Hearth and Home Technologies 8000CFLP-OAKIPI manuale d’uso
- Visualizza on-line o scarica il manuale
- 62 pagine
- 3.5 mb
Vai alla pagina of
Manuali d’uso simili
-
Indoor Fireplace
Hearth and Home Technologies NBV3933
56 pagine 4.26 mb -
Indoor Fireplace
Hearth and Home Technologies QV32E (120V)
24 pagine 1.45 mb -
Indoor Fireplace
Hearth and Home Technologies 42H-B
36 pagine 6 mb -
Indoor Fireplace
Hearth and Home Technologies LCOR-HVB-IPI
41 pagine 2.29 mb -
Indoor Fireplace
Hearth and Home Technologies CD4236LR
80 pagine 8.29 mb -
Indoor Fireplace
Hearth and Home Technologies SILH50ENH
28 pagine 1.41 mb -
Indoor Fireplace
Hearth and Home Technologies GO35-IPI-LP
27 pagine 9.54 mb -
Indoor Fireplace
Hearth and Home Technologies CUMBGAP-PMH
36 pagine 5.25 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Hearth and Home Technologies 8000CFLP-OAKIPI. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Hearth and Home Technologies 8000CFLP-OAKIPI o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Hearth and Home Technologies 8000CFLP-OAKIPI descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso Hearth and Home Technologies 8000CFLP-OAKIPI dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Hearth and Home Technologies 8000CFLP-OAKIPI
- nome del fabbricante e anno di fabbricazione Hearth and Home Technologies 8000CFLP-OAKIPI
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Hearth and Home Technologies 8000CFLP-OAKIPI
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Hearth and Home Technologies 8000CFLP-OAKIPI non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Hearth and Home Technologies 8000CFLP-OAKIPI e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Hearth and Home Technologies in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Hearth and Home Technologies 8000CFLP-OAKIPI, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Hearth and Home Technologies 8000CFLP-OAKIPI, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Hearth and Home Technologies 8000CFLP-OAKIPI. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 1 • DO NOT store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance. • What to do if you smell gas - DO NOT try to light any appliance. - DO NOT touch any electrical switch. DO NOT use any phone in your building. - Immediately[...]
-
Pagina 2
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 2 Listing Label Information/Location Model Name: ___________________________________________ Date purchased/installed: __________________ Serial Number: __________________________________________ Location on fi replace: _____________________ Dealership purchased from: ______________[...]
-
Pagina 3
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 3 Safety Alert Key: • DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury . • W ARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury . • CAUTION! Indicates a hazardous situation wh[...]
-
Pagina 4
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 4 = Contains updated information. 13 Finishing A. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 46 B. Facing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 14 Appliance Setup A. Remove Fixed Glass Assembly . . . . . . . .[...]
-
Pagina 5
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 5 B. Limited Lifetime W arranty Hearth & Home T echnologies LIMITED W ARRANTY Hearth & Home T echnologies (“HHT”) and its respective brands extends the following warranty for HHT gas, wood, pellet and electric appliances purchased from an authorized HHT dealer and install[...]
-
Pagina 6
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 6 B. Limited Lifetime W arranty (continued) • This limited warranty does not extend to or include surface fi nish on the appliance or terminations, door gasketing, glass gasketing, glass discoloration, fi rebrick, pellet logs, kaowool or other ceramic insulating materials. Rust a[...]
-
Pagina 7
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 7 B. T empered Glass Speci fi cations Hearth & Home T echnologies appliances manufactured with tempered glass may be installed in hazardous loca- tions such as bathtub enclosures as de fi ned by the Con- sumer Product Safety Commission (CPSC). The tempered glass has been tested[...]
-
Pagina 8
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 8 H. Requirements for the Commonwealth of Massachusetts For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the[...]
-
Pagina 9
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 9 Figure 2.1 General Operating Parts B. Y our Fireplace W ARNING! DO NOT operate fi replace before read- ing and understanding operating instructions. Failure to operate fi replace according to operating instructions could cause fi re or injury . DECORA TIVE DOORS (NOT SHOWN) SECT[...]
-
Pagina 10
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 10 D. Clear Space W ARNING! DO NOT place combustible objects in front of the fi replace or block louvers. High temperatures may start a fi re. See Figure 2.2. Avoid placing candles and other heat-sensitive objects on mantel or hearth. Heat may damage these objects. Figure 2.2 Clear[...]
-
Pagina 11
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 1 1 I. Lighting Instructions (IPI) The IPI system may be operated with two D-cell batteries. When using batteries, unplug the transformer . T o prolong battery life, remove them when using the transformer . 1. Turn off all electric power to the appliance. 2. This appliance is equippe[...]
-
Pagina 12
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 12 Initial Break-in Procedure • The fireplace should be run three to four hours continuously on high. • T urn the fi replace off and allow it to completely cool. • Remove fi xed glass assembly . See Section 14.I. • Clean fi xed glass assembly . See Section 3. • Replace t[...]
-
Pagina 13
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 13 Glass Cleaning Frequency: Seasonally By: Homeowner T ools Needed : Protective gloves, glass cleaner , drop cloth and a stable work surface. CAUTION! Handle fi xed glass assembly with care. Glass is breakable. • Avoid striking, scratching or slamming glass • Avoid abrasive cle[...]
-
Pagina 14
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 14 V enting Frequency: Seasonally By: Homeowner T ools needed: Protective gloves and safety glasses. • Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow , debris, etc. • V erify termination cap clearance to subsequent construc- [...]
-
Pagina 15
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 15 (Either cobrahead or SIT) Figure 3.1 IPI Pilot Flame Patterns[...]
-
Pagina 16
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 16 A. T ypical Appliance System NOTICE: Illustrations and photos re fl ect typical installations and are for design purposes only . Illustrations/diagrams are not drawn to scale. Actual product may vary from pictures in manual Figure 4.1 T ypical System Note: Dual venting conf igura[...]
-
Pagina 17
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 17 B. Design and Installation Considerations Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required. Installation MUST [...]
-
Pagina 18
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 18 5 5 F raming and Clearances A. Selecting Appliance Location When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure 5.1). W ARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service ac[...]
-
Pagina 19
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 19 C B D A B. Constructing the Appliance Chase A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase. NOTICE: T reatment of ceiling fi restops and wall shield fi restops an[...]
-
Pagina 20
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 20 D. Mantel and W all Projections W ARNING! Risk of Fire! Comply with all minimum clear- ances as speci fi ed. Framing or fi nishing material closer than the minimums listed must be constructed entirely of noncom- bustible materials (i.e., steel studs, concrete board, etc). Figure[...]
-
Pagina 21
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 21 Figure 6.3 Leveled T ermination Caps A. V ent T ermination Minimum Clearances Roof Pitch H (Min.) Ft. Flat to 6/12...........................................................1.0* Over 6/12 to 7/12 .................................................1.25* Over 7/12 to 8/12 ............[...]
-
Pagina 22
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 22 O N P R Q V = VENT TERMINAL X = AIR SUPPL Y INLET = AREA WHERE TERMINAL IS NOT PERMITTED Figure 6.4 Minimum Clearances for T ermination A = 12 inches................. clearances above grade, ver anda, porch, deck or balcony B = 12 inches................. clearances to window or do[...]
-
Pagina 23
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 23 A. Approved Pipe This appliance is approved for use with Hearth & Home T echnologies DVP venting systems. Refer to Section 16B for vent component information. DO NOT mix pipe, fi ttings or joining methods from differ- ent manufacturers. The pipe is tested to be run inside an [...]
-
Pagina 24
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 24 INST ALLED HORIZONT ALL Y H 1 H 2 V 1 H 1 V 1 Figure 7.3 Figure 7.4 One Elbow T wo Elbows T op V ent - Horizontal T ermination V 1 Minimum H 1 Maximum 1 ft.. 305 mm 3 ft.. 914 mm 2 ft.. 610 mm 6 ft. 1.8 m 3 ft. 914 mm 9 ft. 2.7 m 4 ft. 1.2 m 12 ft. 3.7 m V 1 + H 1 = 40 ft. (12.2 m[...]
-
Pagina 25
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 25 Figure 7.5 T op V ent - Horizontal T ermination - (continued) Three Elbows H 2 H 1 V 2 V 1 V 1 Min. H 1 Max. V 2 Min. H 2 Max. V 1 + V 2 Min. H 1 + H 2 Max. 1 ft. 305 mm 3 ft. 914 mm 1 ft. 305 mm 3 ft. 914 mm 2 ft. 610 mm 6 ft. 1.8 m 2 ft. 610 mm 6 ft. 1.8 m 2 ft. 610 mm 6 ft. 1.8[...]
-
Pagina 26
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 26 T op V ent - V ertical T ermination No Elbow Figure 7.6 Note: If installing a vertical vent/termination of f the top of the appliance, the fl ue restrictor should be used. V 1 V 1 = 50 ft. Max. (15.2 m) V 1 = 3 ft. Min. (914 mm) Installing the fl ue restrictor Figure 7.7 FLUE RE[...]
-
Pagina 27
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 27 Figure 7.1 1 T wo Elbows H 1 V 1 V 2 V 1 H 1 Maximum V 2 V 1 + V 2 Minimum 1 ft. 305 mm 3 ft. 914 mm * * * 2 ft. 610 mm 6 ft. 1.8 m * * * 4 ft. 1.2 m 12 ft. 3.7 m * * * V 1 + V 2 + H 1 = 50 ft. (15.2 m) Max. *No speci fi c restrictions on this value EXCEPT V 1 + V 2 + H 1 cannot [...]
-
Pagina 28
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 28 A. Pipe Clearances to Combustibles W ARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles: • Between ceiling fi restops • Between wall shield fi restops • Around vent system Failure to keep insulation or other material aw[...]
-
Pagina 29
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 29 A 12 in. 10 in. B Figure 8.6 W all Penetration B. W all Penetration Framing A* B 57-1/2 in. 56-1/2 in. Figure 8.5 Horizontal V enting Clearances to Combustible Materials 3 IN. TOP CLEARANCE HEA T SHIELD HEA T SHIELD WA LL WA LL SHIELD FIRESTOP 1 IN. CLEARANCE BOTTOM SIDES Note: He[...]
-
Pagina 30
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 30 C. Install the Ceiling Firestop A ceiling fi restop MUST be used between fl oors and attics. • DVP pipe only - Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever the vent penetrates a ceiling/ fl oor (see Figure 8.7). • Frame the area with the same sized lumber a[...]
-
Pagina 31
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 31 D. Install Attic Insulation Shield W ARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home T echnologies Inc. requires the use of an attic shield. The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26[...]
-
Pagina 32
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 32 A. Attaching Sheetrock Ledges Attach sheetrock ledges together using the attachment holes (see Figure 9.1). Figure 9.1 The sheetrock ledges will attach to the top of the unit (see Figure 9.2). Figure 9.2 Attach previous assembly to the top of the unit using the provided slots. The[...]
-
Pagina 33
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 33 C. Securing and Leveling the Appliance W ARNING! Risk of Fire! Prevent contact with: • Sagging or loose insulation • Insulation backing or plastic • Framing and other combustible materials Block openings into the chase to prevent entry of blown- in insulation. Make sure insu[...]
-
Pagina 34
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 34 PILOT PLA TE Figure 9.8 Note: E n s u r e p i l o t p l a t e i s i n p l a c e . T h i s w i l l e n s u r e p i l o t stabilit y ( see Figure 9.8) F . Checking Pilot Plate Figure 9.7 Re-install grate in unit RE-INSTALL INTO THE UNIT E. Completing Grate Set-up 1. Straighten the t[...]
-
Pagina 35
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 35 1 0 10 Installing V ent Pipe A. Assemble V ent Sections Attach V ent to the Firebox Assembly Note: The end of t he pipe secti ons with the lanc ed tabs wi ll face toward the applianc e. Attach the fi rst pipe section to the starting collar: • Lanced pipe end to the starting col[...]
-
Pagina 36
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 36 B. Assemble Slip Sections • Slide the inner fl ue of the slip section into the inner fl ue of the pipe section and the outer fl ue of the slip section over the outer fl ue of the pipe section. See Figure 10.6. • Slide together to the desired length. Figure 10.6 Slip Sectio[...]
-
Pagina 37
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 37 D. Disassemble V ent Sections • Rotate either section (see Figure 10.10) so the seams on both pipe sections are aligned as shown in Figure 10.1 1. • Pull carefully to separate the pieces of pipe. Figure 10.1 1 Align and Disassemble V ent Sections Figure 10.10 Rotate Seams for [...]
-
Pagina 38
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 38 E. Install Metal Roof Flashing Note : Skip this section if using the RF4-8. • See minimum vent heights for various pitched roofs (Figure 10.14) to determine the length of pipe to extend through the roof. • Slide the roof fl ashing over the pipe sections extending through the [...]
-
Pagina 39
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 39 G. Install RF4-8 The RF4-8 may be used in place of the roof fl ashing and storm collar (Sections 10.G. and 10.H.) Pipe must be supported within 12 inches of the roofline using plumbers strapping or an SLP-FS when using the RF4-8 Flashing. Refer to Section 10.D. Secure Vent Sectio[...]
-
Pagina 40
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 40 SCREWS CAULK STORM COLLAR (1 of 3) Figure 10.23 Figure 10.23 TERMINA TION CAP H. Install V ertical T ermination Cap • Attach the vertical termination cap by sliding the inner collar of the cap into the inner fl ue of the pipe section while placing the outer collar of the cap ov[...]
-
Pagina 41
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 41 Figure 10.25 Venting through the wall INTERIOR HEA T SHIELD OR EXTENDED HEA T SHIELD W ALL SHIELD FIRESTOP HEA T SHIELD 1-1/2 IN. (38 MM) MIN. OVERLAP SHEA THING VENT DEPTH FROM BACK OF APPLIANCE T O OUTSIDE SURF ACE OF EXTERIOR WA LL (SEE CHART BELOW) SLIP SECTION CAN BE EXTENDED[...]
-
Pagina 42
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 42 A. Fuel Conversion • Make sure the appliance is compatible with available gas types. • Conversions must be made by a qualified service technician using Hearth & Home T echnologies speci fi ed and approved parts. B. Gas Pressure • Optimum appliance performance requires p[...]
-
Pagina 43
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 43 A. Wiring Requirements NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or , in the absence of local codes, with National Electric Code ANSI/NFP A 70-latest edition or the Canadian Electric Code CSA C22.1. • Wire the appliance junctio[...]
-
Pagina 44
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 44 D. Electrical Service and Repair W ARNING! Risk of Shock! Label all wires prior to dis- connection when servicing controls. Wiring errors can cause improper and dangerous operation. V erify proper operation after servicing. Figure 12.1 Intelli fi re Pilot Ignition (IPI) Wiring Di[...]
-
Pagina 45
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 45 F . W all Switch Installation for Fan (Optional) If the box is being wired to a wall mounted switch for use with a fan (See Figure 12.3): • The power supply for the appliance must be brought into a switch box. • The power can then be supplied from the switch box to the applian[...]
-
Pagina 46
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 46 A. Mantel and W all Projections W ARNING! Risk of Fire! Comply with all minimum clear- ances as speci fi ed. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materi- als (i.e., steel studs, concrete board, etc.) Failure to comply could caus[...]
-
Pagina 47
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 47 1 2 4 6 7 8 10 9 A. Remove Fixed Glass Assembly See Section 14.I. B. Remove the Shipping Materials Remove shipping materials from inside or underneath the fi rebox. C. Clean the Appliance Clean/vacuum any sawdust that may have accumulated inside the fi rebox or underneath in the[...]
-
Pagina 48
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 48 G. Ember Placement W ARNING! Risk of Explosion! Follow ember placement instructions in manual. DO NOT place embers directly over burner ports. Replace ember material annually . Improperly placed embers interfere with proper burner operation. Ember material is shipped with this gas[...]
-
Pagina 49
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 49 H. Install the Log Assembly Log Assembly: LOGS-8OAK If the gas logs have been factory installed they should not need to be positioned. If the logs have been packaged separately , refer to the following instructions. CAUTION: Carefully remove the logs from the packaging. Logs are f[...]
-
Pagina 50
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 50 STEP 5: (SR V2057-723): Mate the top of log 4 with the right metal tab on log 3. The bottom of log 4 should touch the inside face of the right grate tine. 2 3 1 2 3 1 5 4 2 3 5 6 STEP 7: (SR V2057-725): Place log 6 on log 2 as shown. The left end of log 6 should touch the upper kn[...]
-
Pagina 51
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 51 M. Air Shutter Setting Air shutter settings should be adjusted by a quali fi ed ser- vice technician at the time of installation. The air shutter is set at the factory for minimum vertical vent run. Adjust air shutter for longer vertical runs. See Figure 14.6. • Loosen the wing[...]
-
Pagina 52
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 52 1 5 15 T roubleshooting With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a quali fi ed service technician in the diagnosis of a problem and th[...]
-
Pagina 53
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 53 Intelli fi re Ignition System - (continued) Symptom Possible Cause Corrective Action 4. Pilot lights but contin- ues to spark, and main burner will not ignite. (If the pilot continues to spark after the pilot fl ame has been lit, fl ame recti fi cation has not occurred.) A. A [...]
-
Pagina 54
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 54 1 6 16 R eference Mater ials A. Appliance Dimension Diagram Dimensions are actual appliance dimensions. Use for reference only . For framing dimensions and clearances refer to Section 5. Figure 16.1 Appliance Dimensions Location Inches Millimeters J 23-1/2 598 K 39-1/4 996 L 43 10[...]
-
Pagina 55
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 55 B. V ent Components Diagrams Figure 16.2 DVP vent components 10-1/2 in. (267 mm) 10-7/8 in. (276 mm) 45 ° 7-3/8 in. (187 mm) 11-3/8 in. (289 mm) 1-1/4 in. (32 mm) 9-1/4 in. (235 mm) 13-1/4 in. (337 mm) 1/2 in. TYP DVP90ST (90° Elbow) 10 in. (254 mm) 10 in. (254 mm) 1 in. (25 mm)[...]
-
Pagina 56
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 56 DVP-TRAP1 DVP-TRAP2 DVP-TRAPK2 DVP-TRAPK1 DVP-TRAP Horizontal T ermination Cap 15-1/8 in. (384 mm) 12 in. (305 mm) 8 in. (203 mm) Max Effective Length Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4[...]
-
Pagina 57
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 57 13-1/4 in. (367 mm) 24-5/8 in. (625 mm) 27-1/2 in. (127 mm) RF6M Roof Flashing Multi-pak 31 in. (787 mm) 24-5/8 in. (625 mm) 13-1/4 in. (367 mm) RF12M Roof Flashing Multi-pak BEK Trap Ca p Brick Extension 13-3/4 in. (349 mm) 5 in. (127 mm) 13-3/4 in. (349 mm) Cap Shield DRC-RADIUS[...]
-
Pagina 58
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 58 DVP-TB1 BasementVent Cap 12 in. (305 mm) 1-1/2 in. (38 mm) 7-3/8 in. (187 mm) 14 in. (356 mm) 17-3/4 in. (451 mm) 7-1/4 in. 12 in. 305 mm (184 mm) 5-1/4 in. (133 mm) 12-1/2 in. (318 mm) DVP-TVHW VerticalTermination Cap (Highwind) PVK-80 (For use with IPI and DSI appliances only.) [...]
-
Pagina 59
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 59 C. Service Parts Part number list on following page. Service Parts Diagram 8000CF-OAK-IPI Beginning Manufacturing Date: Jan. 2005 Ending Manufacturing Date: ______ Log Set Assembly 6 3 5 1 4 2 7 8 9 10 11 12 13 14 15[...]
-
Pagina 60
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 60 C. Service Parts List 8000CF-OAK-IPI IMPORT ANT : THIS IS DA TED INFORMA TION. When requesting service or replacement parts for your appliance please provide model number and serial number . All parts listed in this manual may be ordered from an authorized dealer . Stocked at Depo[...]
-
Pagina 61
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 61 Intermittent Pilot Ignition V alve Assembly Service Parts V alve Assembly Diagram/ Parts List 8000CF-OAK-IPI Beginning Manufacturing Date: Jan. 2005 Ending Manufacturing Date: ______ 1 2 3 4 5 6 7 8 9 10 Note: Shutter sleeve not used on LP models IMPORT ANT : THIS IS DA TED INFORM[...]
-
Pagina 62
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev . Q • 1 1/08 62 Heat & Glo, a brand of Hearth & Home T echnologies Inc. 7571 215th St, Lakeville, MN 55044 www .heatnglo.com D. Contact Information Please contact your Heat & Glo dealer with any questions or concerns. For the location of your nearest Heat & Glo dealer , please vis[...]