American Power Conversion SYMF800KH manuale d’uso
- Visualizza on-line o scarica il manuale
- 54 pagine
- 1.83 mb
Vai alla pagina of
Manuali d’uso simili
-
Power Supply
American Power Conversion 480kW400V
32 pagine 3.5 mb -
Power Supply
American Power Conversion LVD300, LVD400, LVD500, LVD600, LVD1000
20 pagine 0.06 mb -
Power Supply
American Power Conversion 1400
2 pagine 0.27 mb -
Power Supply
American Power Conversion SURTA1500XL
16 pagine 0.61 mb -
Power Supply
American Power Conversion 400V
100 pagine 2.13 mb -
Power Supply
American Power Conversion 620 VA
14 pagine 0.34 mb -
Power Supply
American Power Conversion K250EI
40 pagine 0.29 mb -
Power Supply
American Power Conversion AP9554
68 pagine 1.74 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso American Power Conversion SYMF800KH. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica American Power Conversion SYMF800KH o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso American Power Conversion SYMF800KH descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso American Power Conversion SYMF800KH dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo American Power Conversion SYMF800KH
- nome del fabbricante e anno di fabbricazione American Power Conversion SYMF800KH
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature American Power Conversion SYMF800KH
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio American Power Conversion SYMF800KH non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti American Power Conversion SYMF800KH e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio American Power Conversion in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche American Power Conversion SYMF800KH, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo American Power Conversion SYMF800KH, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso American Power Conversion SYMF800KH. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
Inst allation Symmetra ® MW 800 kW 400 V ON OFF EMO[...]
-
Pagina 2
[...]
-
Pagina 3
Contents Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llati on - 990- 1510D i Safe ty ....... ..... ..... ........ ...... ........ ..... ........ ..... ...... ....... 1 IMPORTAN T SAFETY IN STRUCTI ONS - SAVE THES E INSTRU CTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Symbols us ed in this guid e . . . . . . . . . . . . . . . . . . . .[...]
-
Pagina 4
ii Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llati on - 990- 1510D Extern al Bypa ss Static Sw itch Wiri ng . . . . . . . . . . . . . . . . . . . . 18 Top cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 9 Bottom cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Commu nication cable overview . . [...]
-
Pagina 5
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llati on - 990- 1510D iii IT Syst ems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Chara cter istics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Refere nce to IEC 603 64-4-4 1 413.1. 5 . . . . . . . . . . . . . . . . . 39 Protectiv e devices in I[...]
-
Pagina 6
[...]
-
Pagina 7
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llati on - 990- 1510D 1 Safety IMPORT ANT SAFETY INS TRUCTIONS - SA VE THESE INSTRUCTIONS This gui de contain s importan t instru ction s for SYMF800KH tha t should b e followed when handli ng the UPS, External Bypas s S tatic S witch, Batt ery Enclosure s, and Ba tteries. Symbols used in this guide W ARNI[...]
-
Pagina 8
Safety: IMPORTANT S AFETY INSTRUC TIONS - SAVE THES E INSTRUCTIONS 2 Symmetr a MW 800 k W 3 × 400/ 230 V Insta llation - 990-1510D Installation safe ty Press the optional EPO (Emer gency Power Of f) button to switch off all AC and DC power supply to con nected equi pment in t he room and t o cut of f the load sup ply . The EPO is typic a lly loc a[...]
-
Pagina 9
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 3 System Over view UPS Sections Serial numb er The seri al number i s stated on the type label behind t he finish ing pan el above t he displa y unit. Remove fini shing pane l to s ee seria l number . Inver ter Section The Inver ter Secti on regula tes the UPS output an d operates from [...]
-
Pagina 10
4 Symmetr a MW 800 k W 3 × 400/ 230 V Insta llation - 990-1510D Configurations The UPS syst em can b e configur ed in two ways. The Inverter Section can be placed ei ther to the le ft or to th e right o f the Contr ol Secti on. The two configur ations ar e shown belo w . Configu rati on 1 (Inverte r Section place d to the lef t) ON OFF EMO 2032 mm[...]
-
Pagina 11
System Overview: Configurations Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 5 Configu rati on 2 (Inverte r Section place d to the right) Width: 1012 mm Widt h: 1014 mm Control Section Input/Output Sectio n 2032 mm 1 0 6 7 m m Width: 1690 mm Inverter Section T o tal width of U PS sections: 3716 mm Weight : Without Power Modu les: [...]
-
Pagina 12
6 Symmetr a MW 800 k W 3 × 400/ 230 V Insta llation - 990-1510D External Bypass Static Switch The Exter nal Bypass S tatic Swit ch (Exter nal Bypass S SW ) trans fers th e load (m anually or auto maticall y) from the UPS to an alternat e sour ce without inte rrupting the supp ly to the load. Serial numb er The seri al number i s stated on the type[...]
-
Pagina 13
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 7 Electrical Installation Electrical Wiri ng Principle See also See separ ate guide on para llel oper ation fo r wiring o verview in parallel systems. Maintenance Bypass Panel (MBP) Symmetra MW External Bypass Static Switch Battery Breaker Box 1 Battery Breaker Box 2 Batteries 1 Batteri[...]
-
Pagina 14
Electrical Installation: Electri cal Wiring Principle 8 Symmetr a MW 800 k W 3 × 400/ 230 V Insta llation - 990-1510D Extern al discon nection switc hes Input/Output wiring pr ecautions W ARNING! The UPS has no i nternal manual disconnec t devices to switch off exter nal AC (Q1 and Q5) and DC (Q7 and Q8) input power . Ensur e that disconnect ion d[...]
-
Pagina 15
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 9 To p C a b l e E n t r y Pr eparing for top cable entry (Defau lt) Cable ent ry in T op Cover of Input/Out put Secti on. Loosen the 8 bolt s in both cable e ntry c overs (4 b olts i n each cov er). Drill h oles for t he grommets i n areas sh own. Instal l the gro mmets and re- fit[...]
-
Pagina 16
Electrical Installation: Top C able Entry 10 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Battery cable connecti ons (top cable entry) W ARNING! Make sur e that the batter y br eakers ar e open (OFF) pri or to running the cables . CAUTION! Refer to t he batte ry manuf acturer’ s installa tion manual . CAUTION! The minimu m DC vo[...]
-
Pagina 17
Electrical Installation: Top Cable Entry Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 1 1 Feed the battery c ables thr ough the gr ommets Connect c a bles fro m batte ry system. Connect c a bles fro m batte ry system. BA T1+ BA T2- L3 In L2 In L1 In L2 Out L3 Out L1 Out BA T1- BA T1+ BA T2+ BA T2— N N BA T1- BA T2+ 2[...]
-
Pagina 18
Electrical Installation: Top C able Entry 12 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D PE and AC cable conn ections (top ca ble entry) Feed the AC and PE cab les through the t op of Inpu t/Output Sectio n. Connec t cables. N N Protective Earthing conductors (red) for Battery 1 & AC IN Protective Earthing conductors [...]
-
Pagina 19
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 1 3 Bottom Cable Entry Pr eparing for bottom cable ent ry Cable ent ry in bot tom cover of Input/Out put Secti on AC I N AC O U T N N A C IN A C OUT BA T 1 BA T 2 BA T 1 BA T 2 M14 M14 90 95 93 92 91 94 M14 M14 M10 M10 M10 M10 M10 M10 M10 L1 OUT L2 OUT L3 OUT L1 IN L2 IN L3 IN L3 O UT L[...]
-
Pagina 20
Electrical Installation: Bottom Cable Entry 14 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Prepara tion for bottom cabl e entry a. Loosen bol ts of bot h cable entry cov ers and re move. b. Drill h oles for grommets f or AC, DC, and Outp ut circu it groundi ng elect rode cabl e in areas shown. c. Instal l grommets. d. Remount[...]
-
Pagina 21
Electrical Installation: Bottom Cab le Entry Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 1 5 Battery cabl e connection (bottom cable ent ry) W ARNING! Make sur e that the batter y br eakers ar e open (OFF) pri or to running the cables . CAUTION! Refer to t he batte ry manuf acturer’ s installa tion manual . CAUTION! The minimu [...]
-
Pagina 22
Electrical Installation: Bottom Cable Entry 16 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Connect c a bles fr om batte ry system. Connect c a bles fr om batte ry system. BA T1+ BA T2- BA T1- BA T2+ L3 In L2 In L1 In L2 Out L3 Out L1 Out BA T1- BA T1+ BA T 2+ BA T2— N N IN/OUT power cable (bottom entry) Bottom view of I[...]
-
Pagina 23
Electrical Installation: Bottom Cab le Entry Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 1 7 PE and AC cable conn ections (b ottom cable entry) Feed the AC and PE cab les throu gh the bott om of Input /Output Sec tion. Connec t cables. N N Protective Earthin g Conductors for Battery 1 & AC IN Protective Earthing Condu[...]
-
Pagina 24
External Bypass Static Switch Wiring W ARNING! Befor e starti ng instal lation, check an d test that all AC and DC power sour ce break ers are in op en position . W ARNING! Use only manual r eset pr otection as input over -curr ent pr otection. W ARNING! Over -curre nt pro tection r equire d by national wiring rul es. W ARNING! The UPS has no i nte[...]
-
Pagina 25
Electrical I nstal lation: External Bypa ss Sta tic Swit ch Wir ing Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 1 9 T op cable ent ry Loosen th e 8 screws to remove to p covers. Drill ho les for g rommets. Re-f it the c overs and insta ll th e grom met s. Feed the cables th rough t he grommets. Co nnect cables at cab le c[...]
-
Pagina 26
Electrical Installation: Extern al Bypass Static Switch Wir ing 20 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Bottom cable entry Loosen th e 8 screws to remove bot tom cove rs. Drill holes for the grommets. Re- fit the covers and in stall the grom mets . Feed the cables th rough t he grommets. Co nnect cables at cab le c[...]
-
Pagina 27
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 2 1 Communication cable overview Connection plane 0P 0957 X131 X130 Ext er nal EPO placed on wall X133 A 2 1 X185 UPS EMO (Display) X134A X128 1 12 2 X129 1 2 Backfeed protection EPO ou t EPO ou t C o n n e c t i o n p l a n e 0 P 0 9 5 7 Externa l Byp ass Sta tic S witch X128 X126A X12[...]
-
Pagina 28
22 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Relay Boar d (Optional) Location of optional Rela y Boar d 123 123 123 12 3 123 123 NC 3 123123[...]
-
Pagina 29
Ele ctrica l Ins tal lation : Rel ay Bo ard ( Opti onal ) Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 2 3 Communication cables with opti onal Relay Board Shunt trip 24V External Lamp supply V or V Max . 250V 5A DC DC AC AC[...]
-
Pagina 30
Electrical Installation: Relay Board (Optional) 24 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Relay Boar d functions The Relay Boa rd informs the user of the opera tion mode, status, a nd alarm con ditionsa nd has 8 port s on the i nput side a nd 16 output terminal s. Note Use Normally Closed (NC) contac ts for Fai l safe Mode a[...]
-
Pagina 31
Ele ctrica l Ins tal lation : Rel ay Bo ard ( Opti onal ) Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 2 5 K1 1 Bypass op eration • UPS i s running in normal op eration/ bypass operati on accordin g to AS400/ Novell. Active on Op r . mode K12 Maintenance bypass ON • The main tenance bypass switch is active. Active on Opr . mod[...]
-
Pagina 32
[...]
-
Pagina 33
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 2 7 Specifications Low-Impedance/High-Impedance Earthing The Symmetra ® MW i s easily integrat ed into e ither a s olid grou nded syste m, or a hi gh-impedanc e grounded sys tem. In a solid grounded syst em, the neutral power source (mains, genera tor , or UPS) is solid ly grounded. In[...]
-
Pagina 34
28 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Electrical Specifications AC Input W ARNING! Supply the UPS f rom a de dicated, 3 × 400/ 230 V , L1, L2, L3, N, PE sourc e or a high-impedanc e gro unded sys tem. CAUTION! Ensure cl ockwise phas e rotati on (L1, L2, L3) of input voltages . CAUTION! AC and DC discon nect s witches an[...]
-
Pagina 35
Specifications: Electrical Specifica tions Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 2 9 DC Input AC Output AC Input Ex ternal Bypass SSW The Exter nal Bypass S SW is designe d to accommodat e a conti nuous ov erload of 25%. Heat dissipation 24.74 kW / 84.4 kBTU/hr ( note 6) DC Input Nominal V olta ge (note 3) 2 x 384 V I Nom D[...]
-
Pagina 36
Specifications: Electrical Specificati ons 30 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D Notes 1. Nominal (Nom): Inpu t current based on r ated loa d, nominal in put volta ge and ful ly char ged batter ies. 2. Current limit ation is maximum all owed via el ectronic current limit ing and is based o n full batter y rechar ge + nom[...]
-
Pagina 37
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 3 1 Requir ed Br eaker Settings (400 V Systems) The Symmetra ® MW is a fault- tolerant system cap able of ha ndling and survivin g overload s and intern al/exte rnal faul ts. The ove rload performances a nd fault clear ings are possible wh en the sys tem meets spe cified minimum r equi[...]
-
Pagina 38
Specifications: Required Breaker Settin gs (400 V Systems) 32 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 22 kA is the maxi mum peak let-t hrough cu rrent (i ncluding sa fety fact or) avail able duri ng clearin g of an inte rnal faul t in a 200 kW section or a Power Module. Durin g or afte r a contro lled fau lt clear ing, none o[...]
-
Pagina 39
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 3 3 Appendix System and Pr otective Earthing The purpos e of this appendi x is to de scribe t he system- and prote ctive ear thing principl es of the Symmetra ® MW . CAUTION! All w iring to be in ac cord ance w ith a ppl icabl e natio nal a nd/ or loc al el ectric al wi ring rules .[...]
-
Pagina 40
34 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D TN S ystems Characteristics TN systems h ave one poi nt conne cted direct ly to ground. All exposed conductiv e parts mus t be connecte d to that point by pr otecti ve conducto rs. Depending on the way th e neutral and pr otective conductor s are fed , there are thr ee types of TN sy[...]
-
Pagina 41
Appendix: TN Systems Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 3 5 Additional r equir ements for genera ting sets ( IEC 60 364-5-5 5 551. 4.2) T o be used when the gener ating set provides a switche d alterna tive to t he public supply . Protect ion by automat ic discon nection of supply must not rely on the connecti on to the [...]
-
Pagina 42
Appendi x: TN Systems 36 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D The ch aracterist ics o f protecti ve devi ces and the circuit impedan ces shall be such t hat, if a fault of negligi ble imp edance occu rs anywhere in the installatio n betwee n a phase co nductor and a prot ectiv e conducto r or exposed conduc tive par t, aut[...]
-
Pagina 43
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 3 7 TT Systems Characteristics TT systems have one poi nt connect ed direc tly to gr ound and all exposed co nductive p a rts of t he instal lation mus t be con nected to an earth el ectrode. This ea rth elec trode is i ndepen dent of the power system ea rthed point. Refer ence to IE C [...]
-
Pagina 44
Appendix : TT Systems 38 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D When the pr otective device is an overcurr ent prote ctive devic e, it must be ei ther: • a device with inver se time c haracteristi cs and I a must be the cu rrent cau sing automati c operati on within 5 seconds, or • a device with an instant aneous tr ippi[...]
-
Pagina 45
Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D 3 9 IT Systems Characteristics In IT s ystem s the instal lati on is i nsula ted from earth o r conn ecte d to e arth t hroug h a su fficient ly hi gh impeda nce. Exposed conduct ive part s are ear thed indi vidually , in grou ps, or collecti vely . Refer ence to IE C 60364-4 -41 413. 1[...]
-
Pagina 46
Appendi x: IT System s 40 Symm etra MW 8 00 kW 3 × 400/ 230 V Insta llation - 990-1510D In inst allati ons where the neut ral is distri buted, the foll owing condi tions mu st be ful filled: In the c ondition: Pr o tective d evices in IT systems The fo llowing pr otectiv e devices are recognized i n IT sys tems: • Insulat ion monito ring devi ce[...]
-
Pagina 47
Residual Current S ense Mains - input UPS - output PE N PE PE PE Bypass - input Bypass - output L1 L3 L2 L1 L3 L2 N L1 L3 L2 L1 L3 L2 Protective Earthing Condu ctor Protective Earthing Condu ctor Main Protective Earthing Terminal External SSW-Bypass Symmetra MW ( PDU ) Service Entrance Mai n inverter u u u M Main Protective Earthing Terminal N PE P[...]
-
Pagina 48
Residual Current S ense Mains - input UPS - output PE N PE PE PE Bypass - input Bypass - output L1 L3 L2 L1 L3 L2 N L1 L3 L2 L1 L3 L2 Protective Earthing Condu ctor Protective Earthing Conducto r Main Protective Earthing Terminal External SSW-Bypass Symmetra MW ( PDU ) Service Entrance Mai n inverter u u u M Main Protective Earthing Terminal N PE P[...]
-
Pagina 49
Residual Current S ense Mains - input UPS - output PE N PE PE PE Bypass - input Bypass - output L1 L3 L2 L1 L3 L2 N L1 L3 L2 L1 L3 L2 PE Protective Earthing Conducto r Main Protective Earthing Terminal External SSW-Bypass Symmetra MW ( PDU ) Service Entrance Mai n inverter u u u M Main Protective Earthing Terminal PEN PE Q1 Q6 Q3 Q5 Earthing arrang[...]
-
Pagina 50
Mains - input UPS - output PE N PE PE PE Bypass - input Bypass - outpu t L1 L3 L2 L1 L3 L2 N L1 L3 L2 L1 L3 L2 Main Protective Earthing Terminal External SSW-Bypass Symmetra MW ( PDU ) Service Entrance Mai n inverter u u u M Main Protective Earthing Terminal PEN PE Q1 Q6 Q3 Q5 Earthing arrangements and protective conductors - Symmetra MW in TN-C in[...]
-
Pagina 51
Residual Current S ense Mains - input UPS - output PE N PE PE PE Bypass - input Bypass - output L1 L3 L2 L1 L3 L2 N L1 L3 L2 L1 L3 L2 PE Protective Earthing Condu ctor Main Protective Earthing Terminal External SSW-Bypass Symmetra MW ( PDU ) Service Entrance Mai n inverter u u u M Main Protective Earthing Terminal N PE Q1 Q6 Q3 Q5 Earthing arrangem[...]
-
Pagina 52
Residual Current S ense Mains - input UPS - output PE N PE PE PE Bypass - input Bypass - output L1 L3 L2 L1 L3 L2 N L1 L3 L2 L1 L3 L2 ( Alternative to earth e lectrode ) Earthing Conducto r Main Protective Earthing Terminal External SSW-Bypass Symmetra MW ( PDU ) Service Entrance Mai n inverter u u u M Main Protective Earthing Terminal N PE Q1 Q6 Q[...]
-
Pagina 53
[...]
-
Pagina 54
02/2007 990-1510D *990-1510D* APC W orldwide Customer Support Customer s upport for this or any oth er APC pro duct is av ailable at no char ge in any of the foll owing ways: • V isit the APC W eb site to acce ss documents in t he APC Knowled ge Base and t o submit custome r support requests . – www .apc.com (C orporate Headquarte rs) Connect t[...]