Mitsumi electronic PKA-A12HA4 manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 36 pages
- 2.2 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Air Conditioner
Mitsumi electronic LGH-F470RX3-E
4 pages 1.27 mb -
Air Conditioner
Mitsumi electronic MUZ-ANA
40 pages 0.28 mb -
Air Conditioner
Mitsumi electronic PLA-A18AA
44 pages 1.67 mb -
Air Conditioner
Mitsumi electronic PUY-A12/18/24/30/36/42NHA3-BS
52 pages 4.11 mb -
Air Conditioner
Mitsumi electronic PKA-A12HA4
36 pages 2.2 mb -
Air Conditioner
Mitsumi electronic MS09NW(WH)
57 pages 2.37 mb -
Air Conditioner
Mitsumi electronic SUZ-KA25
8 pages 0.9 mb -
Air Conditioner
Mitsumi electronic MSY-GANA
40 pages 0.28 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation Mitsumi electronic PKA-A12HA4. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel Mitsumi electronic PKA-A12HA4 ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation Mitsumi electronic PKA-A12HA4 décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation Mitsumi electronic PKA-A12HA4 devrait contenir:
- informations sur les caractéristiques techniques du dispositif Mitsumi electronic PKA-A12HA4
- nom du fabricant et année de fabrication Mitsumi electronic PKA-A12HA4
- instructions d'utilisation, de réglage et d’entretien de l'équipement Mitsumi electronic PKA-A12HA4
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage Mitsumi electronic PKA-A12HA4 ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles Mitsumi electronic PKA-A12HA4 et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service Mitsumi electronic en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées Mitsumi electronic PKA-A12HA4, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif Mitsumi electronic PKA-A12HA4, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation Mitsumi electronic PKA-A12HA4. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
SER VICE MANUAL SPLIT -TYPE, HEA T PUMP AIR CONDITIONERS SPLIT -TYPE, AIR CONDITIONERS NOTE: • This manual describes only service data of the indoor units. • RoHS compliant products have <G> mark on the spec name plate. CONTENTS 1. REFERENCE MANUAL ................................... 2 2. SAFETY PRECAUTION ................................[...]
-
Page 2
2 1 REFERENCE MANUAL 1-1. OUTDOOR UNIT SERVICE MANUAL Service Ref. Service Manual No. PUZ-A18/24/36NHA4 PUZ-A18/24/36NHA4-BS PUY -A12/18/24/36NHA4 PUY -A12/18/24/36NHA4-BS OCH481 OCB481 Radio frequency interface Wired remote controller IR wireless remote controller ON/OFF TEMP. COOL DRY AUTO FAN HEAT RF thermostat Remote controller (Optional parts)[...]
-
Page 3
3 SAFETY PRECAUTION 2 Cautions for units utilising refrigerant R410A 2-2. CAUTIONS RELA TED TO NEW REFRIGERANT Use new refrigerant pipes. Store the piping to be used indoors during installation, and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.) Charge refrigerant from liquid phase of g[...]
-
Page 4
4 Gravimeter Unit [3] Service tools Use the below service tools as exclusive tools for R410A refrigerant. 3 P ART NAMES AND FUNCTIONS Indoor unit Filter Air intake Louver Air outlet V ane No. T ool name Specifications 1 Gauge manifold · Only for R410A · Use the existing fitting specifications . (UNF1/2) · Use high-tension side pressure of 5.3MPa[...]
-
Page 5
5 ● Wired remote controller (Option) °F°C °F°C ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SA T ON OFF Hr AFTER FIL TER FUNCTION ONL Y1Hr. WEEKL Y SIMPLE AUT O OFF P AR-21MAA ON/OFF FIL TER CHECK OPERA TION CLEAR TEST TEMP . MENU BACK D A Y MONITOR/SET CLOCK ON/OFF • • Display Section For purposes of this explanation, all parts of[...]
-
Page 6
6 ● IR wireless remote controller (Option) ON/OFF TEMP FA N VA N E TEST RUN AUTO ST OP AUTO ST ART h min LOUVER MODE CHECK RESET SET CLOCK MODEL SELECT NOT A VAILABLE SWING CHECK FA N TEST RUN °F °C AMPM STOP ST ART AMPM COOL DRY AUTO FA N HEA T V ANE CONTROL button Changes the air flow direction. CLOCK button RESET button SET button ON/OFF but[...]
-
Page 7
7 SPECIFICA TIONS 4 A A kW F.L.A m 3 /min(CFM) Pa(mmAq) dB mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs) Service Ref. Power supply(phase, cycle, voltage) Max. Fuse Size Min.Circuit Ampacity External finish Heat exchanger Fan Fan(drive) % No. Fan motor output Fan motor Airflow(Low-Middle-High) External static pressure Operation control & Thermostat No[...]
-
Page 8
8 5 NOISE CRITERION CUR VES 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMA TE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 μ bar) BAND CENTER FREQUENCIES, Hz PKA-A12HA4 PKA-A18HA4 High NOTCH Low 43 SPL(dB) 36 LINE UNIT WA L L 3.3ft 3.3ft MI[...]
-
Page 9
9 OUTLINES AND DIMENSIONS 6 PKA-A12HA4 PKA-A18HA4 Unit: inch (mm) 1/2F ( : 12.7) 1/4F ( : 6.35) Refrigerant Piping Drain hose Gas pipe Liquid pipe : 2-1/2~ : 3-1/8 ( : 65~ : 80) : 2-1/2~ : 3-1/8 ( : 65~ : 80) Through hole Sleeve (purchased locally) Center measurement hole : 3/32( : 2.5) 5/32(3.8) 2-1/4(58) 0 Wall hole for left rear piping Knock out[...]
-
Page 10
10 WIRING DIAGRAM 7 PKA-A12HA4 PKA-A18HA4 The black square ( ■ ) indicates a switch position. Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring m[...]
-
Page 11
11 REFRIGERANT SYSTEM DIAGRAM 8 Thermistor TH2 Pipe temperature(Liquid) Distributor with strainer (#50/#50) Thermistor TH5 (Cond./ Eva.temperature) Thermistor TH1 (Room temperature) Refrigerant flow in cooling Refrigerant flow in heating Strainer (#50) Strainer (#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Refrigerant LIQUID pipe con[...]
-
Page 12
12 TROUBLESHOOTING 9 <Error code display by self-diagnosis and actions to be taken for service (summary)> Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below . Check the [...]
-
Page 13
13 13 [Procedure] 1. Press the CHECK button twice. 2. Press the temperature buttons. 3. Point the remote controller at the sensor on the indoor unit and press the HOUR button. 4. Point the remote controller at the sensor on the indoor unit and press the ON/OFF button. ON/OFF TEMP FA N VA N E MODE CHECK LOUVER TEST RUN A UTO ST OP AU TO S T A RT h m[...]
-
Page 14
14 [Output pattern A] Errors detected by indoor unit [Output pattern B] E9 *1 If the beeper does not sound again after the initial 2 beeps to confirm the self-check star t signal w as received and the OPERA TION INDICA T OR lamp does not come on, there are no error records. *2 If the beeper sounds 3 times continuously “beep , beep , beep (0.4 + 0[...]
-
Page 15
15 • If the unit cannot be operated properly after the test run, refer to the f ollowing table to find out the cause . Symptom Cause Wired remote controller LED 1, 2 (PCB in outdoor unit) On the IR wireless remote controller with condition abov e, f ollowing phenomena take place . • No signals from the remote controller can be received. • OPE[...]
-
Page 16
16 9-3. SELF-DIAGNOSIS ACTION T ABLE Note: Refer to the manual of outdoor unit for the details of display su ch as F , U , a nd ot he r E . Error Code Abnormal point and detection method Cause Countermeasure P1 Room temperature thermistor (TH1) The unit is in 3-minute resume prevention mode if short/open of thermistor is detected. Abnormal if the u[...]
-
Page 17
17 Error Code Abnormal point and detection method Cause Countermeasure P6 Freezing/overheating protection is operating Freezing protection (Cooling mode) The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/evapo- rator> temperature stays under the compressor started. Abnormal if it again within 16 minutes after 6-minut[...]
-
Page 18
18 Error Code Abnormal point and detection method Cause Countermeasure P9 Pipe temperature thermistor/ Condenser-Evaporator (TH5) The unit is in 3-minute resume protec- tion mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within 3 minutes. (The unit returns to normal operation, if it has been reset nor[...]
-
Page 19
19 E6 Contact failure, short circuit or , miswiring (converse wiring) of indoor/outdoor unit connecting wire Defective transmitting receiving circuit of outdoor controller circuit bo ar d. Defective transmitting receiving circuit of indoor controller board Noise has entered into indoor/ outdoor unit connecting wire. Check LED display on the outdoor[...]
-
Page 20
20 Note: Refer to the manual of outdoor unit for the detail of remote co nt ro l le r . (1)Upward/downward vane performance failure The vane is not downward during defrosting and heat preparation and when the thermostat is OFF in HEA T mode. (Working of COOL protection function) V ane motor does not rotate. • Defective vane motor • Breaking of [...]
-
Page 21
21 9-5. EMERGENCY OPERA TION 9-5-1. When IR wireless remote controller fails or its battery is exhausted 9-5-2. When wired remote controller or indoor unit microprocessor fails When the remote controller cannot be used DEFROST/ST AND BY lamp (ORANGE) Operation lamp (GREEN) Emergency operation switch (cooling/heating) Receiver [Heat [...]
-
Page 22
22 9-6. HOW TO CHECK THE P ARTS Parts name Check points V ane motor (MV) Measure the resistance between the terminals with a tester . (Coil temperature 77 " F ) Normal 350 ± 7% Abnormal - Brown-Red - Brown-Orange - Brown-Y ellow - Brown-Green Open or short Fan motor (MF) Red Y ellow Brown Orange[...]
-
Page 23
23 9-6-2. DC Fan motor (fan motor/indoor controller circuit board) Notes · High voltage is applied to the connecter (CNMF) for the fan motor . Pay attention to the service. · Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit board and fan motor .) Self check Symptom : [...]
-
Page 24
24 9-7. TEST POINT DIAGRAM Indoor controller board PKA-A12HA4 PKA-A18HA4 { CN51 Centrally control 1 - 2 : Control signal 13VDC pulse input ( 1 : +) 3 - 4 : Operation indicator 13VDC ( 3 : +) 3 - 5 : Malfunction indicator 13VDC ( 3 : +) CN44 Pipe temperature thermistor 1 - 2 : Liquid (TH2) 3 - 4 : Condenser/Evaporator (TH5) CN20 Room temp. thermisto[...]
-
Page 25
25 SW1 Setting by the dip switch and jumper wire Functions Jumper wire Model settings Capacity settings Pair number setting with IR wireless remote controller Remarks SW2 J41 J42 Indoor controller board type setting JP3 0 1 2 3 ~ 9 Wireless remote controller setting Control PCB setting J41 J42 <Initial setting> IR wireless remote controller: [...]
-
Page 26
26 10 SPECIAL FUNCTION Note: · When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start oper- ation. · T o operate the main unit, refer to the 10-1-2. and set the request code No. which is not the same as the current one, and set again the former request code No. (2) 2nd stage cut[...]
-
Page 27
27 27 System constraint · This function is available only in cooling mode. Ex.) Set temp. by R/C = 20 : (68°F) Set point = 26 : (79°F) When request code number is “323”. 26 : 2nd unit Cut-in 4 degree C 22 : 2nd unit Cut-out 20 : 10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function) Y ou can set these functions by[...]
-
Page 28
28 (2) Setting method of each function by wired remote controller B: Refrigerant address C: Data display area D: Request code display area TEST CHECK FIL TER FIL TER ON/OFF 1. Stop operation( ). 2. Press the button ( ) for 3 seconds so that [Maintenance mode] appears on the screen ( ). After a while, [00] appear[...]
-
Page 29
29 DISASSEMBL Y PROCEDURE 11 Be careful when removing heavy parts. Push Push Down Be careful not to damage the airflow adjustment plate with the screw driver . Corner hole 1. REMOVING THE LOWER SIDE OF THE INDOOR UNIT FROM THE INST ALLA TION PLA TE (1) Remove the front panel. (2) Insert the screw driver to the corner hole at both left and right sid[...]
-
Page 30
30 4. REMOVING THE ELECTRICAL BOX (1) Remove the front panel. (Refer to step 2) (2) Remove the electrical box covers. (See Photo 3) (3) Remove the nozzle assembly . (Refer to step 5) (4) Disconnect the connecting wire from terminal block (TB4) and terminal block for MA-remote controller (TB5). (5) Disconnect the connectors on the indoor controller [...]
-
Page 31
31 5. REMOVING THE NOZZLE ASSEMBL Y (with V ANE and V ANE MOT OR) AND DRAIN HOSE (1) Remove the front panel (Refer to step 2). (2) Remove the electrical box cover . (3) Disconnect the vane motor connector (CN151) on the indoor controller board. (4) Remove the corner box. (5) Pull the nozzle assembly and detach. (6) Push the fixture and remove the d[...]
-
Page 32
32 8. REMOVING THE LIQUID PIPE THERMISTOR AND COND/EV A TEMP . THERMIST OR (1) Remove the front panel. (Refer to step 2) (2) Remove the electrical box cover . (3) Remove the motor band. (4) Cut the wiring fixed band. (5) Remove the liquid pipe thermistor and cond/eva temp. ther- mistor . (6) Disconnect the connector (CN44) on the indoor controller [...]
-
Page 33
33[...]
-
Page 34
34[...]
-
Page 35
35[...]
-
Page 36