Warning: mysql_fetch_array() expects parameter 1 to be resource, boolean given in /home/newdedyk/domains/bkmanuals.com/public_html/includes/pages/manual_inc.php on line 26
Siemens 400 V / 210...590 A manuale d’uso - BKManuals

Siemens 400 V / 210...590 A manuale d’uso

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166

Vai alla pagina of

Un buon manuale d’uso

Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Siemens 400 V / 210...590 A. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Siemens 400 V / 210...590 A o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.

Che cosa è il manuale d’uso?

La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Siemens 400 V / 210...590 A descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.

Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.

Quindi cosa dovrebbe contenere il manuale perfetto?

Innanzitutto, il manuale d’uso Siemens 400 V / 210...590 A dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Siemens 400 V / 210...590 A
- nome del fabbricante e anno di fabbricazione Siemens 400 V / 210...590 A
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Siemens 400 V / 210...590 A
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti

Perché non leggiamo i manuali d’uso?

Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Siemens 400 V / 210...590 A non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Siemens 400 V / 210...590 A e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Siemens in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Siemens 400 V / 210...590 A, come nel caso della versione cartacea.

Perché leggere il manuale d’uso?

Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Siemens 400 V / 210...590 A, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.

Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Siemens 400 V / 210...590 A. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.

Sommario del manuale d’uso

  • Pagina 1

    Operating Instructions Edition: AB simovert A ctive Front End (AFE) A FE Rectifie r / Regenerative Feedback Unit AC-DC Chassis Type G and J 400 V / 210...590 A[...]

  • Pagina 2

    The reproduction, transmission or us e of this document or its con- tents is not permitted without ex press written authority . Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. We have checked the contents of th is document to ensure that they coin[...]

  • Pagina 3

    01.2004 Contents Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 1 Content s 1 DEFINITIONS AND WARNINGS ..................................................................... 1-1 2 DESCRIPTION ................................................................................................. 2-1 3 INITIAL STAR T-UP .....[...]

  • Pagina 4

    Contents 01.2004 6SE7087-6CX86-2BA1 Siemens AG 2 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.4 Connecting up cont rol cabl es ......................................................................... 7-12 7.5 Terminal assi gnments ..................................................................................... 7-12 7.6 Digital inputs/ o[...]

  • Pagina 5

    01.2004 Contents Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 3 12.11 Diagnostic functions ...................................................................................... 12-31 12.12 Gating uni t .................................................................................................... 12-34 12.13 [...]

  • Pagina 6

    Contents 01.2004 6SE7087-6CX86-2BA1 Siemens AG 4 Operating Instructions SIMOVERT MASTERDRIVES AFE 16 FORMING ....................................................................................................... 16-1 17 TECHNICAL DATA ........................................................................................ 17-1 17.1 AFE basic mains[...]

  • Pagina 7

    01.2004 Definitions and Warnings Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 1-1 1 Definitions and W arnings For the purpose of this documentation and the produ ct warning labels, a "Qualified person" is someone who i s familiar with the installation, mounting, start-up, operation and maintenan ce of the[...]

  • Pagina 8

    Definitions and Warnings 01.2004 6SE7087-6CX86-2BA1 Siemens AG 1-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Hazardous voltages are pr esent in this electrical equipment du ring operation. Non-observance of the warning s can thus result in severe personal injury or property damage. Only qualified personnel should work on or aroun d the equip[...]

  • Pagina 9

    01.2004 Definitions and Warnings Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 1-3 Components which can be destroyed by electrostatic discharge (ESD) The board contains component s which can be destroyed by electrostatic discharge. These compone nts can be easily destroyed if not carefully handled. If you have to ha[...]

  • Pagina 10

    Definitions and Warnings 01.2004 6SE7087-6CX86-2BA1 Siemens AG 1-4 Operating Instructions SIMOVERT MASTERDRIVES AFE Safety and Operating Instructions for Drive Converters (in conformity with the lo w-voltage d irective 73/23/EEC) 1. General In operation, drive conver ters, depending on their degree of protection, may have liv e, uninsulated, and po[...]

  • Pagina 11

    01.2004 Description Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 2-1 2 Description The AFE (Active Front End) rect ifier/re generativ e feedback units belonging to the SIMOVERT MASTERDRIVES AFE series are power electronics devices that are available a s cabinet units, as chassis units and as compact units. The chas[...]

  • Pagina 12

    Description 01.2004 6SE7087-6CX86-2BA1 Siemens AG 2-2 Operating Instructions SIMOVERT MASTERDRIVES AFE On the 3-phase end, a mains angle- oriented high -speed vector control is subordinate to the DC link volt age co ntrol and impresses an almost sinusoidal current on the network so as to minimize system perturbations with the aid of the subsequentl[...]

  • Pagina 13

    01.2004 Description Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 2-3 Both one and several inverters can be conne cted to the output. The maximum connected power of the inverters may amount to 4 times the rated power of the AFE inverter. The sum of active power extracted from the network must not exceed t he rated p[...]

  • Pagina 14

    01.2004 Initial Start-Up Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 3-1 3 Initial S t art-Up After remov ing the packaging, check th at the unit is intact and undamaged. Only int act units may be st arted up. Plea se also check t hat all th e necessary option boards ar e present and cor rect. Unpack and check the[...]

  • Pagina 15

    Initial Start-Up 01.2004 6SE7087-6CX86-2BA1 Siemens AG 3-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Carry out the basic function check See chapter entitled "Basic function check" It must be ensured that no danger for persons and equipment c an occur by energizing the power and the unit. You are advised to only c onnect the inverto[...]

  • Pagina 16

    01.2004 Transport, Storage, Unpacking Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 4-1 4 T ransport, S torage, Unp acking The units and component s are packed in the manufacturing plant corresponding to that specified when ordered. A packing label is located on the outside of the packagin g. Please observe the inst[...]

  • Pagina 17

    Transport, Storage, Unpacking 01.2004 6SE7087-6CX86-2BA1 Siemens AG 4-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Line-side components: 1. AFE reactor 6SE7036-0ES87-1FG1 2. CleanPower filter 6SE7036-0EE87-1FC5, 3. AFE basic mains module 6SE7036-0ED83-2NB1 (with cable harness), These can be combined as standard with both the 510 A AFE inverte[...]

  • Pagina 18

    01.2004 Transport, Storage, Unpacking Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 4-3 AFE i nv e r t e r CU SA control /c ontrol sect i on 6 -L2 -C 4 ..C 5 L1 -K 1 -K 4 -R 1..R 3 VSB AF E reactor E box: opti o ns -R 7 ..R 9 cable harness 6 Ud Cg AFE Basic mains module CleanPower filte r AFE basic mains module: 6SE[...]

  • Pagina 19

    01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-1 5 Inst allation 5.1 Installing the units Safe converter operation requires that the equipment is mounted and commissioned by qualified personn el taking into account the warning information provided in these Operating Instruction s. The general a[...]

  • Pagina 20

    Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 5.2 Mounting dimensions and dimension sheets 5.2.1 AFE basic mains modul e with CleanPower filter Fig. 5-1 Example of cons truction type J: Mounting di mension AFE basic mains module with CleanPower filter The dimensions of const ruction type G d[...]

  • Pagina 21

    01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-3 5.2.2 Mounting dimensi ons of AFE reactor a 2 n 2 b h 2 h 3 h 1 a 1 a 1 n 1 l d 2 d 2 d 1 d 1 Fig. 5-2 Dimension draw ings of AFE reactors Current [A ] Voltage [V] l [mm] b [mm] n 1 [mm] n 2 [mm] h 1 [mm] h 2 [mm] h 3 [mm] a 1 [mm] a 2 [mm] d 1 d[...]

  • Pagina 22

    Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 5.2.3 AFE inverter (construction type G) H h 350 b aa B c Type G a b 119 270 B 508 H 1450 c2 5 h 1375 Mounting surfac e Cutouts fo r M8 scr ew Dimen- sions [mm] Side v iew Front v iew Fig. 5-4 Mounting dimens ion, construction type G Door/roof op[...]

  • Pagina 23

    01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-5 Partitions should be executed up to the cabinet fram e and should be designed in such a way that the di scharged air flow is taken around the cabinet beams and not pressed into the m. Partitions are necessary with all ty pes of protection hi gher[...]

  • Pagina 24

    Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-6 Operating Instructions SIMOVERT MASTERDRIVES AFE The following filter mat is approved for use: FIBROIDELASTOV made by DELBAG-Luftfilter GMBH Technical filter data in accordance with DIN 2418 5: Design FIBROID ELASTOV 10 Filter class EU 2 Volumetric flow V (m 3 /h) x m 2 2500 - 10000 Initial pre[...]

  • Pagina 25

    01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-7 The units with water cooling (MLFB Annex: -1AC0 ) are suitable for installing in an enclosed cabinet (IP5 4). The mains filter connection module is identical for water and air cooling. The co mponents not mounted on the heat sink, such a s the el[...]

  • Pagina 26

    Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-8 Operating Instructions SIMOVERT MASTERDRIVES AFE 5.2.4 AFE inverter (construction type J) Si de v ie w Front view 550 b 800 213 483 708 h H [mm] 1400 H Type Dimen- sions 1345 h 45 b Mounting surface Cutouts fo r M8 / M10 scre w J Elong at ed ho les 9 x 12 cons truc tio n type J for M8 screw s F[...]

  • Pagina 27

    01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-9 If the units are operated with an arcing s hort-circuit, this will result in the failure of the units or in their destruction! An arcing short-circuit must be pr evented by the prov ision of partitions. The control cabinets or si milar eq uipment[...]

  • Pagina 28

    Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-10 Operating Instructions SIMOVERT MASTERDRIVES AFE The following filter mat is approved for use: FIBROIDELASTOV made by DELBAG-Luftfilter GMBH Technical filter data in accordance with DIN 2418 5: Design FIBROID ELASTOV 10 Filter class EU 2 Volumetric flow V (m 3 /h) x m 2 2500 - 10000 Initial pr[...]

  • Pagina 29

    01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-11 MLFB 6SE7035-1TJ80 6SE7036-0TJ80 Fan 2 x RH28M Minimum flow rate [m3/s] 0.46 Min. opening cross-section in cabinet doors [m2] Degree of protection IP00 to I P42 0.26 Min. opening cross-section in top plate [m2] Degree of protection < IP20 0.2[...]

  • Pagina 30

    Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-12 Operating Instructions SIMOVERT MASTERDRIVES AFE Inverters with water cooling (item number suffix: -1AA0) are suitable for mounting in enclosed cabinets (IP54 ). The components not mounted on the heat sink, such as the electronics a nd the DC link capacitors, are cooled by heat transfer at the[...]

  • Pagina 31

    01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-13 5.3 Installing the optional boards The boards may only be replaced by qualified pe rsonnel. It is not permitted to withdraw or insert the boards under voltage. The electronics box of the unit contai ns up to three slots in which y ou can insert [...]

  • Pagina 32

    Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-14 Operating Instructions SIMOVERT MASTERDRIVES AFE The optional boards contain compone nts which could be damaged by electrostatic discharge. These comp onents can be very easily destroyed if not handled with caut ion. You must observe the ESD cautionary measures when handling th ese boards. Dis[...]

  • Pagina 33

    01.2004 Installation in Conformance with EMC Regulations Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 6-1 6 Inst allation in Conformance with EMC Regulations The following contains a summary of general informat ion and guidelines which will make it easier for you to comply with EMC and CE regulations. ♦ Pay atten[...]

  • Pagina 34

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 7-1 7 Connecting-Up and Wiring SIMOVERT MASTERDRIVES converters are operated at high voltages. The equipment must always be di sc onnected from the supply before any work is carried out! Only qualified personnel should be allowed to work [...]

  • Pagina 35

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.1 Connection overviews 7.1.1 AFE basic mains modul e and CleanPower filter AF E reactor connection L1 L2 L3 Clean-Pow er-Filter Components: - L1 Line reactor - C4, C5 Filter capacitor - R7, R8 Damping resistors - Cg Basic RI suppres[...]

  • Pagina 36

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 7-3 7.1.2 AFE Inverter construction type G PE/GND Electro nics box for boards CUSA -X101, -X 102 3AC connect ion for AFE reactor X9 connector 24 V DC power s upply and for prec hargin g 230 V 1 AC DC conne ction For motor-end inver ter Fa[...]

  • Pagina 37

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.1.3 AFE Inverter construction type J 3AC connection for AFE reactor Fan connection 230 V 1 AC F101 / F102 fuse X9 connector 24 V DC power supply and for precharging 230 V AC 1AC Electronics box for boards (CUSA) DC connection For mo[...]

  • Pagina 38

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 7-5 7.1.4 Overview of core and system components for AFE functionality with example configuration Control CUSA / control section VSB E box: Options Udc Control transformer AC230 V 50/60Hz 1 kVA DC 24 V / 6 A AF E basic mains module -K4 -R[...]

  • Pagina 39

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-6 Operating Instructions SIMOVERT MASTERDRIVES AFE AFE inverter order number / rating Input current Mains fuse 3AC Utilization category gR or Mains fuse 3AC Utilization category gL 6SE7035-1EJ80 / 340 kW 400 V 6SE7036-0EJ80 / 380 kW 400 V 510 A 560 A 3NE1435-0 560 A 3NE1436-0 630 A 3N[...]

  • Pagina 40

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-7 -K4 -X2: U2 V2 W2 C/ L+ 3PE AC380-460V 50/60Hz L1 L2 L3 PE1 -Q1 < 8 > -F1...3 6 5 4 3 2 1 < 12 >: Power con nection 3 AC -K1 12 34 56 12 34 56 -R1 -R2 -R3 VSB3 VSB2 VSB1 -U1 < 57 > -L2 D/ L- -U1-X1: -F41... -F44 M &[...]

  • Pagina 41

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-8 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.2 Power connections The connection cross-sect ions are determined for copper cable s at 40 °C (104 °F) ambient temperatu re (according to DIN VDE 0298 Part 4 / 02.88 Group 5). 7.2.1 AFE inverter and AFE reactor The supply terminal[...]

  • Pagina 42

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-9 7.2.2 Auxiliary powe r supply, precharging The 5-pole terminal strip is used for connectin g up a 24 V voltage supply and for connecting a pre charging contactor. The connections for the co ntactor control are floating. The position [...]

  • Pagina 43

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-10 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.3 Control terminals 7.3.1 Standard connections of the AFE inverter The basic version of the converter featur es the following control terminals on the CUSA board: ♦ Control terminal strips X100, X101 and X102 on CUS A electronics[...]

  • Pagina 44

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-11 -X100 -X101 -X102 PMU Fig. 7-8 View of CUSA X1 00 ≥ 1 1 2 3 4 5 6 7 8 9 PM U X3 00 RS485N RS485P 1 2 3 4 5 X1 01 13 14 15 16 17 P24 M M 5V 24V 5V 24V 5V 24V 5V 24V 5V 24V 18 19 20 X1 02 25 33 34 D A AO 0...+10 V list +5V D C B A 6[...]

  • Pagina 45

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-12 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.4 Connecting up control cables Generally, control lines that are co nnected to the AFE inverter must be shielded to achieve maximum possible interferen ce immunity. The shield must be grounded a t both ends. To avoid noise coupling[...]

  • Pagina 46

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-13 The terminals on the control terminal stri p are as follows: Terminal Name Function Range 13 P24 AUX Aux. voltage s upply DC 24 V / 150 mA 14 M24 AU X Refere nce potential 0 V 15 Reference potential f or digital inputs 1 t o 5 with [...]

  • Pagina 47

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-14 Operating Instructions SIMOVERT MASTERDRIVES AFE The terminals on the control terminal stri p are as follows: Terminal Name Function Range 25 Cannot be used Analog input 3 0 V to 5 V 26 Cannot be used Analog input 4 0 V to 5 V 27 Assigned Analog input 1 0 V t o ± 10 V 28 Assigned [...]

  • Pagina 48

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-15 A serial connection to an automation uni t or PC can be made via connector X300 on the PMU. The unit can therefore be controlled and operated from the central contro l station or control room. Pin Nam e Function Range 1 n.c. Not ass[...]

  • Pagina 49

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-16 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.6 Digital inputs/output s Four parameterizable digital inputs (24 V) are avail able on the control terminal strip (-X101) of the CUSA board. These inputs can be used to input commands, ex ternal faults/alarms and for returning stat[...]

  • Pagina 50

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-17 The USS protocol (universal serial interface ) is implemented on the basic converter interface SCom1. The following documentati on is available depending on the particu lar application of the SCom1 basi c converter interface : ♦ C[...]

  • Pagina 51

    Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-18 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.7 V oltage Sensing Board (VSB) The supply voltage is sensed usi ng the analog board VSB (Voltage Sensing Board) via the two anal og inputs on control b oard CUSA. Furthermore, the 24 V power supply is monitored on this board and a [...]

  • Pagina 52

    01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-19 VSB X3 -15-V output 10 CUSA Do not connect Line voltage component V sa 9 X102:27 Analog input 1 Line voltage component V sb 8 X102:30 Analog input 2 Ex t. 2 4 V m o ni t or ( OK ) 7 X101:19 Digital input 4 Ref. ground for V sa , V s[...]

  • Pagina 53

    01.2004 Basic Function Check Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 8-1 8 Basic Function Check It imperative to observe the procedure described here for initial commissioning of the equipment. CUSA control/control section VSB E box: Options Vd Control transformer AC230 V 50/60Hz 1 kVA DC 24 V / 6 A AFE basic [...]

  • Pagina 54

    Basic Function Check 01.2004 6SE7087-6CX86-2BA1 Siemens AG 8-2 Operating Instructions SIMOVERT MASTERDRIVES AFE ♦ Main contactor -K1 and prech arging contactor -K4 must be op en ♦ Main switch must be open ♦ Mains voltage must be applied to the main switch ♦ Ensure clockwise rotating field ♦ Control panel (PMU) must still be dark ♦ Contr[...]

  • Pagina 55

    01.2004 Basic Function Check Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 8-3 Issue the ON command via PMU (by def ault, ON command P554 already s et on PMU) ♦ Reaction: Precharging begins with picking up of the contactor -K4, and the DC link voltage (see display parameter r006) rises within approximately 1 se co[...]

  • Pagina 56

    Basic Function Check 01.2004 6SE7087-6CX86-2BA1 Siemens AG 8-4 Operating Instructions SIMOVERT MASTERDRIVES AFE → After successful precharging and a ctual value check P561 = 1 ♦ Reaction: The AFE inverter pulse is audibly and evenly The DC link voltage (r006) goe s to the value P071 x P125, and is stable with slight fluctuations ± approx. 1 %.[...]

  • Pagina 57

    01.2004 Explanation of Terminology and Functionality of the AFE Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 9-1 9 Explanation of T erminology and Functionality of the AFE ♦ Operating modes are set via P164 "Operating mode" ♦ See Section "Function diagrams" ♦ Applications: • Supplying th[...]

  • Pagina 58

    Explanation of Terminology and Functionality of the AFE 01.2004 6SE7087-6CX86-2BA1 Siemens AG 9-2 Operating Instructions SIMOVERT MASTERDRIVES AFE These parameters are divided into vario us "indices" (i001, i002, etc.). A separate parameter value can be assigned to ea ch index. The meaning of the "indices" of t he relevant para [...]

  • Pagina 59

    01.2004 Function Diagrams Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 10-1 10 Function Diagrams Line synchronization Analog input 1 Vsa Analog input 2 Vsb Line filter pre-control Current transformation P081 Line filter L Phase current 1 Phase current 3 SST1 CB/TB SCB 1 with SCI (Slave 1) SCB 1 with SCI (Slave 2) S[...]

  • Pagina 60

    Function Diagrams 01.2004 6SE7087-6CX86-2BA1 Siemens AG 10-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 0 1 2 3 ... ... ... ... Content of parameter 001 0 CU-AA act. values P655 CU-AA gain P656 CU-AA offset P657 # I Smoothing 20 ms +10 V -10 V to the terminal strip V off = Parameter values [%] 100 % ( x Gain [V] ) + Offset [V] Fields whi ch c[...]

  • Pagina 61

    01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-1 11 Parameterization The functions stored in the converte rs are adjusted to suit specific applications by means of parameters. Every param eter is uniquely identified by its name and number. In addition to a parameter name and number, many p[...]

  • Pagina 62

    Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 11.1 Setting p arameters via the PMU The parameterization unit (PMU) is p rovided for direct parameterization, operation and visuali z ation of the converter/inverter. It is an integral component of basic units and features a four-digit, sev[...]

  • Pagina 63

    01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-3 Since the seven-segment display on t he PMU has onl y four digits, the 3 descriptive elements of a parameter, i.e. ♦ parameter number, ♦ parameter index (for an indexed param eter) and ♦ parameter value cannot be displayed simultaneous[...]

  • Pagina 64

    Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-4 Operating Instructions SIMOVERT MASTERDRIVES AFE The following example shows the sequence of operat or inputs via the PMU required to select operating m ode "Reactive power compensation". P Ê Ì P052 ∇ Ê Ì ∇ Ê Ì P Ê Ì 0000 0001 0005 P052 Increas e num ber to P164: Sele[...]

  • Pagina 65

    01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-5 11.2 "S tart-up" parameterization P050 = Select language: 0 = Deutsch , 1 = English, 2 = Es panol, 3 = Frac ais, 4 = Italian o P051 = 3 A ccess level "Expert M ode" Define and parameterize option bo ards: Option boards: 0[...]

  • Pagina 66

    Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 11.2.1 Function selection (P052) Start-up functions are selected via parameter P052 . These provide start-up variants specially adapted to start-up mode. Access sta ge 2 (P051 = 2) must be en abled and the AFE infeed must not be set to OPERA[...]

  • Pagina 67

    01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-7 11.2.3 Initialization (ML FB input) (P052 = 2) This function is used to alter the order number (device type) of the converter. "Initialization" can be select ed in operating states CONTROL SETTINGS (005), FAULT (007), STARTING LOCK[...]

  • Pagina 68

    Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-8 Operating Instructions SIMOVERT MASTERDRIVES AFE P052 = 0 Select "Return" The operating display appears and, if the MLFB has been altered, the f ollowing param eters ar e set to new values: Converter and m otor da ta (as der ived fr om c onverter MLFB (P070) ) and open-loop and c[...]

  • Pagina 69

    01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-9 11.2.5 Hardware conf iguration (P052 = 4) The purpose of this function is to define option bo ards (SCB, TSY, CB, TB) installed in the electron ics box of the converter. The "Hardware configuratio n" function can be selected in the[...]

  • Pagina 70

    Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-10 Operating Instructions SIMOVERT MASTERDRIVES AFE P052 = 5 Select "Closed-loop control settings" (see Sect ion "Closed-loo p control s ettings") P052 = 0 Select "Return" The operating display (r000) appea rs. At the sam e time, param eters and internal quant i[...]

  • Pagina 71

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-1 12 Parameter List General Visualization Parameters to 49 Analog Input/Output from 650 General Parameters from 50 In terface Configurati on from 680 Drive Data from 70 Diag nostic Functions from 720 Hardware Configuration from 89 Gating Un it f[...]

  • Pagina 72

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.1 General visuali zation pa rameters PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r000 Oper ation D isplay Displays the operating status, fault and alarm messages[...]

  • Pagina 73

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-3 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r012 CHex Base/Reserve Basic/reserve settings of t he process data connections for setpoints and control word bits Param[...]

  • Pagina 74

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.2 General parameters PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P050 * 32Hex Language Plain text display language on th e optional OP operator panel and in the [...]

  • Pagina 75

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-5 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P053 * 35Hex Parameter access Release of interfaces for parameterization. This parameter can always be written at any ti[...]

  • Pagina 76

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.3 Drive data PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P070 * 46Hex MLFB(6SE70..) MLFB (order number) of basic unit For parameter values, see Section "Ini[...]

  • Pagina 77

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-7 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P081 51Hex Line filter L/mH Inductance L of AFE filter reactor in mH. Type=O2; PKW: 1HEX=0.001 PZD Gr.: 0 0.000 to 20.00[...]

  • Pagina 78

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-8 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.4 Hardware configuration PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P090 * 5AHex Board Position 2 PCB in slot #2 (right) of the electronics box Parameter values[...]

  • Pagina 79

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-9 12.5 Closed-loop control PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P120 78Hex CosPhi set Power factor cos(PHI) setpoint. Parameter values: 0.800 ... 1.00 0 ⇒ in[...]

  • Pagina 80

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-10 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P131 83Hex Vd regulator Ti Integration time constant of the DC-link voltage (Vd) controller RDS(2) parameter Type=O2; P[...]

  • Pagina 81

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-11 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P155 9BHex max. t. pow.fail Maximum time until the power failure fault (F009) or line supply undervoltage fault (F004) [...]

  • Pagina 82

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-12 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P173 ADHex Imax Maximum current (fundamental r.m.s.) Setpoint for current limitation (Imax controller) to protect the A[...]

  • Pagina 83

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-13 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r303 12FHex Vd(act) Actual unsmoothed DC-link voltage value Analog output: 100 % with code number (PWE) = 4 x P071 Type[...]

  • Pagina 84

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-14 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.6 Functions PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P366 16EHex Aut o R es ta rt Automatic restart (WEA) after power failure Parameter values: 0 = Inhibited[...]

  • Pagina 85

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-15 12.7 Setpoint channel PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P443 * 1BBHex Src. Ud (set) Source for the DC-link voltage setpoint. Parameter values: 1001: Fixe[...]

  • Pagina 86

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-16 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P517 205Hex SetActValDev.Ud Setpoint/actual value deviation in DC-link voltage Vd In the case of a large deviation betw[...]

  • Pagina 87

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-17 12.8 Control and st atus bit connections PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r550 226Hex Control Word 1 Display of control word 1, bits 0 to 15 (see Sec ti[...]

  • Pagina 88

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-18 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P557 * 22DHex Src3 OFF2 (coast) Source 3 of the OFF2 control command (control word 1, bit 1) See P555 for description B[...]

  • Pagina 89

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-19 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P569 * 239Hex Src Jog2 ON Source for the Inching 2 setpoint (control word 1, bit 8) See Section "Control word"[...]

  • Pagina 90

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-20 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P578 * 242Hex Src. RDS bit 0 Source for bit 0 for selection of reserve data set (RDS) (control word 2, bit 18) Paramete[...]

  • Pagina 91

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-21 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P589 * 24DHex Src No Ext Warn2 Source for control command "External alarm 2" (control word 2, bit 29) Paramet[...]

  • Pagina 92

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-22 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P604 * 25CHex Dst NO OFF2 Destination of the status bit 'No OFF2 command' (status word 1, bit 4) Parameter va[...]

  • Pagina 93

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-23 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P618 * 26AHex DstCurrLimAct. Destination of the status bit "Current limit active' (status word 2, Bit 18) Not[...]

  • Pagina 94

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-24 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P624 * 270Hex DstWar OvertmpA FE Destination of the status bit "I nverter overtemperat ure alarm" (status wor[...]

  • Pagina 95

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-25 12.9 Analog inputs/outputs PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P655 * 28FHex CU A A na O ut Ac t Va l Actual value output via the analog output of the CUSA[...]

  • Pagina 96

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-26 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P661 295Hex SCI AnaInSmooth Smoothing time constant of analog inputs on SCI boards Formula: T=2 ms x 2 P661 Indices: Se[...]

  • Pagina 97

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-27 12.10 Interface configuration PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P680 * 2A8Hex SCom1 Act Value Output of actual values via serial interface SST1 Defines w[...]

  • Pagina 98

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-28 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P685 * 2ADHex SCom/SCB PCV Number of words (16-bit) in PKW section in the net data block of the telegram (see Section &[...]

  • Pagina 99

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-29 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P690 * 2B2Hex SCB Act Values Output of actual values via the serial interface of the SCB board Defines which parameter [...]

  • Pagina 100

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-30 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P696 2B8Hex CB Parameter 1 Communication Board parameter 1 Refer to documentation of installed COM BOARD Setting instru[...]

  • Pagina 101

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-31 12.11 Diagnostic functions PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r720 2D0Hex SW Version Software version of the PCBs in positions 1 to 3 of the electronics b[...]

  • Pagina 102

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-32 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r725 2D5Hex CalcTimeHeadroom Available CPU computation time reserve on CUSA as % of total computing power. Relevant par[...]

  • Pagina 103

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-33 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r731 2DBHex CB/TB Diagnosis For detailed information please refer to the operating manuals of the relevant Com board (C[...]

  • Pagina 104

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-34 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.12 Gating unit PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r764 2FCHex Modulation Depth Control factor of closed-loop control for gating unit. Analog output: 10[...]

  • Pagina 105

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-35 12.14 Profile parameters PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P918 396Hex CB Bus Address Protocol-dependent bus address for communication boards: see board [...]

  • Pagina 106

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-36 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r947 3B3Hex Fault Memory Display of faults which caused th e last 8 fault events (r748); up to 8 faults can be stored f[...]

  • Pagina 107

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-37 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P952 * 3B8Hex # of Faults Number of faults Contains the number of fault events stored in the fault memory (max. 8). If [...]

  • Pagina 108

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-38 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r958 3BEHex Warning Param6 Alarm parameter 6 (CB alarms) If one of the alarms numbered from 81 to 96 occurs , the corre[...]

  • Pagina 109

    01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-39 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P970 * 3CAHex Factory Settings Parameter reset to factory settings Parameter values: 0: Parameter reset: All parameters[...]

  • Pagina 110

    Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-40 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r986 3DAHex Par # List Pt7 List of available parameter numbers, part 7 See r980. Type=O2; PKW: 1HEX=1.0 PZD Gr.: 0 116 [...]

  • Pagina 111

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-1 13 Control and S tatus W ords 13.1 Control word Operating states can be read in vi sualization paramet er r001: e.g. READY FOR ON: r001 = 009 The functional sequence s are described in the order in whi ch they occur. An individual so[...]

  • Pagina 112

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-2 Operating Instructions SIMOVERT MASTERDRIVES AFE ♦ Multiple connections are permitted! ♦ The control word commands "OFF2 “ (bit 1), "OFF3“ (bit 2) and "Acknowledge“ (bit 7) are always simultaneously effective from 3 sources (can be parameterized)! ♦ "[...]

  • Pagina 113

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-3 13.1.2 Control word 1 (visualiz ation parameter r550 or r967) The factory setting applies only when P077 = 0. Designation High / Low values Parameter No. Fact. setting Possible Bit No. (meaning) (1 = High, 0 = Low ) GRD (RES) GRD (RE[...]

  • Pagina 114

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.1.3 Control word 2 (vis ualization parameter r551) The factory setting applies only when P077 = 0. Designation High / Low values Parameter No. Fact. setting Possible Bit No. (meaning) (1 = High, 0 = Low ) GRD (RES) GRD (RES) sourc[...]

  • Pagina 115

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-5 13.1.4 Sources for control words 1 and 2 Table X (external terminals) 1001 BE1 terminal -X101:16 1002 BE2 terminal -X101:17 1003 BE3 terminal -X101:18 1004 Assi g ned 1005 BE5 terminal -X101:20 4101 SCI, slave1, terminal 01 4102 SCI,[...]

  • Pagina 116

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-6 Operating Instructions SIMOVERT MASTERDRIVES AFE Table A 0000 Constant value 0 1010 PMU o p erator p anel 2001 SCom1 word 1 3001 CB/TB word 1 4501 SCB1/2 p ee r -to- p eer, SCB2 USS, word 1 4502 SCB1/2 p ee r -to- p eer, word 2 4503 SCB1/2 p ee r -to- p eer, word 3 4504 SCB1/2 p ee[...]

  • Pagina 117

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-7 Table E 0000 Constant value 0 0001 Constant value 1 1010 PMU o p erator p anel 2001 SCom1 word 1 3001 CB/TB word 1 4501 SCB1/2 p ee r -to- p eer, SCB2 USS, w o r d 1 4502 SCB1/2 p ee r -to- p eer, word 2 4503 SCB1/2 p ee r -to- p eer[...]

  • Pagina 118

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-8 Operating Instructions SIMOVERT MASTERDRIVES AFE Table I 0000 Constant value 0 0001 Constant value 1 2004 SCom1 word 4 3004 CB/TB word 4 4501 SCB1/2 p ee r -to- p eer, word 1 4502 SCB1/2 p ee r -to- p eer, word 2 4503 SCB1/2 p ee r -to- p eer, word 3 4504 SCB1/2 p ee r -to- p eer, [...]

  • Pagina 119

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-9 13.1.5 Description of t he control word bits Bit 0: ON / OFF1 command ( ↑ "ON") / (L "OFF1") Positive edge change from L to H (L → H) in READY FOR ON (009) state. ♦ PRECHARGING (010) The precharging contacto[...]

  • Pagina 120

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-10 Operating Instructions SIMOVERT MASTERDRIVES AFE Bit 7: Acknowledg e command ( ↑ "Ackno wledge") Positive edge change from L to H (L → H) in FAULT (007) stat e. ♦ Reset all current faults after they have been transferred to the diagnostics memory. ♦ STARTING LOCK[...]

  • Pagina 121

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-11 Bit 11: Reserv ed Bit 12: Regenerativ e feedback enable command (H "Regenerative feedba ck enable") HIGH signal ♦ Regenerative feedback o peration is enabled. Bit 13: Reserv ed Bit 14: Reserv ed Bit 15: External fault 1 [...]

  • Pagina 122

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-12 Operating Instructions SIMOVERT MASTERDRIVES AFE Bit 21: Reserv ed Bit 22: Reserv ed Bit 23: Reserv ed Bit 24: Reserv ed Bit 25: Reserv ed Bit 26: External fault 2 comm and (L "External fault 2") LOW signal; Command is not activated until converter switches to READY TO R[...]

  • Pagina 123

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-13 Bit 30: Select reserve/basic setting (H "R eserv e setting") / (L "Basic setting") HIGH signal ♦ The parameter values for the rese rve setting for the control word itself, the setpoint channel and cl osed-l oop[...]

  • Pagina 124

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-14 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.2 S tatus word Status words are proce ss data as def ined by the explanation in Section "Process data". A "destination" at which the bit stat us can be identified (digital outputs of CUSA, SCI 1/2 terminals, T[...]

  • Pagina 125

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-15 Bit # Value 1 = High Select Value Destin ation 0 = Low destin. Bit 0 1 Ready for ON P600. x 0 Not ready for ON x = 1 0000 No destinati on Bit 1 1 Ready to RUN P601. x 1001 Assigned (precharging) 0 Not ready to RUN 1002 Assigned (mai[...]

  • Pagina 126

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-16 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.2.2 Status word 2 (vis ualization parameter r553) PMU display "Status word 2" 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 16[...]

  • Pagina 127

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-17 Bit # Value 1 = High Select Value Destination 0 = Low destin. Bit 16 Reserv ed x = 1 0000 No destination Bit 17 Reserved 1001 Assigned Bit 18 2) 1 Current limit ac tive P618. x 1002 Assigned 0 Current limit not active 1003 BA3, -X10[...]

  • Pagina 128

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-18 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.2.3 Description of t he status word bits Bit 0: "Ready for ON" signal (H ) STARTING LOCKOUT (008) or READY FOR ON (009) state ♦ The power supply, open-l oop control and closed -loop control are all operative. ♦ The [...]

  • Pagina 129

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-19 Bit 6: "Starting lockout" signal (H) STARTING LOCKOUT state (008) ♦ The power supply, open-l oop control and closed -loop control are all operative. ♦ The signal is continuously applie d as long as an OFF2 command v ia[...]

  • Pagina 130

    Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-20 Operating Instructions SIMOVERT MASTERDRIVES AFE Bit 13: Reserv ed Bit 14: "Motor operation" signal (L) AFE operates in rectifier mode (active current >= 0) Bit 15: Reserv ed Bit 16: Reserv ed Bit 17: Reserv ed Bit 18: "Current limit active" signal (L) AFE o[...]

  • Pagina 131

    01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-21 Bit 23: "AFE overtem perature fault" signal (H) "Inverter temperature too high" fault (F023) ♦ The inverter temperature limit value has been exceeded. See Section "Fault and alarm messages" . Output a[...]

  • Pagina 132

    01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-1 14 Fault s and Alarms 14.1 Faults General information about faults The available information for ea ch fault event comprises the following parameters: Parameter r947 Fault number r949 Fault value r951 Fault texts P952 Number of faults r748 [...]

  • Pagina 133

    Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Fault messages No. Descrip tion of fault Remedial measures F006 DC-link overvoltage The drive has been shut down due to an excessive DC- link voltage. Line voltage range I Shutdo wn threshold 380 V to 460 V I approx. 820 V 500 V to 575 V I [...]

  • Pagina 134

    01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-3 Fault messages No. Descrip tion of fault Remedial measures F025 UCE Ph. L1 A UCE shutdown has occurred in phase L1 Check • phase L1 for short circuit or earth fault (-X2:U2 - including motor). • the contacts on the CU . F026 UCE Ph. L2 [...]

  • Pagina 135

    Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-4 Operating Instructions SIMOVERT MASTERDRIVES AFE Fault messages No. Descrip tion of fault Remedial measures F046 Par.con. Switch the device off and on again. Replace the CUSA (-A10) board. F047 Int.comp.time Replace the CUSA (-A10) board. F048 Interf. pulse fre q Fault during power O FF o[...]

  • Pagina 136

    01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-5 Fault messages No. Descrip tion of fault Remedial measures F076 Aninput1 SL2 Amps at analog input 1, sl ave2, have dropped below 4mA Check connection from signal source to SCI1 (slave1) -X428:4, 5. F077 Aninput2 SL2 Amps at analog input 2, [...]

  • Pagina 137

    Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 14.2 Alarms An alarm message is periodically displayed on the PMU by A=alarm and a 3-digit number. An alarm cannot be acknowledged. It is automatically deleted once the ca use has been rem oved. Several alarms can be active simultaneously, [...]

  • Pagina 138

    01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-7 Alarm messages Ala rm No. Param- No. Bit No. Description Remedial measures A039 P955 6 Electrical off The electronics voltage supply is not o.k. Check • the ext. 24 V voltage supply -G1 • the digital input and signal lead for monitoring[...]

  • Pagina 139

    Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-8 Operating Instructions SIMOVERT MASTERDRIVES AFE Alarm messages Ala rm No. Param- No. Bit No. Description Remedial measures A065 P957 0 WEA active The WEA option (P366) restarts the drive. No time monitor is activated when the DC link is precharging. The automatic restart process can be a[...]

  • Pagina 140

    01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-1 15 Maintenance SIMOVERT MASTERDRIVES units ar e operated at high voltages. All work carried out on or with the equipment mu st conform to all the national electrical codes (VBG 4 in Germany). Maintenance and service work ma y only be executed by [...]

  • Pagina 141

    Maintenance 01.2004 6SE7087-6CX86-2BA1 Siemens AG 15-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 15.1 Electrical components 15.1.1 AFE basic mains module Position Equipment designation Brief description 1 -A52 VSB module Line angle and voltage sensing 6SE7090-0XX84-1GA1 2 -K1 Main contactor Main contactor 230 V, 50/60 Hz 3RT1476-6AP36 (for 3[...]

  • Pagina 142

    01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-3 15.2 AFE inverter maintenance 15.2.1 Replacing the fan The fan is designed for an operating time of L 10 ≥ 35 000 ho urs at an ambient temperature of T u = 40 °C. It should be replaced in good time to maintain the availability of the unit. The[...]

  • Pagina 143

    Maintenance 01.2004 6SE7087-6CX86-2BA1 Siemens AG 15-4 Operating Instructions SIMOVERT MASTERDRIVES AFE ♦ Disconnect the cable conn ections and terminals o n the fan. ♦ Remove the fan support plate from the fan assembly and deta ch the fan from the support plate. ♦ Install the new fan assembly in reverse sequen ce. Prior to start-up, check th[...]

  • Pagina 144

    01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-5 15.2.4 Replacing the capacitor battery The unit is an assembly which consists of the DC link capacitors, the capacitor support and the DC link bus module. ♦ Remove the terminal for the balancing resi stor (cable eye M6). ♦ Undo the mechanical[...]

  • Pagina 145

    Maintenance 01.2004 6SE7087-6CX86-2BA1 Siemens AG 15-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 15.2.5 Replacing the PMU ♦ Remove the grounding cable on the si de. ♦ Press the spring catches o n the adapter section caref ully together, remove the PMU with adapter from the e lectronics box. ♦ Withdraw connector X108 on the CUx board. ?[...]

  • Pagina 146

    01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-7 15.3 Fuses 15.3.1 Fan fuses for AFE inverters Line voltage 3AC 380 V to 460 V Order No. 6SE70.. Fan Fuse (F101 / F102) 35-1TJ80 FNQ-R-5 36-0TJ80 FNQ-R-5 Order No. 6SE70.. Fan Fuse (F1 / F2) 32-1EG80 32-1EG80-1AA0 FNQ-R-5 32-6EG80 32-6EG80-1AA0 FN[...]

  • Pagina 147

    01.2004 Forming Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 16-1 16 Forming For units in the 400 V and 690 V voltage classes (cf. 9th digit of the MLFB, letter E or H), the DC link capacitors m ust be formed again after an idle period of more than 2 years. For units in the 500 V voltage class (cf. 9th digit of the[...]

  • Pagina 148

    Forming 01.2004 6SE7087-6CX86-2BA1 Siemens AG 16-2 Operating Instructions SIMOVERT MASTERDRIVES AFE P408 Set forming time ( 60.0 to 600.0 min utes) P052 = 20 Select "Form DC link" P ke y The op erating display appears: The AFE m ust be switched on within 20 s or else a shut down on faults (F091) will occur ( fault value 4) . Swi tch on AF[...]

  • Pagina 149

    01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-1 17 T echnical Dat a CleanPower filter AFE basic mains module Fig. 17-1 AFE basic mains module mounted on CleanPower filter Fig. 17-2 AFE reactor for AFE inverters 510...590 A / 400 V[...]

  • Pagina 150

    Technical Data 01.2004 6SE7087-6CX86-2BA1 Siemens AG 17-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 17.1 AFE basic mains module and CleanPower filter EU low-voltage directive 73/23/EEC and RL93/68/EEC EN 50178 EU machine directive 89/392/ EEC EN 60204-1 Type of cooling Air cooling Permissible ambient and cooling- medium temperature • durin[...]

  • Pagina 151

    01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-3 Supply system type T N-C; 3/PEN Mains voltage 3AC 400 V Mains frequency 50 Hz / 60 Hz Rated operating voltage 3 AC 380 (-20 %) V to 3AC 460 (+5 %) V) Rated current 210 A, 260 A, 315 A, 370 A, 510...590 A Power loss CleanPower filter Approx. 30[...]

  • Pagina 152

    Technical Data 01.2004 6SE7087-6CX86-2BA1 Siemens AG 17-4 Operating Instructions SIMOVERT MASTERDRIVES AFE The electronic and asso ciated electrical comp onents are installed according to the recommendations of the relevant com ponent manufacturers. The characteristics specified in Section 3 apply onl y on condition that the low-voltage switchgea r[...]

  • Pagina 153

    01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-5 17.4 AFE inverter EU low-voltage directive 73/23/EEC and RL93/68/EEC EN 50178 EU directive EMC 89/336/EEC EN 61800-3 EU machine directive 89/392/ EEC EN 602 04-1 Approval UL: E 145 153 CSA: LR 21 927 Type of cooling Air cooli ng with built-in [...]

  • Pagina 154

    Technical Data 01.2004 6SE7087-6CX86-2BA1 Siemens AG 17-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 10 30 50 0 25 50 75 100 0 Cooling-medi um tem p. in ° C Permis sible rat ed current in % 20 40 Temp [°C] Derating factor K 2 50 0.76 0.879 45 1.125 * 35 1.0 40 1.25 * 30 1.375 * 25 1000 2000 3000 4000 0 75 100 50 Inst allat ion altit ude abo[...]

  • Pagina 155

    01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-7 Designation Value Order No. 6SE70... 35-1EJ80 36-0EJ 80 33-7EG80 33-2EG80 32-6EG80 32-1EG8 0 Rated voltage [V] • Input • Output 3 AC 380 (-20 %) to 460 (+5 %) DC to 740 Rated frequency [Hz] 50 / 60 Rated current [A] • Input 3 AC • Outp[...]

  • Pagina 156

    01.2004 Environmental Friendliness Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 18-1 18 Environmental Friendliness The number of component s has been significa ntly reduced over earlier converter series by the use of highly integrated com ponents and the modular design of the complete se ries. Thus, the energy requ[...]

  • Pagina 157

    01.2004 Certificates Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 19-1 19 Certificates Autom ation an d Dr ives Confir mation Er langen, 01. 05.19 98 This confir ms that Eq uipment AC drive conver ter • Type SI MOVE RT MASTERDRIVES • O rder No. 6S E70 ... • S ervic e wo rk in operat ion is onl y per mis sible[...]

  • Pagina 158

    Certificates 01.2004 6SE7087-6CX86-2BA1 Siemens AG 19-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Te st cer tif ic ate Erlan gen, 01.05. 19 98 Eq uipment • Type • Ord er No. : A C d r iv e c onv ert e r SI MOVERT MASTERDRIV ES 6SE70 ... 1) The r outine test ing accord ing t o thes e test inst ructions 475 1 00. 900 0.00 QP 476 1 00. 900 [...]

  • Pagina 159

    01.2004 Certificates Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 19-3 This declaration does not guarantee any features. A&S DS 4 102x Page 1 of 1 *) acc. to EN 10204 (DIN 50049) Cop yright (  ) SIEMENS AG 1997 All rights reserved EN 61800- 3 10-1 996 EN 61000- 4-2 ( old IEC 801-2 ) EN 61000- 4-4 ( old IEC 8[...]

  • Pagina 160

    01.2004 Appendix Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 20-1 20 Appendix Order number: 6SE708x-xCX86-2BA1 x-x stands for language code e.g. 0-0 for German SIMOVERT MASTERDRIVES Active Front End (AFE) AFE rectifier/regenerative feedback unit AC-DC Chassis unit construction t ypes G and J 400 V / 210 A to 590 A[...]

  • Pagina 161

    [...]

  • Pagina 162

    [...]

  • Pagina 163

    [...]

  • Pagina 164

    nderung )%')!'%' Datum 1 Name Datum Bearb. Gepr. Norm 16.04. 2 003 Heeg 2 Urspr. SIMOVERT -MASTE RDRIVES A FE Modulare Netza nbindung 3 Ers.f. Ers.d. 4 SIEMENS AG A&D SE W KC Netzbasi smodul (315kW) Stromlau fplan 56 MLFB-Nr.6S E7036- 0ED83-2NB 1 A5E0020098 6 B-A1 7 = + 8 Bl. 1 Bl. 1 vom Net zansch luá Kunde PE 3PE A[...]

  • Pagina 165

    nderung )%')!'%' Datum 1 Name Datum Bearb. Gepr. Norm 16.04.2003 Heeg 2 Urspr. SIMOVERT -MASTE RDRIVES A FE Modulare Netza nbindung 3 Ers.f. Ers.d. 4 SIEMENS AG A&D SE W KC Clean Po wer Fi lter (315kW) Stromlau fplan 56 MLFB-Nr.6S E7036- 0EE87-1FC 5 A5E0020099 9 B-A1 7 = + 8 Bl. 1 Bl. 1 1) -C5 pa rallel geschalt et zu[...]

  • Pagina 166

    Siemens AG A utomatisierungs- un d Antriebstechnik Motion Control Systems Postfach 3180, D – 9 1050 Erlangen Bundesrepublik D eutschland www.ad.siemens.de © Siemens AG 2004 Subject to change Order No.: 6SE7087-6CX86- 2BA1 Printed in Germany The following editions have been publi shed so far: Edition Internal Item Number AB A5E00243916 Version AB[...]