American Power Conversion MX28B4800 manuale d’uso
- Visualizza on-line o scarica il manuale
- 70 pagine
- 3.39 mb
Vai alla pagina of
Manuali d’uso simili
-
Power Supply
American Power Conversion PDRPPNX10
80 pagine 1.87 mb -
Power Supply
American Power Conversion RS 1500
2 pagine 0.54 mb -
Power Supply
American Power Conversion P D U
24 pagine 0.72 mb -
Power Supply
American Power Conversion BR1200
2 pagine 0.46 mb -
Power Supply
American Power Conversion 1400XLT
30 pagine 0.87 mb -
Power Supply
American Power Conversion 2200 VA, 120 Vac, 230 Vac, 3000 VA, 100 Vac, 120 Vac, 208 Vac, 230 Vac
17 pagine 0.31 mb -
Power Supply
American Power Conversion 475I
2 pagine 0.19 mb -
Power Supply
American Power Conversion SUDP10000I
24 pagine 0.81 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso American Power Conversion MX28B4800. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica American Power Conversion MX28B4800 o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso American Power Conversion MX28B4800 descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso American Power Conversion MX28B4800 dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo American Power Conversion MX28B4800
- nome del fabbricante e anno di fabbricazione American Power Conversion MX28B4800
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature American Power Conversion MX28B4800
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio American Power Conversion MX28B4800 non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti American Power Conversion MX28B4800 e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio American Power Conversion in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche American Power Conversion MX28B4800, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo American Power Conversion MX28B4800, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso American Power Conversion MX28B4800. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
MX28B1200/2400 MX28B1200/4800 -48 VDC POWER SYSTEMS User’s Manual (Document # 990-1 148A)[...]
-
Pagina 2
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page ii Table of Contents 1 SAFETY FIRST! .................................................................................................................. ...1 1.1. W ARNING S YMBOLS .........................................................................................................1 1[...]
-
Pagina 3
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page iii 3.10. E XTERNAL A LARM I NPUT C ONNECTIONS .......................................................................... 25 3.11. R ECTIFIER M ODULE I NSTALLATION ...................................................................................26 4 COMMISSIONING AND PREVEN TIVE MAINTE[...]
-
Pagina 4
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page iv 6.3. C OMMAND AND M ONITORING P ROTOCOL .........................................................................54 7 PREVENTIVE MA INTENA NCE............................................................................................ 55 7.1. E QUIPMENT ...............................[...]
-
Pagina 5
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page v Revision History Revision Date By Description 1 31 JAN, 2002 JNF Converted to APC numbering 2 28 SEP, 2003 BET Updated Format and added 4800 Table of Figures FIGURE 2.2-1 MX28B-1200 –48 VDC PO WER PLANT RECTIFIER BAY.............................................3 FIGURE 2.2-2 MX28B BL[...]
-
Pagina 6
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 1 1 Safety First! It is very important to follow all safety procedures when unpacki ng, installing and operating any sort of power equipment. 1.1. Warning Symbols CAUTION : An indication that special care is required to prevent injury, equipment damage or misuse WARNING : An indication o[...]
-
Pagina 7
2 Introduction 2.1. General Information DC Power Plants from APC have unique features that make them easy to in stall, maintain, and upgrade. The rectifier units are modular and tr uly “hot-pluggable” into the shelf assembly without any separate AC wiring. All system settings are made from the system control unit that provides monitoring and co[...]
-
Pagina 8
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 3 Figure 2.2-1 MX28B-1200 –48 VDC Power Plant Rectifier Bay[...]
-
Pagina 9
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 4 Figure 2.2-2 MX28B Block Diagram[...]
-
Pagina 10
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 5 3 Installation 3.1. Unpacking Equipment Remove equipment from packing material and inspect for shipping damage or missing items. It is important to report damage or material shortages to the shipping carrier while a representative is on site. If concealed damage or material shortages a[...]
-
Pagina 11
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 6 Mounting The box frame housing the MX28B components is self-supporting, but designed to be bolted to the floor of the housing structure. Figure 3.2-1 shows the footprint of the box frame and the mounting points with dimensions (shown in inches). Consult the system design specifications[...]
-
Pagina 12
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 7 Figure 3.2-2 MX28B-1200-2400 has a maximum capacity of 2400 Amps. Figure 3.2-3 The MX28B1200-4800 can be expanded to 4800 Amps. Figure 3.2-4 Splice Plate Installation[...]
-
Pagina 13
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 8 Circuit Breaker/LVD Ri bbon Cable Connections Additional cables must be conne cted between cabinets to ensure that the circuit breaker alarms in the expansion bays are repor ted correctly. The circuit breakers and LVDs are connected together through the use of a Circu it Breaker / LVD [...]
-
Pagina 14
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 9 Fuse Alarm Ribbon Cable Connections There is a 16-conductor ribbon cable, if any bay has fu ses installed. This cable ties together the Wago breakout board in each bay with fuses. The ribbon cable must connect all the Wago breakout boards together with one ribbon cable. The idea is tha[...]
-
Pagina 15
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 10 input. The AC wiring, from the AC input terminal block connections to the hot-pluggable AC input connector for each rectif ier, is factory installed. The AC input enclosure, located at the top rear of the MX28B rectif ier bay, is provided with nine ¼ -inch pilot holes in the top plat[...]
-
Pagina 16
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 11 If the AC input power is prov ided from a three-phase distribut ion panel, the circuit breaker positions should be selected such that the load is balanced as much as possible. WARNING : The MX28B DC power plant is supplied from a high voltage source. Keep the AC input enclosure in pla[...]
-
Pagina 17
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 12 Connecting the Battery Cables WARNING : Make certain that the battery polarity is correct when making connections to the Model MX28B DC po wer plant. Incorrect connection could cause severe equipment damage. The battery cable connections are located at the top rear of the unit as sh o[...]
-
Pagina 18
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 13 Battery Temperature Probe Installation The optional temperature probe is used to monitor the battery string temperature. To get the most representative temperatur e measurement, the probe should be placed in contact with a battery cell that is centrally loca ted. The probe should be p[...]
-
Pagina 19
Figure 3.5-1 DC System Grounding Figure 3.5-2 Box Frame Ground 3.6. DC Power Output Over-Current Protection There are several different options for DC output power distribution. Distribution provides a convenient method of connecting the load cables as well as over-current protection. DC Plug-in Circuit Breakers A standard 48-position plug-in circu[...]
-
Pagina 20
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 15 the Wago connectors based on what bay the circuit br eaker tiers are in. Typical circuit breaker numbering is bay 1: Cir Bkr 1-48, Bay 2: Cir Bkr 49-50, Bay 3: Cir Bkr 51-52 and Bay 4: Cir Bkr 53-54. Figure 3.6-1 shows the power plant’s main bay (with ribbon cables) DC distribution [...]
-
Pagina 21
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 16 10 A FFA-0017 70 A 530-9089 15 A 530-9093 80 A 530-9090 20 A FFA-0018 100 A 530-9091 30 A FFA-0019 Figure 3.6-2 Plug-in Circuit Breakers BreakerRating Part Number Adaptor Size 60 A FFA-0021-1 #10 studs on 5/8” centers 60 A FFA-0021-2 #10 studs on ¾” centers 60 A FFA-0021-3 ¼” [...]
-
Pagina 22
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 17 DC Bolt-in Circuit Breakers Bolt in Breakers in a variety of sizes up to 700 Amps are avai lable. Triple pole breakers are available in sizes ranging from 400-700 Amps. Double pole brea kers are available in sizes ranging from 250-400 Amps. Single pole breakers are available in sizes [...]
-
Pagina 23
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 18 Telecom Fuses Telecom fuses in sizes ranging from 70 – 600 Amps are available. A panel in each rectifier bay will accommodate 4 fuse holders. Typical fuse numbering is Bay 1: Fuse 1- 4, Bay 2: Fuse 5-8, Bay 3: Fuse 9-12 and Bay 4: Fuse 13-16. Only one fuse can be hooked up to any al[...]
-
Pagina 24
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 19 3.7. Installat ion of Circuit Breakers and Fuses Plug-in Circuit Breaker Installation CAUTION During circuit breaker installation, carefully align the breaker alarm terminals with the alarm terminal board to avoid breaker terminal damage. 1) Remove the circuit breaker cover panel and [...]
-
Pagina 25
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 20 Bolt-in Circuit Breaker Installation 1) Remove the circuit breaker cover panel and the pl astic cover(s) from the desired location(s). 2) Install the circuit breaker(s) by bolting the ci rcuit breaker onto the bus at the bottom of the assembly. Bolt the lug landing bus to the top of t[...]
-
Pagina 26
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 21 Telecom Fuse Installation 1) Remove the fuse(s) from the desired location(s) by pulling the fuse holder straight out of the fuse holder base. 2) Install the fuse(s) by bolting t he fuses(s) into the fuse holder. 3) Re-install the fuse holder by pushing the holder straight in. 4) Conne[...]
-
Pagina 27
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 22 3.8. Load Connections Cable Size Considerations The DC load cable(s) should be sized sufficiently large to limit the voltage drop from the MX28B DC power plant to the loads per system design requirement s. The cable(s) must also carry the full load current during battery operation. Du[...]
-
Pagina 28
Figure 3.8-1 Load connections for snap-in breakers Figure 3.8-2 Return Connections GMT Fuse Connections GMT fuses are only connected to -48VDC if the system has been purchased with the GMT fuse option. This option supplies -48VDC to lugs on the interface card through #6 AWG power cables controlled by a 50 Amp circuit breaker loca ted in circuit bre[...]
-
Pagina 29
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 24 The DB9 connector on the top right hand side of the unit, behind a blank pa nel directly above the controller, uses the s pecial RS-232 cable (APC part number 940-0024C) to allow local access through a Terminal Emulation progr am like HyperTerminal™ or Procomm™ . RJ45 Ethernet Con[...]
-
Pagina 30
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 25 RELAY OUTPUT TERMINAL DESIGNATION NO-NC-C USER ALARM NOTES RELAY #1 RELAY #2 RELAY #3 RELAY #4 RELAY #5 RELAY #6 MINOR MAJOR NO1-NC1-C1 NO2-NC2-C2 NO3-NC3-C3 NO4-NC4-C4 NO5-NC5-C5 NO6-NC6-C6 NO7-NC7-C7 NO8-NC8-C8 ________________________ ________________________ ______________________[...]
-
Pagina 31
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 26 3.11. Rectifier Module Installation WARNING : Rectifier DC output circuits would be damaged if battery were installed incorrectly. Before rectif ier installation, ensure proper battery polarity and that the battery is isol ated from the rest of the system The rectifier modules are shi[...]
-
Pagina 32
4 Commissioning and Preventive Maintenance 4.1. Pre-Commissioning Inspection Environment 1. Ensure the DC system environment is suitable for operation. 2. Ensure that there is sufficient clearance around the system for service. 3. Ensure that there is no sign of damage to the DC system. 4. Consult with customer to disable installed customer alarms [...]
-
Pagina 33
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 28 b. Case leaks . c. Post- seal leaks. d. Pressure relief valve leaks (VRLA only). e. Case swelling (VRLA only). f. Case swelling (VRLA only). 10. Check the torque of all battery inter- cell connector in accordance with the battery manufacturer’s specifications. 4.2. Commissioning Ini[...]
-
Pagina 34
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 29 DC Power Up: 1. Verify with a voltmeter that the dc voltage is within 0.1 Vdc of the System Voltage. If the voltage is off adjust the R offs et setting under the OEM menu. If the R Offset setting is more than +/- 1.00 Volt dc, contact APC for a replacement controller module. 2. Adjust[...]
-
Pagina 35
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 30 Circuit Breaker/ Fuse Test: 1. For plug- in circuit breakers. Monitor al arm screen for circuit break er alarm while shorting out each pair of alarm contacts (using a pair of tweezers) on the circ uit breaker interface circuit board. Verify proper voltag e at the circuit breaker commo[...]
-
Pagina 36
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 31 4.3. Final Inspection: 1. Verify that the interi or and exterior of the syste m is clean and free from debris. 2. Ensure all wires connect ed and bolts are properly tightened. 3. Ensure the following the User, Service, and Calibration parameters are set properly on the controller (def[...]
-
Pagina 37
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 32 5 Operation 5.1. Technical Description The MX28B-1200/2400 Powe r System is designed to supp ly s afe –54 VDC primary power through the use of up to 24 rectifier modules. One rectifier bay may be added to increase the capacity to 48 rectifiers. The MX28B-1200/4800 Powe r System is d[...]
-
Pagina 38
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 33 5.3. System Management System Output Capacity The power plant has two basic configurations: The MX28B-1200/2400 supplies a maximum of 2400 amps or 2350 amps with N+1 redundancy. The housing for this configuration provides two rectifier bays with integrated DC output distribution, a co[...]
-
Pagina 39
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 34 System Status and Alarm Reporting The PSCU monitors system voltage using a high accuracy digital voltmeter attached to the system bus. The PSCU monitors system temperature using a tem perature IC mounted in the PSCU. The PSCU monitors system current by summing the current reported by [...]
-
Pagina 40
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 35 Battery Temperature Compensation The Battery Float Voltage is set to the value recommended by the battery manufacturer in order to maintain correct battery charge at 25ºC. As temperature rises, electrochemical activity in a battery increases. Similarly, as temperature falls, electroc[...]
-
Pagina 41
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 36 right corner of the display. If a security level higher than the one presently set is required to modify the parameter, "s+" is displayed instead of “m+”. Status, alarms, and information screens have "+" in the upper right corner of the disp lay (or “#” in [...]
-
Pagina 42
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 37 1. Use the right or left arrow keys to position the cycling cursor below “SYSTEM”. 2. Press the down arrow key once. 3. Use the right arrow key to positi on the cycling cursor below “IN-RLY”. 4. Press the down arrow key once; the cursor will be cycling below “RLY-MAP”. 5. [...]
-
Pagina 43
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 38 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Battery High Temperature Alarm Security Level {1} [BATT/SET-ALM] The output relay energized if the battery temperature exceeds the Battery High Temperature threshold. Batt HT Alm m+ Minor Battery High Tempe[...]
-
Pagina 44
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 39 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Circuit Breaker 1 Tripped Security Level {1} [MODULES/CIRBKR /SET- ALM] • • • Circuit Breaker 24 Tripped Security Level {1} [MODULES/CIRBKR /SET- ALM] An alarm that indicates Circuit Brea ker 1 is tri[...]
-
Pagina 45
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 40 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS FUSE 1 Blown Security Level {1} [MODULES/FUSE/SET-ALM] • • • FUSE 8 Blown Security Level {1} [MODULES/FUSE/SET-ALM] The Output Relay that is energized whe n FUSE Fuse 1 is blown. • • • The Outpu[...]
-
Pagina 46
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 41 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS LVD 1 or 2 Option Security Level {1} [MODULES/LVD/SET-ALM] Must be set to “Enable” if the unit has an LVD. If the unit has an LVD, but it is disabled, the controller will not di sconnect the LVD. LVD Op[...]
-
Pagina 47
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 42 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Output Relay 1 Delay Security Level {1} [SYSTEM/OUT-RLY/RLY- MAP] • • • Output Relay 6 Delay Security Level {1} [SYSTEM/OUT-RLY/RLY- MAP] Delay between sensing of the alarm co ndition and activation o[...]
-
Pagina 48
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 43 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Rectifier De scription {Status Only} [MODULES/RECT/INFO] Displays the model number of the installed rectifier. NOTE : This information can be viewed for each rectifier installed by using the horizontal arro[...]
-
Pagina 49
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 44 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS System High Voltage alarm Security Level {1} [SYSTEM/SET-ALM] The output relay energized if the System Voltage is above the System High Voltage threshold. Sys HV Alm m+ Minor System High Voltage Threshold S[...]
-
Pagina 50
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 45 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Time Security Level {1} [SYSTEM/DATE] Internal system clock time (24-hour format). Used as a date stamp in the event log. Time m+ 9:00:25[...]
-
Pagina 51
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 46 Control Unit Menu Structure The complete menu structure sho wn in the order in which it is acces sed from the control unit display is presented in out line form below. Each indentation to th e right represents a m enu level b elow the indicated title. Top Level S e c o n d L e v e l T[...]
-
Pagina 52
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 47 Top Level S e c o n d L e v e l T h i r d L evel Fourth Level • • Hw Batt C Alm • • Hw Batt T Alm • • Hw Sys T Alm • • Hw LVD Alm • SYS: + LM SETUP DATE PIN 1 • • PIN 2 • • Address 1 • • Address 2 • • Address 3 • • Model • • Fahrenheit • •[...]
-
Pagina 53
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 48 Top Level S e c o n d L e v e l T h i r d L evel Fourth Level • • • Out-Rly 3 • • • Out-Rly 4 • • • Out-Rly 5 • • • Out-Rly 6 • • • Relay Minor • • • Relay Major • SYS: + LY IN-RLY DIAG SYS:IN-: + RLY-MAP ALIAS In-Rly 1 Alm • • • In-Rly 2 Al[...]
-
Pagina 54
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 49 Top Level S e c o n d L e v e l T h i r d L evel Fourth Level • • • Rect Fail Comm • • MOD:REC: + AM INFO Rect # Desc • • • Rect # Curr • • • Rect # CL • • • Rect # Stdby • • • Rect # FF • • • Rect # RFA • MOD: + CT CIR-BKR FUSE MOD:CIR: + SET[...]
-
Pagina 55
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 50 Top Level S e c o n d L e v e l T h i r d L evel Fourth Level • • • FUSE 6 Alm • • • FUSE 7 Alm • • • FUSE 8 Alm • • • FUSE 9 Alm • • • FUSE 10Alm • • • FUSE 11Alm • • • FUSE 12Alm • • • FUSE 13Alm • • • FUSE 14Alm • • • FUSE[...]
-
Pagina 56
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 51 Top Level S e c o n d L e v e l T h i r d L evel Fourth Level • • MOD:LVD: + LM PARAM LVD 1 Trip • • • LVD 1 Reset • • • LVD 2 Trip • • • LVD 2 Reset MX28B 1200 + ES BATT PIN OEM BAT: + SET-ALM PARAM C Batt Disc Thr • • Batt Disc Alm • • Batt HV Thr • ?[...]
-
Pagina 57
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 52 Front Panel LED Indicators Major (Red) On when Major Relay is de-energized* Minor (Yellow) On when Minor Relay is energized Normal (Green) On when no alarms are active ALM 1 (Red) On when Output Relay 1 is energized ALM 2 (Red) On when Output Relay 2 is energized ALM 3 (Red) On when O[...]
-
Pagina 58
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 53 5.8. External Alarm Inputs (Input Relays) The controller can monitor any exte rnal device that uses a swit ch or relay to output status information. Connecting the external device to the input relay connections is the first step. The four external alarm inputs (also referred to as “[...]
-
Pagina 59
6 Remote Monitoring 6.1. Description Remote monitoring and control of the DC power system is acco mplished through the use of the optional APC Network Manage ment card. This c ard is a s eparate module mounted into the top panel of the system controller module. Complete documentation for the use of the management card accompanies the DC power syste[...]
-
Pagina 60
7 Preventive Maintenance Preventive Maintenance is typically performed on a quarterly basis. 7.1. Equipment 1. 4 Digit Voltmeter. 2. Clamp-on Ampere meter. 3. Standard Insulated tools. 7.2. Inspection Environmental Inspection 1. Ensure the DC system environment is suitable for operation. 2. Ensure that there is sufficient clearance around the syste[...]
-
Pagina 61
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 56 a) DC Voltage Rating. b) DC Current Rating c) Interrupting Current Rating Battery Visual and Safety Inspection 1. Check that the battery temperature probe is firmly attached to the battery. 2. Check the mechanical integrit y of the battery framing, racki ng, or cabinet. Tighten where [...]
-
Pagina 62
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 57 Rectifier Current Share Test Verify that the highest rectifier current and the lowest current are within 5 amps. System Current Test Verify the System current equal to the total of the rectifier currents. System current should equal the total current of the loads as well as any batter[...]
-
Pagina 63
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 58 Battery Temperature Test If the battery teperature probe is used in this syst em, verify that the battery temperature i s correct. LVD Test 1. Verify that the Battery Float voltage is set to negative (-) 54.00 Volts via the control panel and verify the temperature compensation setti n[...]
-
Pagina 64
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 59 9. Ensure that all protective covers are repl aced and that the battery is electrically non- hazardous to personnel that c ould be working in the vicinity. Detail any discrepancies. 10. Download the Cellcorder to a PC and create a data file for each battery string. Keep a copy of the [...]
-
Pagina 65
8 Specifications The overall system specifications can vary, depending upon the number of rectifier modules. Note that some specification items are provided on a “per rectif ier” basis and must be combined or totaled for a give system configuration. 8.1. AC Input 1MRF28H54BV Rectifiers Nominal Input Voltage 208, 230 VAC Input Voltage Range 176 [...]
-
Pagina 66
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 61 8.2. DC Output (with either 1MRF28H54BV Rectifiers and 1MRF28H54BV50 Rectifiers) Nominal Output Voltage (f actory set) 54.5 VDC Operating Voltage Range 44 – 58 VDC Rated Output Current (per Rectifier) 50 A Rated Output Power (per Rectifier) 2800 W (45ºC) Efficiency 91% Typical 8.3.[...]
-
Pagina 67
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 62 Float / Boost/Equalize Switch Used to Control voltage on systems without a PSCU Float Trim Pot The float pot is used to adjust the default float voltage (54.5 VDC). Boost/Equalize Trim Pot The boost/equalize pot is used to adjust the default boost equalize voltage (57.5 VDC). Power Sh[...]
-
Pagina 68
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 63 8.4. Mechanical Dimensions 84” high x 26” wide x 26” deep Housing 400-600 lbs. (181-272 Kg) Weight Rectifier (each) 11 lbs (5Kg) Color Dawn Gray Mounting Floor Mounting 8.5. Environmental (Operating) -45ºC to +55ºC (+ 65ºC with reduced power output) Ambient Temperature (Stora[...]
-
Pagina 69
MX28B1200/2400 MX28B1200/4800 –48 V DC User’s Manual Page 64 9 APC W orldwide Customer Support Customer Support for this or any other APC product is available at no charge. You can contact APC Customer Support in any of the following ways: • Use an APC web page to find answers to fr equently asked questions (FAQs), to access documents in the [...]
-
Pagina 70
10 Limited Pr oduct W arranty The limited warranty pro vided by American Power Co nversion Corporation ("APC") in this Statement of Limited Factory Warranty applies only to Produc ts Buyer purchases for your commerc ial or industrial use in the ordinary course of Buyer's business. APC PRODUCTS COVERED ("Product or Produc ts"[...]