Energy Tech Laboratories EDP70 manuale d’uso
- Visualizza on-line o scarica il manuale
- 65 pagine
- 1.78 mb
Vai alla pagina of
Manuali d’uso simili
-
Heat Pump
Energy Tech Laboratories 6356
20 pagine 1.54 mb -
Power Supply
Energy Tech Laboratories EDP70
65 pagine 1.78 mb -
Boiler
Energy Tech Laboratories F3
52 pagine 4.18 mb -
Heat Pump
Energy Tech Laboratories 8357
20 pagine 1.54 mb -
Air Conditioner
Energy Tech Laboratories DHG180
28 pagine 0.45 mb -
Fan
Energy Tech Laboratories LB300
32 pagine 1.04 mb -
Air Conditioner
Energy Tech Laboratories DHG240
28 pagine 0.45 mb -
Refrigerator
Energy Tech Laboratories ZISW360DR
1 pagine 0.09 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Energy Tech Laboratories EDP70. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Energy Tech Laboratories EDP70 o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Energy Tech Laboratories EDP70 descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso Energy Tech Laboratories EDP70 dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Energy Tech Laboratories EDP70
- nome del fabbricante e anno di fabbricazione Energy Tech Laboratories EDP70
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Energy Tech Laboratories EDP70
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Energy Tech Laboratories EDP70 non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Energy Tech Laboratories EDP70 e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Energy Tech Laboratories in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Energy Tech Laboratories EDP70, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Energy Tech Laboratories EDP70, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Energy Tech Laboratories EDP70. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
EDP70 PLUS UNINTERRUPTIBLE POWER SYSTEM 24/36/50/80kVA – 3 phase input / 3 phase output USER HANDBOOK PART NUMBER 10H52152PU9C rev.1[...]
-
Pagina 2
page 2 -- MI00/10056 rev.1--05/2001 IMPORTANT SAFETY INSTRUCTIONS READ BEFORE INSTALLING 1) SAVE THESE INSTRUCTIONS This manual contains important instructions for the EDP70 PLUS which should be followed during installation and maintenance of the UPS and associated batteries. 2) The installation must be inspected by trained technicians. The instruc[...]
-
Pagina 3
MI00/10056 rev.1--05/2001-- page 3 WARNING The UPS contains hazardous voltages, even when all switches are open. In case of fire in the installation area, do not use water to extinguish fire. ELECTRICAL PRECAUTIONS: If the UPS is in By-pass mode and the Output switch is closed, no indications will be displayed; fans will however function, and hazar[...]
-
Pagina 4
page 4 -- MI00/10056 rev.1--05/2001 Contents 1.0 INTRODUCTION ................................................................................................................ 6 1.1 Su mmary of the manual ................................................................................................ 6 1.2 Summary of the equipment ..................[...]
-
Pagina 5
MI00/10056 rev.1--05/2001-- page 5 Figures Figure 1 – Block diagrams – 24/36kVA .................................................................................... 7 Figure 2 – Block diagram – 50/80kVA ...................................................................................... 8 Figure 3 – Normal operation ....................[...]
-
Pagina 6
page 6 -- MI00/10056 rev.1--05/2001 1.0 INTRODUCTION 1.1 Summary of the manual This handbook provides for the safe installation, startup and use of the EDP70 PLUS Uninterruptible Power System (UPS). The Company recommends that the equipment be installed and regularly maintained by a Chloride Authorized personnel. DO: - read the User Handbook before[...]
-
Pagina 7
MI00/10056 rev.1--05/2001-- page 7 Figure 1 – Block diagrams – 24/36kVA 24kVA - STANDARD CONFIGURATION Battery Contactor 36kVA - STANDARD CONFIGURATION Battery Contactor 36kVA - 480V/208V CONFIGURATION Battery Contactor S3 S3 IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESRVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS[...]
-
Pagina 8
page 8 -- MI00/10056 rev.1--05/2001 Figure 2 – Block diagram – 50/80kVA The uninterruptible power system consists of the following: 1 - RECTIFIER/INVERTER S1 = Equipment ON/OFF switch 2 - BATTERY S2 = Equipment Reserve switch 3 - BACKFEED PROTECTION S3 = Equipment By-pass switch 4 - INVERTER STATIC SWITCH S4 = Equipment OUTPUT switch 5 - RESERV[...]
-
Pagina 9
MI00/10056 rev.1--05/2001-- page 9 1.5 Operational modes Figure 3 – Normal operation During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies the current for recharging and maintaining the battery in a fully charged state. Figure 4 – Utility Supply failure When the utility supply [...]
-
Pagina 10
page 10 -- MI00/10056 rev.1--05/2001 Figure 5 – Re-establishing the Utility Supply When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will re[...]
-
Pagina 11
MI00/10056 rev.1--05/2001-- page 11 2.0 SAFETY Read all instructions carefully before installing or operating the equipment. 2.1 General safety The procedure described in these instructions is intended for use by persons experienced in the operation of Uninterruptible Power Systems and ancillary equipment. Persons unfamiliar with this type of equip[...]
-
Pagina 12
page 12 -- MI00/10056 rev.1--05/2001 Page Right Control For explanation see Para. 6.2. of this manual Record Up For explanation see Para. 6.2. of this manual Record Down For explanation see Para. 6.2. of this manual 2.3 Electrical precautions Never handle a component or assembly without first confirming that no voltage is applied or present. Remove[...]
-
Pagina 13
MI00/10056 rev.1--05/2001-- page 13 3.0 STORAGE If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is du[...]
-
Pagina 14
page 14 -- MI00/10056 rev.1--05/2001 Figure 7 – 24 Footprint and cabinet dimensions ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES) 600,0 (25.39) 30,0 (1.18) 645,0 260 (10.24) X 66 (2.6) ( ø 0 , 3 1 ) (23.62) NR 4 X ø 8 CABLE ENTRY 726,0 (28.58) 58,0 (2.28) 1417,0 (55.79) 700,0 (27.56) (2.64) 67,0 63,0 (2.48) 728,0 (28.66) (26.77) 680,0[...]
-
Pagina 15
MI00/10056 rev.1--05/2001-- page 15 Figure 8 – 36 Footprint and cabinet dimensions 50,0 ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES) 600,0 (25.39) (1.18) 645,0 30,0 (23.62) 125,0 NR 4 X ( ø 0 , 3 1 ) ø 8 (4.92) 1417,0 (55.79) 700,0 (27.56) CABLE ENTRY 500 (19.68) X 110 (4.33) (1.97) (28.66) 728,0 88,0 (3.46) (26.77) 680,0[...]
-
Pagina 16
page 16 -- MI00/10056 rev.1--05/2001 Figure 9 – 50/80 Footprint and cabinet dimensions 50,0 ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES) 800,0 (25.39) (1.18) 645,0 30,0 (31.5) 100,0 NR 4 X ø 8 ( ø 0 , 3 1 ) (3.94) 1600 (63.0) 900,0 (35.43) 700 (27.56) X 110 (4.33) CABLE ENTRY (1.97) (2.68) 68,0 740,0 (29.13)[...]
-
Pagina 17
MI00/10056 rev.1--05/2001-- page 17 Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings[...]
-
Pagina 18
page 18 -- MI00/10056 rev.1--05/2001 Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings[...]
-
Pagina 19
MI00/10056 rev.1--05/2001-- page 19 Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings[...]
-
Pagina 20
page 20 -- MI00/10056 rev.1--05/2001 Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings[...]
-
Pagina 21
MI00/10056 rev.1--05/2001-- page 21 4.2 Installation Check the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/output voltages, frequency and load are all within the rating of the UPS. EDP70 PLUS is designed to operate in an office environment with an optimum temperature of 68 ° F [20 C]. A gap of at least 4In[...]
-
Pagina 22
page 22 -- MI00/10056 rev.1--05/2001 Recommended wire sizes 1) It is recommended that the external cables and protection be selected for the highest rated unit of the model in use. 2) Reserve (or primary) input and output Neutral cable size should be greater than that of the line cables in order to be able to supply non-linear loads having a Crest [...]
-
Pagina 23
MI00/10056 rev.1--05/2001-- page 23 A.C. Supply Reserve Supply UPS Type V in /V out Rated current (A) Protection device (A) Output Nominal current (A) Nominal current (A) Protection device (A) 24/12kVA 42 50 33 33 50 24/18kVA 60 80 50 50 75 24/24kVA 208/208 78 100 67 67 100 36/24kVA 78 100 67 67 100 36/30kVA 97 100 83 83 125 36/36kVA 208/208 118 12[...]
-
Pagina 24
page 24 -- MI00/10056 rev.1--05/2001 4.4 Ventilation UPS can work in a continuous environment within 18 ° F[-10 ° C] to 104 ° F [+40 ° C ] temperature range, although, ideally the ambient temperature should be below 78 ° F [25 ° C]. The heat, dissipated by the UPS (indicated on figure 7), is extracted by internal fans and then dissipated into[...]
-
Pagina 25
MI00/10056 rev.1--05/2001-- page 25 5.0 CONNECTION Figure 15 – Connection diagrams THE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH CIRCUIT PROTECTION. NOTE: INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN GR[...]
-
Pagina 26
page 26 -- MI00/10056 rev.1--05/2001 UNINTERRUPTIBLE POWER SYSTEM NO UNAUTHORIZED OPERATION[...]
-
Pagina 27
MI00/10056 rev.1--05/2001-- page 27 CAUTION! WARNING! All power connection must carried out by qualified licensed personnel experienced in wiring this type of equipment The safety ground wire must be connected before the power input cables The correct phase rotation (phase A leads B leads C) must be observed on the UPS terminals. An input grounded [...]
-
Pagina 28
page 28 -- MI00/10056 rev.1--05/2001 5.1 Electrical connec tions WARNING! All electrical connections must be made by a qualified electrician and meet local electrical code standards Before attempting to connect the mains supply, the reserve/bypass supply or the load, ensure that all supplies, including the battery, are isolated and that all the equ[...]
-
Pagina 29
MI00/10056 rev.1--05/2001-- page 29 5.2 24 – 12/18/24kVA Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see Figure 16 . The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure t[...]
-
Pagina 30
page 30 -- MI00/10056 rev.1--05/2001 Figure 17 - 24 – 12/18/24kVA: Switches Access to the terminals for electrical connections is as follows: a) Remove front panel see Figure 16 . b) Remove the two securing screws for the hinged front panel. c) This exposes the electrical terminal rail, see Figure 18 d) Remove the screws securing the access pl at[...]
-
Pagina 31
MI00/10056 rev.1--05/2001-- page 31 Figure 18 - 24 – 12/18/24kVA: Cable Connections Modem and Multicom power supplies V1 U1 W1 N PE U V W N V2 U2 N W2 RESERVE INPUT GROUND M6 sec. max 14 AWG PRIMARY INPUT OUTPUT EXTERNAL BATTERIES Battery Charger Inhibited E.P.O. FRONT Label REAR Computer relay interface - FEMALE RAU - FEMALE RS232 - MALE[...]
-
Pagina 32
page 32 -- MI00/10056 rev.1--05/2001 5.3 36 – 24/30/36kV A Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see figure 13. The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure [...]
-
Pagina 33
MI00/10056 rev.1--05/2001-- page 33 Figure 20 - 36 – 24/30/36kVA: Connections Access to the terminals for electrical connections is as follows: a) Remove front panel see Figure 20 . b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front. c) This exposes the electrical terminal rail, see Figure 21 d) Remove the[...]
-
Pagina 34
page 34 -- MI00/10056 rev.1--05/2001 Figure 21 - 36 – 24/30/36kVA: Cable Connections QS4 Modem and Multicom power supplies NEUTRAL (RES/OUT) W2 U1 PE U V W N U2 V2 V1 W1 PRIMARY INPUT GROUND EXTERNAL BATTERIES RESERVE INPUT OUTPUT QS1 FRONT QS2 E.P.O. Battery charge inhibited QS3 RAU - FEMALE RS232 - FEMALE Computer relay interface - FEMALE REAR[...]
-
Pagina 35
MI00/10056 rev.1--05/2001-- page 35 5.3 EDP70 PLUS 50/80kVA Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see figure 16. The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure t[...]
-
Pagina 36
page 36 -- MI00/10056 rev.1--05/2001 Figure 23 – 50/80kVA: Connections Access to the terminals for electrical connections is as follows: a) Remove front panel see Figure 20 . b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front. e) This exposes the electrical terminal rail, see Figure 21 f) Remove the screws[...]
-
Pagina 37
MI00/10056 rev.1--05/2001-- page 37 Figure 24 – 50/80kVA: Cable Connections Modem and Multicom power supplies RAU - FEMALE Computer relay interface - FEMALE RS232 - MALE QS3 RESERVE INPUT PRIMARY INPUT EXTERNAL BATTERIES QS1 U U1 V1 W1 V W QS2 FRONT E.P.O. OUTPUT Battery charge inhibited Thermostick contacts QS5 1 2 3 4 5 6 W2 N N U2 V2 PE QS4 RE[...]
-
Pagina 38
page 38 -- MI00/10056 rev.1--05/2001 5.4 Sig nal connections a) Emergency Power Off When the connection between terminals 1 and 2 is opened, the UPS will stop, and it will automatically restart when the switch is closed. This allows a remote E.P.O. to be installed, in series with the standard one installed inside the UPS. (See Para. 9.1) Warning: T[...]
-
Pagina 39
MI00/10056 rev.1--05/2001-- page 39 6.0 CONTROLS 6.1 User Controls The user controls are situated on the front panel, see Figure 25 . Access to the Equipment Power Switches can be obtained by removing the front cover. Figure 25 – Control panel Illuminated Liquid Crystal Display User Switches Audible Alarm Cancel Switch Inverter Start Inverter Sto[...]
-
Pagina 40
page 40 -- MI00/10056 rev.1--05/2001 6.2 Control Panel Inverter Start Up This allows the user to turn on and reset the inverter. This is normally only used when starting the UPS. Inverter Shutdown The switch incorporates a safety feature to prevent inadvertent operation yet still allow rapid shutdown in the event of an emergency. This is achieved b[...]
-
Pagina 41
MI00/10056 rev.1--05/2001-- page 41 7.0 START UP 1. Switch on the AC reserve and the main AC Utility supply to the UPS. 2. Turn on the Utility s upply Input, Reserve Input (if fitted) and UPS Output switches located behind the front panel, see figure 14 for 24kVA, figure 17 for 36kVA or figure 20 for 50/80kVA. 3. Replace the front panel. 4. Press t[...]
-
Pagina 42
page 42 -- MI00/10056 rev.1--05/2001 8.0 MAINTENANCE BYPASS The EDP70 PLUS UPS is equipped with Manual Maintenance Bypass systems. If a unit requires servicing, the Manual Maintenance Bypass allows the load to be connected directly to the AC supply so that the unit may be serviced in safety. The following instructions must be followed: 1. Ensure th[...]
-
Pagina 43
MI00/10056 rev.1--05/2001-- page 43 To ensure that the EPO functions correctly, the signal should remain active for a period > 400 msec.[...]
-
Pagina 44
page 44 -- MI00/10056 rev.1--05/2001 10.0 VISUAL AND AUDIBLE ALARMS The EDP70 PLUS UPS is equipped with visual and audible alarms which indicate the status of the UPS to the operator. The visual alarms are displayed on the LCD and the mimic panel. 10.1 Silencing Audible Alarm The audible alarm sounds when the UPS is in an alarm condition. The sound[...]
-
Pagina 45
MI00/10056 rev.1--05/2001-- page 45 10.4 Display Page Headings After initial power up, under normal operating conditions, the main page heading will be displayed: UPS xx KVA SYSTEM NORMAL The first line displays the power rating of the EDP70 PLUS UPS, the second line is the system status. During normal operating conditions, the display reading alwa[...]
-
Pagina 46
page 46 -- MI00/10056 rev.1--05/2001 By pressing the button marked again, the selected battery test period appears on the display: BATTERY TEST WEEKLY The button marked is pressed to scroll through the 4 battery test period available (WEEKLY, FORTNIGHTLY, MONTHLY and NONE). The button marked is pressed to scroll through the list in reverse order. W[...]
-
Pagina 47
MI00/10056 rev.1--05/2001-- page 47 If at any time the inverter is blocked then the power history heading appears: POWER HISTORY DOWN TO ACCESS The power history page is described in detail in section 10.6. The machine measurement signals are accessed from the main page heading as follows: UPS xx kVA SYSTEM NORMAL press once RECTIFIER Vdc xxx V Idc[...]
-
Pagina 48
page 48 -- MI00/10056 rev.1--05/2001 RESERVE F xx.x Hz AB xxx V BC xxx V CA xxx V Displays the frequency and the phase-phase voltage of the reserve supply. press once LOAD F xx.x Hz A xxx V B xxx V C xxxV Displays the frequency and phase-neutral voltage supplied to the load. press once LOAD F xx.x Hz AB xxx V BC xxx V CA xxxV Displays the frequency[...]
-
Pagina 49
MI00/10056 rev.1--05/2001-- page 49 TIME ON RESERVE xxg: xxh: xxm: xxs Displays the total time the load has been supplied by the reserve since the machine was last switched off. press once LAST MAINS FAILURE xxd: xxh: xxm: xxs Displays the duration time of the most recent Mains Failure press once MAINS FAILURE yy xxgg: xxh: xxm: xxs Displays the nu[...]
-
Pagina 50
page 50 -- MI00/10056 rev.1--05/2001 The measurement signals are accessed from the battery rectifier page as follows: RECT/BATT ALARMS NO ALARMS ACTIVE Normal operating mode press once RECTIFIER Vdc xxx V Idc xxx A Displays the output voltage and current supplied by the rectifier. press once BATTERY Vdc xxx V Ib xxxx A Displays the battery voltage [...]
-
Pagina 51
MI00/10056 rev.1--05/2001-- page 51 The measurement signals are accessed from the load output - reserve supply page as follows: LOAD/RES ALARMS NO ALARMS ACTIVE Normal operating mode press once LOAD f xx.x Hz A xxx V B xxx V C xxx V Displays the frequency and phase-neutral voltage supplied to the load. press once LOAD f xx.x Hz AB xxx V BC xxx V CA[...]
-
Pagina 52
page 52 -- MI00/10056 rev.1--05/2001 10.5 Abnormal operating mode messages Under abnormal operating conditions, the normal functioning heading on the main page UPS xx KVA SYSTEM NORMAL is replaced with the alarm page: UPS xx KVA SYSTEM ALARM If at least 1 alarm is activated for each block; the »NO ALARMS ACTIVE» message in the second line on the [...]
-
Pagina 53
MI00/10056 rev.1--05/2001-- page 53 a) When the battery is discharging, the machine displays the residual autonomy and the discharging time information. 1. If no information on autonomy is available, then the following message is displayed: BATTERY DISCHARGING AUT calc DIS xx min where xx represents the discharging time 2. Where AUTONOMY informatio[...]
-
Pagina 54
page 54 -- MI00/10056 rev.1--05/2001 RECTIFIER/BATTERY ALARMS MESSAGE CONDITION NOT CALIBRATED FAULT DC FEEDBACK FAULT FAULT VERIFY DC FEEDBACK NORMAL PRIMARY SUPPLY FAULT WARNING PHASE SEQUENCE ERROR FAULT BATTERY FAULT FAULT PCB SUPPLY FAULT FAULT BATT CONTACTOR OPEN - BATTERY DISCHARGING WARNING SHUTDOWN IMMINENT WARNING DC VOLTAGE HIGH FAULT DC[...]
-
Pagina 55
MI00/10056 rev.1--05/2001-- page 55 INVERTER ALARMS MESSAGE CONDITION NOT CALIBRATED FAULT PCB SUPPLY FAULT FAULT OUT OF SYNC WARNING DESATURATION FAULT OVER TEMPERATURE FAULT BYPASS SWITCH CLOSED FAULT SHUTDOWN IMMINENT WARNING DC VOLTAGE HIGH FAULT DC VOLTAGE LOW WARNING INVERTER NOT RUNNING FAULT INVERTER INHIBITED FAULT INVERTER BLOCKED FAULT I[...]
-
Pagina 56
page 56 -- MI00/10056 rev.1--05/2001 LOAD/RESERVE ALARMS MESSAGE CONDITION NOT CALIBRATED FAULT LOAD ON RESERVE WARNING LOAD NOT SUPPLIED FAULT BYPASS SWITCH CLOSED FAULT RESERVE SUPPLY FAULT WARNING RESERVE FREQ FAULT WARNING RESERVE VOLTS HIGH WARNING RESERVE VOLTS LOW WARNING ST. SW. BLOCKED ON INV FAULT ST. SW. BLOCKED ON RES FAULT INV.ST. SWIT[...]
-
Pagina 57
MI00/10056 rev.1--05/2001-- page 57 10.6 Power History The power history is only available when the inverter is blocked; it provides a visual display of the status of the alarms and measurements over a period of 10 seconds before and 1 second after the inverter stops in steps of 0.1 s. The power history is lost when the inverter is restarted. Figur[...]
-
Pagina 58
page 58 -- MI00/10056 rev.1--05/2001 10.7 Battery Test The EDP70 PLUS has an automatic battery control function which checks the condition of the battery periodically without affecting the output in any way. While this test is being carried out, the message »TESTING BATTERY» will appear. This test can also be activated manually. Return to the mai[...]
-
Pagina 59
MI00/10056 rev.1--05/2001-- page 59 data has still been lost and the intervention of a qualified technician is required.It is, nevertheless, possible to reset the normal operating mode by selecting the language desired as described under sect. 7.0.[...]
-
Pagina 60
page 60 -- MI00/10056 rev.1--05/2001 11.0 COMPUTER INTERFACE 11.1 AS400 The EDP70 PLUS UPS is fitted with a 9 pin female ‘D’ type socket for direct connection to a IBM AS/400 computer or equivalent, see figure 21. This facility can also be used with operating system software of other manufacturers. The function of the pins on the socket[...]
-
Pagina 61
MI00/10056 rev.1--05/2001-- page 61 11.2 RS232 The EDP70 PLUS UPS is fitted with a 9 pin male ‘D’ type plug which enables a communication link to be established between a computer and the microprocessor controller in the EDP70 PLUS UPS. The link allows the Chloride ‘EASY PLUS’ and ‘LIFE 2000’ software to be run on an IBM compatible PC. [...]
-
Pagina 62
page 62 -- MI00/10056 rev.1--05/2001 13.0 BATTERIES 13.1 EDP70 PLUS/24/18/12 : Battery Installation/Start-up SAFETY - Ensure all the Switches are turned to OFF before starting to install the batteries. If any Switches are not turned to OFF the equipment and battery may be damaged. It is also essential for safety reasons that the battery connectors [...]
-
Pagina 63
MI00/10056 rev.1--05/2001-- page 63 13.2 EDP70 PLUS/24/18/12 : Optional Battery Cubicle The battery autonomy can be increased by employing either one or two optional battery cubicles. Both the UPS and battery cubicles are similar in appearance, however, there is no display panel in the battery cubicle. The battery cubicle has independent fuse locat[...]
-
Pagina 64
page 64 -- MI00/10056 rev.1--05/2001 13.3 EDP70 PLUS above 20kVA: Battery Installation/Start-up SAFETY - En sure the Equipment ON/OFF Switch is turned to OFF before starting to install the batteries. If the Equipment ON/OFF Switch is not turned to OFF the equipment and battery may be damaged. It is also essential for safety reasons that the battery[...]
-
Pagina 65
MI00/10056 rev.1--05/2001-- page 65 EDP70 PLUS SYSTEM LOG It is recommended that any maintenance action or failure of the SYSTEM be recorded in this log. Date Time Event Action/Result[...]