Warning: mysql_fetch_array() expects parameter 1 to be resource, boolean given in /home/newdedyk/domains/bkmanuals.com/public_html/includes/pages/manual_inc.php on line 26
Emerson BACNET IP manuale d’uso - BKManuals

Emerson BACNET IP manuale d’uso

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372

Vai alla pagina of

Un buon manuale d’uso

Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Emerson BACNET IP. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Emerson BACNET IP o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.

Che cosa è il manuale d’uso?

La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Emerson BACNET IP descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.

Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.

Quindi cosa dovrebbe contenere il manuale perfetto?

Innanzitutto, il manuale d’uso Emerson BACNET IP dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Emerson BACNET IP
- nome del fabbricante e anno di fabbricazione Emerson BACNET IP
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Emerson BACNET IP
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti

Perché non leggiamo i manuali d’uso?

Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Emerson BACNET IP non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Emerson BACNET IP e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Emerson in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Emerson BACNET IP, come nel caso della versione cartacea.

Perché leggere il manuale d’uso?

Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Emerson BACNET IP, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.

Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Emerson BACNET IP. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.

Sommario del manuale d’uso

  • Pagina 1

    Li eb er t ® Inte lliS lot ® Modbu s 485, Modbu s IP and BA Cnet IP Re fe r en ce G u id e[...]

  • Pagina 2

    [...]

  • Pagina 3

    i T ABLE OF CONTENTS 1.0 L IEBERT E QUIPMENT C OMP ATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 What’s New in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Connectivity to Liebert IntelliSlot Using Modbus 485, Modbus IP o[...]

  • Pagina 4

    ii Table 18 Liebert XDC ™ - Status and Co il . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Table 19 Liebert XDC ™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Table 20 Liebert XDP ™ - Status and Coil . . . . . . . . . . . . . . . . .[...]

  • Pagina 5

    iii Table 51 Liebert Nfinity ® - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Table 52 Liebert NX ™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Table 53 Liebert NX ™ - Input and Holding . . . . . . . . . . . . . . . . [...]

  • Pagina 6

    iv Table 79 Extra Notes to Table 78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 Table 80 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Lieber t Deluxe System/3 ™ , Liebert DS ™ , Liebert DS E ™ , Liebert HPM ™ , Liebert PeX ™ - Multistate Data . . . [...]

  • Pagina 7

    Liebert Equipment Compatibility - What’s New in This Manual 1L i e b e r t ® IntelliSlot ® Modbus/BACnet IP 1.0 L IEBERT E QUIPMENT C OMP ATIBILITY 1.1 What’ s New in This Manu al Emerson Network Power ® has introduced a new Liebert IntelliSlot ® card platform —the Liebert IntelliSlot Unity ™ card. This platform combines the Mo dbus 485[...]

  • Pagina 8

    Liebert Equipment Compatibility - Compatibility with Liebert Equipme nt Liebert ® IntelliSlot ® Modbus/BACnet IP 2 1.3 Comp atibility with Liebert Equipment T able 1 Liebert Equipment and Compatib le Liebert IntelliSlot ® Cards Product Supported Refer to Ta b l e s : Controller / Protocol Comp atible Card Part Number Liebert IntelliSlot Modbus 4[...]

  • Pagina 9

    Liebert Equipment Compatibility - Compatibility with Liebert Equipme nt 3L i e b e r t ® IntelliSlot ® Modbus/BACnet IP • Power Distributi on & Power C onditioning Prod ucts Liebert Datawave ™ 33 PMP , PM2 for Liebert FPC & Liebert PPC OC485-ADPT IS-WEBADPT — Liebert FPC ™ 33 Liebert PPC ™ 33 Liebert FPC, Liebert RDC ™ , Liebe[...]

  • Pagina 10

    Liebert Equipment Compatibility - Compatibility with Liebert Equipme nt Liebert ® IntelliSlot ® Modbus/BACnet IP 4 BACNET IP PROT OCOL • Thermal Manageme nt Products Liebert Challenger 3000 ™ 76 - 82 Liebert iCOM v4 —— IS-IPBML IS-UNITY IS-UNITY -DP Liebert Challenger IT R ™ 76 - 82 Liebert CRV ™ 83 - 86 Liebert CW ™ 76 - 82 Liebert[...]

  • Pagina 11

    Modbus Communicatio ns - Implementation Basics 5L i e b e r t ® IntelliSlot ® Modbus/BACnet IP 2.0 M ODBUS C OMMUNICATIONS 2.1 Implement ation Basics Modbus protocol pr ovides control and data acquisit ion, through query and response, between master and slave devices. This protocol comprises the rules for communication, controlling the message fo[...]

  • Pagina 12

    Modbus Commu nications - RTU Framing Liebert ® IntelliSlot ® Modbus/BACnet IP 6 2.3.2 Function Code The function code field tells the addressed slaves what function to perfor m. Function codes are designed to invoke a specif ic action by the slav e device. The function code ranges from 1 to 127. Liebert Intell iSlot ® Modbus server supports the [...]

  • Pagina 13

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 7L i e b e r t ® IntelliSlot ® Modbus/BACnet IP 3.0 M ODBUS 485 AND M ODBUS IP P ROTOCOLS 3.1 Thermal Management Product s T able 6 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert H[...]

  • Pagina 14

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 8 Compressor Pump Down Issue 2 10044 — 1 Active on Ala rm 1, 2, 3, 4, 5, 6 Dig Scroll Comp Over T emp 1 10045 — 1 Active on Ala rm 1, 2, 3, 4, 5, 6 Dig Scroll Comp Over T emp 2 10046 — 1 Active on Ala rm 1, 2, 3, 4, 5, 6 Smoke Detected[...]

  • Pagina 15

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 9L i e b e r t ® IntelliSlot ® Modbus/BACnet IP Electric Reheater Hours Exceeded 2 10085 — 1 Active on Alarm 1, 2, 3, 4, 5, 6 Electric Reheater Hours Exceeded 3 10086 — 1 Active on Alarm 1, 2, 3, 4, 5, 6 Hot W ater / Hot Gas V a lve Hours Exceeded 10087 — 1 Active on Alarm 1,[...]

  • Pagina 16

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 10 RAM Battery Issue 10227 — 1 Active on Alarm 1, 2, 3, 4, 5, 6 W ater Leakage Detector Sensor Issue 10228 — 1 Active on Alarm 1, 2, 3, 4, 5, 6 External Fire Detected 10229 — 1 Active on Alarm 1, 2, 3, 4, 5, 6 Chilled W ater Control V [...]

  • Pagina 17

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 11 Liebert ® IntelliSlot ® Modbus /BACnet IP Remote Sensor Over T emperature 6 10361 — 1 Active on Alarm 2, 3, 4, 5, 6 Remote Sensor Over T emperature 7 10362 — 1 Active on Alarm 2, 3, 4, 5, 6 Remote Sensor Over T emperature 8 10363 — 1 Active on Alarm 2, 3, 4, 5, 6 Remote Se[...]

  • Pagina 18

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 12 Condenser Circuit Unspecified General Event 10494 — 1 Active on Alarm 3, 4, 5, 6 Input Undervoltage 1 10500 — 1 Active on Alarm 6 Input Undervoltage 2 10501 — 1 Active on Alarm 6 Input Undervoltage 3 10502 — 1 Active on Alarm 6 In[...]

  • Pagina 19

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 13 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 8 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Input and Holding Controller Liebert iCOM v4 Dat a [...]

  • Pagina 20

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 14 Compressor Hours Threshold 1 30071 4007 1 1 — hr 1, 2, 3, 4, 5, 6 Compressor Hours Threshold 2 30072 4007 2 1 — hr 1, 2, 3, 4, 5, 6 Humidifier Hours Threshold 30073 40073 1 — hr 1, 2, 3, 4, 5, 6 Dehumidifier Hours Threshold 30074 40[...]

  • Pagina 21

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 15 Liebert ® IntelliSlot ® Modbus /BACnet IP Dig Scroll Comp Discharge T emp 2 30751 — 1 — deg F 1, 2, 3, 4, 5, 6 Return Humidity 30130 — 1 10 % RH 1, 2, 3, 4, 5, 6 Ext Air Sensor A Humidity 30132 — 1 10 % RH 1, 2, 3, 4, 5, 6 Ext Air Sensor B Humidity 30133 — 1 10 % RH 1,[...]

  • Pagina 22

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 16 Infrared Humidifier Flush Rate 30273 4027 3 1 — % 1, 2, 3, 4, 5, 6 Fan Control Mode 30274 4 0274 1 — 0 = Auto 1 = Manual 2 = Economy 4 = Delta 1 Analog Input Reading 1 30275 — 1 100 — 1, 2, 3, 4, 5, 6 Analog Input Reading 2 30276 [...]

  • Pagina 23

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 17 Liebert ® IntelliSlot ® Modbus /BACnet IP Ext Condenser Pump High W ater - Eve nt Control 30297 40297 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6 Ext Condenser Pump High W ater - Eve nt Ty p e 30298 40298 1 — 0 = Message 1 = W arning 2 = Alarm 1, 2, 3, 4, 5, 6 Ext S tandby[...]

  • Pagina 24

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 18 Service Required - Event Contro l 30317 40317 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6 Service Required - Event T ype 30318 40318 1 — 0 = Message 1 = W arning 2 = Alarm 1, 2, 3, 4, 5, 6 Shutdown - Loss Of Power - Event Control 30[...]

  • Pagina 25

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 19 Liebert ® IntelliSlot ® Modbus /BACnet IP Compressor Low Suctio n Pressure - Event T ype 1 30337 4 0337 1 — 0 = Message 1 = W arning 2 = Alarm 1, 2, 3, 4, 5, 6 Compressor Low Suctio n Pressure - Event T ype 2 30338 4 0338 1 — 0 = Message 1 = W arning 2 = Alarm 1, 2, 3, 4, 5,[...]

  • Pagina 26

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 20 Ext Air Sensor A Low Humidity - Event Control 30357 40357 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6 Ext Air Sensor A Low H umidity - Event T ype 30358 4035 8 1 — 0 = Message 1 = W arning 2 = Alarm 1, 2, 3, 4, 5, 6 Ext Air Sensor A[...]

  • Pagina 27

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 21 Liebert ® IntelliSlot ® Modbus /BACnet IP Condenser Issue - Event Control 1 30377 40377 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6 Condenser Issue - Event Control 2 30378 40378 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6 Condenser Issue - Event T ype 1 30379 40379 1 —[...]

  • Pagina 28

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 22 Adjusted Humidity 30499 — 1 10 % RH 2, 3, 4, 5, 6 Return Dew Point 30500 — 1 1 0 deg C 2, 3, 4, 5, 6 Return Dew Point 30762 — 1 1 0 deg F 2 , 3, 4, 5, 6 Actual Air T emperatu re Set Point 30501 — 1 1 0 deg C 2, 3, 4, 5, 6 Actual A[...]

  • Pagina 29

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 23 Liebert ® IntelliSlot ® Modbus /BACnet IP Remote Sensor T emperature 9 30559 — 1 10 deg C 2 , 3, 4, 5, 6 Remote Sensor T emperature 9 30779 — 1 10 deg F 2, 3, 4, 5, 6 Remote Sensor T emperature 10 30560 — 1 10 deg C 2, 3, 4, 5, 6 Remote Sensor T emperature 10 30780 — 1 1[...]

  • Pagina 30

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 24 Condenser Low Noise Mode St art Time 30681 40681 2 — Seconds since Midnight 3, 4, 5, 6 Condenser Low Noise Mode Stop T ime 30 683 4068 3 2 — Seconds since Midnight 3, 4, 5, 6 Pump Hours 1 30685 4 0685 2 — hr 5 Pump Hours 2 30687 4 0[...]

  • Pagina 31

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 25 Liebert ® IntelliSlot ® Modbus /BACnet IP Instantaneous Power 1 30860 — 1 - W 6 Instantaneous Power 2 30861 — 1 — W 6 Instantaneous Power 3 30862 — 1 — W 6 Instantaneous Power 4 30863 — 1 — W 6 Instantaneous Power 5 30864 — 1 — W 6 Instantaneous Power 6 30865 ?[...]

  • Pagina 32

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 26 T able 10 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Glossary Controller Liebert iCOM ® v4 Data Label D[...]

  • Pagina 33

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 27 Liebert ® IntelliSlot ® Modbus /BACnet IP Compressor Capacity Control St a t e Compressor capacity control state. When 'O N', the cooling capacity of the compressor has been reduced. Compressor Capacity Reduced Compre ssor capacity has been reduced. Compressor High Hea[...]

  • Pagina 34

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 28 Compressor Utilization Present compressor utilization expressed as a percentage of the ma ximum rated capacity . Condenser Circuit Unspecified General Event One or more unspecified condenser circuit events active. See loca l unit display [...]

  • Pagina 35

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 29 Liebert ® IntelliSlot ® Modbus /BACnet IP Customer Input 4 - Event Control Enable/disable the activation of the [Custome r Input 4] event. If set to 'disabled', the event will not be annunciated. This implie s that the event will not be placed in an y active event list[...]

  • Pagina 36

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 30 Ext Air Sensor A High Humidity Threshold Threshold va lue used in the [External Air Sensor A High Humidity] event. Ext Air Sensor A High Humidity [Ext Air Sensor A Humidity] has exceeded [Ext Air Senso r A High Humidity Threshold]. Ext Ai[...]

  • Pagina 37

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 31 Liebert ® IntelliSlot ® Modbus /BACnet IP Ext Dew Point Over T emp Threshold Threshold va lue used in the [Ext Dew Point Over T emperature] even t. Ext Dew Point Over T emperature At least one dew point temperatur e reading ([Ext Air Sensor A De w Point T emp], [Ext Air Sensor B[...]

  • Pagina 38

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 32 Ext S tandby Glycol Pump On - Event T ype The event type for the [Ext S tandby Glycol Pump On] event. Ext S tandby Glycol Pump On The st andby glycol pump is on, as indicated by an external input signal. Ext S tandby Unit On - Event Contr[...]

  • Pagina 39

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 33 Liebert ® IntelliSlot ® Modbus /BACnet IP Free Cooling Internal T emperature Delta Minimum temperature delta required between supply fluid and internal ambient air temperatures in order to enable free cooling. Free Cooling S tate Free cooling ope rational state. Free Cooling S t[...]

  • Pagina 40

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 34 Humidifier Issue Humidifier issue detec ted, causing it to be locked out. Humidifier Lockout Enable/disable the use of the humidifi er . Humidifier Low Water The water level in the humidifier has droppe d below its threshold. Humidifier O[...]

  • Pagina 41

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 35 Liebert ® IntelliSlot ® Modbus /BACnet IP Master Unit Communication Lost - Event T ype The event type for the [Master Unit Communication Lo st] event. Master Unit Communication Lost Communi cation with master unit has been lost. Minimum Chilled W ater T emp Set Point Enable Enab[...]

  • Pagina 42

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 36 Return Air Over T emperature Return ai r high temperature event. Return Air Sensor Event Control Enable/disable the activation of events re lated to measurements by the return air sensor . Return Air Sensor Issue The air sensor at the inl[...]

  • Pagina 43

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 37 Liebert ® IntelliSlot ® Modbus /BACnet IP Supply Air T emperatu re Sensor Control Control mode to be used with th e supply air temperature se nsor . Supply Air T emperat ure Set Point Desired s upply air temperatur e. Supply Air T emperatur e Air te mperature measured at the out[...]

  • Pagina 44

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 38 Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit S tandby Unit was placed in standby mode. Unit S tatic Pressure S tatic pressu re measurement for a single unit. Unsp[...]

  • Pagina 45

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 39 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 1 1 Liebert CR V ™ - St atus and Coil Controller Liebert iCOM ® v4 Data Label Stat us C o il Number of Bits Sca le Notes / Un its Supply Air Over T emperature 10001 — 1 — Active on Alarm Supply Air Under T emperat ure 10002[...]

  • Pagina 46

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 40 Supply Chilled Water Over T emp 10047 — 1 — Active on Alarm Chilled Water Control V alve Position 10048 — 1 — Active on Alarm Supply Chilled Water Loss of Flow 10049 — 1 — Active on Alarm Supply Fluid T emp Sensor Issue 10050 [...]

  • Pagina 47

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 41 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 12 Liebert CRV ™ - Input and Holding Controller Liebert iCOM ® v4 Dat a Label Input Register Holding Register # of Reg. Scale Not es / Units Supply Air T emperature 30385 — 1 1 0 deg C Supply Air T emperature 30386 — 1 1 0 [...]

  • Pagina 48

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 42 Remote Sensor T emperature Module Inde x 4 30427 — 1 10 deg C Remote Sensor T emperature Module Inde x 5 30428 — 1 10 deg C Remote Sensor T emperature Module Inde x 6 30429 — 1 10 deg C Remote Sensor T emperature Module Inde x 7 304[...]

  • Pagina 49

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 43 Liebert ® IntelliSlot ® Modbus /BACnet IP Fan Control Sensor 30 463 40463 1 — 0 = Supply 1 = Remote 2 = Return Remote Sensor Function Modul e Index 1 30464 40464 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function Modul e Index 2 30465 40465 1 — 0 = Disable 1 [...]

  • Pagina 50

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 44 Condenser Low Noise Mode Sched ule Control 30491 4 0491 1 — 0 = disabled 1 = enabled Condenser Low Noise Mode Max Fan S peed 30492 40492 1 — % Condenser Normal Mode Max Fan 30493 4 0493 1 — % Condenser Low Noise Mode - Interval Days[...]

  • Pagina 51

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 45 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 13 Liebert CRV ™ - Glossary Controller Liebert iCOM ® v4 Data Label Data Description Air T emperature Con trol Sensor Sensor from which air tempe rature measurements will be used for cooling and heating control. Air T emperatur[...]

  • Pagina 52

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 46 Condenser Refrigerant Pressure Over Threshold Condenser refrigeran t pressure has exceeded a threshold. Condenser Refrigerant Pressure Sensor Issue Condenser refrigeran t pressure sensor is disconne cted or the signal is out of range. Con[...]

  • Pagina 53

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 47 Liebert ® IntelliSlot ® Modbus /BACnet IP Fan S peed Proportio nal Band T emperature control band above the te mperature set point cal culated for proportional fan speed control. If m easu red air temperature is within this band, fan sp eed operations are p roportionally control[...]

  • Pagina 54

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 48 Return Air Over T emp Threshold Threshold value us ed in the [Return Air Over T emperature] event. Return Air O ver T emperature Return air high te mperature event. Return Air Sensor Issue The ai r sensor at the inlet of the unit is d isc[...]

  • Pagina 55

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 49 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 14 Liebert HPC ™ (Chiller) - St atus and Coil Controller Liebert iCOM ® v4 Data Label Status C oil Number of Bits Notes Extra Notes Compressors Compressor Not S toppin g 10001 — 1 Active on Alarm 1, 2 Compressor Superheat Ove[...]

  • Pagina 56

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 50 Fluid Low Fluid Pressure 10070 — 1 Active on Alarm 1, 2 Supply (Outlet) Fluid — Supply Fluid Over T emp 10081 — 1 Active on Alarm 1, 2 Supply Fluid Under T emp 10082 — 1 Active on Alarm 1, 2 Supply Fluid T emp Sensor Issue 10083 ?[...]

  • Pagina 57

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 51 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 15 Liebert HPC ™ (Chiller) - Input and Holding Controller Liebert iCOM ® v4 Data Label Input Holdi ng # of Reg Scale Notes/Unit s Extra Notes Protocol Server Class 30385 — 1 — 1 = UPS 2 = AIR 3 = PMP 4 = PDU 1, 2 Compressor[...]

  • Pagina 58

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 52 Condensers 4 Condenser Fan S peed 30417 — 1 — Units: % Uint16 1, 2 Fluid Fluid Pressure 30418 — 1 10 Units: bar Int16 1, 2 Fluid Cooling Proportional Band 30419 40419 1 10 Units: deg C Uint16 1, 2 Fluid Cooling Proportional Band 304[...]

  • Pagina 59

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 53 Liebert ® IntelliSlot ® Modbus /BACnet IP Evaporators Evaporator Return Fluid T e mperature 30469 — 1 10 Units: deg C Int16 1, 2 Evaporator Return Fluid T e mperature 30470 — 1 10 Units: deg F Int16 1, 2 Evaporator Return Fluid Over T emp Alarm Threshold 30615 4 0615 1 — U[...]

  • Pagina 60

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 54 System Operations Return Fluid T emperature 30491 — 1 10 Units: deg C Int16 1, 2 Return Fluid T emperature 30492 — 1 10 Units: deg F Int16 1, 2 Supply Fluid T emperature 30493 — 1 10 Units: deg C Int16 1, 2 Supply Fluid T emperature[...]

  • Pagina 61

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 55 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 16 Extra notes key to T able 15 Number Descriptio n 1 Thi s point is supported on iCOM_SC31 2 Thi s point is supported on iCOM_SC101 T able 17 Liebert HPC ™ (Chiller) - Glossary Controller Liebert iCOM ® v4 Data Label Data Desc[...]

  • Pagina 62

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 56 Evaporator Fluid Freeze - Auto Reset Evaporator outl et fluid temperature has dropped below the fre eze threshold. Evaporator has been sh ut down, but will restart when th e temperature rises above the threshold. Evaporator Fluid Fr eeze [...]

  • Pagina 63

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 57 Liebert ® IntelliSlot ® Modbus /BACnet IP Reheat Utilization Present reheating utili zation expressed as a percentage of the ma ximum rated capacity . Return Fluid Over T emp Alarm Threshold Threshol d value used to generate a [Return Fl uid Over T emp] alarm. Return Fluid Over [...]

  • Pagina 64

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 58 T able 18 Liebert XDC ™ - St atus and Coil Controller Liebert iCOM ® v4 Data Des cription St atus Coil Number of Bit s Scale Notes / Units Pump 1 Loss of Flow 10001 — 1 — Active on Alarm Pump 2 Loss of Flow 10002 — 1 — Active o[...]

  • Pagina 65

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 59 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 19 Liebert XDC ™ - Input and Holding Controller Liebert iCOM ® v4 Data Description Input Register Holding Register # of Reg. Scale Notes / Unit s Pump 1 S tate 30385 — 1 — 0 = Off / 1 = On Pump 2 S tate 30386 — 1 — 0 = [...]

  • Pagina 66

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 60 System S tatus 30422 — 1 — 1 = Normal Opera tion 2 = S tartup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation System Control Mode 30423 — 1 — 0 = Internal (Auto) 1 = External (Manual) Maintenance Ramp 30424 [...]

  • Pagina 67

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 61 Liebert ® IntelliSlot ® Modbus /BACnet IP External Air Ext Air Sensor A Over T em perature 1001 1 — 1 Active on Alarm Ext Air Sensor A Under T emperature 10012 — 1 Active on Alarm Ext Air Sensor A Issue 10013 — 1 Active on Alarm Ext Air Sensor B Over T emperature 10 014 ?[...]

  • Pagina 68

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 62 T able 21 Liebert XDP ™ - Input and Holding Dat a Label Input Holding # of Reg Scale Notes/Units Pump s Pump 1 S tate 30385 — 1 — 0 = off 1 = on Pump 2 S tate 30386 — 1 — 0 = off 1 = on Refrigerant Supply Refrigerant T emperatur[...]

  • Pagina 69

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 63 Liebert ® IntelliSlot ® Modbus /BACnet IP Minimum Room T emperature Set Point 30403 40403 1 10 Units : deg C Minimum Room T e mperature Set Point 30404 40404 1 10 Units : deg F Ext Air Over T emp Threshold 30405 40405 1 10 Units : deg C Ext Air Over T emp Threshold 30406 40406 1[...]

  • Pagina 70

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 64 Hot Aisle Over T emp Threshold 30459 40459 1 — Units : deg C Hot Aisle Over T emp Threshold 30460 40460 1 — Units : deg F Hot Aisle Under T emp Thresh old 30461 40461 1 — Units : deg C Hot Aisle Under T emp Thresh old 30462 40462 1 [...]

  • Pagina 71

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 65 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 20 Communication St atus 30976 — 1 — 0 = Connected 1 = Not Co nnected Fan On/Off Control 30977 409 77 1 — 0 = off 1 = on Primary Fan Group S tate 30978 — 1 — 0 = off 1 = on 2 = economy Fan Button Control 30979 40979 1[...]

  • Pagina 72

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 66 XD System 1 Secon dary Fans Fan S tate 31032 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31033 41033 1 — 0 = disabled 1 = automatic 2 = manual XD System 2 T emperature Senso r 1 Remote Sensor T e mperature 31039 — 1 10 Units[...]

  • Pagina 73

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 67 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 4 Secon dary Fans Fan S tate 31 137 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31 138 41 138 1 — 0 = disabled 1 = automatic 2 = manual XD System 5 T emperature Senso r 1 Remote Sensor T e mperature 31 144 — 1 10 [...]

  • Pagina 74

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 68 XD System 7 Secon dary Fans Fan S tate 31242 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31243 41243 1 — 0 = disabled 1 = automatic 2 = manual XD System 8 T emperature Senso r 1 Remote Sensor T e mperature 31249 — 1 10 Units[...]

  • Pagina 75

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 69 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 10 Secondary F ans Fan S tate 31347 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31348 41348 1 — 0 = disabled 1 = automatic 2 = manual XD System 1 1 T emperature Sensor 1 Remote Sensor T e mperature 31354 — 1 10 Un[...]

  • Pagina 76

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 70 XD System 13 Secondary F ans Fan S tate 31452 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31453 41453 1 — 0 = disabled 1 = automatic 2 = manual XD System 14 T emperature Sensor 1 Remote Sensor T e mperature 31459 — 1 10 Unit[...]

  • Pagina 77

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 71 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 16 Secondary F ans Fan S tate 31557 — — — 0 = off 1 = on 2 = economy Fan Economy Mode 31558 41558 1 — 0 = disabled 1 = automatic 2 = manual XD System 17 T emperature Sensor 1 Remote Sensor T e mperature 31564 — 1 10 U[...]

  • Pagina 78

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 72 XD System 19 Secondary F ans Fan S tate 31662 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31663 41663 1 — 0 = disabled 1 = automatic 2 = manual XD System 20 T emperature Sensor 1 Remote Sensor T e mperature 31669 — 1 10 Unit[...]

  • Pagina 79

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 73 Liebert ® IntelliSlot ® Modbus /BACnet IP Ext Air Sensor A Under T emperature [Ext Air Sensor A T emper ature] has dropped below [Ext Air Under T emp Threshold]. Ext Air Sensor B Dew Point T emp Dew point temper ature as measured by external air sensor B. Ext Air Sensor B Humidi[...]

  • Pagina 80

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 74 Pump Hours Exceeded [Pump Hours] has exceeded [Pu mp Hours Threshold]. Pump Hours Threshold Thresho ld value used in the [Pump Hours Exceeded] event. Pump Hours Operating hours for pump since last reset of this value. Pump Short Cycle Pum[...]

  • Pagina 81

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 75 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 23 Liebert DS ™ and Liebert PeX ™ - St atus and Coil Controller Liebert iCOM ™ v3 Data Description St atus Coil Number of Bit s Scale Notes / Unit s Sleep on Monda y 10001 1 1 — — Sleep on Tuesday 10002 2 1 — — Sleep[...]

  • Pagina 82

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 76 Comp 1 Overload 10039 — 1 — — Comp 1 Pumpdown Fail 10040 — 1 — — Comp 2 High Pressure 10041 — 1 — — Comp 2 Low Pressure 10042 — 1 — — Comp 2 Overload 10043 — 1 — — Comp 2 Pumpdown Fail 10044 — 1 — — Dig[...]

  • Pagina 83

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 77 Liebert ® IntelliSlot ® Modbus /BACnet IP HW/HG Hrs Exceeded 10087 — 1 — — Hum Hrs Exceeded 10088 — 1 — — Dehum Hrs Exceeded 10089 — 1 — — Network Failure 10091 — 1 — — No Connection W/Unit 10092 — 1 — — Unit(s) Disconnected 1 0093 — 1 — — Uni[...]

  • Pagina 84

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 78 T able 24 Liebert DS ™ and Liebert PeX ™ - Input an d Holding Controller Liebert iCOM ® v3 Data Description Input Register Holding Register # of Reg. Scale Not es / Units V endor ID 30001 40001 1 — — Device ID 30002 40002 1 — ?[...]

  • Pagina 85

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 79 Liebert ® IntelliSlot ® Modbus /BACnet IP Electrical Heaters #1 Run Hours Threshol d 30076 40076 — — Hours Electrical Heaters #2 Run Hours Threshol d 3 0077 4 0077 — — Hours Electrical Heaters #3 Run Hours Threshol d 3 0078 4 0078 — — Hours Hot W ater / Hot Gas Run H[...]

  • Pagina 86

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 80 Daily Low T emp Time 30154 — — — Hh :mm Daily High Humidity 30155 — — — %RH Daily High Hum T ime 3015 6 — — — Hh:mm Daily Low Humidity 3 0157 — — — %RH Daily Low Hum T ime 30158 — — — Hh:mm If the Scale colum[...]

  • Pagina 87

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 81 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 25 Liebert XDF ™ - St atus and Coil Controller Liebert iCOM ® v3 Data Description Statu s Co i l Number of Bits Scale Notes / Units T emperature Indication 1 1001 1 1 1 1 — — Unit Control — 25 1 — — Reset Alarm — 26[...]

  • Pagina 88

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 82 T able 26 Liebert XDF ™ - Input a nd Holding Controller Liebert iCOM ® v3 Data Description Input Register Holding Register # of Reg. Scale Notes / Unit s V endor ID 30001 40001 1 — — Device ID 3 0002 40002 1 — — V ersion number[...]

  • Pagina 89

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 83 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 27 Liebert Challenger 3000 ™ , Liebert Deluxe System/3 ™ , Liebert Himod ™ , Liebert ICS ™ - Input and Holding - LAM Controller Advanced Microprocessor - LAM Liebert Product s Liebert Challenger 300 0 Liebert Deluxe System[...]

  • Pagina 90

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 84 Inverter on Bypass — 40291 1 — Bit 3 S tandby Fan On — 40291 1 — Bit 4 Loss of Emergency Power — 4 0291 1 — Bit 5 Local Alarm 1 — 4 0291 1 — Bit 6 Local Alarm 2 — 4 0291 1 — Bit 7 Off by Remote Shutdown — 4 0291 1 ?[...]

  • Pagina 91

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 85 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 28 Liebert Dat aMate ™ , Liebert Mini-Mate Plus ™ , Liebert Mini-Mate2 ™ - Input and Holding - L0B Controller Small Systems - L0B Liebert Products Liebert DataMate Liebert Mini-Mate Plus Liebert Mini-Mate2 A vailable Poin t [...]

  • Pagina 92

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 86 T able 29 Liebert Dat aMate ™ , Liebert Mini-Mate2 ™ - Input and Holding - MM2 Controller MM2 Liebert Products Liebert DataMate Liebert Mini-Mate2 A vailable Poin t s Data Description Input Register Holding Regist er # of Reg. Scale N[...]

  • Pagina 93

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 87 Liebert ® IntelliSlot ® Modbus /BACnet IP Setpoints (V iew) T emperature — 40010 1 — — T emp T olerance — 4001 1 1 — — Humidity — 40012 1 — — Humidity T olerance — 40013 1 — — High T emperature Alarm — 40014 1 — — Low T emperature Alarm — 40 015 1[...]

  • Pagina 94

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 88 T able 30 Liebert Mini-Mate2 ™ 8 T on - Input and Holding - L8T Controller L8T Liebert Products Lieber t Mini-Mate2 8 T on A vailable Poin t s Data Description Input Register Holding Register # of Reg. Scale Notes / Units St atus Points[...]

  • Pagina 95

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 89 Liebert ® IntelliSlot ® Modbus /BACnet IP EPO Shutdown — 40291 1 — Bit 8 Local Alarm 3 — 43291 1 — Bit 9 Local Alarm 4 — 40291 1 — Bit 10 Run Times (View) Compressor 1 Run Hours — 40019 1 — — Compressor 2 Run Hours — 40020 1 — — Glycol R un Hours — — [...]

  • Pagina 96

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 90 T able 31 Liebert Atlas Air ™ , Liebert Atlas PEC ™ , Liebert LECS 15 ™ - Input and Hold ing - C10 2- step Controller C10 Liebert Products Liebert Atlas Air Liebert Atlas PEC Liebert LECS 15 A vailable Poin t s Data Description Inpu[...]

  • Pagina 97

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 91 Liebert ® IntelliSlot ® Modbus /BACnet IP Setpoints (V iew) Return Air T emperature — 40016 1 10 d e g C (R/W) Return Air Humidity — 40017 1 10 deg C (R/W) Supply Air T emperature — 400 18 1 10 deg C (R/W) High T emp Alarm — 40025 1 10 deg C (R/W) Low T emp Alarm — 400[...]

  • Pagina 98

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 92 T able 32 Liebert Atlas Air ™ , Liebert Atlas PEC ™ , Liebert CE MS 100 ™ - Input and Holding - C1 00 4-step Controller CEMS 100 Liebert Products Liebert Atlas Air Liebert Atlas PEC Liebert CEMS 100 A vailable Poin t s Data Descript[...]

  • Pagina 99

    Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 93 Liebert ® IntelliSlot ® Modbus /BACnet IP Humidity Low Level — 402 90 1 — Bit 4 Battery Level Low — 402 90 1 — Bit 5 Loss of Power — 40290 1 — Bit 6 Local Alarm 1 — 40290 1 — Bi t 7 Local Alarm 2 — 40290 1 — Bi t 8 Cool 3 Low Pressure — 40290 1 — Bit 9 Co[...]

  • Pagina 100

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 94 3.2 Power Distribution and Po wer Conditioning Produ ct s T able 33 Liebert Datawave ™ , Liebert FPC ™ , Liebert PPC ™ - Input and Hold ing - PMP , PM2 Opt ions for Liebert FPC and Lie bert PPC Controller Powe[...]

  • Pagina 101

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 95 Liebert ® IntelliSlot ® Modbus /BACnet IP Alarm Point s Discrete alarm objects available; use auto-discover for this unit Communications — 40289 1 — Bit 0 Output Undervoltage — 40 289 1 — Bit 1 Output Overvoltage — 40289 1 — Bit 2 Output Overcu[...]

  • Pagina 102

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 96 T able 34 Liebert Datawave ™ , Liebert FPC ™ , Liebert PPC ™ - Input and Holding - PM P Option for Liebert FPC and Lieber t PPC Controller Power Monitoring Panel - PMP Option for Liebert FPC and Liebert PPC Li[...]

  • Pagina 103

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 97 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 35 Liebert FDC ™ , Liebert FPC ™ , Liebert RDC ™ , Liebert RX ™ - St atus and Coil Controller Liebert iCOM ® v4 Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX A vailable Poin t s[...]

  • Pagina 104

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 98 Panel 4 Panel Summary Alarm 101 16 — 1 — Active on Alar m Panel Overvoltage 101 17 — 1 — Active on Alarm Panel Undervoltage 101 18 — 1 — Active on Alarm Panel Phase Overcurrent 1 01 19 — 1 — Active o[...]

  • Pagina 105

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 99 Liebert ® IntelliSlot ® Modbus /BACnet IP Panel 4 Position 1 Branch Overcurrent 13409 — 1 — Active on Alar m Branch Overcurrent 13410 — 1 — Active on Warning Branch Undercurrent W arning 1341 1 — 1 — Active on Alarm Panel 4 Position 2 Branch Ov[...]

  • Pagina 106

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 100 T able 36 Liebert FDC ™ , Liebert FPC ™ , Liebert RDC ™ , Liebert RX ™ - Input and Ho lding Controller Liebert iCOM ® v4 Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Lie bert RX A vailable Poin [...]

  • Pagina 107

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 101 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Power 2 Output V oltage X-Y 30430 — 1 — V AC Output V oltage Y -Z 30431 — 1 — V AC Output V oltage Z-X 30432 — 1 — V AC Output V oltage Vx 30433 — 1 — V AC Output V oltage Vy 30 434 — 1 ?[...]

  • Pagina 108

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 102 Panel Main Current Ix 30471 — 1 — A AC Panel Main Current Iy 30472 — 1 — A AC Panel Main Current Iz 30473 — 1 — A AC Panel Main Neutral Cu rrent 30474 — 1 — A AC Panel Main Ground Current 30475 — [...]

  • Pagina 109

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 103 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Panel Main V oltage V y THD 30514 — 1 10 % THD Panel Main V oltage Vz THD 30515 — 1 10 % THD Panel Main Current Ix THD 30 516 — 1 1 0 % THD Panel Main Current Iy THD 30 517 — 1 1 0 % THD Panel Main Current[...]

  • Pagina 110

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 104 Panel 1 Position 1 Breaker position 30587 — 1 — — Branch Curre nt Phase 1 30588 — 1 10 A AC Branch Curre nt Phase 2 30589 — 1 10 A AC Branch Curre nt Phase 3 30590 — 1 10 A AC Branch Output Power (kW) 3[...]

  • Pagina 111

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 105 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Panel 2 Position 2 Breaker position 31607 — 1 — — Branch Curre nt Phase 1 31608 — 1 10 A AC Branch Curre nt Phase 2 31609 — 1 10 A AC Branch Curre nt Phase 3 31610 — 1 10 A AC Branch Output Power (kW) [...]

  • Pagina 112

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 106 Panel 3 Position 84 Breaker position 33599 — 1 — — Branch Curre nt Phase 1 33600 — 1 10 A AC Branch Curre nt Phase 2 33601 — 1 10 A AC Branch Curre nt Phase 3 33602 — 1 10 A AC Branch Output Power (kW) [...]

  • Pagina 113

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 107 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Subfeed 1 Subfeed Current Ix 34 619 — 1 — A AC Subfeed Current Iy 34 620 — 1 — A AC Subfeed Current Iz 34 621 — 1 — A AC Subfeed Neutral Current 34622 — 1 — A AC Subfeed Ground Current 34623 — 1 [...]

  • Pagina 114

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 108 Subfeed 64 Subfeed Current Ix 35 879 — 1 — A AC Subfeed Current Iy 35 880 — 1 — A AC Subfeed Current Iz 35 881 — 1 — A AC Subfeed Neutral Current 35882 — 1 — A AC Subfeed Ground Current 35883 — 1 [...]

  • Pagina 115

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 109 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 37 Liebert FDC ™ , Liebert FPC ™ , Liebert RDC ™ , Liebert RX ™ - Gloss ary Data Label Data Description Branch Current Phase 1 Branch breaker Phase 1 RMS current Branch Current Phase 2 Branch Breake[...]

  • Pagina 116

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 110 Output V oltage THD Unit outpu t V oltage T otal Harmonic Distortion has exceeded the limit. Output V oltage Vx THD Unit V oltage T otal Harmonic Disto rtion for phase X. Output V oltage Vx Unit output RMS voltage [...]

  • Pagina 117

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 111 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Phase Rotation Error Unit input phase sequence is not A, B, C. The p hase sequence should be verified and correcte d. Subfeed Current Ix Crest Fact or Subfeed breaker phase X Curr ent Crest Factor (pea k/RMS). Sub[...]

  • Pagina 118

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 112 T able 38 Liebert STS ™ , Liebert STS/PDU ™ - Input and Holding - STS Controller STS Liebert Products Liebert STS Liebert STS/PDU A vailable Poin t s Data Description Input Register Holding Register # of Reg. S[...]

  • Pagina 119

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 113 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Source 2 Overload — 40290 1 — Bi t 3 Power Supply 2 Fault — 40290 1 — Bit 4 Frequency Deviation — 40 290 1 — Bit 5 T ransfer Inhibi t — 40 290 1 — Bit 6 Auto Retransfer Primed — 40290 1 — Bit 7[...]

  • Pagina 120

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 114 T able 39 Liebert STS2 ™ , Liebert STS2/PDU ™ - Input and Holdin g - STS2 Controller STS2 Liebert Produc t s L iebert STS2 Liebert STS2/PDU A vailable Poin t s Data Description Input Register Holding Register #[...]

  • Pagina 121

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 115 Liebert ® IntelliSlot ® Mo dbus/BACnet IP LoadKV A % — 40026 1 — % Source 1 V olts A-N — 40027 1 — V (4 Pole only) Source 1 V olts B-N — 40028 1 — V (4 Pole only) Source 1 V olts C-N — 40029 1 — V (4 Pole only) Source 2 V olts A-N — 4003[...]

  • Pagina 122

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 116 Internal Comm Fail — 40290 1 — Bit 5 External Comm Fail — 40290 1 — Bit 6 CB1 Shunt T rip Fa il — 40290 1 — Bit 7 CB2 Shunt T rip Fa il — 40290 1 — Bit 8 CB6 Neutral Open — 40290 1 — Bit 9 (N/A [...]

  • Pagina 123

    Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 117 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Load Over-current — 40292 1 — Bit 13 Ground Over-curre nt — 40292 1 — Bit 14 Neutral Over-current — 40292 1 — Bit 15 Customer Alarm #1 — 40293 1 — Bit 0 Customer Alarm #2 — 40293 1 — Bit 1 Cust[...]

  • Pagina 124

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 118 3.3 UPS Systems T able 40 Liebert APM ™, Liebert NXC ™ , Liebert NXR ™ - St atus and Coil Data Label Stat us C o il Number of Bits Scale N otes / Unit s System St atus Battery Auto T est In Progress 10001 — 1 — Active on Alarm Battery Equalize[...]

  • Pagina 125

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 119 Liebert ® IntelliSlot ® Mo dbus/BACnet IP User Operation Invalid 10050 — 1 — Active on Alarm Power Sub Module Fault 1 0051 — 1 — Active on Alarm Battery Discharging 1 0052 — 1 — Active on Al arm UPS Output on Bypass 10053 — 1 — Active on Alarm Output Load on Maint. Bypass 10054[...]

  • Pagina 126

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 120 T able 41 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Input and Holding Data Label Input Register Holding Regist er # of Reg. Scale N otes / Units Input System Input RMS A-B 30385 — 1 — V AC System Input RMS B-C 30386 — 1 — V AC System[...]

  • Pagina 127

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 121 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Power Factor Phs C 30431 — 1 100 — System Output Pct Power Phase A 30432 — 1 — % System Output Pct Power Phase B 30433 — 1 — % System Output Pct Power Phase C 3 0 434 — 1 — % MMS Output Apparent Power 30435 — 1 — kV A [...]

  • Pagina 128

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 122 T able 42 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Glossary Data Label Dat a Description Battery Auto T est In Progress Auto matic ba ttery test is in progress Battery Capacity Low Battery capacity is low Battery Charging Error The battery [...]

  • Pagina 129

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 123 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Load Sharing Fau lt Difference between any phase inverter curr ent of u nit and t he relevant average output current of parallel system is more t han a specific percent of nominal current. Main Battery Disconnect Open Ma in battery disconnect is open M[...]

  • Pagina 130

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 124 System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power The sum total power of all system output phases System Output RMS Current Phs A The[...]

  • Pagina 131

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 125 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Output Overload 10050 — 1 Active on Alarm Output Off Pending 10051 — 1 Active on Alarm System Output Off 10052 — 1 Active on Alarm System Shutdown - T ransformer Ove r T emperature 10053 — 1 Active on Alarm Inverter Shutdown - Overload 1[...]

  • Pagina 132

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 126 T able 44 Liebert APS ™ - Input and Holding Data Label Input Register Holding Register # of Reg. Scale Notes / Unit s Protocol Server Class 30385 — — — 1 = UPS 2 = AIR 3 = PMP 4 = PDU Input System Input RMS L1-N 30396 — 1 10 Units : V AC Uint [...]

  • Pagina 133

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 127 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery Battery T ime Remainin g 30437 — 1 — Units : min Uint 16 Battery V olts for Cabinet 30438 — 1 10 Units : VDC Uint 16 DC Bus Current 30439 — 1 100 U nits : A DC Uint 16 Battery Percentage Charge 30440 — 1 — Units : % Uint16 UPS Batte[...]

  • Pagina 134

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 128 System Output Apparent Power L1 30473 — 1 100 Units : kV A Uint 16 System Output Apparent Power L2 30474 — 1 100 Units : kV A Uint 16 System Output Power 30475 — 1 10 0 Units : kW Uint 16 System Output Power L 1 30476 — 1 100 Units : kW Uint 16 [...]

  • Pagina 135

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 129 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Auto Restart — — 40519 1 0 = disabled 1 = enabled Auto Restart Delay — — 405 20 1 Units : sec Uint 16 Auto Restart Minimum Battery Setting — — 40521 1 0 = 0% 1 = 10% 2 = 20% 3 = 30% 4 = 40% 5 = 50% 6 = 60% 7 = 70% 8 = 80% 9 = 90% No Load W [...]

  • Pagina 136

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 130 BatteryModule 2 Module Operating S tatus 3 0670 — 1 — 0 = Normal 1 = W arning 2 = Alarm 4 = Fault Battery S tring V oltage 30671 — 1 10 Units : VDC Uint16 Battery Module T emperature 30672 — 1 10 Units : deg C Int16 Battery Module T emperature 3[...]

  • Pagina 137

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 131 Liebert ® IntelliSlot ® Mo dbus/BACnet IP[...]

  • Pagina 138

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 132 T able 45 Liebert APS ™ - Glossary Data Label Data Description Accumulated Discharge T ime The highest accumulated battery discharg e time among installed battery modules. Accumulated Discharge Time T otal accumulated discharge time for the Battery Mo[...]

  • Pagina 139

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 133 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Frame Capacity T otal system capacity supp orted when the maximum number of power modules are installed. Frame Fan Fault The frame t op outlet fan has faile d. Inverter On/Off S tate inverter on/off state Inverter Shutdown - Overload The inverter has s[...]

  • Pagina 140

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 134 Output Qualificati on S tatus output qualific ation status Power Module Failure One or more conditio ns indica te a power module fai lure, service is required. Power Module Fan Fault The Power Modul e has detected a fan fault. Power Module Over T empera[...]

  • Pagina 141

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 135 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Power L 2 The sy stem output powe r on Line 2. System Output Power The sum tota l power of all system output phases System Output RMS Current L1 The sy stem output RMS current for Line 1 System Output RMS Current L2 The sy stem output RMS[...]

  • Pagina 142

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 136 T able 46 Liebert GXT2 ™ and Liebert GXT3 ™ - S tatus and Coil Data Description Stat us C oi l Number of Bit s Scale Notes / Un its Audible Alarm Enabled 10002 2 1 — — Automatic Battery T est Enabled 10003 3 1 — — DC-to-DC Converter On 10042[...]

  • Pagina 143

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 137 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 47 Liebert GXT2 ™ and Liebert GXT3 ™ - Inp ut and Holding Data Description Input Regist er Holding Register # of Reg. Sc ale Notes / Units Number of Input Line s 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 [...]

  • Pagina 144

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 138 Output Current L1 30164 — 1 — A Input Maximum V oltage L1 30180 — 1 — V Input Minimum V oltage L1 30181 — 1 — V Output Maximum V oltage L1 30182 — 1 — V Output Minimu m V oltage L1 30183 — 1 — V Black Out Count 30301 — 1 — — Br[...]

  • Pagina 145

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 139 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 50 Liebert Nfinity ® - St atus and Coil Data Description St a tus C oi l Number of Bits Sc ale No tes / Units Automatic Battery T est Enabled 10003 3 1 — — Battery Charger On 10044 — 1 — — Inverter Ready 10047 — 1 — — Power Fact[...]

  • Pagina 146

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 140 T able 51 Liebert Nfinity ® - Input a nd Holding Data Description Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 3 0004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output L[...]

  • Pagina 147

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 141 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 52 Liebert NX ™ - St atus and Coil Data Description Statu s Coi l Number of Bit s Scale Notes / Unit s Economode 10005 5 — — — DC-T o-DC Converter On 1004 2 — — — — Battery Charge Compensation 1004 6 — — — — Inverter Read[...]

  • Pagina 148

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 142 DC Bus Balancer Faul t 10240 — — — — DC Bus 1 Power Su pply Fail 10251 — — — — Rectifier Fuse Fail 1025 7 — — — — Rectifier S tartup Failure 10258 — — — — Rectifier Fault 10259 — — — — Rectifier Current Limit 1026[...]

  • Pagina 149

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 143 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 53 Liebert NX ™ - Input and Holding Data Description Input Register Holding Register # of Reg. Sc ale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 3000 4 40004 1 — Bit s 4 - 7 Number of Output Lin[...]

  • Pagina 150

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 144 Input Current L1 30154 — 1 — A Input Power Factor L1 30155 — 1 1 00 — Bypass V oltage L1 30159 — 1 — V Output V oltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Output Load L1 3016 5 — 1 — — Output Power F actor L1 30166[...]

  • Pagina 151

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 145 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 54 Liebert NX 225-600kV A UPS - Input and Holding 3 Data Description Input Holding Register # of Reg Scale Notes/Unit s Identification Modbus Protocol V ersion — 40002 1 — XX.YY Manufacturer — 40003 1 — 0 = Chloride Model — 40004 1 —[...]

  • Pagina 152

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 146 Output Source — 40050 1 — 1 = Other 2 = None 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Frequency — 40051 1 10 Units: Hz Number Lines — 400 52 1 — — V oltage L1 — 40053 1 — Units: V V oltage L2 — 40054 1 — Units: V V o[...]

  • Pagina 153

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 147 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Diagnostic T est Failed — 400 89 1 — Bit 3 Communications Lost — 400 89 1 — Bit 4 Shutdown Pending — 40089 1 — Bit 6 T est In Progress — 40090 1 — Bit 0 General Warning — 40090 1 — Bit 2 Condition Bypass — 40091 1 — 0 = Bypass n[...]

  • Pagina 154

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 148 T able 55 Liebert NXL ™ - 60Hz, UL version (Model 40) - St atus and Coil Data Label St atus Coil # of Bit s Notes NXL T ype Battery Self T est 1 0082 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Low Shutdown 10092 — 1 Active on Alarm N+1, 1+N, 1[...]

  • Pagina 155

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 149 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery Over T emperature 10350 — 1 Acti ve on Warning N+1, 1+N, 1+1, SMS DC Bus Ground Fault - Positive 10351 — 1 Active on Alarm N+1, 1+N, 1+1, SMS DC Bus Ground Fault - Negative 10352 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Output Low Po[...]

  • Pagina 156

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 150 Controls Reset Required 10397 — 1 Active on Alarm SCC, N+1, 1+ N, 1+1, SMS Battery T est Failed 10398 — 1 Active on Al arm N+1, 1+N, 1+1, SMS Auto Restart Inhibited - Ext 10399 — 1 Active on Alarm SCC, SMS Battery T est Inhibited 10400 — 1 Activ[...]

  • Pagina 157

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 151 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 56 Liebert NXL ™ - 60Hz, UL version (Model 40) - Input and Holding Dat a Label Input Register Holding Register # of Regs Scale Units / Notes NXL Ty p e s System Date and T ime 3 0005 — 2 — Masks: Y ear 0xFF FF 0000 Mon 0x0000 FF0 0 Day 0x0[...]

  • Pagina 158

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 152 System Output Pct Power Phase A 30165 — 1 — % N+1, 1+ N, 1+1, SMS System Output Power Factor Phs A 30166 — 1 100 — N+1, 1+N, 1+1, SMS System Input RMS B-C 30201 — 1 — V AC N+1, 1+N, 1+1, SMS System Input RMS Current Phase B 3020 4 — 1 — [...]

  • Pagina 159

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 153 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery T otal Discharge Time 30316 — 1 — hr N+1, 1+N, 1+1, SMS Battery Discharge Power 3 0317 — 1 — W N+1, 1+N, 1+1, SMS Battery Last Discharge Date 30318 — 2 — Masks: Y ear 0xFF FF 0000 Mon 0x0000 FF0 0 Day 0x0000 00FF N+1, 1+N, 1+1, SMS [...]

  • Pagina 160

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 154 Rectifier Active Filter 30340 — 1 — 0 = Not Installed 1 = Installed N+1, 1+N, 1+1, SMS Rectifier S tatus 30341 — 1 — 0 = off 1 = on N+1, 1+N, 1+1, SMS System S tat us 30342 — 1 — 1 = Normal Oper ation 2 = S tartup 8 = Normal with W arn ing 1[...]

  • Pagina 161

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 155 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery V olts for Cabinet 4 3036 1 — 1 — VDC N+1, 1+N, 1+1, SMS Battery V olts for Cabinet 5 3036 2 — 1 — VDC N+1, 1+N, 1+1, SMS Battery V olts for Cabinet 6 3036 3 — 1 — VDC N+1, 1+N, 1+1, SMS Battery V olts for Cabinet 7 3036 4 — 1 —[...]

  • Pagina 162

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 156 Maintenance Isola tion Breaker (MIB) 30383 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, 1+N, 1+1, SMS Output Series S tatic Switch 3 0384 — 1 — 0 = Open 1 = Close 2 = Not Installed LEU/LA P only Module Output Brea ker (MOB) 3 0385 — 1 — 0[...]

  • Pagina 163

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 157 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Configuration Description 30497 — 1 — 0 = Single Module System 33 1 = Single Module System 34 2 = Single Module System 44 3 = 1+1 33 4 = 1+1 34 5 = 1+1 44 6 = 1+N 33 7 = 1+N 34 8 = 1+N 44 9 = N+1 33 10 = N+1 34 1 1 = N+1 44 12 = SCC w/Continuous Du[...]

  • Pagina 164

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 158 Sum of MMS Output RMS Currents for Phase B 30512 — 1 — Units : A AC 1+N, SCC Sum of MMS Output RMS Currents for Phase C 30513 — 1 — Un its : A AC 1+N, SCC MMS Output Frequency 3 0514 — 1 10 Units : Hz 1+N, SCC MMS Output Power 30515 — 1 — [...]

  • Pagina 165

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 159 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Bypass Isolation Breaker for Module 1 (BIB1) 30537 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 2 (BIB2) 30538 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for[...]

  • Pagina 166

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 160 MMS Module Output V oltage S tatus 30557 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal Hi gh 1+N, SCC MMS Module Output Source 3055 8 — 1 — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass 1+N, SCC MMS Module T otal kW Output 30559[...]

  • Pagina 167

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 161 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS Module T otal kV A Output 30651 — 1 — Units : kV A SCC MMS Module DC Bus V o ltage 30652 — 1 — Units : VDC SCC MMS Module Battery Current 30653 — 1 — Units : A DC SCC MMS Module Battery T i me Remaining 3065 4 — 1 — Units : min SCC [...]

  • Pagina 168

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 162 EcoModeSchedule 2 Schedule Operation S tate - ECO Mode 30682 — 1 — 0 = disabled 1 = enabled SMS, 1+N, SCC Schedule Action - ECO Mode 30683 — 1 — 0 = stop 1 = start SMS, 1+N, SCC Schedule Day of Week - ECO Mode 30684 — 1 — 0 = Unknown 1 = Mon[...]

  • Pagina 169

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 163 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 57 Liebert NXL ™ - 60Hz, UL version (Model 40) - Glossary Data Label Dat a Description Auto Restart In Progress Au to restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal Auto Retransfer T i me R[...]

  • Pagina 170

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 164 Battery T otal Discharge T ime The cu mul ative battery discharge time Battery V olts at Main Disconnect The voltage between the positive and the negative batte ry terminals of the common battery disconnect Battery V olts for Cabinet T he voltage betwee[...]

  • Pagina 171

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 165 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Inlet Air T emperature The te mperature of the inlet ai r Input Breaker (CB1/RIB) Input breaker (CB1/R IB) Input Contact 01 The external input contact 1 Input Contact 02 The external input contact 2 Input Contact 03 The external input contact 3 Input C[...]

  • Pagina 172

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 166 Multiple Fan Failure Multiple fan failure On Generator A generator is su pplying the power to the system Output Amp Over User Limit-Phs A The phase A output has exceede d the user amperag e threshold Output Amp Over User Limit-Phs B The phase B output h[...]

  • Pagina 173

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 167 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has bee n detected in the system output System Output Frequency [...]

  • Pagina 174

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 168 T able 58 Liebert NXL ™ - 50Hz, CE version (Models 48 and 49) - S tatus and Coil Data Description Statu s C oi l Number of Bits Notes / Units Input System Input Power Problem 10001 — 1 Active on Alarm System Input Phs Rotation Error 10002 — 1 Acti[...]

  • Pagina 175

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 169 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus Low Fault 10074 — 1 Active on Alarm Output System Shutdown - EPO 10085 — 1 Active on Alarm System Shutdown - REPO 10086 — 1 Active on Alarm System Output Low Power Factor 10088 — 1 Active on Alarm Output Amp Over User Limit-Phs A 10089 ?[...]

  • Pagina 176

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 170 UPS Output on Bypass 10177 — 1 Active on Alarm Output Load on Maint. Bypass 10 178 — 1 Active on Alarm Backfeed Breaker Open 10179 — 1 Active on Ala rm Auto Restart In Progre ss 10180 — 1 Active on Alarm Power Supply Failure 10181 — 1 Active o[...]

  • Pagina 177

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 171 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 59 Liebert NXL™ - 50Hz, CE versi on (Models 48 and 49) - Input and Holding Data Label Inpu t Holding # of Reg Scale Notes /Units Input System Input RMS A-B 30385 — 1 10 Units : V AC Uint16 System Input RMS B-C 30386 — 1 10 Units : V AC Uin[...]

  • Pagina 178

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 172 Battery V olts for Cabinet 4 3042 8 — 1 — Units : VDC Uint16 Battery V olts for Cabinet 5 3042 9 — 1 — Units : VDC Uint16 Battery V olts for Cabinet 6 3043 0 — 1 — Units : VDC Uint16 Battery T emper ature for Cabinet 30431 — 1 10 Units : d[...]

  • Pagina 179

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 173 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus DC Bus V ol tage 30465 — 1 — Units : VDC Uint16 DC Bus Current 30466 — 1 — Units : A DC Int16 DC Bus Qualification S tatus 30467 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal Hi gh Output System Output V oltage RMS A-B 3047[...]

  • Pagina 180

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 174 Inverter Inverter Overload Time Remaining 30510 — 1 — Units : sec Uint16 Inverter Output Qualif ication St atus 3051 1 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal Hi gh Inverter On/Off S tate 30512 — 1 — 0 = of f 1 = on Environme[...]

  • Pagina 181

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 175 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Wire Configuration 3 0556 — 1 — 0 = T wo Wi re (single phase + return) 1 = T w o Wire (2 phase, no neutral) 2 = Three Wire (2 phase + neutral) 3 = Three Wire (3 phase, no neutral) 4 = Four Wi re (3 phases + neutral) S tatic Switch T ype 3055[...]

  • Pagina 182

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 176 Ratings Bypass Nominal V oltage 3057 6 — 1 — Units : V AC Uint16 System Input Nominal V oltage 30577 — 1 — Units : V AC Uint16 System Input Nominal Frequency 30578 — 1 10 Units : Hz Uint16 System Output Nominal V oltage 30579 — 1 — Units :[...]

  • Pagina 183

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 177 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Module Output Breaker 30609 — 1 — 0 = Open 1 = Close 2 = Not Installed MultiModule Multi-module System Output V oltage RMS A-B 30620 — 1 1 0 Units : V AC Uint16 Multi-module System Output V oltage RMS B-C 30621 — 1 10 Units : V AC Uint16 Multi-[...]

  • Pagina 184

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 178 Module Output Breaker for Module 3 30646 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 4 30647 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 5 30648 — 1 — 0 = Open 1 = Close 2 = Not[...]

  • Pagina 185

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 179 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS UPS Output Source 30665 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer ModuleList 1 MMS Inter-Module Comm St atus 30676 — 1 — 0 = Failed 1 = Normal MMS Event Summary 3067 7 — 1 — 0 = None 1 = Alarm 2 =[...]

  • Pagina 186

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 180 Intelligent Paralleling Intelligent Paralle l Operation S tate 30796 — 1 — 0 = disable d 1 = enabled Intelligent Paralle l Minimum Redundancy 3079 7 — 1 — Uint16 Intelligent Pa rallel Maximum Time in S tandby 30798 — 1 — Units : day Uint16 E[...]

  • Pagina 187

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 181 Liebert ® IntelliSlot ® Mo dbus/BACnet IP EcoModeSch edule 14 Schedule Operation St ate - ECO Mod e 31019 — 1 — 0 = disabled 1 = enabled Schedule Action - ECO Mode 3102 0 — 1 — 0 = stop 1 = start Schedule Day of Week - ECO Mode 31021 — 1 — 0 = Unknown 1 = Monday 2 = T uesday 3 = We[...]

  • Pagina 188

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 182 T able 60 Liebert NXL ™ - 50Hz, CE version (Models 48 and 49) - Gloss ary Data Label Data Description Auto Restart In Progress Au to restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal Auto Retransfer T[...]

  • Pagina 189

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 183 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery T ime Remainin g The calculated available ti me on battery Battery T otal Discharge T ime The cu mulative batt ery discharge time Battery V olts at Main Disconnect The voltage between the positive and the negative battery terminals of the commo[...]

  • Pagina 190

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 184 Controls Reset Required A controls reset is required due to one or more critical settings chang ing DC Bus Current The current at the battery input terminals . In charging mode, the cu rrent will be a positive value. In discharging mode, the current wil[...]

  • Pagina 191

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 185 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Internal Communications Failure T he control has detecte d a communication fai lure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter Inhibit - External Restart of the in verter is inhi[...]

  • Pagina 192

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 186 MMS Output Pct Power Phase A The multi-module system output power on phase A as a percent age of the rated capacity MMS Output Pct Power Phase B The multi-module system output power on phase B as a percent age of the rated capacity MMS Output Pct Power [...]

  • Pagina 193

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 187 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Series S tatic Switch o utput series static switch Output Wire Configuratio n Output wire configuration Power Supply Failure Power supply failu re Program Input Contact 01 When the signal from [Program Input Contac t 01] is active the function a[...]

  • Pagina 194

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 188 Schedule Minute - ECO Mode This setting represents the minute of the hour when an associated schedule entry action will take effect. Schedule Operation St ate - ECO Mode This setting gives the user the ability to either enabl e or disable a sch edule en[...]

  • Pagina 195

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 189 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Nominal V oltage The no mi nal (or rated) system output voltage System Output Pct Power Phase A The system output power on phase A as a percent age of the rated capacity System Output Pct Power Phase B The system output power on phase B a[...]

  • Pagina 196

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 190 T able 61 Liebert PowerSure ™ Interactiv e (before July 2008 ) - St atus and Coil Data Description Sta tu s Co i l Number of Bits Scale Notes / Unit s Audible Alarm Enabled 10002 2 1 — — Automatic Battery T est Enabled 10003 3 1 — — Battery Ch[...]

  • Pagina 197

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 191 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 62 Liebert PowerSure ™ Interactive (b efore July 2008) - Input and Holding Data Description Input Register Holding Register # of Reg. Scale Notes / Unit s Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 4000 4[...]

  • Pagina 198

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 192 T able 63 Liebert PowerSure ™ Interactiv e 2 - St atus and Coil Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153) Data Description Stat us C oi l Number of Bit s Scale Notes / Un its Audible Alarm Enabled 10002 2 1 — —[...]

  • Pagina 199

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 193 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 64 Liebert PowerSure ™ Interactive 2 - Input and Holding Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153) Data Description Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 [...]

  • Pagina 200

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 194 T able 65 Liebert Series 300 ™ UPS - St atus and Coil Data Description Status C oi l Number of Bits Scale Notes / Un its Automatic Restart Enabled 100 01 1 1 — — Battery Charge Compensation 100 46 — 1 — — Inverter Ready 10047 — 1 — — L[...]

  • Pagina 201

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 195 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 66 Liebert Series 300 ™ UPS - Input and Holding Data Description Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 4 0004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of [...]

  • Pagina 202

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 196 Bypass Current L2 30210 — 1 — A Output V oltage L2 30213 — 1 — V Output Current L2 30214 — 1 — A Input V oltage L3 30253 — 1 — V Input Current L3 30 254 — 1 — A Bypass V oltage L3 30259 — 1 — V Bypass Current L3 30260 — 1 — A[...]

  • Pagina 203

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 197 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 67 Liebert Series 600 ™ UPS - St atus and Coil Data Description Stat us C oi l Number of Bit s Scale Notes / Units Auto Retransfer Primed 10049 — 1 — — Load On Inverter 10073 — 1 — — Load On Bypass 10074 — 1 — — Battery data [...]

  • Pagina 204

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 198 T able 68 Liebert Series 600 ™ UPS - Input and Holding Data Description Input Register Holding Register # of Reg. Sc ale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 3000 4 40004 1 — Bit s 4 - 7 Number of[...]

  • Pagina 205

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 199 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 69 Liebert Series 610 ™ SCC UPS - St atus and Coil Data Description Stat us C o il Number of Bits Scale Notes / U nit s Auto Retransfer Primed 10049 — 1 — — Load On Inverter 10073 — 1 — — Load On Bypass 10074 — 1 — — Load On [...]

  • Pagina 206

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 200 T able 70 Liebert Series 610 SCC UPS - Input and Holding Data Description Input Register Holding Regist er # of Reg. Scale Notes / Unit s Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bi ts 4 - 7 Number of[...]

  • Pagina 207

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 201 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 71 Liebert HiPulse ™, Liebert SICE 7200 ™ - Input and Holding - SMM/SSM Controller Multi Module Series - SMM Liebert Products Liebert HiPulse Liebert SICE 7200 A vailable Poin t s Data Description Input Register Holding Register # of Reg. Sc[...]

  • Pagina 208

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 202 Rectifier Block — 40290 1 — Bit 7 Rectifier Current Limit — 40290 1 — Bit 8 Rectifier Overtemperature — 40290 1 — Bit 9 Rectifier Fuse Failure — 40290 1 — Bit 10 Inverter V oltage Fault — 40291 1 — Bit 0 Inverter Disable — 40291 1 [...]

  • Pagina 209

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 203 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 72 Liebert SICE 7200 ™ - Input and Holding - SSC Controller System Control Cabinet - SSC Liebert Produ cts Liebert SICE 7200 A vailable Poin t s Data Description Input Register Holding Register # of Reg. Scale Notes / Units Output V oltage L1-[...]

  • Pagina 210

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 204 Output Undervoltage — 4029 0 1 — Bi t 7 Output Waveform Error — 4029 0 1 — Bit 8 T ransfer Count Block — 40290 1 — Bit 9 Overload Shutdown — 40290 1 — Bit 10 Overtemperature Shutdown — 40291 1 — Bit 0 Emergency S top — 4029 1 1 —[...]

  • Pagina 211

    Modbus 485 and Modbus IP Protoc ols - UPS Systems 205 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 73 Liebert Npower ™ - Input and Holding - IMP Controller Single Mo dule Series - SMS Liebert Product s Liebert Npower - SMS A vailable Poin t s Data Description Input Register Holding Register # of Reg. Scale N otes / Unit s St atus Points (Vi[...]

  • Pagina 212

    Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 206 Equipment Over T emperature — 40290 1 — Bit 0 Any of Battery / Heatsink / Ambient / Timeout Shutdown Battery Ground Fault CB Trip — 40290 1 — Bit 1 Power Supply Fail — 40290 1 — Bit 2 Any of Input / Byp ass / Output / F1 / SWGR / MM / Option[...]

  • Pagina 213

    Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 207 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 3.4 Battery Monitoring Product s T able 74 Alber ® BDSU ™ - St atus and Coil Data Description Stat us C o il Number of Bit s Notes / Unit s Battery Entity Battery Discharging Battery 1 - 32 10001-10032 — 1 Active on Alarm Str in g [...]

  • Pagina 214

    Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products Liebert ® IntelliSlot ® Modbus/BACnet IP 208 Thermal Runaway Charger Current Level One Event S tring 1 - 32 13297-13328 — 1 Active on Alarm Thermal Runaway Charger Current Level T wo Event S tring 1 - 32 13329-13360 — 1 Active on Alarm Ground Fault Detected S tring 1 - 32 14041[...]

  • Pagina 215

    Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 209 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 75 Alber ® BDSU ™ - Input and Holding Data Description Input Register Holding Register # of Reg. Scale Notes / Units Battery Measurement and Control System S tatus 30385 — 1 — 1 = Normal Operation 2 = S tartUp 8 = Normal w[...]

  • Pagina 216

    Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products Liebert ® IntelliSlot ® Modbus/BACnet IP 210 Cell to Cell T emperature Deviation Threshold S tring 1 - 32 33042-33073 — 1 — Units : deg C Cell to Cell T emperature Deviation Threshold S tring 1 - 32 33074-33105 — 1 — Units : deg F Cell to Ambient T emperature Deviatio n Thr[...]

  • Pagina 217

    Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 211 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Cell T emp erature Low Global Th reshold S tring 1 - 32 32818-32849 — 1 Scale : x / 10 Units : deg F Cell T emperature High Global Threshol d S tring 1 - 32 32850-32881 — 1 Scale : x / 10 Units : deg C Cell T emperature High Global [...]

  • Pagina 218

    Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products Liebert ® IntelliSlot ® Modbus/BACnet IP 212 Cell to Ambient T emperature Deviatio n Threshold S tring 1 - 32 39123-39152 — 1 Scale : x / 10 Units : deg F Ordinal Position of S tring S tring 1 - 32 33522-33553 — 1 — — Index of Parent Ba ttery S tring 1 - 32 33554-33585 — [...]

  • Pagina 219

    Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 213 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Cell T emp erature Cell 321 – 360 39195-39234 — 1 Scale : x / 10 Units : deg C Cell T emp erature Cell 321 – 360 39235-39274 — 1 Scale : x / 10 Units : deg F Internal Resistance V a lue Cell 321 – 360 39275-39314 — 1 Units :[...]

  • Pagina 220

    BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 214 4.0 BAC NET C OMMUNICATIONS 4.1 BACnet Protocol Implemen t ation Conformance St atement The Liebert IntelliSlot ® Web IS-IPBML, IS-WEBADPT, IS-UNITY ™ and the IS- UNITY-DP ™ cards provide BACnet IP to E merson Network Pow[...]

  • Pagina 221

    BACnet Communications - BACnet Protocol Implementation Conformance Statement 215 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 4.1.2 Supported Services Service Originate Res pond Alarm and Event Services • AcknowledgeAlarm — — • ConfirmedCOVNoti fication x — • UnconfirmedCOVNotifi cation x — • ConfirmedEventNotification — — • Un[...]

  • Pagina 222

    BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 216 4.1.3 St andard Object T ypes Supported Object T ype X=Supported Accumulator — Analog Input x Analog Output x Analog V alue x Averaging — Binary Input x Binary Output x Binary V alue x Calendar — Command — Device x Eve[...]

  • Pagina 223

    BACnet Communications - BACnet Protocol Implementation Conformance Statement 217 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 4.1.4 Object Properties The following object properties are supported. Device Object The Device object represents the agent (t he card) rather than the managed device. NOTE All properties are read-only unless otherwise noted [...]

  • Pagina 224

    BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 218 Analog Object Unit s Possible values of the Units prop erty include the BACnet Engineering Units defined in the BACnet standard, plus these additiona l proprietary u nits values: Analog Object Property Analog Input Analog Outp[...]

  • Pagina 225

    BACnet Communications - BACnet Protocol Implementation Conformance Statement 219 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Binary Object Properties Multist ate Object Properties Binary Object Property Binary Input Binary Output Binary Va l u e C o m m e n t s Object_Identifier x x x — O b j e c t _ N a m e xxx — Object_T ype x x x — Present[...]

  • Pagina 226

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 220 4.2 Thermal Management Product s T able 76 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Binary Data Controller Lieber[...]

  • Pagina 227

    BACnet Communicati ons - Thermal Management Pro ducts 221 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressors - Compressor 1 Compressor Hours Exceeded Binary_V alue 77 5269 _1_1 RD Active on Alarm 1, 2, 3, 4, 5, 6 Compressor High Head Pressure Binary_V alue 78 5270 _1_1 RD Active on Alarm 1, 2 , 3, 4, 5, 6 Compressor Low Suction Pressure Binary[...]

  • Pagina 228

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 222 Free Cooling / Chilled Water Free Cooling V alve Ho urs Exceeded Binary_ V alue 1 17 5306_1 RD Active on Alarm 1, 2, 3, 4, 5, 6 Ext Free Cooling Lockout Binary_V alue 1 18 5361_1 RD Active on Alarm 1, 2, 3, 4, 5, 6 Free Cooling T emp Sensor Issue Bi[...]

  • Pagina 229

    BACnet Communicati ons - Thermal Management Pro ducts 223 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Condensers Condenser TVSS Issue Binary_V alue 218 5073_1 RD Acti ve on Alarm 1, 2, 3, 4, 5, 6 Condenser VFD Issue Binary_ V alue 219 5072_1 RD Active on Alarm 1, 2, 3, 4, 5, 6 Ext Condenser Pump High Water Binary_V alue 220 5106_1 RD Active on Alar[...]

  • Pagina 230

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 224 Supply Chilled Water Over T emp Binary_V a lue 271 4626_1 RD Acti ve on Alarm 1, 2, 3, 4, 5, 6 Unit Code Missing Binary_ V alue 272 5418_1 RD Active on Alarm 1, 2, 3, 4, 5, 6 Unit Communication Lost Binary_V alue 273 5419_1 RD Active on Alarm 1, 2, [...]

  • Pagina 231

    BACnet Communicati ons - Thermal Management Pro ducts 225 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Events - iCOM DO Board 3 Digital Output Board Not Detected Binary_V alue 349 5 417_1_3 RD Acti ve on Alarm 1, 2, 3, 4, 5, 6 Remote Sensors Remote Sensor Average Over T emperature Binary_V alue 361 559 3_1 RD Active on Alarm 2, 3, 4, 5, 6 Rem[...]

  • Pagina 232

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 226 Low S tatic Pressure Binary_V alue 565 563 1_1 RD Active on Alarm 3, 5, 6 S tatic Pressure Sensor Out of Range B inary_V alue 566 5910_1 RD Acti ve on Alarm 5, 6 EconoPhase Pump Unspecified General Event Binary_V alue 623 563 6_1 RD Active on Alarm [...]

  • Pagina 233

    BACnet Communicati ons - Thermal Management Pro ducts 227 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 78 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Analog Dat a Dat a Label Object T ype Instanc eO b j e c t N [...]

  • Pagina 234

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 228 Return Air T emperature Set Point Analog_V alue 100 32 5333_1_1_deg _F RW Units: deg F 1 Return Air Over T emp Thre shold Analog_V alue 33 5022_1_1 RW Units: deg C 1, 2, 3, 4, 5, 6 Return Air Over T emp Thre shold Analog_V alue 10033 5 022_1_1_deg _[...]

  • Pagina 235

    BACnet Communicati ons - Thermal Management Pro ducts 229 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T oday's High Humidity Analog_V alue 68 5343_1 RD Units: % RH 1, 2, 3, 4, 5, 6 T oday's High Humidity Time Analog_V alue 69 5344_1 RD Units: Seconds since Midnigh t 1, 2, 3, 4, 5, 6 T oday's Low Humidity Analog_V alue 70 5345_1 RD Un[...]

  • Pagina 236

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 230 Compressors - Compressor 2 Compressor Hours Analog_ V alue 1 10 5267_1 _2 RW Units: hr 1, 2, 3, 4, 5, 6 Compressor Hours Thresho ld Analog_V alue 1 1 1 5268_1 _2 RW Units: hr 1, 2, 3, 4, 5, 6 Dig Scroll Comp D ischarge Te m p Analog_ V alue 1 12 535[...]

  • Pagina 237

    BACnet Communicati ons - Thermal Management Pro ducts 231 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Humidifier Humidifier Hours Analog_V alue 186 5369_ 1 RW Uni ts: hr 1, 2, 3, 4, 5, 6 Humidifier Hours Threshold Ana log_V alue 187 5370_ 1 RW Units: hr 1, 2, 3, 4, 5, 6 Infrared Humidifi er Flush Rate Ana log_V alue 188 5 445_1 RW Uni ts: % 1, 2, 3[...]

  • Pagina 238

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 232 Calculated Next Maintenance Month Analog_V alue 284 4868_1 RD — 1, 2, 3, 4, 5, 6 Calculated Next Maintenance Y ear Ana log_V alue 285 4869_1 RD — 1, 2, 3, 4, 5, 6 Hot W ater / Hot Gas V alve Open Position Analog_V alue 286 5380_1 RD Units: % 1, [...]

  • Pagina 239

    BACnet Communicati ons - Thermal Management Pro ducts 233 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sensor Average T emperature Analog_V alue 314 5007_1 RD Units: deg C 2, 3, 4, 5, 6 Remote Sensor Average T emperature Analog_V alue 10314 5007_ 1_deg_F RD Uni ts: deg F 2, 3, 4, 5, 6 Remote Sensor Maximum T emperature Analog_V alue 315 5006_[...]

  • Pagina 240

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 234 Condenser Low Noise Mode - Interval Days Analog_V alue 533 5550_1_1 RW 1 = Monday 2 = Tuesday 4 = Wednesday 8 = Thursday 16 = Frida y 32 = Saturday 64 = Sunday 3, 4, 5, 6 Condenser Low Noise Mode - Full Days Ana log_V alue 534 5551_1_1 RW 1 = Monday[...]

  • Pagina 241

    BACnet Communicati ons - Thermal Management Pro ducts 235 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Fluid 1 Fluid Input T emperature Analog_ V alue 87 1 5897_1 RD Units: deg C 6 Fluid Input T empera ture Analog_V alue 10871 5897_1_deg_F RD Units: deg F 6 Fluid Output T e mperature Ana log_V alue 872 5 898_1 RD Units: deg C 6 Fluid Output T empera[...]

  • Pagina 242

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 236 T able 80 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Multistate Dat a Data Label Object T ype Inst ance Object Name[...]

  • Pagina 243

    BACnet Communicati ons - Thermal Management Pro ducts 237 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Fan Control Mode MultiS tate_V alue 82 5 373_1 RW 1 = Auto 2 = Manual 3 = Economy 4 = Delta 1 Fan Control Sensor MultiS tate_V alue 83 5 586_1 R W 1 = Supply 2 = Remote 3 = Return 4 = Manual 2, 3, 4, 5, 6 System Info System S tatus MultiSt ate _V a[...]

  • Pagina 244

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 238 System Event Configuration Customer Input 1 - Event Control MultiS tate_V alu e 126 4718_1 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6 Customer Input 1 - Event T y pe MultiSt ate _V alue 127 4719_1 RW 1 = Message 2 = W arning 3 = Alarm 1, 2, 3, 4, [...]

  • Pagina 245

    BACnet Communicati ons - Thermal Management Pro ducts 239 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ext Over T empera ture - Event Control MultiS tate_V alu e 146 5090_1 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6 Ext Over T empera ture - Event Ty p e MultiS tate_V alue 147 5091_1 R W 1 = Message 2 = W arning 3 = Alarm 1, 2, 3, 4, 5, 6 Ext Rehea[...]

  • Pagina 246

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 240 Clogged Air Filter - Event T ype MultiS tate_V alu e 167 5136 _1 RW 1 = Message 2 = W arning 3 = Alarm 1, 2, 3, 4, 5, 6 Ext Loss of Air Blower - Event Control MultiS tate_V alu e 168 5393_1 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6 Ext Loss of Ai[...]

  • Pagina 247

    BACnet Communicati ons - Thermal Management Pro ducts 241 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressor Pump Down Issue - Event T ype MultiSt ate _V alue 207 53 96_1_2 RW 1 = Message 2 = W arning 3 = Alarm 1, 2, 3, 4, 5, 6 Compressor Short Cycle - Event Control MultiS tate_V alue 208 5397_1_2 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6 Co[...]

  • Pagina 248

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 242 Low Return Hu midity - Event Ty p e MultiS tate_V alue 237 51 40_1_1 RW 1 = Message 2 = W arning 3 = Alarm 1, 2, 3, 4, 5, 6 Return Air Over T emp - Event Control MultiS tate_V alu e 238 5024_1_1 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6 Return Ai[...]

  • Pagina 249

    BACnet Communicati ons - Thermal Management Pro ducts 243 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Reheat Reheater Lockout MultiS tate_V alue 316 5582_1 R W 1 = disabled 2 = enabled 2, 3, 4, 5, 6 Humidifier Humidifier Lockout MultiS tate_V alue 328 5583_1 RW 1 = disabled 2 = enabled 2, 3, 4, 5, 6 Air Economiz er Air Economizer Availability Multi[...]

  • Pagina 250

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 244 T able 82 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Glossary Data Label Data Description Actual Air T emperature S[...]

  • Pagina 251

    BACnet Communicati ons - Thermal Management Pro ducts 245 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressor Capacity Control S tate Compressor cap a city control state. When 'ON', the cooling capacity of the compressor has been reduced. Compressor Capacity Reduced Compressor capacity has been reduced. Compressor High Head Pressure - [...]

  • Pagina 252

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 246 Condenser Circuit Unspecified General Event One or more unsp ecified condenser circuit eve nts active. See local unit display for further details. Condenser Issue - Event Control Enable/disable the activa tion of the [Condenser Issue] event. If set [...]

  • Pagina 253

    BACnet Communicati ons - Thermal Management Pro ducts 247 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Customer Input 4 Customer Input 4 Dehumidifier Hours Exceeded Operating ho urs for the dehumidifier have exceeded th e threshold. Dehumidifier Hours Threshold Threshold value used in the [Deh umidifier Hours Exceeded] event. Dehumidi fier Hours Ope[...]

  • Pagina 254

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 248 Ext Air Sensor A Issue The external air sensor A is disconnected or the signal is out of ra nge. Ext Air Sensor A Low Humidity - Event Control Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set to 'disabled'[...]

  • Pagina 255

    BACnet Communicati ons - Thermal Management Pro ducts 249 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ext Free Cooling Lockout - Event Control Enable/disable the acti vation of the [Ext Free Cooling Lockout] event. If set to 'disabled', the event will not be annuncia ted. This implies that the event will not be placed in any active event [...]

  • Pagina 256

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 250 Fan Hours Exceeded - Event Control Enable/disable the acti vation of the [F an Hours Exceeded] event. If set to 'disabled', the event will not be annuncia ted. This implies that the event will not be placed in any active event list or in a[...]

  • Pagina 257

    BACnet Communicati ons - Thermal Management Pro ducts 251 Liebert ® IntelliSlot ® Mo dbus/BACnet IP High Power Shutdown - Event T ype The event type for the [High Power Shutdown] event. High Power Shutdown Supply to high power components has been shutdown. High Return Humidity - Event Control Enable/disable the acti vation of the [High Return Hum[...]

  • Pagina 258

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 252 Humidity Set Point Desired relative humidity . Infrared Humidi fier Flush Rate A multiple of an internal time consta n t that determines the flush duration of the infrared humidifier water pan. Input Undervoltage One or more of the inpu t phase volt[...]

  • Pagina 259

    BACnet Communicati ons - Thermal Management Pro ducts 253 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sensor Average T emperature Average val ue of remote sensor te mperature measurements. Remote Sensor Average Under T emperature [Remote Sensor Average T emperature] has dropped bel ow [Remote Sensor Under T emp Threshold]. Remote Sensor Issu[...]

  • Pagina 260

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 254 Service Required Unit requi res servicing. Shutdown - Loss Of Power - Event Control Enable/disable the acti vation of the [Shutd own - Loss Of Power] event . If set to 'disabled', the event will not be annuncia ted. This implies that the e[...]

  • Pagina 261

    BACnet Communicati ons - Thermal Management Pro ducts 255 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T emperature Control Sensor Issue The air sensor selected for coolin g control is disconnected or the signal is out of range. T oday's High Air T emperature T i me [T od ay's High Air T emperature] w as measured at this time. T oday'[...]

  • Pagina 262

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 256 T able 83 Liebert CRV ™ - Binary Dat a Controller Liebert iCOM ® v4 Dat a Label Object T ype Instance Object Name Access Notes Air T emperature Supply Air Over T emperature Binary_V alue 1 5015_1 RD Active on Alarm Supply Air Under T emperature B[...]

  • Pagina 263

    BACnet Communicati ons - Thermal Management Pro ducts 257 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sen sors 10 Remote Sensor Issue Binary_V a lue 151 5060_10 RD Active on Alarm Compressor Compressor 1 High Head Pressure Binary_V a lue 162 4669_1 RD Active on Alarm Compressor 1 Low Suction Pressure Bina ry_V alue 163 5062_1 RD Active on Al[...]

  • Pagina 264

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 258 Unit Partial Shutdown Binary_V alue 237 51 12 _1 RD Active on Alarm Unit Shutdown Binary_V a lue 238 51 13 _1 RD Active on Alarm W ate r Leakage Detector Sensor Issue Binary_V alue 239 51 14_1 RD Active on Alarm BMS Communications Timeout Binary_V a[...]

  • Pagina 265

    BACnet Communicati ons - Thermal Management Pro ducts 259 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 84 Liebert CRV ™ - Analog Dat a Controller Liebert iCOM ® v4 Dat a Label Object T ype Instance Object Name Access Notes Air T emperature Supply Air T emperature Analog_V alue 1 5002_1 RD Uni ts: deg C Supply Air T emperature Analog_V alue[...]

  • Pagina 266

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 260 Remote Sen sors 1 Remote Sensor T emperature Anal og_V alue 56 5059_1 RD Units: deg C Remote Sensor T emperature Analo g_V alue 1 0056 5059_1 _deg_F RD Units: deg F Remote Sen sors 2 Remote Sensor T emperature Anal og_V alue 67 5059_2 RD Units: deg [...]

  • Pagina 267

    BACnet Communicati ons - Thermal Management Pro ducts 261 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Condenser Low Noise Mode - Interval Days Analo g_V alue 287 5550_1_1 RW 1 = Monday 2 = T uesday 4 = Wednesday 8 = Thursday 16 = Friday 32 = Saturday 64 = Sunday Condenser Low Noise Mode - Ful l Days Analog_V al ue 288 5551 _1_1 RW 1 = Monday 2 = T [...]

  • Pagina 268

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 262 T able 85 Liebert CRV ™ - Multist ate Dat a Controller Liebert iCOM ® v4 Data Label Object T ype Inst ance Object Name Access Notes Protocol Server Class MultiS tate_V al ue 1 4553_1 RD 1 = UPS 2 = AIR 3 = PMP 4 = PDU Air T emperature Air T emper[...]

  • Pagina 269

    BACnet Communicati ons - Thermal Management Pro ducts 263 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Event Configuration System Event Acknowledge/Reset MultiS tate_V alue 171 4717_1 WO 1 = Reset 2 = Acknowledge Smoke Detected - Event Control MultiS tate_V alue 172 4721_1 RW 1 = disabled 2 = enabled Smoke Detected - Event T ype Multi S tate_V alue [...]

  • Pagina 270

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 264 Ext Reheat Lockout - Event T ype MultiS tate_V al ue 191 5085_1 RW 1 = Message 2 = W arning 3 = Alarm Ext Humidifier Lockout - Event Control MultiSt ate_V alue 192 5086_1 RW 1 = disabled 2 = enabled Ext Humidifier Lockout - Event T ype MultiSt ate_V[...]

  • Pagina 271

    BACnet Communicati ons - Thermal Management Pro ducts 265 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 86 Liebert CRV ™ - Glossary Data Label Data Description Air T emperature Con trol Sensor Sens or from which air temperature mea surements will be used for coo ling and heating control. Air T emperature Dead Band V alue that is di vided eve[...]

  • Pagina 272

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 266 Condenser Low Noise Mode S top Time The time of day at which the condenser will transition out of low noise mo de. Condenser Max Fan S peed Ove rride Fan speed exceed ing the maximum set point in order to alleviate a high temperatur e or pressure co[...]

  • Pagina 273

    BACnet Communicati ons - Thermal Management Pro ducts 267 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Customer Input 3 - Event T y pe The event type fo r the [Customer Input 3] event. Customer Input 3 Customer input 3. Customer Input 4 - Event Control Enable/disable the activation of the [Custo mer Input 4] event. If set to 'disabled', th[...]

  • Pagina 274

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 268 Fan Hours Exceeded Operating hours fo r the unit blower fan have exceede d the threshold. Fan S peed Manual Set Point Manual fan speed. Fan S peed Maximum Set Point Maximum fan speed. Fan S peed Minimum Set Point Minimum fan speed. Fan S peed Propor[...]

  • Pagina 275

    BACnet Communicati ons - Thermal Management Pro ducts 269 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sensor T emperature Calculation Calculation method applie d to temperatur e readings from the remote sensors to determine a single te mperature measur ement value fo r cooling and heating control. Remote Sensor T emperature Air temperature a[...]

  • Pagina 276

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 270 System Operating S tate Current operating state of the system. System S tatus T he operating status for the system T op Fan Issue T he top fan is not operating within its normal parameters. Unit Off Unit was turned off. Unit On Unit was turned on. U[...]

  • Pagina 277

    BACnet Communicati ons - Thermal Management Pro ducts 271 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 87 Liebert HPC ™ - Binary Data Controller Liebert iCOM ® v4 Dat a Label Object T ype Inst ance Object Name Access Notes Extra Notes Compressors Compressor Not S toppi ng Binary_V alue 1 5263_1 RD Acti ve on Alarm 1, 2 Compressor Superheat[...]

  • Pagina 278

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 272 Fluid - Supply (Outlet) Flu id Supply Fluid Over T emp Binary_V alue 84 4645_ 1_1 RD Active on Alarm 1 , 2 Supply Fluid Under T emp Binary_V alue 85 4648_1_1 RD Active on Alarm 1, 2 Supply Fluid T emp Sensor Issue Binary_V alue 86 4651_1_1 RD Active[...]

  • Pagina 279

    BACnet Communicati ons - Thermal Management Pro ducts 273 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 88 Liebert HPC ™ - Analog Data Controller Liebert iCOM ® v4 Dat a Label Obje ct T ype Instance Object Name Access Notes Extra Notes Compressors Compressor Shut Down - Ambient Air Low Te m p L i m i t Analog_V alue 1 5262_1 RW Units: deg C[...]

  • Pagina 280

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 274 Free Cooling Free Cooling External T emperature Delta A nalog_V alue 1 12 5301_1 RW Units: deg C 1, 2 Free Cooling External T emperature Delta A nalog_V alue 101 12 5301_1_deg_F RW Units: deg F 1, 2 Free Cooling V a lve Open Position Ana log_V alue [...]

  • Pagina 281

    BACnet Communicati ons - Thermal Management Pro ducts 275 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 89 Liebert HPC ™ - Multist ate Data Controller Liebert iCOM ® v4 Dat a Label Object T ype Inst ance Object Name Access Notes Extra Notes Protocol Server Class MultiS tate_V al ue 1 4553_1 RD 1 = UPS 2 = AIR 3 = PMP 4 = PDU 1, 2 Compressor[...]

  • Pagina 282

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 276 T able 90 Extra Notes Number Descript ion 1 This point is supported on: FDM v32 iCOM Controller V ersion 2.02.xxx 2 This point is supported on: FDM v10 1 iCOM Controller V ersion 2.03.xxx T able 91 Liebert HPC ™ - Glossary Data Label Data Descript[...]

  • Pagina 283

    BACnet Communicati ons - Thermal Management Pro ducts 277 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Customer Input 1 Customer input 1. Customer Input 2 Customer input 2. Customer Input 3 Customer input 3. Customer Input 4 Customer input 4. EEV Unspecified General Event One or more unspecified el ectronic expansion valve events active. See local u[...]

  • Pagina 284

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 278 Pump Hours Threshold Threshold value us ed in the [Pump Hours Exceeded] event. Pump Hours Operating hours for pump since last reset of this value. RAM Battery Issue RAM or RAM backup battery is no t operating correctly . Reheat Utilization Present r[...]

  • Pagina 285

    BACnet Communicati ons - Thermal Management Pro ducts 279 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 92 Liebert XDP ™ , Liebert XDC ™ - Binary Data Controller Liebert iCOM ® v4 Data Label Object T ype Inst ance Object Name Access Note s External Air Ext Air Sensor A Over T emperature Binary_V alue 1 4601_1 RD — Ext Air Sensor B Over [...]

  • Pagina 286

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 280 XD System 1 Ext System Condensation Detected Binary_V al ue 1 12 5 492_1 RD — Ext Fan Issue Binary_V alue 1 13 5495_1 RD — Sensor Issue Binary_V alue 1 14 5060_1 RD — Ext Remote Shutdown Binary_V al ue 1 15 5500_1 RD — Hot Aisle T emp Out of[...]

  • Pagina 287

    BACnet Communicati ons - Thermal Management Pro ducts 281 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 93 Liebert XDP ™ , Liebert XDC ™ - Analog Data Controller Liebert iCOM ® v4 Data Label Object T ype Instance Object Name Access No tes External Air Dew Point T emperatu re Analog_V alue 1 4867_1 RD — Minimum Room T emperature Set Poin[...]

  • Pagina 288

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 282 XD System 1 T empe rature Sensor 4 Remote Sensor T emperature Analog_V alue 143 5059_1_4 RD — XD System 2 Cooling Capacity Analog_V al ue 154 5490_ 2 RD — Cooling Capacity Analog_V al ue 155 5491_ 2 RD — Hot Aisle Over T emp Threshol d Analog_[...]

  • Pagina 289

    BACnet Communicati ons - Thermal Management Pro ducts 283 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 94 Liebert XDP ™ , Liebert XDC ™ - Multistate Dat a Controller Liebert iCOM ® v4 Data Label Object T ype Instance Object Name Access Notes External Air Ext Air Sensor A Over T emp - Ev ent Control Multistate_V alue 1 460 2_1 RW 1 = Disa[...]

  • Pagina 290

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 284 Refrigerant Supply Refrig Over T emp - Event Control Multistate_V alue 41 4635_1 RD 1 = Di sabled 2 = Enabled Supply Refrig Over T emp - Event T ype Multistate_V alue 42 463 6_1 RW 1 = Message 2 = W arning 3 = Alarm Supply Refrig Under T emp - Event[...]

  • Pagina 291

    BACnet Communicati ons - Thermal Management Pro ducts 285 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressors Compressor 1A S tate Multistate_V a lue 91 4665_1 RD 1 = Off / 2 = On Compressor 1B S tate Multistate_V a lue 92 4666_1 RD 1 = Off / 2 = On Compressor 2A S tate Multistate_V a lue 93 4667_1 RD 1 = Off / 2 = On Compressor 2B S tate Multi[...]

  • Pagina 292

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 286 Circuit 2 Low Suction Pressure - Event Ty p e Multistate_V alue 1 14 4698_1 RW 1 = Message 2 = W arning 3 = Alarm Hot Gas Hot Gas Solenoid V alve 1 Po sition Mul tistate_V alue 125 4701_1 RD 1 = Closed 2 = Open Hot Gas Solenoid V alve 2 Po sition Mu[...]

  • Pagina 293

    BACnet Communicati ons - Thermal Management Pro ducts 287 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Fan Button Control Multistate_V alue 175 5488_2 RW 1 = Enabled 2 = Disabled Visual ID Control Multistate_V alue 176 5489_2 RW 1 = Disa bled 2 = Enabled Ext System Condensation Detected - Event Control Multistate_V alue 177 5493_2 RW 1 = Disabled 2 [...]

  • Pagina 294

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 288 Sensor Issue - Event T ype Multistate_V a lue 812 5499_20 R W 1 = Message 2 = W arning 3 = Alarm Ext Remote Shutdown - Event Control Mul tistate_V alue 813 5501_ 20 RW 1 = Di sabled 2 = Enabled Ext Remote Shutdown - Event T y pe Multistate_V a lue 8[...]

  • Pagina 295

    BACnet Communicati ons - Thermal Management Pro ducts 289 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Smoke Detected - Event T ype Multistate_V alue 859 4722_1 RW 1 = Message 2 = W arning 3 = Alarm W ater Under Floor - Event Con trol Multistate_V alue 860 4724_1 RW 1 = Disabled 2 = Enabled W ater Under Floor - Event T ype Multistate_V a lue 861 472[...]

  • Pagina 296

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 290 T able 95 Liebert XDP ™ , Liebert XDC ™ - Glossary Data Label Data Description Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the un it. Calculated Next Maintenance Month[...]

  • Pagina 297

    BACnet Communicati ons - Thermal Management Pro ducts 291 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressor 1B Short Cycle - Event T ype Th e event ty pe for the [Compressor 1B Short Cycle] event. Compressor 1B Short Cycle Compressor 1B short cycle. A short cycle is defined as turning on and off a number of times ove r a set time period. Compr[...]

  • Pagina 298

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 292 Ext Air Sensor A Over T emp - Event Control Enable/disable the activation of the [Ext Air Sensor A Over T emperature] event. If set to 'dis abled', the event wil l not be annunciated. This imp lies that the event will n ot be placed in any[...]

  • Pagina 299

    BACnet Communicati ons - Thermal Management Pro ducts 293 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ext Remote Shutdown Uni t is shut down by a remote signal. Ext System Condensation Detected - Event Control Enable/disable the activation of the [Ext System Condensation Detected] event. If set to 'disabled' , the event wil l not be annun[...]

  • Pagina 300

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 294 Pump Hours Operating hours for pump since last reset of this value. Pump Short Cycle - Event Control Enable/disable the activation of the [Pump Sh ort Cycle] event. I f set to 'disabled', the event will not be annunciate d. This implies th[...]

  • Pagina 301

    BACnet Communicati ons - Thermal Management Pro ducts 295 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Supply Fluid Over T emp Thre shold Threshold value used in the [Supply Fluid Over T emp ] event. Supply Fluid Over T emp [Supply Fluid T emperature] has e xceeded [Supply Fluid Over T emp Threshold]. Supply Fluid T emp Sensor Issue - Event Control [...]

  • Pagina 302

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 296 Unit Code Missing Unit code has not been ente red and saved. Unit Communication Lost Master has l ost comm unication with one or more networked units. Unit Off Unit was turned off. Unit On Unit was turned on. Unit Partial Shutdown An event has occur[...]

  • Pagina 303

    BACnet Communicati ons - Thermal Management Pro ducts 297 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 96 Liebert Dat aMate ™ , Liebert Mini-Mate2 ™ - MM2 Controller MM2 Liebert Products Liebert DataMate Liebert Mini-Mate2 Data Description BACnet Instance Notes St atus Points (View) T emperature BS01_x — Humidity BS 02_x — Cooling BS0[...]

  • Pagina 304

    BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 298 T able 97 Liebert Mini-Mate2 ™ 8 T on - L8T Controller L8T Liebert Product s Liebert Mini-Mate2 8 T on Data Description BACnet Instance Notes St atus Points (View) T emperature BS01_x — Humidity BS02_ x — Cooling BS03_x 1=On / 0=Off Heating BS[...]

  • Pagina 305

    BACnet Communications - UPS Systems 299 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 4.3 UPS Systems T able 98 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Binary Data Data Label Object T ype Instance Object Name Access Notes System St atus Battery Auto T est In Progress Binary_V alue 1 4172_1 RD Active on Alarm Battery Equalize Binary_V al[...]

  • Pagina 306

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 300 Power Sub Module Fault Binary_V alue 51 5158_1 RD Active on Alarm Battery Discharging Binary_V alue 52 4168 _1 RD Active on Alarm UPS Output on Bypass Binary_V alue 53 4298_1 RD Active on Alarm Output Load on Maint. Bypass Bi nary_V alue 54 4299_1 RD Active on Alarm [...]

  • Pagina 307

    BACnet Communications - UPS Systems 301 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 99 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Analog Dat a Data Label Object T ype Inst ance Object Name Access Notes System Input RMS A-B An alog_V alue 1 4097_1 RD Units: V AC System Input RMS B-C Analog_V alu e 2 4099 _1 RD Units: V AC System In[...]

  • Pagina 308

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 302 MMS Output Apparent Power Analog_V alue 69 4812_1 RD Units: kV A MMS Output Power Analog_V alue 70 481 1_1 RD Units: kW System Output Apparent Power Analog_V alu e 71 4209 _1 RD Units: kV A System Output Power Analog_V alue 72 4208_1 RD Units: kW Output Current Crest[...]

  • Pagina 309

    BACnet Communications - UPS Systems 303 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 101 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Gl ossary Data Label Data Description Battery Auto T est In Progress Auto matic battery te st is in progress Battery Capacity Low Battery capacity is low Battery Charging Error The battery is not charg[...]

  • Pagina 310

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 304 Load Sharing Fault Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nom i nal current. Loss of Redundancy The multi-module collection doesn't have en oug h modules[...]

  • Pagina 311

    BACnet Communications - UPS Systems 305 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power[...]

  • Pagina 312

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 306 T able 102 Liebert APS ™ - Binary Data Data Label Object T ype Instance Object Name Access Note s Input Rectifier Failure Binary_V alue 1 4295_1 RD Active on Alarm System Input Power Problem Binary_V alue 2 4122_1 RD Active on Alarm System Input Current Imbalance B[...]

  • Pagina 313

    BACnet Communications - UPS Systems 307 Liebert ® IntelliSlot ® Mo dbus/BACnet IP PowerModule 1 Power Module Fan Fault Binary_V alue 99 5838_1 RD Active on Alarm Power Module Over T emperature Binary_V alue 100 5839_1 RD Active on Alarm Power Module Shutdown - Over T emperature Binary_V alue 101 5840_1 RD Active on Alarm PowerModule 2 Power Modul[...]

  • Pagina 314

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 308 T able 103 Liebert APS ™ - Analog Dat a Data Label Object T ype Instance Object Name Access Notes Input System Input RMS L1-N Analog _V alue 1 4096_1 RD Units: V AC System Input RMS L2-N Analog _V alue 2 4098_1 RD Units: V AC System Input RMS L3-N Analog _V alue 3 [...]

  • Pagina 315

    BACnet Communications - UPS Systems 309 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Apparent Power L2 Analog_V alue 71 5869_1 RD Units: kV A System Output Power Analog_V alue 72 4208_1 RD Units: kW System Output Power L 1 Analog_V alu e 73 5859_1 RD Units: kW System Output Power L 2 Analog_V alue 74 5860 _1 RD Units: kW System Output [...]

  • Pagina 316

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 310 T able 104 Liebert APS ™ - Multistate Dat a Dat a Label Object T ype Instance Object Name Access Notes Protocol Server Class Multi S tate_V alue 1 4553_1 RD 1 = UPS 2 = AIR 3 = PMP 4 = PDU Byp ass Bypass Qualification S tatus MultiS tate_V al ue 12 4737_1 RD 1 = Fa[...]

  • Pagina 317

    BACnet Communications - UPS Systems 311 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Auto Restart Minimum Battery Setting MultiS tate_V al ue 64 5832_1 RW 1 = 0% 2 = 10% 3 = 20% 4 = 30% 5 = 40% 6 = 50% 7 = 60% 8 = 70% 9 = 80% 10 = 90% PowerModule 1 Module Operating St atus Mul tiS tate_V alue 75 5 833_1 RD 1 = Normal 2 = W arning 3 = Alarm 4 = Fault[...]

  • Pagina 318

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 312 T able 105 Liebert APS ™ - Glossary Data Label Data Description Accumulated Discharge T ime The highest accumulated ba ttery discharge time among installed battery modules. Accumulated Discharge T ime T otal accumulated discharge time for the Battery Module since i[...]

  • Pagina 319

    BACnet Communications - UPS Systems 313 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus Current The current at the battery input te rminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value Frame Capacity T otal system capacity supporte d when the maximum number of power modules ar[...]

  • Pagina 320

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 314 Output Load on Maint. Bypass Th e output power is supplied by the maintenance bypass Output Off Pending Outp ut off pending - shutdown imminent. Output On Dela y When a value is written to this poin t the output will be turned on after the specified time has elapsed.[...]

  • Pagina 321

    BACnet Communications - UPS Systems 315 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Off The system output is off System Output Pct Pow er L1 The system output power on Line 1 as a perce ntage of the rated capacity System Output Pct Pow er L2 The system output power on Line 2 as a perce ntage of the rated capacity System Output Power F[...]

  • Pagina 322

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 316 T able 106 Liebert NXL ™ - 60Hz, UL version (Model 40) - Binary Data Dat a Label Object T ype Instance Object Name Access Notes Liebert NXL T ype Input System Input Power Problem Binary_V alue 1 41 22_1 RD Active on Alarm SMS, 1+N, N+1 System Input Phs Rotation Err[...]

  • Pagina 323

    BACnet Communications - UPS Systems 317 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery Self T est Binary_V alue 46 4741_1 RD Active on Alarm SMS, 1+N, N+1 Main Battery Disconnect Open Binary_ V alue 47 4173_1 RD Active on Alarm SMS, 1+N, N+1 Battery Low Binary_ V alue 48 4162_1 RD Active on Alarm SMS, 1+N, N+1 Battery T emperature Sensor Fault[...]

  • Pagina 324

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 318 Output Amp Over User Limit-Phs A Bi nary_ V alue 91 4286_1 RD Active on Alarm SMS, 1+N, SCC Output Amp Over User Limit-Phs B Bi nary_ V alue 92 4287_1 RD Active on Alarm SMS, 1+N, SCC Output Amp Over User Limit-Phs C Bi nary_V alue 93 4288_1 RD Active on Alarm SMS, 1[...]

  • Pagina 325

    BACnet Communications - UPS Systems 319 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Input Contact 09 Binary_V alue 146 42 78_1 RD Active on Alarm SMS, 1+N, N+1, SCC Input Contact 10 Binary_V alue 147 42 79_1 RD Active on Alarm SMS, 1+N, N+1, SCC Input Contact 1 1 Bina ry_V alue 148 4280_1 RD Active on Alarm SMS, 1+N, N+1, SCC Input Contact 12 Binar[...]

  • Pagina 326

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 320 Input Filter Cycle Lock Binary_V alue 192 4755_1 RD Active on Alarm SMS, 1+N, N+1 EMO Shutdown Binary_V alue 1 93 5769_1 RD Active on Alarm SMS, 1+N, N+1, SCC Service Code Active Binary_V alue 194 4756_1 RD Active on Alar m SMS, 1+N, N+1 LBS Active Binary_V alue 195 [...]

  • Pagina 327

    BACnet Communications - UPS Systems 321 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 107 Liebert NXL ™ - 60Hz, UL version (Model 40) - Analog Dat a Dat a Label Object T yp e Instance Object Name Ac cess Notes Liebert NXL T ype Input System Input RMS A-B Analog_V alue 1 4097_1 RD Uni ts: V AC SMS, 1+N, N+1 System Input RMS B-C Ana log_V alue[...]

  • Pagina 328

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 322 Battery V olts for Cabinet 8 Analog_V a lue 45 4155_1_8 RD Units: VDC SMS, 1+N, N+1 Battery T emperature for Cabinet 1 Analog_V alue 46 4156_1_1 RD Units: deg C SMS, 1+N, N+1 Battery T emperature for Cabinet 1 Anal og_V alue 100 46 4156_1_1_deg_F RD Units: deg F SMS,[...]

  • Pagina 329

    BACnet Communications - UPS Systems 323 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus DC Bus V oltage Analog_V alue 72 4148_1 RD Units: VDC SMS, 1+N, N+1 DC Bus Current Analog_V alue 73 4149_1 RD Units: A DC SMS, 1+N, N+1 Output System Output V oltage RMS A-B Analog_V alue 84 4201_1 RD Units: V AC SMS, 1+N, N+1, SCC System Output V oltage RMS [...]

  • Pagina 330

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 324 Environment Inlet Air T emperature Analog_V alue 126 4291_1 RD Units: deg C SMS, 1+N, N+1 Inlet Air T emperatu re Analog_V alue 10126 4291_1_deg_F RD Units: deg F SMS, 1+N, N+1 T otal System Operating Time Analog_V alue 12 7 4292_1 RD Units: hr CE mode ls only System[...]

  • Pagina 331

    BACnet Communications - UPS Systems 325 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MultiModule Multi-module System Output V o ltage RMS A-B Analog_V a lue 177 4801_1 RD Units: V AC 1+N, SCC Multi-module System Output V o ltage RMS B-C Analog_ V alue 178 4802_1 RD Units: V AC 1+N, SCC Multi-module System Output V o ltage RMS C-A Analog_ V alue 179 [...]

  • Pagina 332

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 326 ModuleList 2 MMS Module T o tal kW Output Analog_V alue 226 4861_2 RD Units: kW SCC MMS Module T otal kV A Output Analog_V alue 227 4862 _2 RD Units: kV A SCC MMS Module DC Bus V oltage Analog_V alue 228 4863_2 RD Units: VDC SCC MMS Module Battery Current Analog_V al[...]

  • Pagina 333

    BACnet Communications - UPS Systems 327 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 108 Liebert NXL ™ - 60Hz, UL version (Model 40) - Multist ate Dat a Dat a Label Object T ype Instance Object Name Access Notes Liebert NXL T ype Input Input Qualification S tatus MultiS tate_V alue 1 4735_1 RD 1 = Fail 2 = Marginal Low 3 = Normal 4 = Margin[...]

  • Pagina 334

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 328 System UPS Module T ype MultiS tate_V alu e 84 4303_1 RD 1 = Single Module System 2 = Module (1 + 1) 3 = Module (1 + N) 4 = Module (N + 1) 5 = System Control Cabinet 6 = Main S tatic Switch SMS, 1+N, N+1, SCC Bypass Input Wire Configuration MultiS tate_V alue 85 4304[...]

  • Pagina 335

    BACnet Communications - UPS Systems 329 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System S tatus MultiS tate_V alue 91 4123_1 RD 1 = Normal Operation 2 = S tartUp 3 = Normal with Wa r n i n g 4 = Normal with Alarm 5 = AbNormalOperation SMS, 1+N, N+1, SCC UPS Output Source MultiS tate_V alue 92 4872_1 RD 1 = Other 2 = off 3 = Normal 4 = Bypass 5 =[...]

  • Pagina 336

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 330 Module Output Breaker (MOB) MultiS tate_V alue 126 477 5_1 RD 1 = Open 2 = Close 3 = Not Installed 1+N, SCC MultiModule Module Output Breaker for Module 1 (MOB1) MultiS tate_V alue 137 483 6_1 RD 1 = Open 2 = Close 3 = Not Installed 1+N, SCC Module Output Breaker for[...]

  • Pagina 337

    BACnet Communications - UPS Systems 331 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Isolation Output Breaker (IOB) MultiS tate_V alue 1 55 4854_1 RD 1 = Open 2 = Close 3 = Not Installed SCC SCC Event Summary MultiS tate_V alu e 156 4855_1 RD 1 = None 2 = Alarm 3 = Fault SCC MMS UPS Battery S tatus MultiS tate_V alue 157 4873_1 RD 1 = Unknown[...]

  • Pagina 338

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 332 MMS Module Inverter S tatus MultiS tate_V alue 276 4858_8 RD 1 = off 2 = on 1+N MMS Module Output V oltage S tatus MultiS tate_V alue 277 485 9_8 RD 1 = Fail 2 = Marginal Low 3 = Normal 4 = Marginal High 1+N, SCC MMS Module Output Source MultiS tate_V alue 278 486 0_[...]

  • Pagina 339

    BACnet Communications - UPS Systems 333 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 109 Liebert NXL ™ - 60Hz, UL version (Model 40) - Glossary Data Label Data Description Auto Restart I n Progress Auto restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal Auto Retransfer Time Remaining Time re[...]

  • Pagina 340

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 334 Battery T ime Remain ing The calculated availabl e time on battery Battery T otal Discharge T i me The cumulative battery discha rge time Battery V o lts at Main Disconnect The voltage between the positive and th e negative battery terminals of the common battery dis[...]

  • Pagina 341

    BACnet Communications - UPS Systems 335 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Continuous Operation - ECO Mode This se tting gives the user the ability to En able/Disable ECO Mode continuous operation. Controls Reset Required A controls reset is requir ed due to one or more critical settings changi ng DC Bus Current The current at th e battery[...]

  • Pagina 342

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 336 Intelligent Parallel Minimum R edundancy This is the minimum Number of Redundant Modules that the system will allow before bringing one or more modules back to norma l operation and terminating Intelligent Paralleling. Intelligent Pa rallel Mode This setting gives th[...]

  • Pagina 343

    BACnet Communications - UPS Systems 337 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS Module DC Bus V oltage DC bus voltage of this module in a multi-module system MMS Module Inverter S tatus Multi-module in verter st atus of this modu le (on/off) MMS Module Number MMS modu le number MMS Module Output Source Module output source in a multi-module[...]

  • Pagina 344

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 338 Multi-module System Output V o ltage RM S A-N Multi-module system output RMS voltage between phase B and Neutral Multi-module System Output V o ltage RMS B-C Multi-module system output RMS voltage between phases B and C Multi-module System Output V o ltage RM S B-N M[...]

  • Pagina 345

    BACnet Communications - UPS Systems 339 Liebert ® IntelliSlot ® Mo dbus/BACnet IP SCC Event Summary Summary of any active user alarms or faults on the SCC Schedule Action - ECO Mode This setting gives the user the abil it y to choose the action of a schedule entry to be either stop or start. Schedule Day of Week - ECO Mode This setting represents[...]

  • Pagina 346

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 340 System Output Frequency The system outpu t frequency System Output Low Power Factor The s ystem output pow er factor is low , resulting in reduced output capacity System Output Maximum Amp Rating System output maximum amperage rating System Output Nominal Frequency T[...]

  • Pagina 347

    BACnet Communications - UPS Systems 341 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ta b l e 11 0 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—Binary Dat a Data Label Object T ype In stance Object Name Access Notes Input System Input Power Problem Bina ry_V alue 1 4122_1 RD Active on Alarm System Input Phs Rotation Error B inary[...]

  • Pagina 348

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 342 DC Bus DC Bus Low Fault Bina ry_V alue 74 5563_1 RD Active on Alarm Output System Shutdown - EPO Binary_V alue 85 4213_1 RD Active on Alarm System Shutdown - REPO Binary_V a lue 8 6 4214_1 RD Active on Alarm System Output Low Power Factor Bi nary_V alue 88 4230_1 RD [...]

  • Pagina 349

    BACnet Communications - UPS Systems 343 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Rectifier Rectifier Failure Bina ry_V alue 160 4295_1 RD Active on Alarm Vdc Backfeed Binary_V alue 162 587 9_1 RD Active on Alarm Rectifier Configuration Chang e Request Binary_V a lue 163 5880_1 RD Active on Alarm System System Fan Failure - Redundant Bina ry_V al[...]

  • Pagina 350

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 344 Program Input Contact 09 Binary_V alue 237 589 2_1 RD Active on Alarm Program Input Contact 10 Binary_V alue 238 589 3_1 RD Active on Alarm Program Input Contact 1 1 Bina ry_V alue 239 5894_1 RD Active on Alarm Program Input Contact 12 Binary_V alue 240 589 5_1 RD Ac[...]

  • Pagina 351

    BACnet Communications - UPS Systems 345 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ta b l e 11 1 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—An alog Data Dat a Label Object T ype Instance Object Name Access Notes Input System Input RMS A-B Analog_V a lue 1 4097_1 RD Units: V AC System Input RMS B-C Analog_V alue 2 4099_1 RD Un[...]

  • Pagina 352

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 346 DC Bus DC Bus V oltage Analog_V a lue 66 414 8_1 RD Units: VDC DC Bus Current Analog_V alue 67 4149_1 RD Units: A DC Output System Output V oltage RMS A-B Analog_V a lue 78 420 1_1 RD Un its: V AC System Output V oltage RMS B-C Analog_V alue 79 4202_1 RD Units: V AC [...]

  • Pagina 353

    BACnet Communications - UPS Systems 347 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MultiModule Multi-module System Output V o ltage RM S A-B Analog_V alue 155 480 1_1 RD Un its: V AC Multi-module System Output V o ltage RM S B-C Analog_V alue 156 4802_1 RD Units: V AC Multi-module System Output V o ltage RM S C-A Analog_V a lue 157 4803_1 RD Units[...]

  • Pagina 354

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 348 Ta b l e 11 2 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—Multist ate Data Data Label Object T ype Instance Object Name Access Notes Input Input Qualification S tatus MultiS tate_V alue 1 4735_1 RD 1 = Fail 2 = Marginal Low 3 = Normal 4 = Margina[...]

  • Pagina 355

    BACnet Communications - UPS Systems 349 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System UPS Module T ype MultiS tate_V alue 87 4303_1 RD 1 = Single Module System 2 = Module (1 + 1) 3 = Module (1 + N) 4 = Module (N + 1) 5 = System Control Cabinet 6 = Main S tatic Switch Bypass Input Wire Configuration MultiS tate_V alue 88 4304_1 RD 1 = T wo Wire[...]

  • Pagina 356

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 350 Configuration Descri ption MultiS tate_V alue 91 4751_1 RD 1 = Single Module System 33 2 = Single Module System 34 3 = Single Module System 44 4 = 1+1 33 5 = 1+1 34 6 = 1+1 44 7 = 1+N 33 8 = 1+N 34 9 = 1+N 44 10 = N+1 33 1 1 = N+1 34 12 = N+1 44 13 = SCC w/ Continuou[...]

  • Pagina 357

    BACnet Communications - UPS Systems 351 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ratings Input Isolation Transformer Mu ltiS tate_V alue 109 4266_1 RD 1 = Not Installed 2 = Installed Device S tatu s Backfeed Breaker MultiSt ate_V alue 120 47 64_1 RD 1 = Open 2 = Close 3 = Not Installed SBS Load Disconnect MultiS t ate_V alue 121 4765_1 RD 1 = Op[...]

  • Pagina 358

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 352 Module Output Breaker for Module 7 MultiSt ate_V alue 147 4842_ 1 RD 1 = Open 2 = Close 3 = Not Installed Module Output Breaker for Module 8 MultiSt ate_V alue 148 4843_ 1 RD 1 = Open 2 = Close 3 = Not Installed Bypass Isolation Breaker for Module 1 MultiS tate_V alu[...]

  • Pagina 359

    BACnet Communications - UPS Systems 353 Liebert ® IntelliSlot ® Mo dbus/BACnet IP ModuleList 1 MMS Inter-M odule Comm S tatus MultiS tate_V alue 173 4856_1 RD 1 = Failed 2 = Normal MMS Event Summary MultiS tate_V alue 174 4857_1 RD 1 = None 2 = Alarm 3 = Fault MMS Module I nverter S tatus MultiS tate_V alue 175 4858_1 RD 1 = off 2 = on MMS Module[...]

  • Pagina 360

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 354 ECO Mode ECO Mode Operation S tate MultiS tate_V alue 3 04 5454_1 RW 1 = disabled 2 = enabled Continuous Operation - ECO Mode MultiSt ate_V alue 305 5455_1 RD 1 = disabled 2 = enabled ECO Mode - EcoModeSchedule 1 Schedule Operation St ate - ECO Mode Mu ltiS tate_V al[...]

  • Pagina 361

    BACnet Communications - UPS Systems 355 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ta b l e 11 3 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—Glossary Data Label Data Description Auto Restart In Progress Au to restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal Auto Retransfer T [...]

  • Pagina 362

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 356 Battery V olts at Main Disconnect The voltage between the positive and the negative battery terminals of the common battery disconnect Battery V olts for Cabinet The voltage between the positive and ne gative battery terminals of a battery cabinet Bypass - Manual Rex[...]

  • Pagina 363

    BACnet Communications - UPS Systems 357 Liebert ® IntelliSlot ® Mo dbus/BACnet IP ECO Mode Operation S tate This setting is used to enable or disable ECO Mode. ECO Mode Suspend ed ECO Mode session is suspe nded. EMO Shutdown An Emerge ncy Module Off command has been detected. Equipment T emperature Sensor Fail One or more te mperature sensors rep[...]

  • Pagina 364

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 358 Inverter Overload Phase C Inverter is operating with an overload on phase C Inverter Overload Time Remaining The calculated time remaining before inverter shutdown Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload Inverter S tatic Swi[...]

  • Pagina 365

    BACnet Communications - UPS Systems 359 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS Output Power The sum to tal power of all system output modules MMS Overload Multi-module system overload MMS UPS Output Source Multi-module UPS output source Module Output Breaker for Module 1 Mod ule output breaker for module 1 Module Output Breaker for Module [...]

  • Pagina 366

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 360 Program Input Contact 03 When the signal from [Program Input Cont act 03] is active the function assi gned to this contact is executed. Program Input Contact 04 When the signal from [Program Input Cont act 04] is active the function assi gned to this contact is execu[...]

  • Pagina 367

    BACnet Communications - UPS Systems 361 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Sum of MMS Output RMS Current s for Phase A The sum of the multi-module syste m output RMS currents for phase A Sum of MMS Output RMS Current s for Phase B The sum of the multi-module syste m output RMS currents for phase B Sum of MMS Output RMS Current s for Phase [...]

  • Pagina 368

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 362 System Output Pct Pwr (V A) Phs B The system output apparent power on phase B as a percentage of the rated capacity System Output Pct Pwr (V A) Phs C The system output apparent power on phase C as a percentage of the rated capacity System Output Power Factor Phs A Th[...]

  • Pagina 369

    BACnet Communications - UPS Systems 363 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Notes[...]

  • Pagina 370

    BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 364[...]

  • Pagina 371

    [...]

  • Pagina 372

    While eve r y precaution has been take n to ensure the accuracy and complete ness of this litera ture, Liebert Corporation assume s no responsibility and disclaims all liability for damages re sulting from use of this inform ation or for any errors or omissions. © 2013 Liebert Corporation All rights reserved throughout the world. Specifications su[...]