State Water Heaters SBD71 120 manuale d’uso
- Visualizza on-line o scarica il manuale
- 56 pagine
- 2.22 mb
Vai alla pagina of
Manuali d’uso simili
-
Water Heater
State Water Heaters 50 YRVIT
2 pagine 0.05 mb -
Water Heater
State Water Heaters SUF 130-300/400
1 pagine 0.23 mb -
Water Heater
State Water Heaters 196114-000
16 pagine 0.19 mb -
Water Heater
State Water Heaters Select SMGSS01207
2 pagine 0.32 mb -
Water Heater
State Water Heaters GP6 50 YTVIT
4 pagine 0.06 mb -
Water Heater
State Water Heaters Select SRGSS01706
2 pagine 0.56 mb -
Water Heater
State Water Heaters SBD100400NE/A
8 pagine 0.56 mb -
Water Heater
State Water Heaters 195115-000
2 pagine 0.08 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso State Water Heaters SBD71 120. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica State Water Heaters SBD71 120 o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso State Water Heaters SBD71 120 descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso State Water Heaters SBD71 120 dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo State Water Heaters SBD71 120
- nome del fabbricante e anno di fabbricazione State Water Heaters SBD71 120
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature State Water Heaters SBD71 120
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio State Water Heaters SBD71 120 non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti State Water Heaters SBD71 120 e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio State Water Heaters in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche State Water Heaters SBD71 120, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo State Water Heaters SBD71 120, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso State Water Heaters SBD71 120. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
MODELS COVERED SBD71 120 Through SBD85 500 T h e Ex p e r t’ s C h o ic e® COMMERCIAL T h e Ex p e r t’ s C h o ic e® COMMERCIAL Self Cleaning Commercial Gas W ater Heaters with Flue Damper and Electronic Ignition Part Number STC-072 Printed in the U.S.A. - 0106 State Water Heaters 500 T ennessee W altz Parkway Ashland City , TN 37015 800-365[...]
-
Pagina 2
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 1 SBD HANDBOOK TABLE OF CONTENTS PAGE PAGE Troubleshooting (continued) Introduction 1-2 Troubleshooting the Efflkal 28-30 W i r e H a r n e s s T e s t 3 1 Installation 3 IID Module 32 Clearances 4 Pilot Spark 33 Air Requirements 5-8 Pilot Valve 34-35 Conta[...]
-
Pagina 3
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 2 Qualifications: Installation or service of this wa ter heater requires ability equivalent to that of a licensed tradesman in the field involved. Plumbing, air supply, venting, gas supply and electrical testing skills are required. Tools Required: • Phil[...]
-
Pagina 4
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 3 INSTALLATION This portion of the handbook will review some oft en overlooked installation considerations, taking note of necessary installation requirements for the SBD 71120 through SBD 85500 model heaters. The installation manual cove rs most of these i[...]
-
Pagina 5
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 4 EXTERIOR CLEARANCE This illustrates the exterior roof clearances for SBD units with natural draft venting. The vent shall extend at least 3 feet above the hi ghest point where it passes through a roof of a building, and at least 2 feet higher than any por[...]
-
Pagina 6
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 5 AIR FOR COMBUSTION 10 CUBIC FEET OF AIR PER 1,000 BTU Stoichiometric or theoretical complete com bustion requires 10 cubic feet of air per 1000 BTUH input of the gas input. The National Fuel Gas Code also recommends an additional 2.5 cu.ft. of "exces[...]
-
Pagina 7
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 6 MAKE-UP AIR DIRECT COMMUNICATION A fresh supply of make-up air for combusti on can be supplied to t he heater through make- up air ducts which directly communicate wit h the out of doors. Tw o openings are required - one within 12 inches of the top of the[...]
-
Pagina 8
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 7 MAKE-UP AIR VERTICAL DUCTS Often it is more practical to install vertical make-up air ducts to the out doors. Again, two openings are required - one within 12 inches of the top of the enclosure and one within twelve inches of the bottom of the enclosu re.[...]
-
Pagina 9
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 8 INSUFFICIENT MAKE-UP AIR BACKDRAFT Insufficient make-up air is a major cause of combustion problems. One common example is in a restaurant installation where exhaust vent equipment was not considered in sizing make-up air requirements. This may result in [...]
-
Pagina 10
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 9 CONTAMINATED AIR Along with adequate make-up air, the quality of the air is important. Contaminants in combustion air can lead to premature heat er failure. Vapors from bleaches, soaps, waxes, salts, etc. are draw n into the combustion chamber with the ma[...]
-
Pagina 11
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 10 GAS PRESSURE REQUIREMENTS Natural Gas Propane Gas Maximum Supply Pressure 10.5" W.C. 13.8" W.C. Minimum Supply Pressure 5.0" W.C. 11" W.C. Manifold Pressure 4.0 " W.C. 10" W.C. The supply gas pressure is normally measured at[...]
-
Pagina 12
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 11 SBD GAS VALVE The gas valves used on all SBD water heaters are 24 volt AC combination step opening gas valves. They incorporate the pilot valve, main valve, and gas pressure regulators into one body. The inlet view of the valve features a filt er screen [...]
-
Pagina 13
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 12 VENTING Atmospheric, Single, and Multiple Heaters All SBD water heaters are classified by ANSI as category I (non-condensing, negative pressure venting) appliances. They are approved for type B vent. For larger applications, SBD water heaters can be comm[...]
-
Pagina 14
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 13 Nine Rules for Good Vents (continued) 2. The diameter of a vent pipe should NEVER be reduced, no matter what the circumstances. 3. In some cases it may be necessary to run a vent larger than the draft diverter outlet. 4. Take the maximum vertical rise po[...]
-
Pagina 15
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 14 Nine Rules for Good Vents (continued) 6. Horizontal pipe should be sloped upward at a minimum of ¼” per foot. 7. Horizontal elements should be limited to 75% of the vertical rise of the vent above the connection. 8. Flue gases must be kept hot for pro[...]
-
Pagina 16
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 15 POWER VENT KITS FOR SIDEWALL VENTING Water Heater Models Part Number SBD-120-200 193933-0 SBD-250-500 193933-1 SBD water heaters can be used with power vent kits for sidewall venting. State offers power vent kits for use on installations with a maximum o[...]
-
Pagina 17
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 16 SBD SEQUENCE OF OPERATION 1. Thermostat calls for heat 2. Flue damper opens 3. Intermittent Ignition Control 5. Main gas valve opens 7. Thermostat satisfies 4. Pilot gas opens, Pilot sparks and flame proves 6. Main burner ignites 8. Main and pilot burner[...]
-
Pagina 18
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 17 SBD ELECTRICAL SEQUENCE 100 – 109 Series[...]
-
Pagina 19
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 18 SBD ELECTRICAL SEQUENCE OF OPERATION 115/60/12A IID Module (24V) Receives Voltage Module (PV) Terminal Sends 24V to Pilot Coil Module (Spark) Sends 10,000V Spark to Pilot Spark Stops Damper Motor Energized and Damper Closed Power to Damper #2 Interru p t[...]
-
Pagina 20
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 19 TROUBLESHOOTING SBD WATER HEATERS To troubleshoot a SBD water heater check that: • 120 VAC is supplied to the heater • the tank is full of water • gas is supplied to the unit STEP 1 TEST THE TRANSFORMER STEP 1 - TO TEST THE TRANSFORMER - Using a mu[...]
-
Pagina 21
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 20 STEP 2 HIGH LIMIT, LEFT TERMINAL TEST STEP 2. HIGH LIMIT, LEFT TERMINAL TEST. Test for 24 VAC between the left high limit terminal and ground. IF THEN The meter does not read 24 VAC: • Check wiring between transformer and high limit. The meter reads 24[...]
-
Pagina 22
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 21 STEP 3 TEST HIGH LIMIT RIGHT TERMINAL STEP 3. TO TEST HIGH LIMIT RIGHT TERMINAL . Ensure that the jumper wire between the high limit and thermostat is c onnected, and the damper motor power line is connected. Test for 24 VAC between the high limit right [...]
-
Pagina 23
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 22 STEP 4 INSPECT THE DAMPER STEP 4. INSPECT THE DAMPER. Lower the thermostat setting so the unit will not be calling for heat, then inspect the damper. IF THEN If the damper is open: • Go to step 5. If the damper is closed: • Go to step 7. Note: If the[...]
-
Pagina 24
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 23 STEP 6 PC BOARD MOTOR TEST STEP 6. PC BOARD/MOTOR TEST. Check for 24 VAC between the two motor lead terminals of the PC board. Disconnect the wires for this test. IF THEN 24 VAC is not present: • Replace the Damper Drive (part # 194484) and go to step [...]
-
Pagina 25
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 24 STEP 7 THERMOSTAT TEST STEP 7. THERMOSTAT TEST. Set the thermostat to call for heat. Using your multimeter, test for 24 VAC between right terminal and ground. IF THEN The meter does not read 24 VAC and the jumper wire between the high limit and the t her[...]
-
Pagina 26
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 25 EFFIKAL DAMPER The wiring colors from the damper PC Board ar e different colors than the wires on the heater wiring harness. The male/female plugs to connect the damper board to the heater harness join in only one way. Adapter not necessary on production[...]
-
Pagina 27
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 26 HARNESS CHART Heater Harness Function Damper Harness Black 24V Hot 1-Brown Yellow 24V from Thermostat 2-Orange Red 24V from damper 3-Yellow White 24V common 4-Black NORMAL OPERATION Condition: • Heater on standby • Damper closed • High Limit closed[...]
-
Pagina 28
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 27 NORMAL OPERATION (continued) Condition: • Thermostat closed, damper in process of opening STEP 8A TEST FOR 24VAC BETWEEN BLACK AND ORANGE IF THEN 24VAC is present Continue to Step 8B. 24VAC is not present See Troubleshooting Step 9B. Condition: • The[...]
-
Pagina 29
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 28 TROUBLESHOOTING THE EFFIKAL DAMPER Condition: Thermostat closed, damper closed STEP 9A TEST BETWEEN BLACK (COMMON) AND BROWN ON THE DAMPER BOARD IF THEN 24VAC is present This is correct 24VAC is not present • See Steps 1 thru 4 Check the harness plugs [...]
-
Pagina 30
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 29 TROUBLESHOOTING THE EFFIKAL DAMPER (continued) Condition: Thermostat closed, damper open. STEP 9B A1 IS CORRECT, CHECK SERVICE SWITCH POSITION IF THEN Switch is incorrect position Replace damper board/motor assembly. Switch is not in correct position •[...]
-
Pagina 31
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 30 TROUBLESHOOTING THE EFFIKAL DAMPER (continued) Condition: Thermostat closed, damper is open fully STEP 10A TEST FOR 24VAC BETWEEN BLACK AND YELLOW IF THEN 24VAC is present This is correct – continue to Step 11 24VAC is not present • See Step 9B. • [...]
-
Pagina 32
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 31 STEP 11 WIRE HARNESS TEST STEP 11. WIRE HARNESS TEST. Test for 24 VAC between terminal 24V on the IID module, and 24V GND. IF THEN 24 VAC is not present: • Check the wiring harness. 24 VAC is present: • Go to step 12. Note: This test may be easier to[...]
-
Pagina 33
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 32 STEP 12 IID MODULE TEST STEP 12. IID MODULE TEST (Power to the Pilot Valve). Using a multimeter, test for 24 VAC between terminal PV and 24V (GND) on t he IID during the 90 second trial for ignition. IF THEN The meter does not read 24 VAC and the IID mod[...]
-
Pagina 34
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 33 STEP 13 PILOT SPARK TEST STEP 13. PILOT SPARK TEST. Visually check for spark at the pilot assembly. Note: The pilot burner mounts on the left side of the main burner. IF THEN The igniter is not sparking: Check for: • A 7/64” spark gap • Spark cable[...]
-
Pagina 35
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 34 STEP 14A PILOT VALVE - OHM TEST SBD 120 – 400 GAS VALVE STEP 14A. PILOT VALVE - OHM TEST. If pilot assembly is sparking but no pilot flame is established, disconnect the pilot valve solenoid leads. Using a multimeter, (set to read ohms) test for 20* oh[...]
-
Pagina 36
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 35 STEP 14B PILOT VALVE TEST – SBD 500 ONLY STEP 14B. PILOT VALVE TEST – SBD 500 ONLY. Testing the two coils of the Honeywell VR8404P 5004 gas valve used on the model SBD 500 only. Because of built in diodes, it is difficult to test for ohms resistance [...]
-
Pagina 37
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 36 STEP 15 MAIN BURNER TEST STEP 15. MAIN BURNER TEST. Visually check for main burner. IF THEN The main burner ignites: • Sequence is complete The main burner does not ignite • Go to step 16[...]
-
Pagina 38
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 37 STEP 16 FLAME RECTIFICATION STEP 16. FLAME RECTIFICATION Note: Flame rectification means that an alternating cu rrent (AC) signal is changed to a direct current (DC) signal. The pilot flame is the 'switch' which connects the pilot hood to the i[...]
-
Pagina 39
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 38 STEP 17 IID MODULE TEST Pilot is lit - Sparking has stopped. STEP 17. IID MODULE TEST (Power to the Main Valve). Using a multimeter, test for 24 VAC between terminal MV on the IID and 24V (GND). IF THEN 24 VAC is not present: • Replace the IID module. [...]
-
Pagina 40
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 39 STEP 18A MAIN GAS VALVE CHECK SBD 120 – 400 GAS VALVE STEP 18A. MAIN GAS VALVE CHECK. Disconnect wires from gas valve TH and TR terminals. Using a multimeter, test for 68 ohms plus or minus 5 between TH and TR on the main valve coil. IF THEN The meter [...]
-
Pagina 41
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 40 STEP 18B MAIN GAS VALVE COIL CHECK STEP 18B. MAIN GAS VALVE COIL CHECK – SBD 500 ONLY Condition: • Pilot lights • Sparking stops • No main burner ignition Test Procedure: • Power off • Disconnect red, main valve wire from module MV terminal ?[...]
-
Pagina 42
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 41 GENERAL SERVICE CHART CONDITION CAUSE SOLUTION DAMPER OPENS NO POWER TO IID MODULE . DAMPER NOT FULLY OPEN . DEFECTIVE PROTECTOR SWITCH .EFFIKAL – REPLACE DAMPER CONTROL ASSEMBLY . REPLACE DAMPER . REPLACE PC BOARD PILOT LIGHTS, SPARKS CONTINUOUSLY PIL[...]
-
Pagina 43
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 42 GENERAL QUESTIONS AND ANSWERS Q. What is unique about the Canadian – SBC-CGA – models vs. U.S. SBD models? A. The Canadian models have different dimensions to meet Canadian code requirements. Q: How much electrical power is required for a SBD water h[...]
-
Pagina 44
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 43 SBD MODELS 120 THRU 500A SERIES 110-111 GAS VALVES HONEYWELL VALVE SBD 500A EFFIKAL DAMPER DRIVE ASSEMBLY PARTIAL REPLACEMENT PARTS LIST MODELS SBD 120 THRU 500A: STANDARD AND ASME (A) SERIES 110/111 WHITE RODGERS VALVE SBC 120 – 400A[...]
-
Pagina 45
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 44 SBD MODELS 120 THRU 500A (continued) SERIES 110-111[...]
-
Pagina 46
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 45 SBD MODELS 120 THRU 500A (continued) SERIES 110-111 Series 110-111 1 ..........Flue Baffl e ................................. 193595 .............. 192199-3 ........... 193795-1 ......... 193696 .......... .... 193696 3 ..........Main Burner Orif ice Bra[...]
-
Pagina 47
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 46 SBD MODELS 120 THRU 500A (continued) SERIES 110-111 ITEM PARTS DESCRIPTION SBD81190NE S BD100199NES/A SBD100250NE/A S BD65251NE/A SBD100275NE/A 1 ..........Flue Baffl e ................................... 193795-1 ....... 193889 ................ 193595 .[...]
-
Pagina 48
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 47 SBD MODELS 120 THRU 500A (continued) SERIES 110-111 1 ........... Flue Baffle ........................................ 193595 ....................... 193696 ............................ 1 93995 ................ 193995 3 ........... Main Burner Orifice Br[...]
-
Pagina 49
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 48 SBD MODELS 120 THRU 500A (continued) SERIES 110-111 CGA CGA CGA CGA 1 ............. Flue Baffle ...................................... 193595........... 192199-3 ....... 193795-0 ......... 193696 193795-0 3 ............. Main Burner Orifice Bracket .....[...]
-
Pagina 50
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 49 SBD MODELS 120 THRU 500A (continued) SERIES 110-111 1 ............ Flue Baffle ..................................... 193889 ............ 193595 .............. 193595 .............. 193945 .. ....... 193595 3 ............ Main Bur ner Orifice Bra cket ...[...]
-
Pagina 51
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 50 SBD MODELS 120 THRU 500A (continued) SERIES 110-111 1 ............ Flue Baffl e ................................................... 193945 ........................ 193995 ................ ......... 193995 3 ............ Main Burner Orifice Bracket ......[...]
-
Pagina 52
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 51 COMPONENT PART INFORMATION NAME SPECIFICATIONS STATE PART NUMBERS DUAL CONTROLLER THERMOST AT 120-180 O RANGE, + 4 O , 5 O DIFFERENTIAL, LIQUID FILLED, ANTI- STACKING # 192828 HIGH LIMIT (ECO) OPENS - 205 O FIXED, MANUAL RESET BELOW 185 O GAS VALVE NATUR[...]
-
Pagina 53
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 52 SBD SERVICE CHECKLIST (This service checklist may be photo copied to assist with SBD service call.) This checklist is intended to aid the Servic e Agent in determini ng that the State SBD Water Heater has been properly installed and is operating correctl[...]
-
Pagina 54
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 53 V. WATER PIPING Is the system properly sized? yes no Is the system properly installed? yes no Are there any water leaks? yes no Does the installation have a recirculating system? yes no If so, is it operational? yes no VI. PROPER SEQUENCE OF OPERATION Du[...]
-
Pagina 55
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 54 COMMENTS Author: Terry Mulder[...]
-
Pagina 56
MODELS COVERED SBD71 120 Through SBD85 500 T h e Ex p e r t’ s C h o ic e® COMMERCIAL T h e Ex p e r t’ s C h o ic e® COMMERCIAL Self Cleaning Commercial Gas W ater Heaters with Flue Damper and Electronic Ignition Part Number STC-072 Printed in the U.S.A. - 0106 State Water Heaters 500 T ennessee W altz Parkway Ashland City , TN 37015 800-365[...]