Mitsubishi Electronics PUHY-80TMU-A manuale d’uso
- Visualizza on-line o scarica il manuale
- 95 pagine
- 1.34 mb
Vai alla pagina of
Manuali d’uso simili
-
Air Conditioner
Mitsubishi Electronics MSZ12UN
30 pagine 2.57 mb -
Air Conditioner
Mitsubishi Electronics MSZ-D30/36NA
8 pagine 0.5 mb -
Air Conditioner
Mitsubishi Electronics MXZ-2A20NA
9 pagine 1.8 mb -
Air Conditioner
Mitsubishi Electronics MXZ-3B24NA
86 pagine 6.3 mb -
Air Conditioner
Mitsubishi Electronics PUZ-ANHA3-BS
36 pagine 0.79 mb -
Air Conditioner
Mitsubishi Electronics MUZ-GE25VAD
96 pagine 7.04 mb -
Air Conditioner
Mitsubishi Electronics PEFY-P-VMR-E-L/R
15 pagine 0.74 mb -
Air Conditioner
Mitsubishi Electronics 36FL3
12 pagine 0.86 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Mitsubishi Electronics PUHY-80TMU-A. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Mitsubishi Electronics PUHY-80TMU-A o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Mitsubishi Electronics PUHY-80TMU-A descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso Mitsubishi Electronics PUHY-80TMU-A dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Mitsubishi Electronics PUHY-80TMU-A
- nome del fabbricante e anno di fabbricazione Mitsubishi Electronics PUHY-80TMU-A
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Mitsubishi Electronics PUHY-80TMU-A
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Mitsubishi Electronics PUHY-80TMU-A non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Mitsubishi Electronics PUHY-80TMU-A e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Mitsubishi Electronics in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Mitsubishi Electronics PUHY-80TMU-A, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Mitsubishi Electronics PUHY-80TMU-A, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Mitsubishi Electronics PUHY-80TMU-A. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
AIR CONDITIONERS CITY MUL TI Series Y Models PUHY-80TMU-A, 100TMU-A Ser vice Handbook Service Handbook PUHY-80TMU-A, 100TMU-A HEAD OFFICE MITSUBISHI DENKI BLDG. MAR UNOUCHI TOKY O 100-0005 TELEX J24532 CABLE MELCO TOKY O Issued in March 2004 MEE03K198 Printed in Japan New pub lication effective March 2004. Specifications subject to change without n[...]
-
Pagina 2
- Inadequate connection and fastening may generate heat and cause a fire. • Prepare for typhoons and other strong winds and earth- quakes and install the unit at the specified place. - Improper installation may cause the unit to topple and result in injury. • Always use an air cleaner, humidifier, electric heater, and other accessories specifie[...]
-
Pagina 3
Contents 1 COMPONENT OF EQUIPMENT 1 [1] Appearance of Components 1 [2] Refirigerant Circuit Diagram and Thermal Sensor Standard operation data iger 6 [3] PUHY-80, 100TMU-A ELECTRICAL WIRING DIAGRAM 7 9 [4] [5] Function of dip SW and rotary SW 11 2 TEST RUN 15 [1] Before Test Run 15 [2] Test Run Method 19 3 GROUPING REGISTRATION OF INDOOR UNITS WITH[...]
-
Pagina 4
Propeller fan Fan motor - 1 -[...]
-
Pagina 5
Rear Controller Box INV board MAIN board Choke coil(L2) Interrigent Power Module(IPM) Magnetic contactor(52C) Capacitor (C1)(Smoothing capacitor) Gate Amplifier board(G/A board) Diode stack(DS) Power board Terminal block(TB7)Transmission Terminal block (TB3) Transmission Terminal block (TB1) Power source - 2 -[...]
-
Pagina 6
MAIN board CNS1 M-NET Transmission (DC30V) CNS2 M-NET Transmission (Centralized control) (DC30V) CN40 M-NET Transmission Power supply CNVCC3 Power source for contorl 1 - 2 DC30 V 1 - 3 DC30 V 4 - 6 DC12 V 5 - 6 DC5 V CN51 Indication distance 3 - 4 Compressor ON/ Off 3 - 4 trouble LD1 Service LED CNRS53 Serial transmission to INV board CN3D CN3S CNF[...]
-
Pagina 7
INV board CNDC2 1 - 3 DC310 V CN15V2 Power supply IPM control 1 - 2 DC15 V 5 - 6 DC15 V 9 - 0 DC15 V C - D DC15 V CNL2 Choke coil CNRS2 Serial transmission to MAIN board CNAC2 Power source 1 L2 5 N CNFAN Control for MF1 CN52C Control for 52C CNVCC2 power supply CNCT CNVCC4 CNTH CNDR2 IPM control signal SW1 - 4 -[...]
-
Pagina 8
G/A board Power board DC310V CNDC1 1 - 3 DC310V CN15V1 Power Supply IPM control 1 - 2 DC15V 5 - 6 DC15V 9 - 0 DC15V C - D DC15V CNDR1 IPM control signal - 5 -[...]
-
Pagina 9
[2] Refirigerant Circuit Diagram and Thermal Sensor 1 PUHY-80TMU-A, 100TMU-A TH1 TH6 TH7 TH8 TH5 TH2 O/S 63HS CJ1 Comp HEXF HEXB SCC LEV1 ST7 BV2 ST2 Indoor Unit BV1 ST1 CJ2 CV1 ST6 SV1 CP1 SV2 SLEV SA MA CP2 63H High pressure safety valve Accumulator - 6 -[...]
-
Pagina 10
[3] PUHY-80, 100TMU-A ELECTRICAL WIRING DIAGRAM CNS2 (3P) FN3 FN2 1 2 C CNS2 (3P) FN3 FN2 C 1 R 1 52C DCCT 1 2 3 TH6 TH5 TH8 TH7 TH2 TH1 63HS SW3-10 are OFF for Model 80. and ON for Model 100. Trouble Compressor ON/OFF Snow sensor Compressor ON/OFF Night mode Ground 1 2 3 4 5 1 2 3 4 5 5 4 3 2 1 3 2 1 3 2 1 1 2 3 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 3 2 1[...]
-
Pagina 11
S W U 1 ~ 2 T B 1 Switch unit address set Terminal block power source T B 3 T B 7 Terminal block transmisson GR Ground terminal Terminal block transmisson centralized control L D 1 S W 1 S W 2 ~4 Switch function selection Switch display selection self-diagnosis Luminous diode T H 8 bypass outlet temp. detect at Sub-cool coil T H H S Rediator panel [...]
-
Pagina 12
[4] Standard operation data 1 Cooling operation 75 81 111 157 Discharge (TH1) Heat exchanger outlet (TH5) Inlet Accumulator Outlet Suction (Comp) low pressure saturation temperature (TH2) Shell bottom (Comp) SCC outlet (TH7) Bypass outlet (TH8) LEV inlet Heat exchanger outlet Outdoor units Items Condition Pressure LEV opening Sectional temperature [...]
-
Pagina 13
00 87 111 Discharge (TH1) Heat exchanger inlet (TH5) Inlet Accumulator Outlet Suction (Comp) low pressure saturation temperature (TH2) Shell bottom (Comp) Heat exchanger inlet LEV inlet 2 Heating operation Outdoor units Items Condition Pressure LEV opening Sectional temperature Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pi[...]
-
Pagina 14
[5] Function of dip SW and rotary SW (1) Outdoor unit Switch Function Function According to Switch Operation Switch Set Timing When Off When On When Off When On Unit Address Setting For self diagnosis/ operation monitoring – Centralized Control Switch Deletion of connection information. Deletion of error history. Adjustment of Refrigerant Volume [...]
-
Pagina 15
2. SW4-9 setting Fan characteristics curve:DIPSW4-7ON,230V/60Hz Fan characteristics curve:DIPSW4-7ON,208V/60Hz 0 5 10 15 20 25 30 35 40 45 50 150 160 180 190 200 210 220 230 240 Standard Airflow rate 200(m 3 /min) Fan characteristics curve:DIPSW4-7OFF[FactorySetting],208V • 230V/60Hz Continuous operation range Airflow rate (m 3 /min) External sta[...]
-
Pagina 16
(2) Indoor unit DIP SW1, 3 Model 32 40 48 Capacity (model name) code 16 20 25 SW2 setting Model 08 10 12 16 20 24 Capacity (model name) code 45 68 1 0 1 3 SW2 setting ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the table belo[...]
-
Pagina 17
Setting of DIP SW4 Setting of DIP SW5 1234 ON OFF ON OFF OFF OFF OFF ON ON OFF OFF ON OFF OFF ON ON –––– OFF OFF ON – PDFY -10 ~ 32 PLFY -12 ~ 24 PLFY -32 ~ 48 PKFY -P-8 PKFY -P-12 PDFY -40, 48 Model Circuit board used SW4 Phase control Relay selection ✻ ✻ ✻ - 14 -[...]
-
Pagina 18
TEST RUN [1] Before Test Run (1) Check points before test run 1 Neither refrigerant leak nor loose power source/ transmission lines should be found, if found correct immediately . 2 Confirm that the resistance between the power source terminal block and the ground exceeds 2M Ω by measur- ing it with a DC500V megger . Do not run if it is lower tha[...]
-
Pagina 19
(3) Check points for test run when mounting options (4) Attention for mounting drain water pump mechanism Check point Local remote controller displays code No. “ 2503 ” , and the mechanism stops. No overflow from drain pan. Drain water comes out by operation of drain pump. Sound of pump operations is heard, and drain water comes out. No water l[...]
-
Pagina 20
T rouble Not operate. Not cool (at cooling). Not heat (at heating). Not cool, not heat, error stop. Condensation drip in piping. Not cool, not heat, error stop. Water leak, condensation drip in drain piping. Error stop, not operate. Electric shock. Error stop, not operate. Classification Installation and piping Power source wiring Portion 1 2 3 Che[...]
-
Pagina 21
Classification T ransmission line Portion 1 2 3 4 5 6 7 8 Check item Limitation of transmission line length followed? For example, 200m (656ft) or less (total length : 500m (1640ft)) at the farthest. 1.25mm 2 (A WG16) or more transmission line used? (Remote controller 10m (32ft) or less 1.25mm 2 (A WG16)) 2-core cable used for transmission line? T [...]
-
Pagina 22
[2] Test Run Method Operation procedure T urn on universal power supply at least 12 hours before starting → Displaying “ HO ” on display panel for about two minutes Press TEST 1 2 3 4 5 6 7 8 9 button twice → Displaying “ TEST RUN ’’ on display panel Press MODE button → Make sure that air is blowing out Press MODE button to change f[...]
-
Pagina 23
3 GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER (1) Switch function • The switch operation to register with the remote controller is shown below: Registration/ ordinary mode selector switch Registration/ordinary mode selection switch Switch to assign indoor unit address Registration switch Confirmation switch Delete switch Re[...]
-
Pagina 24
(2) Attribute display of unit • At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the unit is displayed with two English characters. Display T ype (Attribute) of unit/controller Indoor unit connectable to remote controller Outdoor unit Local remote controller System controller [...]
-
Pagina 25
(3) Group registration of indoor unit 1) Registration method • Group registration of indoor unit ........................................................................ The indoor unit to be controlled by a remote controller is registered on the remote controller . [Registration procedure] With the remote controller under stopping or at the disp[...]
-
Pagina 26
2) Method of retrieval/confirmation 2 1 2 • Retrieval/confirmation of group registration information on indoor unit ............... The address of the indoor unit being registered on the remote controller is displayed. [Operation procedure] With the remote controller under stopping or at the display of “ HO ” , continuously press the FILTER +[...]
-
Pagina 27
3) Method of deletion • Deletion of group registration information of indoor unit ...................................... [Operation procedure] With the remote controller under stopping or at the display of “ HO ” , continuously press the FILTER + LOUVER button ( + ) at the same time for 2 seconds to change to the registration mode. Press the [...]
-
Pagina 28
4) Deletion of information on address not existing • Deletion of information on address not existing ................................................... This operation is to be conducted when “ 6607 ” error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alt[...]
-
Pagina 29
4 CONTROL [1] Control of Outdoor Unit (1) Initial processing • When turning on power source, initial processing of microcomputer is given top priority. • During initial processing, control processing corresponding to operation signal is suspended. The control processing is resumed after initial processing is completed. (Initial processing : Dat[...]
-
Pagina 30
– 30 – (4) Frequency control • Depending on capacity required, capacity control change and frequency change are performed to keep constant evaporation temperature (0 ˚ C) in cooling operations, and high pressure (18kg/cm 2 G) in heating operation. • Frequency change is perfprmed at the rate of 3Hz/second across 20 ~ 110Hz range. 1) Frequen[...]
-
Pagina 31
28˚C (82.4 ° F) or more 111 111 157 20 ~ 30˚C (68~86 ° F) 87 87 134 22˚C (71.6 ° F) or less 64 64 87 3 Back up of frequency control by bypass valve During 20Hz operations, frequency is backed up by turning on (opening) bypass valve (SV2). • Cooling During 20Hz operations 3 minutes after starting compressor, bypass valve is turned on when ET[...]
-
Pagina 32
5) Change in number of operating indoor units during defrosting operations • In case number of operating indoor units changes during defrosting operations, the defrosting operations continue, and control of unit number change is performed after the defrosting operations are finished. • Even in case all indoor units stop or thermostat is turned [...]
-
Pagina 33
Starts Finish 30 seconds LEV opening before change LEV opening at refrigerant recovery (Indoor unit LEV opening 500 pulse) (10) Refrigerant recovery control Refrigerant recovery is conducted to prevent refrigerant from accumulating in the stopped unit (fan unit), the unit under cooling mode and that with heating thermostat being turned off. 1) Star[...]
-
Pagina 34
YES NO YES NO YES YES NO NO 2 2 [2] Operation Flow Chart (1) Outdoor unit (Cooling, heating modes) Note: 1 For about 2 minutes after turning on power source, address and group information of outdoor unit, indoor unit, and remo t e controller are retrieved by remote controller, during which "HO" blinks on and off on remote controller. In c[...]
-
Pagina 35
YES NO YES NO YES NO YES NO YES NO YES NO YES NO YES NO 1 1 2 (2) Indoor unit (Cooling, heating, dry, and fan modes) Start Breaker turned on Operation SW turned on 1. Protection function self-holding cancelled 2. Indoor unit LEV fully closed Remote controller display extinguished Aux. heater ON FAN stop Drain pump ON 1. Aux. heater OFF 2. 1 minute [...]
-
Pagina 36
YES NO YES YES NO NO (3) Cooling operation Note : 1 Indoor unit fan operates at set notch in cooling operation regardless of thermostat ON/OFF. Cooling operation 4-way valve OFF Indoor unit fan operations Test run start Thermostat ON Note: 1 3-minute restart pre- vention 1. Inverter output 0Hz 2. Indoor unit LEV, oil return LEV, Subcool coil bypass[...]
-
Pagina 37
YES NO YES YES NO NO YES NO (4) Heating operation (Only for PUHY) Normal operations Defrosting operations Stop Test run Heating operation Defrosting operation 4-way valve ON Test run start Thermostat ON 3-minute restart pre- vention Defrosting finish Defrosting finish 4-way valve OFF Note: 1 Note: 2 YES 1 : (6) 4 or 3 : (6) 2 1. Indoor unit fan ver[...]
-
Pagina 38
YES NO YES YES NO (5) Dry operation Normal operations Thermostat ON Stop Dry operations 4-way valve OFF Thermostat ON Test run start Inlet temp. > = 18 ˚ C Note: 2 Note: 1 1. Indoor unit fan stop 2. Inverter output 0Hz 3. Indoor unit LEV, oil return LEV, Subcool bypass LEV fully closed 4. Solenoid valve OFF 5. Outdoor unit fan stop 1. Outdoor u[...]
-
Pagina 39
Low pressure shell scroll type with capacity control mechanism Winding resistance: Each phase 0.107 Ω (20 ˚ C) Setting 30kg/cm 2 G OFF R 120 =7.465k Ω B 25/120 =4057 Rt = 7.465exp{4057( – )} R 0 =15k Ω B 0/100 =3460 Rt = 15exp{3460( – )} R 50 =17k Ω B 25/50 =4170 Rt = Com- MC pressor Pressure 63HS sensor Pressure 63H switch Thermistor [...]
-
Pagina 40
Symbol (function) Part code Application Specification Check method Name Solenoid valve Electronic expansion valve Liquid level detection heater Electronic expansion valve Thermistor SV1 (discharge - suction by- pass) SV2 (discharge - suction by- pass) SLEV LEV1 (SC coil) CH2, CH3 (accumulator liquid level detection) LEV TH21 (inlet air temperature)[...]
-
Pagina 41
[4] Resistance of Temperature Sensor Thermistor for low temperature Thermistor R o = 15k Ω ± 3% (TH5 ~ 8) Thermistor R 120 = 7.465k Ω ± 2% (TH1) R t = 15exp {3460 ( - )} R t = 7.465exp {4057 ( - )} ∗ ˚ F= × ˚ C + 32 ∗ ˚ F= × ˚ C + 32 Thermistor R o = 33k Ω ± 1% (TH2) Thermistor R 50 = 17k Ω ± 2% (THHS) R t = 33exp {3965 ( - )}[...]
-
Pagina 42
REFRIGERANT AMOUNT ADJUSTMENT 5 Clarify relationship between the refrigerant amount and operating characteristics of CITY MUL TI, and perform service activities such as decision and adjustment of refrigerant amount on the market. [1] Refrigerant Amount and Operating Characteristics The followings are refrigerant amount and operating characteristics[...]
-
Pagina 43
(2) Refrigerant V olume Adjustment Operation 1) Operating Characteristics Refrigerant V olume Characteristic items related to operating characteristics and the refrigerant volume are shown below . If the number of indoor units in operation increases during cooling, the required volume of refrigerant tends to increase (the amount of refrigerant in t[...]
-
Pagina 44
b Check the refrigerant volume by self-diagnosis using the LED. Set the self-diagnosis switch (SW1) as shown below and check the past information (history) concerning the refrigerant volume. Set SW1 as shown in he figure at right. If LD8 lights up, it indicates the refrigerant charge abnormal delay state just before emergency stop due to refriger- [...]
-
Pagina 45
3) Refrigerant Volume Adjustment Mode Operation 1 Procedure TH1 Self-diagnosis Switch TH5 Self-diagnosis Switch TH7 Self-diagnosis Switch Tc Self-diagnosis Switch Using these, judge TH1, Tc - TH5 and Tc - TH7. 12 34 56 7 89 1 0 ON 12 34 56 7 89 1 0 ON 12 34 56 7 89 1 0 ON 12 34 56 7 89 1 0 ON Operation Measure The outdoor unit LEV1 diverges more th[...]
-
Pagina 46
Refrigerant adjustment method Note 2 , Ensure that no refrigerant is released into the atmosphere Note 1, Operated using outdoor unit DIP SW3-1 and 3-2. Note 3 , Always charge the system with liquid refrigerant, if the system is charged with gas the composition will change and capacity will be reduced Wait for 30minutes of Note 1 compressor operati[...]
-
Pagina 47
6 TROUBLESHOOTING [1] Principal Parts Pressure Sensor (1) Judging Failure 1) Check for failure by comparing the sensing pressure according to the high pressure sensor and the pressure gauge pressure. T urn on switches 1, 3, 5, 6 of the digital display select switch (SW1) as shown below, and the sensor pressure of the high pressure sensors is displa[...]
-
Pagina 48
Solenoid Valve (SV1, SV2) Check if the control board’s output signals and the operation of the solenoid valves match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED’s. Each LED shows whether the relays for the following parts are ON or OFF. When a LED lights up, it[...]
-
Pagina 49
Outdoor LEV The valve opening angle changes in proportion to the number of pulses. (Connections between the outdoor unit ’ s MAIN board and SLEV, LEV1 (outdoor electronic expansion valve)) Pulse Signal Output and Valve Operation LEV Valve Closing and Valve Opening Operations ✻ When the power is switched ON, a 520 pulse valve opening signal is o[...]
-
Pagina 50
Judgment Methods and Likely Failure Mode Caution: The specifications of the outdoor unit (outdoor LEV) and outdoor units (indoor LEV) differ. For this reason, there ar e cases where the treatment contents differ, so follow the treatment specified for the appropriate LEV as indicated in the right column. Disconnect the control board connector and co[...]
-
Pagina 51
Outdoor LEV (SLEV, LEV1) Coil Removal Procedure (configuration) As shown in the figure, the outdoor LEV is made in such a way that the coils and the body can be separated. <Removing the Coils> Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then pull out the coils toward the top. If they catch on t[...]
-
Pagina 52
Intelligent Power Module (IPM) The measured v Measure resistances between each terminal of IPM with tester, and use the results for troubleshooting. alues f or troubleshooting are shown in the tab le below . Diode stack P (Restrictions to applicable tester are the same as those of IPM) erform continuity chec k with tester . Judged as normal if the [...]
-
Pagina 53
1 2 Despite pressing of remote controller switch, operation does not start with no electronic sound. (No powering signal appears.) At about 10 seconds after turning remote controller operation switch ON, the display distinguishes and the operation stops. 1) M-NET transmission power source is not supplied from outdoor unit. 1 Main power source of ou[...]
-
Pagina 54
3 “ HO ” display on re- mote controller does not disappear and switch is ineffective. Symptom Cause (Without using MELANS) 1) Outdoor unit address is set to “ 00. ” 2) Erroneous address 1 Address setting miss of indoor unit to be coupled with remote controller (Remote controller is not set to - 100.) 2 Address setting miss of remote control[...]
-
Pagina 55
Symptom Cause Checking method & countermeasure [Generates at registration and confirmation] 1) Erroneous address of unit to be coupled 2) Slipping off of transmission line of unit to be coupled (No connection) 3) Faulty circuit board of unit to be coupled 4) Installation miss of transmission line [Confirmation of different refrigerant system co[...]
-
Pagina 56
Transmission Power Circuit (30 V) Check Procedure If “ ” is not displayed by the remote control, investigate the points of the trouble by the following procedure and correct it. DC24~30 V Except the above-mentioned Connector disconnected Except the above-mentioned DC24~30 V Except the above-mentioned DC24~30 V Except the above-mentioned 0.5~2.5[...]
-
Pagina 57
(6) Investigation of transmission wave shape/noise Control is performed by exchanging signals between outdoor unit, indoor unit and remote controller by M-NET trans- mission. If noise should enter into the transmission line, the normal transmission will be hindered causing erroneous operation. 1) Symptom caused by the noise entered into transmissio[...]
-
Pagina 58
3) Checking and measures to be taken (a) Measures against noise Check the items below when noise can be confirmed on wave shape or the error code in the item 1) is generated. Items to be checked Measures to be taken 1 Wiring of transmission and power lines in crossing 2 Wiring of transmission line with that of other system in bundle 3 Use of shield[...]
-
Pagina 59
4) Treatment of Inverter and Compressor Troubles If the compressor does not work when error codes 4240 or 4250 are detected, determine the point of malfunction by following the steps in the appropriate sections on the pages starting from page 75, then perform the procedures below. 1 If it was kept on for 2 hours or longer as specified 2 It was kept[...]
-
Pagina 60
5) Troubleshooting at breaker tripping Check items 1 C heck the breaker capacity. 2 Check the a short circuit or grounding in the electrical sys- tem other than the inverter. 3 Check the resistance between terminals on the terminal block TB1 for power source. 1 0 ~ several ohms or improper megohm value 4 Checking by powering again. 1 Main power sou[...]
-
Pagina 61
6) Individual Parts Failure Judgment Methods. [Caution at replacement of inverter parts] 1 The IPM and G/A board should be replaced together at the same time. 2 Fully check wiring for incorrect and loose connection. 3 Coat the grease for radiation provided uniformly onto the radiation surface of IPM/diode modules. Coat the grease for radiation on t[...]
-
Pagina 62
Model PUHY-80TMU-A, 100TMU-A To compressor Red White Blue Blue Red To capacitor (C1) board - 59 -[...]
-
Pagina 63
Check Code List Check Code Check Content 0403 Serial transmission trouble 0900 Trial operation 1102 Discharge temperature trouble 1111 Low pressure saturation temperature sensor trouble (TH2) 1302 High pressure trouble 1500 Refrigerant volume charge trouble 1505 Suction pressure trouble 2500 Leakage (water) trouble 2502 Drain pump trouble 2503 Drai[...]
-
Pagina 64
Check Code Check Content 6606 Communications with transmission processor abnormality 6607 No ACK abnormality 6608 No response abnormality 6831 MA communication, No-reception error 6832 MA communication, Synchronization recov er y error 6833 MA communication, T ransmission/reception handware error 6834 MA communication, Star t bit error 7100 T otal [...]
-
Pagina 65
(1) Mechanical Checking code Meaning, detecting method Cause Checking method & Countermeasure Serial transmission trouble Discharge temperature trouble ( Outdoor unit ) If serial transmission cannot be established between the MAIN and INV boards 1 . When 140 ° C or more dis- charge temperature is de- tected during op-erations (the first time),[...]
-
Pagina 66
Checking code Meaning, detecting method Cause Checking method & Countermeasure 1. 2. When –40 ° C or less temp. is detected again (the second time) within 30 minutes afte r stop of outdoor unit, error stop is observed with code N os. "1111" or displayed. 3 . When –40 ° C or less tem- perature is detected 30 or more minutes after[...]
-
Pagina 67
–1.5 Checking code Meaning, detecting method Cause Checking method & Countermeasure Check operations status by actually performing cooling or heating opera- tions. Cooling : Indoor LEV LEV1 Heating : Indoor LEV See Trouble check of LEV and so- lenoid valve . Confirm that ball valve is fully open- ed. Check indoor unit and take mea- sures to t[...]
-
Pagina 68
Checking code Meaning, detecting method Cause Checking method & Countermeasure Check inlet temperature and press. of sensor with LED monitor. See Trouble check of pressure sensor . Once vacuum operation protection is commenced, do not attempt to re - start until taking the measures be- low. <Checking method> • Check ball valve for negle[...]
-
Pagina 69
Checking code Meaning, detecting method Cause Checking method & Countermeasure Leakage (water) trouble Drain pump trouble Drain sensor trouble Water leak trouble Water suspension trouble Operation of float switch Check water leaking of humidifier and clogging of drain pan. Check operations of drain pump. Measure resistance of indirect heater of[...]
-
Pagina 70
Checking code Meaning, detecting method Cause Checking method & Countermeasure Open phase error Reverse phase error Check before the breaker, after the breaker or at the power supply ter- minal blocks TB1, and if there is an open phase, correct the connec- tions. a) Check if a wire is disconnected. b ) Check the voltage between each of the wire[...]
-
Pagina 71
Checking code Meaning, detecting method Cause Checking method & Countermeasure Power supply sync signal trouble Fan speed trouble (motor trouble) Check before the breaker, after the breaker or at the power supply ter- minal blocks TB1 or TB1A, and if there is an open phase, correct the connections. If the power supply voltage wave- form is dist[...]
-
Pagina 72
Checking code Meaning, detecting method Cause Checking method & Countermeasure 1 If VDC 150 V is detected just before the inverter starts. 2 If VDC 400 V is detected just before the inverter starts. 3 If the voltage of the INV board’s sensor circuit input is what it should not normally be. VDCsensor/ circuit trouble 4200 • Check if an insta[...]
-
Pagina 73
Checking code Meaning, detecting method Cause Checking method & Countermeasure If VDC 220 V is detected dur- ing inverter operation. If the cooling fan stays ON for 5 minutes or longer during in- verter operation, and if THHS 92 ° C is detected. Bus voltage trouble Radiator panel overheat protection 4220 4230 • Check if an instantaneous stop[...]
-
Pagina 74
Checking code Meaning, detecting method Cause Checking method & Countermeasure If IDC 103 A is detected con- tinuously for 10 minutes during operation of the inverter after 5 or more seconds have passed since the inverter started. 1) IPM/VDC trouble 2) If IDC 200 A is detected during inverter operation. 3 ) If VDC 350V or VDC 190V is detected d[...]
-
Pagina 75
Checking code Meaning, detecting method Cause Checking method & Countermeasure If the heat sink temperature (THHS) 60 ° C for 10 minutes or longer just before the inverter starts. If a heat sink temperature of (THHS) 40 ° C is detected just before starting of, and during operation of the inverter. • If IDC 20 A is detected just before the i[...]
-
Pagina 76
Checking code Meaning, detecting method Cause Checking method & Countermeasure <Other than THHS> 1 A short in the thermistor or an open circuit was sensed. The outdoor unit switches to the temporary stop mode with restarting after 3 min- utes, then if the temperature detected by the thermistor just before restarting is in the normal range[...]
-
Pagina 77
Checking code Meaning, detecting method Cause Checking method & Countermeasure 6600 6602 Multiple address error Transmission from units with the same address is detected. Note: The address/attribute shown on remote con- troller indica tes the con- troller which has de- tected error. At the genration of 6600 error, release the error by remote co[...]
-
Pagina 78
6602 Faulty controller of generating unit YES YES Erroneous power source work Erroneous transmission work NO NO YES NO NO NO YES YES YES Transmission line installed while turning power source on? Shut off the power source of outdoor/in- door units/BC controller and make it again. Check power source of in- door unit. 187V ~ 253V? Check transmission [...]
-
Pagina 79
6606 Communications with transmission processor error Communication trouble be- tween apparatus processor and trans-mission processor. Note: The address/attribute shown on remote con- troller indicates the con- troller which has de- tected error. 1) Data is not properly transmitted due to casual errouneous opera- tion of the generating controller. [...]
-
Pagina 80
Shut down OC unit power source, and make it again. It will return to normal state at an ac- cidental case. When normal state can not be re- covered, check for the 1) ~ 4) of the cause. Shut down both OC and IC power so- urces simultaneously for 5 minutes or more, and make them again. It will return to normal state at an accidental case. When normal[...]
-
Pagina 81
Checking code Meaning, detecting method No ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side controller, the transmission side detects error. Note: The address/attribute shown on remote controller indicates the controller not providing the answer (ACK). Generating unit address Display of tro[...]
-
Pagina 82
Checking code Meaning, detecting method No ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side controller, the transmission side detects error. Note: The address/attribute shown on remote controller indicates the controller not providing the answer (ACK). Generating unit address Display of tro[...]
-
Pagina 83
Checking code Meaning, detecting method No ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side controller, the transmission side detects error. Note: The address/attribute shown on remote controller indicates the controller not providing the answer (ACK). Generating unit address Display of tro[...]
-
Pagina 84
Checking code 6608 1) At the collision of mutual transmis- sion data when transmission wiring is modified or the polarity is changed while turning the power source on, the wave shape changes detecting error. 2) Repeating of transmission error due to noise. 3) Damping of transmission line volt- age/signal due to exceeding of the acceptable range for[...]
-
Pagina 85
7102 7105 7111 Connected unit count over Address setting error • Erroneous setting of Outdoor unit address Trouble source : Outdoor unit Remote control sensor error Error not providing the tem- perature designed to remote controller sensor. Trouble source : Indoor unit 2) The Outdoor unit address is being set to 51~100 under automatic address mod[...]
-
Pagina 86
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0000000000 1000000000 0100000000 1100000000 0010000000 1010000000 0110000000 1110000000 0001000000 1001000000 0101000000 1101000000 0011000000 1011000000 0111000000 1111000000 0000100000 1000100000 0100100000 1100100000 0010100000 [3] LED Monitor Display E: E2 Contents stored in the E2PROM; M: Mo[...]
-
Pagina 87
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 1010100000 0110100000 1110100000 0001100000 1001100000 0101100000 1101100000 0011100000 1011100000 0111100000 1111100000 0000010000 1000010000 0100010000 1100010000 0010010000 1010010000 0110010000 1110010000 0001010000 1001010000 0101010000 1101010000 0011[...]
-
Pagina 88
52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 0010110000 1010110000 0110110000 1110110000 0001110000 1001110000 0101110000 1101110000 00111100 10111100 01111100 11111100 00000010 10000010 01000010 11000010 00100010 10100010 01100010 11100010 00010010 10010010 01010010 11010010 00110010 1011[...]
-
Pagina 89
87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 11101010 00011010 10011010 01011010 11011010 00111010 10111010 01111010 11111010 00000110 10000110 01000110 11000110 00100110 10100110 01100110 11100110 00010110 10010110 01010110 11010110 00110110 10110110 01110110 11110110 00001110 10001110 [...]
-
Pagina 90
10101110 01101110 11101110 00011110 10011110 01011110 11011110 00111110 10111110 01111110 11111110 00000001 10000001 01000001 11000001 00100001 10100001 01100001 11100001 00010001 10010001 01010001 11010001 00110001 10110001 01110001 11110001 00001001 10001001 01001001 11001001 00101001 10101001 01101001 11101001 00011001 10011001 01011001 No SW1 I[...]
-
Pagina 91
155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 11011001 00111001 10111001 01111001 11111001 00000101 10000101 01000101 11000101 00100101 10100101 01100101 11100101 00010101 10010101 01010101 11010101 00110101 10110101 01110101 11110101 00001[...]
-
Pagina 92
194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 01000011 11000011 00100011 10100011 01100011 11100011 00010011 10010011 01010011 11010011 00110011 10110011 01110011 11110011 00001011 10001011 01001011 11001011 00101011 10101011 01101011 11101011 [...]
-
Pagina 93
232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 00010111 10010111 01010111 11010111 00110111 10110111 01110111 11110111 00001111 10001111 01001111 11001111 00101111 10101111 01101111 11101111 00011111 10011111 01011111 11011111 00111111 10111111 01111111 11111111 No SW1 Item Display Remarks 1234567891[...]
-
Pagina 94
AIR CONDITIONERS CITY MUL TI Series Y Models PUHY-80TMU-A, 100TMU-A Ser vice Handbook Service Handbook PUHY-80TMU-A, 100TMU-A Issued in March 2004 New pub lication effective March 2004. Specifications subject to change without notice. Service Handbook PUHY-80TMU-A, 100TMU-A[...]
-
Pagina 95
3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications are subject to ch ange without notice.[...]