Warning: mysql_fetch_array() expects parameter 1 to be resource, boolean given in /home/newdedyk/domains/bkmanuals.com/public_html/includes/pages/manual_inc.php on line 26
Heatcraft Refrigeration Products H-IM-79B manuale d’uso - BKManuals

Heatcraft Refrigeration Products H-IM-79B manuale d’uso

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36

Vai alla pagina of

Un buon manuale d’uso

Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Heatcraft Refrigeration Products H-IM-79B. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Heatcraft Refrigeration Products H-IM-79B o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.

Che cosa è il manuale d’uso?

La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Heatcraft Refrigeration Products H-IM-79B descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.

Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.

Quindi cosa dovrebbe contenere il manuale perfetto?

Innanzitutto, il manuale d’uso Heatcraft Refrigeration Products H-IM-79B dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Heatcraft Refrigeration Products H-IM-79B
- nome del fabbricante e anno di fabbricazione Heatcraft Refrigeration Products H-IM-79B
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Heatcraft Refrigeration Products H-IM-79B
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti

Perché non leggiamo i manuali d’uso?

Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Heatcraft Refrigeration Products H-IM-79B non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Heatcraft Refrigeration Products H-IM-79B e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Heatcraft Refrigeration Products in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Heatcraft Refrigeration Products H-IM-79B, come nel caso della versione cartacea.

Perché leggere il manuale d’uso?

Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Heatcraft Refrigeration Products H-IM-79B, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.

Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Heatcraft Refrigeration Products H-IM-79B. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.

Sommario del manuale d’uso

  • Pagina 1

    Installation & Operation Manual H-IM-79B ( 12/02) December , 2002 Part Number 25001401 Replaces H-IM-79A (04/02)[...]

  • Pagina 2

    2 Beacon II Board layout ........................................................................................................ 3 I nstallation Ti ps ................................................................................................................... 4 Brazing Power Supply Wiring ....................................................[...]

  • Pagina 3

    3 Beacon II Board Layout BEACON II BOARD Heater Relay Fan Relay LED Display Room Sensor Defrost Sensor Suction Sensor Suction Pressure Expansion V alve Connection Selection Buttons 24V Te r m inal Block[...]

  • Pagina 4

    4 Installation T ips • Use a minimum 18 gauge wire for all low voltage connections. • The Beacon II board gets its 24 V AC power supply from a transformer mounted in the electrical end of each evaporator . On 208-240 volt systems the multi-tap transformer is shipped from our factory wired for 240 volts. If your supply voltage is 208 volt you mu[...]

  • Pagina 5

    5 Refrigerant Line Brazing ( CAUTION ) The electric expansion valve and the suction temperature sensor on the suction line are factory installed. Care must be taken when brazing these lines at the evaporator . T oo high a temperature may destroy these components. Heat absorbing compounds or “wet rags” must be used to protect the electric expans[...]

  • Pagina 6

    6 WIRING (cont’d.) • Multiple units – The multi-in and multi-out are the communication connections. Connection sequence must follow the multi-out terminal to the multi-in terminal and the multi-out back to the multi-in terminal in a daisy chain loop. • Alarm circuit - The onboard alarm is a dry set of NC contacts which closes to indicate an[...]

  • Pagina 7

    7 BOX TEMPERA TURE CONTROL SETTINGS • There is an on board room thermostat on the Beacon II board which can be adjusted to the desired room temperature. The temperature dif ferential is 2 ° F. T emperature Differential When a system is in the cooling mode and the box setpoint is 35 ° F, the system will continue to cool until the box temperature[...]

  • Pagina 8

    8 CU M M = Master Evaporator CU = Condensing unit Start-Up Operation SINGLE SYSTEM with 1 EV APORA TOR • Check all wiring connections to be sure they are correct and tight. • On condensing unit - Check the setting of T ime Delay relay . It should be set at 1 minute (the second marker). - Check the Low Pressure switch setting on freezer units. I[...]

  • Pagina 9

    9 SINGLE SYSTEM with MUL TIPLE EV APORA TORS • Check all wiring connections to be sure they are correct and tight. • On Condensing unit - Check the setting of T ime Delay relay . It should be set at 1 minute (the second marker). - Check the Low Pressure switch setting on freezer units. It must be set to 0 PSIG cutout, 10 PSIG cut-in to allow po[...]

  • Pagina 10

    10 MUL TIPLE SYSTEMS with MUL TIPLE EV APORA T ORS (Requires a Smart Controller) • Check all wiring connections to be sure they are correct and tight. • On condensing units - Check setting of T ime Delay relay . It should be set at 1 minute (the second marker). - Check the Low Pressure Switch setting on freezer units. It must be set to 0 PSIG c[...]

  • Pagina 11

    11 INITIAL POWER ON At the initial application of power to the system, the compressor and the evaporator fans will be in a 4 minute hold-off cycle and will not start immediately . When there is a call for COOLING, the expansion valve (EEV) opens, then the compressor is started. The compressor will then run for a minimum of 2 minutes in the “hold-[...]

  • Pagina 12

    12 PROGRAMMING AND REVIEWING SETTINGS/CHANGES The Program Review button is used to program, review and change all program settings for the system. Press “PROGRAM REVIEW” button. The Setpoint item will appear on the LED. After a few seconds delay the Setpoint value will display . Each time the button is pressed a different setpoint item is displ[...]

  • Pagina 13

    13 PROGRAMMING AND REVIEWING SETTINGS/CHANGES (cont’d.) Use the “PROGRAM REVIEW” button to select these items: • Defrost T ype – “A-E ” - Selection is made for air defrost or electric defrost coil. This will automatically set the system factory defaults for air defrost and electric defrost. (See default settings.) Please note that the[...]

  • Pagina 14

    14 PROGRAMMING AND REVIEWING SETTINGS/CHANGES (cont’d.) • Alarm High T emperature - “ ALH” - T emperature at which a high box temperature alarm will be triggered. This does not apply during defrost. Defaults: electric defrost +5 ° F and air defrost +50 ° F. • Alarm Low T emperature - “ALL” - T emperature at which a Low Box T emperat[...]

  • Pagina 15

    15 PROGRAMMING AND REVIEWING SETTINGS/CHANGES (cont’d.) Use this button to “CLEAR/TEST” Pressing this button ONCE will return the LED display to the default display . With the system in the OFF mode, pressing and holding this button will start the “TEST” mode. In the “ TEST” mode it will cycle through each output for 10 seconds. The d[...]

  • Pagina 16

    16 ST A TUS INDICA T OR LED • ERRORS E 1 - Room temperature sensor shorted, open or not installed E 2 - Defrost temperature sensor shorted, open or not installed E 3 - Suction temperature sensor shorted, open or not installed E 4 - Suction pressure transducer shorted, open or not installed E 5 - Outdoor temperature sensor shorted E 6 - Low superh[...]

  • Pagina 17

    17 Defrost DEFROST TIMING When power is first applied to the system, its timer starts counting time. If 4 defrost are programmed, it will initiate a defrost every 6 hours from when power was first applied. Beacon II does not have a real time clock. Beacon II does provide the ability to delay the starting of the first defrost. DEFROST DELA Y ST ART [...]

  • Pagina 18

    18 ELECTRIC DEFROST MODE (cont’d.) There is a 2 minute condensate drain-down period after which the compressor is started for a refreeze period. The evaporator fan stays of f (fan delay). The refreeze period will last until the evaporator suction temperature is at 28 ° F or 2 minutes has elapsed. After this sequence, the system is back in the re[...]

  • Pagina 19

    19 ERROR INDICA TOR LED At initial power up, each Beacon board checks for system errors. The system error check involves checking the various temperature sensors to determine whether any of these sensors are shorted or open. The system will pumpdown and cycle off and will not restart until the fault is cleared or the circuit breaker reset, for the [...]

  • Pagina 20

    20 CHECKING OPERA TION OF EXP ANSION V AL VE (EEV) To check if the expansion valve is closing properly: Install a pressure gauge-set to suction line at the condensing unit. With the system running, close the valve on the liquid line, at the condensing unit. The system should pumpdown and shut off on the Low Pressure switch (LPS). If the system does[...]

  • Pagina 21

    21 POWER F AILURES In the event of a power failure Beacon II will automatically close the expansion valve to prevent refrigerant from migrating throughout the system. After power returns, with 24 V AC at the board, the system will restart in the cooling mode after the four-minute hold off period. SP ARE SENSOR TERMINALS Beacon II provides a set of [...]

  • Pagina 22

    22 System Defaults T able 2. System Defaults P ARAMETERS CODE AIR ELECTRIC Refrigerant rEF R-22 R-404A Box T emperature bot 35 ° F- 1 0 ° F Superheat SUP 8 ° F8 ° F Slave Evaporator SLA No No No. of Defrost per Day dFn 24 Defrost Fail-safe time dFF 40 min. 30 min. Defrost End T emperature dFt 45 ° F6 0 ° F Defrost Delay Start T ime dFS 0 hrs.[...]

  • Pagina 23

    23 T able 3. Parts List HRPD P ART P ART DESCRIPTION NUMBER Beacon II Control Board 28910101 *T emperature Sensor kit – Blue Leads 89904902 T ransformers: 120/24 volt– 40 V A 22529601 240/24 volt - 40 V A 22529602 460/24 volt – 40 V A 22529603 575/24 volt – 40 V A 22529701 Pilot Relay 2251 1401 Contactor for Compressor 40 amp with 24 volt C[...]

  • Pagina 24

    24 Beacon II T roubleshooting Guide PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check Primary Power Supply Disconnect 1. Check fuses and circuit breakers 2. Check V oltage to Evaporator T ransformer Go to 2. Check field wiring for breaks LED is not lit. 3. Check T ransformer Secondary Output V olts next step 3. Replace if necessary 4. Check V oltag[...]

  • Pagina 25

    25 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check wiring connection to the board • Correct field wiring to the board 2. Low Pressure Safety (LPS) T ripped: • Check for correct refrigerant type • Change setpoint to match refrigerant • Check refrigerant charge • Add more refrigerant to proper charge • Check LPS setting • Correct LPS [...]

  • Pagina 26

    26 Beacon II T roubleshooting Guide (continued) PROBLEM Step ACTION ITEM IF OK IF NOT OK E9 Multi-out to Multi-in 1. Check for 24 volts power to the board 1. If no voltage, see “LED is not lit” above Communication Wiring for low voltage, see “88888 LED display” (only shows after initial 2. Check for crossed communication wiring Go to 2. Cor[...]

  • Pagina 27

    27 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check system operation: Is it running? 1. Check power to condensing unit Check position of Service Mode switches Check compressor overloads and contactor 2. Check system charge 2. Add or remove refrigerant to proper charge 3. Check for proper operating superheat 3. Check EEV operation Check control boa[...]

  • Pagina 28

    28 W iring[...]

  • Pagina 29

    29 W iring[...]

  • Pagina 30

    30 W iring[...]

  • Pagina 31

    31 W iring Part No. 29684301[...]

  • Pagina 32

    32 W iring Part No. 29684201[...]

  • Pagina 33

    33 W iring Part No. 29684001[...]

  • Pagina 34

    34 EV APORA TORS All evaporator units should be checked once a month or more often for proper defrosting because the amount and pattern of frosting can vary greatly . It is dependent on the coil temperature, the temperature of the room, the type of product being stored, how often new product is brought into the room and the percentage of time the d[...]

  • Pagina 35

    35 Service Record Date of Start-up Location Address CONDENSING UNIT MODEL # SERIAL # COOLER UNIT MODEL # SERIAL # FREEZER UNIT MODEL # SERIAL # ELECTRICAL • Check Primary Supply voltage. If 208 V , change transformer wiring in the Cooler and Freezer to the 208 V tap  YES • Check Compressor Amps for COOLER and FREEZER compressors. Should matc[...]

  • Pagina 36

    36 2175 West Park Place Blvd. • Stone Mountain, GA 30087 770-465-5600 • Fax: 770-465-5990 • www .heatcraftrpd.com Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice. RECORD OUTDOOR TEMPERA TURE ______ ° F SYSTEM VOL T AGE ______V olts ______PH ______Hz Cooler Compressor Amp[...]