Vai alla pagina of
Manuali d’uso simili
-
Uninterruptible power supply (
APC Symmetra PX
57 pagine -
Uninterruptible power supply (
APC MGE Galaxy 3500 15kVA 400V with 2 Battery Modules
40 pagine -
Uninterruptible power supply (
APC BE550GR
6 pagine -
Uninterruptible power supply (
APC Back-UPS ES 350
2 pagine -
Uninterruptible power supply (
APC Back-UPS 550
4 pagine -
Uninterruptible power supply (
APC MGE Galaxy 3500 15kVA 400V 3:1 with 2 Battery Modules
40 pagine -
Uninterruptible power supply (
APC SUVTP10KH4B4S
38 pagine -
Uninterruptible power supply (
APC Power-Saving Back-UPS Pro 900
8 pagine
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso APC Symmetra PX. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica APC Symmetra PX o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso APC Symmetra PX descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso APC Symmetra PX dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo APC Symmetra PX
- nome del fabbricante e anno di fabbricazione APC Symmetra PX
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature APC Symmetra PX
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio APC Symmetra PX non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti APC Symmetra PX e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio APC in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche APC Symmetra PX, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo APC Symmetra PX, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso APC Symmetra PX. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
Symmetra PX 250/500 kW 400/480 V Single and Parallel Operation[...]
-
Pagina 2
[...]
-
Pagina 3
T able of Contents Overview .............................................................................................................................. 1 Symbols used ............................................................................................................... 3 Parallel System Summary ..........................................[...]
-
Pagina 4
Set the Battery T est Settings ....................................................................................26 Set the Display Settings .............................................................................................28 Set the Network Management Card (NMC) Settings ...........................................29 Set the User Passw[...]
-
Pagina 5
Overview Display Overview Note: The screens shown in this manuals are examples only . The UPS graphical user interface is located in the Input/Output/Bypass Enclosure. The UPS utilizes the touch-screen display to congure and monitor the system, and provides the user with visible and audible alarms. The screens are or ganized hierarchically . In [...]
-
Pagina 6
Navigation Parallel System Summary Parallel Input Summary Parallel Bypass Summary Parallel Output Summary UPS System UPS Summary UPS Input Summary UPS Bypass Summary UPS Battery Summary System Status Subfeed Summary UPS Output Summary UPS System System Information System Status Event Log Firmware Overview Predictive Maintenance Conguration User [...]
-
Pagina 7
Symbols used W ARNING: Indicates an electrical hazard, which, if not avoided, could r esult in injury or death. Caution: Indicates a hazard, which, if not avoided, could result in injury or death. Note: Indicates important information. See: Indicates that more information is available on this subject. Parallel System Summary The Parallel System Sum[...]
-
Pagina 8
UPS Summary Screen Single System In single systems, the UPS Summary screen is the home screen. It provides you with an overview of the UPS system and circuit breakers. It shows the system status and the power ow through the system and gives access to the system’ s summary screens and the UPS System screen. A. Access further details on the curr[...]
-
Pagina 9
Operation Modes UPS Modes The UPS operation mode is indicated in the top right corner of the screen under the heading UPS Mode. The UPS mode indicates the current status of the operated UPS. Normal Operation During normal operation, the UPS supports the critical load with conditioned power . While the UPS is operating in normal operation, a single-[...]
-
Pagina 10
Battery operation If the utility/mains supply fails, the UPS transfers to battery operation. During battery operation, battery power ensures uninterrupted support to the critical load. While the UPS system is in battery operation, a single-line diagram will appear on the screen. The green line indicates the power ow from the batteries, through t[...]
-
Pagina 11
Requested static bypass operation/forced static bypass operation The UPS is in requested static bypass following a command from the graphical user interface. And the UPS is in forced bypass when a fault on the system has caused static bypass operation. During static bypass operation, the critical load is supplied directly by utility/mains power . W[...]
-
Pagina 12
Battery test The UPS is in battery test mode when the UPS is performing a battery self-test. During battery test, the battery runtime capacity is reduced by 10%. Note: The battery test will stop if the mains supply fails during the test. Single System Parallel System or 8 Symmetra PX 250/500 kW 400/480 V 990–2748E-001[...]
-
Pagina 13
System Modes The system mode is indicated in the top right corner of the screen under the heading System Mode. The system mode indicates the current output status of the complete system, and not the individual UPS unit. On When the system mode is On, the UPS system supports the critical load with conditioned power . The load is supported by the UPS[...]
-
Pagina 14
Maintenance bypass operation During maintenance bypass operation, the critical load is supplied directly by utility/mains power . While the UPS system is in maintenance bypass operation, a single-line diagram will appear on the screen. The orange line indicates the power ow from the utility/mains, and then to the critical load via the Q3 switch.[...]
-
Pagina 15
Autostart Countdown The system can be set up for an automatic start when AC utility power is restored following a low battery voltage shutdown. The autostart countdown window is shown over all screens until the countdown period expires or the autostart is manually stopped by pressing the stop button. This feature is disabled by default and is not s[...]
-
Pagina 16
Operation Procedures Access Screens Protected by User Password 1. When prompted for the user-password, press the password eld to access the keyboard. 2. T ype in the user password and press Enter . Note: On installation, the user password is set to “apc”. 12 Symmetra PX 250/500 kW 400/480 V 990–2748E-001[...]
-
Pagina 17
Start Up System from Maintenance Bypass Operation Note: Start-up condition: The load is supplied via the Q3 switch from the utility/mains, and the other breakers are open. 1. Close the UPS input breaker (Q1). This will power up the UPS display . 2. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System [...]
-
Pagina 18
5. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow background. Note: Grey buttons are touch-screen functions. Singl[...]
-
Pagina 19
Shut Down System from Normal to Maintenance Bypass Operation Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the Operation button. T ype in the user password and complete with Enter[...]
-
Pagina 20
4. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow background. Note: Grey buttons are touch-screen functions. Singl[...]
-
Pagina 21
T ransfer from Normal to Requested Static Bypass Operation Note: Following this procedure will transfer the entire parallel system to requested static bypass. Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS system button in the bottom left corner to access the UPS System screen. Single System[...]
-
Pagina 22
3. Press the Normal Op. → Static Bypass button. Single System Parallel System 4. Press the Initiate T ransfer button to go to static bypass operation. The Initiate T ransfer button is greyed out when the transfer is not available. 5. Check that the status has changed to Requested Static Bypass in the upper right corner . T ransfer from Requested [...]
-
Pagina 23
1. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the Operation button. T ype in the user password and complete with Enter . 3. Press the Static Bypass -> Normal Op. button on the Operation screen. Single System Parallel System 4. Press the Initiate T ransfer button t[...]
-
Pagina 24
Isolate this Single UPS from the Parallel System Note: Before you start this procedure, ensure that the remaining UPS units can supply the load. Note: This procedure is only applicable to parallel systems. Note: Press the home button to go to the Parallel System Summary screen. 1. Press the UPS System button in the bottom left corner to access the [...]
-
Pagina 25
3. Press the Isolate this UPS button on the Operation screen. 4. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow ba[...]
-
Pagina 26
3. Press the UPS System button in the bottom left corner to access the UPS System screen. 4. Press the Operation button. T ype in the user password and complete with Enter . 5. Press System Start-up button. 22 Symmetra PX 250/500 kW 400/480 V 990–2748E-001[...]
-
Pagina 27
6. Follow the steps which appear on the screen. Steps will appear in the order in which they need to be completed. A step will initially appear in red and then when it is completed, the step will change to green. The next step to be completed will be highlighted in red text and yellow background. 7. Check that the UPS Mode has changed to Normal Ope[...]
-
Pagina 28
See: See the Security Handbook, available on the APC Network Management Card Utility CD or from the APC W eb site, www .apc.com, for more information on selecting and conguring network security . Operate the APC Battery Breaker Manually 1. T urn the selector to Manual position. 2. Check the spring status: a If CHARGED SPRING, go to step 3. b If [...]
-
Pagina 29
Conguration Access the User Conguration Screen The UPS system is congured from the password-protected user conguration area of the display . 1. Press the UPS system button in the bottom left corner to access the UPS System screen Single System Parallel System 2. Press the Conguration button to access the Conguration screen. 3. Pre[...]
-
Pagina 30
Perform a Battery Runtime Calibration Recalibrating the batteries keeps measurements like runtime and battery char ge accurate. 1. Go to the User Conguration screen by following the steps in “Access the User Conguration Screen“ . 2. Press the Battery T est Settings button on the User Conguration screen to access the Battery T est Setti[...]
-
Pagina 31
The test lasts for approximately 10% of the available runtime. 1. Go to the User Conguration screen by following the steps in “Access the User Conguration Screen“ . 2. Press the Battery T est Settings button on the User Conguration screen to access the Battery T est Settings screen. 3. Set the battery test settings a Battery self-test:[...]
-
Pagina 32
Set the Display Settings 1. Go to the User Conguration screen by following the steps in “Access the User Conguration Screen“ . 2. Press the Display Settings button on the User Conguration screen to access the Display Settings screen. 3. Set the display settings: a Brightness: Place the nger on the indicator and slide it left or righ[...]
-
Pagina 33
Set the Network Management Card (NMC) Settings 1. Go to the User Conguration screen by following the steps in “Access the User Conguration Screen“ . 2. Press the NMC Settings button on the User Conguration screen to access the NMC Settings screen. 3. The NMC Settings screen displays the conguration for each NMC in the system. Press [...]
-
Pagina 34
b Network settings mode: Select to use DHCP , BOOTP , or manual IP address. c IP address: Enter a valid IP address for the card. Only visible if manual mode has been selected. d Subnet mask: Enter a valid subnet mask. Only visible if manual mode has been selected. e Gateway: Enter a valid gateway . Only visible if manual mode has been selected. 5. [...]
-
Pagina 35
3. Change the user password: a Press the Enter curr ent password eld and type the current password by using the keyboard on the screen. Complete with Enter . b Press the Enter new password eld and type the new password by using the keyboard on the screen. Complete with Enter . c Press the Conrm new password eld and re-type the new passw[...]
-
Pagina 36
3. Set the threshold values that must trigger the alarms: Note: For parallel systems, shared settings are marked with *. Single System Parallel System a UPS module redundancy: Set the system threshold for generating alarms in the redundant power modules. N+0 indicates that the redundancy alarm is disabled. N+1 indicates that there must be one redun[...]
-
Pagina 37
7. This screen is only visible if subfeed breakers are present. Set the load percentage for each subfeed breaker that should generate a warning alarm. 8. Press Apply to conrm the settings. Set the System T ime Note: The date and time will be synchronized between the UPS units in a parallel system. 1. Go to the User Conguration screen by follo[...]
-
Pagina 38
3. Set the system date and the system time. 4. Press Apply to conrm the settings. Set the Language and Regional Settings Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS system button in the bottom left corner to access the UPS System screen Single System Parallel System 2. Press the Langua[...]
-
Pagina 39
3. Select the preferred language. 4. Select your preferred date format and temperature unit and complete with Finish . 990–2748E-001 Symmetra PX 250/500 kW 400/480 V 35[...]
-
Pagina 40
Maintenance Access Predictive Maintenance Screen Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS System button in the bottom left corner to access the UPS System screen. Single System Parallel System 2. Press the System Information button on the UPS System screen. 36 Symmetra PX 250/500 kW 40[...]
-
Pagina 41
3. Press the Predictive Maintenance button to access the Predictive Maintenance screen. 4. The Predictive Maintenance screen shows the status and the estimated remaining lifetime of the power modules and their fans. The status can be OK, Near end, or Exceeded. Remember to order new spare parts or schedule a maintenance visit when the status is Near[...]
-
Pagina 42
Return Parts to APC Call APC Customer Support to obtain an RMA number . T o return a failed module to APC, pack the module in the original shipping materials, and return it by insured, prepaid carrier . The APC Customer Support representative will provide the destination address. If you no longer have the original shipping materials, ask the repres[...]
-
Pagina 43
APC recommends that a whole battery module (one row of batteries) is replaced at the same time to ensure optimal run-time (see Example 1). However it may only be necessary to replace three battery units at the same time according to Examples 2 and 3 in the table below . Position A Position B Position C Position D Position E Position F Example 1 New[...]
-
Pagina 44
Replace Batteries Use two people to lift components weighing between 18–32 kg (40–70 lbs). 1. Holding the handle, gently lift the battery unit and pull it halfway out. A lock mechanism prevents it from being pulled all the way out. 2. Release the lock by pushing the battery unit upwards and pull the battery unit all the way out while you contin[...]
-
Pagina 45
1. Identify the faulty power module via the display or the red LED indication in the top right corner of the power module. 2. Deactivate the power module by turning the locking latch counter -clockwise to the unlocked position. 3. Unscrew the spring-activated knobs on both sides of the power module. 4. Pull the power module up and out of the enclos[...]
-
Pagina 46
9. Activate the power module by turning the locking latch clockwise to the locked position. The LED in the top right corner of the power module will start to ash (green) which indicates that the power module is initializing and doing a self test. When the self test is complete, the LED will be constant green. Replace Intelligence Modules W ARNIN[...]
-
Pagina 47
Replace Boards in Input/Output/Bypass Enclosure W ARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and r emove system components. W ARNING: Before r eplacing the boards, ensure that the “UPS system rmwar e version” and the “Sys[...]
-
Pagina 48
Replace Boards in the Battery Enclosure W ARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and r emove system components. W ARNING: Replace only one board at a time. 1. Loosen the two/four screws in the corners of the board. a Battery m[...]
-
Pagina 49
T roubleshooting Alarms The color of the top of the screen switches from blue to red and an alarm button is shown when an alarm situation occurs. Alarm Button Press the alarm button to go to the Active Alarms screen that displays all active alarms, along with a corrective action for addressing each alarm. When you press the alarm button, the alarm [...]
-
Pagina 50
Critical T ake immediate action. Call APC for instructions. V iew the Active Alarms 1. Press the Alarm button on the top bar when an alarm situation occurs. 2. A list of the active alarms is shown on the screen. Press the Location button to see the location of the particular module. Press the Graph button to see voltages and currents at the time th[...]
-
Pagina 51
V iew the Event Log Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. The Event Log screen can be accessed either by pressing the Event Log button on the Active Alarms screen see “V iew the active alarms” or by following this procedure: 1. Press the UPS system button in the bottom left corner to access the [...]
-
Pagina 52
4. Active in control indicates which intelligence module is in control of the system. Press the Active Event Log button to view the records from the intelligence module in control or press the RIM Event Log to view the records from the intelligence module that is passive. 5. The Recent Events log contains a detailed record of the 32 latest events. [...]
-
Pagina 53
7. Select to lter the events by source, location and/or timestamp and press OK . 8. Set your lter parameters and press OK to initiate the ltering. 9. T o save the log, insert a USB ash drive into the USB port on the display . Note: Do not remove the USB ash drive before a dialog box on the display indicates that it is safe to remove [...]
-
Pagina 54
10. Press the Save Log button. The full event log is saved as a text and an HTML le. Associated event capture les are also saved. All les are saved in a single compressed Zip-le to the USB ash drive. Bookmark an Entry in the Event Log A maximum of ve entries can be bookmarked in the system. 1. Double press on an event in the event[...]
-
Pagina 55
Y ou can choose to remove all existing bookmarks by pressing the Remove All button or click Cancel to remove them one by one. Press twice on the log entry to clear a bookmark. V iew and Save Information about Firmware V ersion Note: Press the home button to go to the UPS Summary or Parallel System Summary screen. 1. Press the UPS system button in t[...]
-
Pagina 56
3. V erify that the “UPS system rmware version” and “System rmware version stored at memory card” are identical. Press the Firmwar e Overview button. 4. T o save the rmware version list, insert a USB ash drive into the USB port on the display . Note: Do not remove the USB ash drive before a dialog box on the display indicates[...]
-
Pagina 57
5. Press the Save FW*V ersions list button to save the rmware version list as an HTML le. Press the button in the location column to open the Module Status Details screen for the particular module. Reboot the Display 1. Press the reboot button at the bottom of the display to reboot the display . 990–2748E-001 Symmetra PX 250/500 kW 400/480 [...]