68 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation Lochinvar CG200. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel Lochinvar CG200 ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation Lochinvar CG200 décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation Lochinvar CG200 devrait contenir:
- informations sur les caractéristiques techniques du dispositif Lochinvar CG200
- nom du fabricant et année de fabrication Lochinvar CG200
- instructions d'utilisation, de réglage et d’entretien de l'équipement Lochinvar CG200
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage Lochinvar CG200 ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles Lochinvar CG200 et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service Lochinvar en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées Lochinvar CG200, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif Lochinvar CG200, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation Lochinvar CG200. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
1 MODEL S CG(N,L)1 50 & CG(N ,L)200 COMMERCIAL GAS, GLASS-LINED, T ANK-TYPE W A TER HEA TER •INST ALLA TION •OPERA TION •MAINTENANCE•LIMITEDW ARRANTY PLACE THESE INSTRUCTIONS ADJACENT TO HEA TER AND NOTIFY OWNER T O KEEP FOR FUTURE REFERENCE. Printed in U.S.A. 101 1 32288 0- 000 CAUTION TEXT IN BLACK BO[...]
-
Page 2
2 FOREWORD These designs comply with ANSI Z21.10.3 as a Booster type water heater . Detailed installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and methods of piping necessary . It is highly essential that all water , gas piping and wiring be installed as shown on th[...]
-
Page 3
3 GENERAL SAFETY INFORMA TION PRECAUTIONS DO NOT USE THIS APPLIANCE IF ANY P ART HAS BEEN UNDER W A TER. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water . IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERA TE HEA TER UNTIL ALL C[...]
-
Page 4
4 OPERA TION OF THESE F ANS CAN PRODUCE A NEGA TIVE DRAFT IN THE AREA OF THE W A TER HEA TER PREVENTING THE PRODUCTS OF COMBUSTION FROM EXHAUSTING THROUGH THE CHIMNEY OR VENT PIPE. The venting of the water heater should be inspected by a qualied service technician at the time of installation and periodically thereafter to ensure a down-draft con[...]
-
Page 5
5 possibility of changing the orientation by accidentally overtightening the inlet supply . Improper orientation of the Eliminator may cause temperature buildup issues or spells of colder than usual water temperatures. HIGH LIMIT SWITCH The dig ital t her most at ( see Figu re 3 ) co ntains t he high lim it ( ener gy cutof f) s ensor . Th e high li[...]
-
Page 6
6 INST ALLA TION INSTRUCTIONS REQUIRED ABILITY INST ALLA TION OR SERVICE OF THIS W A TER HEA TER REQUIRES ABILITY EQUIV ALENT TO THA T OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING, AIR SUPPL Y , VENTING, GAS SUPPL Y AND ELECTRICAL WORK ARE REQUIRED. W ARNING F AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESUL T IN SERIOUS PERSONAL INJUR Y O[...]
-
Page 7
7 CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND CREA TES A RISK OF ASPHYXIA TION. Where an exhaust fan is supplied in the same room with a heater , sufcient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRA WN INTO THE ROOM THROUGH THE CHIMNEY , CAUSING POOR COMBUSTI[...]
-
Page 8
8 FIGURE 7 • Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe. MUL TIPLE HEA TER MANIFOLD Whe n hor izonta lly manif olding t wo o r more h eaters ven[...]
-
Page 9
9 GAS PIPING Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area. Size the main gas line in accordance with T able 2. The gures shown are for straight lengths of pipe at 0.5 in. W .C. pressure drop, which is considered normal for low pressure systems. N[...]
-
Page 10
10 Do not subject the combination gas valve to inlet gas pressures of more than 14.0” W .C. - natural gas. A service regulator is necessary if higher gas pressures are encountered. Manifold gas pressure in inches of water column is 3.5. The gas pressure specied refers to ow pressure taken at pressure tap of automatic gas valve while heater [...]
-
Page 11
11 INST ALLA TION DIAGRAMS GENERAL The type, size and location of the relief valves must be in accordance with local codes. The locations of the relief valves shown in the installation diagrams are typical. The heater has a factory installed high temperature limit switch and temperature and pressure relief valve. Cold water lines to heater should b[...]
-
Page 12
12 VERTICAL ST ORAGE T ANK AND FORCED CIRCULA TION DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE W A TER TEMPERA TURE CONTROL W ARNING ON P AGE 20. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y T O OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD AN ANTI-SCALD V AL VE FOR HOT W A TER SUPPLIED TO FIXTURES. HORIZONT AL[...]
-
Page 13
13 DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE W A TER TEMPERA TURE CONTROL W ARNING ON P AGE 20. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD AN ANTI-SCALD V AL VE FOR HOT W A TER SUPPLIED TO FIXTURES. TWO TEMPERA TURE - ONE HEA TER HIGH TEMPERA TURE STORAGE WIT[...]
-
Page 14
14 INST ALLA TION DIAGRAMS-SIDE INLET/OUTLET USAGE DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL W ARNING ON P AGE 20. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSARY TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD AN ANTI-SCALD V ALVE FOR HOT W A TER SUPPLIED TO FIXTURES. A listed temper[...]
-
Page 15
15 ONE OR TWO TEMPERA TURE - ONE HEA TERS,HIGH TEMPERA TURE STORAGE WITH OR WITHOUT RECIRCULA TION HEA TER WITH OR WITHOUT MIXING V AL VE HEA TER WITH MIXING V AL VE AND RECIRCULA TED SANITIZING LOOP NO TE 1 : T OGGLE SWITCH CONTROLS 180°F (82°C) W A TER CIRCULA TION. INST ALL ON OR CLOSE TO DISHWASHING MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON) [...]
-
Page 16
16 TWO TEMPERA TURE - TWO PRE-HEA TERS WITH MIXING V AL VE OR BOOSTER HEA TER WITH OR WITHOUT BUILING RECIRCULA TION TWO PRE-HEA TERS WITH MIXING V AL VE TWO PRE-HEA TERS WITH BOOSTER HEA TER DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE W A TER TEMPERA TURE CONTROL W ARNING ON P AGE 20. IF HIGHER PREHEA T TE[...]
-
Page 17
17 MEDIUM TEMPERA TURE - ONE HEA TER WITH AUXILIAR Y ST ORAGE T ANK FORCED CIRCULA TION WITH OR WITHOUT BUILDING RECIRCULA TION VERTICAL ST ORAGE T ANK HORIZONT AL ST ORAGE T ANK DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE W A TER TEMPERA TURE CONTROL W ARNING ON P AGE 20. IF HIGHER PREHEA T TEMPERA TURES A[...]
-
Page 18
18 OPERA TION IMPORT ANT A qualied person must perform the initial ring of the heater . At this time the user should not hesitate to ask the individual any questions which they may have in regard to the operation and maintenance of the unit. An Operational Checklist is included at the rear of this manual. B y using this checklist the user may[...]
-
Page 19
19 A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner . Do not try to light the burner by hand. B. BEFORE OPERA TING smell all around the appliance area forgas.Besure tosmellnexttothe oorbecausesome gasisheavierthanairandwi[...]
-
Page 20
20 be set for 120° to 180°F water temperature, but 120°F is the recommended starting point. It is suggested the dial be placed on the lowest setting which produces an acceptable hot water supply . This will always give the most energy efcient operation. The temperature control has a 4°F (2°C) xed differential. PREVENTIVE MAINTENANCE CHEC[...]
-
Page 21
21 NOTE: 1. Remove main burners from unit. 2. Check that burner venturi and ports are free of foreign debris. 3. Clean burners with bristle brush and/or vacuum cleaner - DO NOT distort burner ports or pilot location. 4. Reinstall burners in unit. Make sure front and rear of burners are installed correctly in burner support brackets. Also check for [...]
-
Page 22
22 RELIEF V AL VE At least once a year , the temperature and pressure relief valve should be checked to ensure that it is in operating condition. Lift the lever at the top of the valve several times until the valve seats properly and operates freely . If the appliance installation includes other relief valves, such as in “remote” storage tanks [...]
-
Page 23
23 Example 2: If initial inspection after 6 months shows 2” of lime accumulation. Therefore, the heater should be delimed every 3 months. FIGURE 14 DELIMING SOL VENTS Hydrochloric base acids are not recommended for use on glass lined tanks. CAUTION Observe handling instructions on label of product bein g used. T ANK CLEANOUT PROCEDURE The followi[...]
-
Page 24
24 VERIFY PROPER OPERA TION AFTER SER VICING. REPLACEMENT P ARTS Replac eme nt par ts may be o rdere d t hrou gh Lo chi nvar deale rs, auth or ized ser v ic ers or dist rib utor s. Refer to the Y ellow Pages for where to call o r c ontac t t he Pa rt s Department, 300 Maddox Simpson Pkwy , Lebanon, TN 37090, Phone: 615-889-8900 • Fax: 615-882-291[...]
-
Page 25
25 SEQUENCE OF OPERA TION FLOW CHART Description of this ow chart can be found in the “SEQUENCE OF OPERA TION” section found on page 18. Switch power on to unit. Thermostat calls for heat. Ignition Control Board performs diagnostic check on components Ignition Control Board sends power to Exhaust Inducer Exhaust Inducer engages Prover Switch[...]
-
Page 26
26 OPERA TIONAL CHECKLIST This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERA TION” should be used as an on-the-job troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction. Because improper piping and wiring can result in unsatisfactory system performance,[...]
-
Page 27
27 Limited Warranty 1 . THE TANK I f the glass-lin ed tank in this water heate r shall pro ve upon exa mination by t he w arrantor to have leaked due to natural corr osion f ro m potable w ater therein, during the f i r st T HR EE year s after initial in stallation, the w arrantor will supply a complete new Lochinvar w ater heater of equi valent si[...]
-
Page 28
28 Copyright © 201 1 Lochinvar , LLC, All rights reserved. 300 Maddox Simpson Parkway Lebanon, TN 37090 Phone: 615-889-8900 • Fax: 615-547-1000 T echnical Service email: 2tech@lochinvar .com www .Lochinvar .com[...]