Advantech I/O Module 5000 Series manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Advantech I/O Module 5000 Series, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Advantech I/O Module 5000 Series one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Advantech I/O Module 5000 Series. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Advantech I/O Module 5000 Series should contain:
- informations concerning technical data of Advantech I/O Module 5000 Series
- name of the manufacturer and a year of construction of the Advantech I/O Module 5000 Series item
- rules of operation, control and maintenance of the Advantech I/O Module 5000 Series item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Advantech I/O Module 5000 Series alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Advantech I/O Module 5000 Series, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Advantech service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Advantech I/O Module 5000 Series.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Advantech I/O Module 5000 Series item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    ADAM-5000 Series I/O Module User's Manual Copyright Notice This doc ument i s copyrig hted, 19 97, by A dvantech C o., Lt d. All ri ghts ar e reserved. A dvantech C o., Ltd. , reserves the right t o make i mprovem ents to t he products described in this manual at any time without notice. No part of this manual m ay be re produce d, copie d, tr[...]

  • Page 2

    I/O Module Introduction ADAM-5000 Series I/O Module Us er’s Manual Table of Contents Chapter 1 Introduction ….……......... .........….......... ........…………. 1-1 Chapter 2 Analog Input Modules....... ...........….................….. ..... 2-1 2. 1 AD AM-50 13 3-channel R TD input modul e….. ....... .............. .....2- 2 2.[...]

  • Page 3

    I/O Module Introduction ADAM-5000 Series I/O Module Us er’s Manual Chapter 5 Serial Communication Module………..….............. ...... 5-1 5.1 AD AM-5090 4-port RS-232 Co mm unicati on Module........ ....... . 5- 2 Chapter 6 Analog I/O Mo dules C alibration............. ............. ........ 6-1 6.1 Analog input module calibration… ……[...]

  • Page 4

    Introduction 1[...]

  • Page 5

    Introduction 1- 2 ADAM 5000 IO modules User’ s Manu al This ma nu al introduces the d etail specifications fun ctions and applicatio n wiring of each ADAM -5000 I/O modul es. T o or ganize an ADAM-5 510 Seri es Contr o ller, you nee d to select I/O m odules to interface the mai n unit wi th field devices or processes that you have previous ly de [...]

  • Page 6

    Analog Input Modules 2[...]

  • Page 7

    Analog Input m odule 2- 2 ADAM 5000 IO modules User’ s Manu al Analog i nput modules use an A/D co nverter to con vert sensor v oltage, current, thermocouple or R TD signals into digital data. The digit al data is t hen translated into engineering units. The anal og input modu les protect y our equipm ent from grou nd loop s and power s urges by [...]

  • Page 8

    Chapter 2 2 - 3 Applicati on wiring Figure 2 - 2: RTD in puts[...]

  • Page 9

    Analog Input m odule 2- 4 ADAM 5000 IO modules User’ s Manu al T echnical specificatio ns of AD AM-5013 Analog in put channels three Input type Pt or Ni RTD Pt -100 to 100°C a=0.00385 Pt 0 to 100°C a=0.00 385 Pt 0 to 200°C a=0.00 385 Pt 0 to 600°C a=0.00 385 Pt -100 to 100°C a=0.00392 Pt 0 to 100°C a=0.00 392 Pt 0 to 200°C a=0.00 392 Pt 0 [...]

  • Page 10

    Chapter 2 2 - 5 2.2 AD AM-5017 8-channel a nalog input mo dule The ADAM-5017 is a 16-bi t, 8-channel analog differential input m odule that provid es programmable input ranges on all channels. It accep ts millivolt inputs (±150mV , ±500mV), voltage inputs (±1V , ±5V and ±10V) and current input (±20 m A, requires 125 ohms resistor). The module[...]

  • Page 11

    Analog Input m odule 2- 6 ADAM 5000 IO modules User’ s Manu al Applicati on wiring Figure2-4: Millivolt and volt inpu t Figure 2-5: Process curre nt input Note: T o keep m easurement accuracy plea se short the channels that are not in use.[...]

  • Page 12

    Chapter 2 2 - 7 T e chnical specificatio ns of AD AM-5017 Analog Input Channels Eight differential Input Type mV, V, mA Input Range ± 150 mV, ± 500 mV, ± 1 V, ± 5 V, ± 10 V and ± 20 mA Isolation Voltage 3000 V DC Sampling Rate 10 samples/sec (total) Analog Input Signal Limit 15 V max. Max. allowable voltage diffe rence between two connectors [...]

  • Page 13

    Analog Input m odule 2- 8 ADAM 5000 IO modules User’ s Manu al 2.3 AD AM-5 017H 8-channel high s peed analog inp ut module The ADAM-5017H is a 12-bit plus sign bit, 8- channel analog differential input module that provide s programm ab le input ranges on each channel. It accepts millivolt inputs (± 500 m V , 0-500 mV), voltage i nputs (±1 V , 0[...]

  • Page 14

    Chapter 2 2 - 9 Applicati on wiring Figure 2 - 7 : Millivolt an d volt input Figure 2 - 8 : Process current input[...]

  • Page 15

    Analog Input m odule 2- 10 ADAM 5000 IO modules Use r ’s Man ual Figure 2 - 9 : Locat ions of 12 5-ohm resist ors Note: T o maintain measuremen t accuracy please short channels not in use.[...]

  • Page 16

    Chapter 2 2 - 11 T e chnical specification s of AD AM-5017H Analog Input Ch annels 8 differential ADC Resolution 12 bits, plus sign bit Type of ADC Successive approximation Isolation Voltage 3000 V DC Sampling Rate 100 Hz Input Impedance 20 Mohms (voltage inputs); 125 ohms (current inputs) Signal Input Band width 1000 Hz for both voltage inputs and[...]

  • Page 17

    Analog Input m odule 2- 12 ADAM 5000 IO modules Use r ’s Man ual Input Range With Overrangi ng Offset Error @ 25°C Offset Error @ - 10 to +70°C Gain Error @ 25°C Gain Error @ - 10 to +70°C Offset Drift Gain Drift Displa y Resolution 0 ~ 10 V 0 ~ 11 V ±1 LSB ±2 LSB ±1 LSB ±2 LSB 17 µV/°C 50 ppm/°C 2.7 m V 0 ~ 5 V 0 ~ 5.5 V ± 1 LSB ±2 [...]

  • Page 18

    Chapter 2 2 - 13 2.4 AD AM-5 018 7-channel thermocouple in put module The ADAM-5018 is a 16-bi t, 7-channel thermocoupl e input module that features programmable input ranges on all channels. It accepts millivolt inputs (±1 5 mV , ±50 m V , ±100 mV , ±5 00 mV), voltage in puts (±1 V , ±2.5 V), cu rr en t inp u t (± 20 mA , r equ ir e s 1 25 [...]

  • Page 19

    Analog Input m odule 2- 14 ADAM 5000 IO modules Use r ’s Man ual Applicati on wiring Figure 2-11: T herm ocouple input[...]

  • Page 20

    Chapter 2 2 - 15 T echnical specificatio ns of AD AM-5018 Analog Input Channels Seven differential Input Type mV, V, m A , Therm ocouple Input Range ± 15 mV, ± 50 mV, ± 100 mV, ± 500 m V, ± 1 V, ± 2.5 V and ± 20 mA T/C Type and Temperature Range JKTERSB 0 to 760 °C 0 to 1370 °C -100 to 400 °C 0 to 1400 °C 500 to 175 0 °C 500 to 1750 °C[...]

  • Page 21

    Analog Output Module 3[...]

  • Page 22

    Analog Output Module 3- 2 ADAM 5000 IO modules User’ s Manu al 3.1 AD AM-5024 4-channel a nal og output mo dule The ADAM-5024 is a 4-ch annel analog output module. It receives its digital inpu t through the RS-485 interface of the ADAM-5510 system module f rom the host com puter . The format of the data is engineering un its. It then us es the D/[...]

  • Page 23

    Chapter 3 3- 3 Applicati on wiring Figure 3-2 : Analog output T echnical specificatio ns of AD AM-5024 Analog Output Channels Four Output Type V, mA Output Range 0-20mA, 4- 20m A , 0-10V Isolation Voltage 3000 Vdc Output Impedanc e 0.5 Ohms Accuracy ±0.1% of FSR for current output ±0. 2 % of FSR for voltage output Zero Drift Voltage output: ±30 [...]

  • Page 24

    Digital Input/Output Modules 4[...]

  • Page 25

    Analog Input m odule 4- 2 ADAM 5000 IO modules User’ s Manu al 4.1 AD AM-5050 1 6-channel universal digi tal I/O mod ule The ADAM- 5050 featu res sixteen digital i nput/output channels . Each channel can b e independe ntly configure d to be an input or an output channel by the setting of its DIP sw itch. Th e digital outputs are open collector t [...]

  • Page 26

    Chapter 4 4- 3 Applicatio n wiring Figure 4 - 3 : Dry contact si gnal input (ADAM-5 050) Figure 4- 4: W et contact signal i nput (A DAM-5050) Figure 4-5: Digital output used with SSR (ADAM-5050 /5056)[...]

  • Page 27

    Analog Input m odule 4- 4 ADAM 5000 IO modules User’ s Manu al T echnical specificatio ns of AD AM-5050 Points 16 Channel Setting Bitwise selectable by DIP swit ch Digital Input Dry C ontact Logic Level 0: close to GND Logic Level 1: o pen Wet Contact Logi c Level 0: +2 V m ax Logic Level 1: +4 V to 30 V Digita l Output Open collector t o 30 V, 1[...]

  • Page 28

    Chapter 4 4- 5 4.2 AD AM-5051 series digital inpu t modul e 4.2.1 AD AM-5051 (D) 16 -channel d ig ital i nput m odul e The ADAM-5 051 provides sixteen digit al input cha nnels. The ADAM- 5510 can use the modul e’ s digital inputs to determine the state of l i mit or saf et y switches or to receive remote digital signals. Figure 4-6: A DA M -5 0 5[...]

  • Page 29

    Analog Input m odule 4- 6 ADAM 5000 IO modules User’ s Manu al Figure 4-8: Contact closu re input (ADAM-505 1/5051D) T e chnical specificatio ns of AD AM-5051/5051D Points 16 Logic level 0: + 1 V max Digital input Logic level 1: + 3.5 to 30 V Pull u p current: 0.5 mA 10 k Ω resistor t o + 5 V Power consumption 0.3 W indicator ADAM-5 051 D only [...]

  • Page 30

    Chapter 4 4- 7 4.2.2 AD AM-5051S 16-channel Isolated Di gital Input Module with LED The ADAM-5051S provides 16 isolated digital input channels for critical environments need individual channel isolating protection. Different from o t h e r ADAM-5 000 I/O modules, ADAM-5051S desi gned with 21 pins pl ug terminal. Figure 4 - 9 : ADAM-50 51S module fr[...]

  • Page 31

    Analog Input m odule 4- 8 ADAM 5000 IO modules User’ s Manu al T e chnical specificatio n of AD AM-5051S Point 16(4- channel/group ) Digital Input Lo gic Level 0: + 3 V m ax Logic Level 1: + 10 to 50 V Optical Is olation 2500 V DC Opto-isolator response time 25 µs Over-volt age Protection 70 V DC Power Consumption 0.8 W LED Indicator On when act[...]

  • Page 32

    Chapter 4 4- 9 4.3 AD AM-5052 8-channel isolate d digital inpu t module The AD AM-5052 provides e ight fully i ndependent i solated c hannels. All have 5000 V RMS isolation to pr event ground loop effects and to pr e- vent damage from power surges on th e input lines. Figure 4-11: ADAM-5052 modu le frontal view Applicati on wiring Figure 4 - 1 2 : [...]

  • Page 33

    Analog Input m odule 4- 10 ADAM 5000 IO modules Use r ’s Man ual T echnical specificatio ns of AD AM-5052 Points 8 Differential Digital input Logic level 0: + 1 V ma x Logic level 1: + 3. 5 to 30 V Isolation voltage: 5000 V RMS Resistance: 3 k Ω / 0.5 W Power consumption 0.4 W T able 4 - 4: T echnical specifications of A DAM-5052[...]

  • Page 34

    Chapter 4 4- 11 4.4 AD AM-5055S 16 -channel Isolated Digital I/O Module with LED The ADAM-5056S provi des 8 isolated digital input and 8 is olated output channels for critical environments need individual channel isolati ng protection. Different from other ADAM-5000 I/O modules, ADAM-5051S d esig ne d wit h 21 pins plug terminal. Figure4-13 : ADAM-[...]

  • Page 35

    Analog Input m odule 4- 12 ADAM 5000 IO modules Use r ’s Man ual T echnical specificatio n of AD AM-5055S Points 16 Digita l Output 8 (8-channel/g roup) Open collector to 40 V 200 m A max load pe r channe l Optical Is olation 2500 V DC Opto-isolator response time 25 µs Supply Voltage 5 ~ 40 V DC Digital Input 8( 4-channel/gr oup) Dry Cont act Lo[...]

  • Page 36

    Chapter 4 4- 13 4.5 AD AM-5056(D) seri es digital ou tput modul e w / L E D 4.5.1 AD AM-5056(D) 16-channel digital output module w / L E D The ADAM -5056 features si xteen digital o utput channels. T he digital outputs a re open-collector t ransistor switche s that you can cont rol from the ADAM-5 000 main unit. Y ou also can use t he switches t o [...]

  • Page 37

    Analog Input m odule 4- 14 ADAM 5000 IO modules Use r ’s Man ual T echnical specificatio ns of AD AM-5056 There are 16-point digi tal input a nd 16-point di gital output modul es in the ADAM-5000 series. The addition of these solid state digital I/O devices allows these m odules to cont rol or m onitor the interfaces between high power DC or AC l[...]

  • Page 38

    Chapter 4 4- 15 Applicati on wiring Figure 4-18: ADAM-5 056S module wirin g diagram Points 16(8-ch annel/group) Digita l Output O pen co llector to 40 V 200 mA max load pe r channel Optical Is olation 2500 V DC Opto-isolator response time 25 µs Supply Voltage 5 ~ 40 V DC Power consumption 0.6 W LED Indicator On when active I/O Connector Type 21- p[...]

  • Page 39

    Analog Input m odule 4- 16 ADAM 5000 IO modules Use r ’s Man ual 4.5.3 AD AM-5056SO 16-channel Isolated Dig ital Output Module wi th LE D The ADAM-5 056SO pro vides 16 chan nels source type isolat ed digita l output f or critical environments need i ndividual chan nel isola ting protection. Addition to the source output wiring, all of the specifi[...]

  • Page 40

    Chapter 4 4- 17 T e chnical Specificatio n of AD AM-5 056SO Points 16(8-channel/g roup) Digita l Output Open collector to 40 V 200 m A max load per c hannel Optical Isol ation 2500 VDC Opto-i solator res pons e time 25 u s Supply Volt age 5 ~ 40 VDC Power consum ption 0.6 W LED Indi cator On wh en active I/O Conn ector Type 21-pin plug-term inal T [...]

  • Page 41

    Analog Input m odule 4- 18 ADAM 5000 IO modules Use r ’s Man ual 4.6 Relay Output Mod ules 4.6.1 AD AM-5060 relay output module The ADAM-5 060 relay output module is a low - cost altern ative to SSR modules. It provides 6 relay ch annels, two of Form A and four of Form C . Figure 4-21: ADAM-5060 modu le frontal view Applicati on wiring Figure 4-2[...]

  • Page 42

    Chapter 4 4- 19 T e chnical specificatio ns of AD AM-5060 Points 6, two Form A and four Form C Contact ratin g A C: 125 V @ 0.6A; 25 0 V @ 0.3 A D C: 30 V @ 2 A; 110 V @ 0.6 A Breakdown v olt age 500 V AC (50/60 Hz) Relay on time (typi c al ) 3 ms Relay off ti me (typic al) 1 ms Total switching time 10 ms Insulation resistance 1000 M Ω min. @ 500[...]

  • Page 43

    Analog Input m odule 4- 20 ADAM 5000 IO modules Use r ’s Man ual Applicati on wiring Figure 4-24: Rela y o utput T echnical specificatio ns of AD AM-5068 Points 8 Form A Contact Ra ting AC: 120 V @ 0.5 A DC: 30 V @ 1 A Breakdown V ol t age 500 V AC (50/60 Hz) Relay On T ime (typic al) 7 ms ec. Relay Off Time (t ypical) 3 msec. Total Switching Tim[...]

  • Page 44

    Chapter 4 4- 21 4.6.3 AD AM-5069 p ow e r relay output module The ADAM-5069 power relay output module p r ovides 8 relay channels of Form A. Switches can b e used to control the relays. Considered to user frien d ly, the ADAM-5069 also built with LED indicator for status reading easily. And it also provides a choi ce to clear or keep output statu s[...]

  • Page 45

    Analog Input m odule 4- 22 ADAM 5000 IO modules Use r ’s Man ual 4.7 Counter/Frequency Module Overview Compatible AD AM-5000 Se ries Ma in Un its ADAM-5 080 is a 4-chan nel counter/fre quency module designed to be impl emented within t he followin g Adva ntech ADAM-50 00 series main units: ADAM-5000/4 85 ADAM-5510 ADAM-5511 ADAM-5 510M ADAM-5 510[...]

  • Page 46

    Chapter 4 4- 23 Alarm Setting Function While i n count er mode, y ou can set alarm status--Disable and Lat ch. If you want to disable it, you can sel ect Disabl e. If Latch status i s selected, it means the Alarm status will be "latched " whenever the alarm b eing triggered. Once the alarm status being "latched," it will thereaf[...]

  • Page 47

    Analog Input m odule 4- 24 ADAM 5000 IO modules Use r ’s Man ual AD AM-5080 Applica tion Wiring Figure 4-27: Isolated Input Level Figure 4-28 : TTL Input Level[...]

  • Page 48

    Chapter 4 4- 25 AD AM-5080 Counter/Frequency Mode Selection Users can selec t Bi-direction, Up/Down Count er or Fre quency option as shown in Figure 44. Fi g u r e 4-29: Co u n t er / F re q u en c y M o d e Note: All four channels of ADAM-5080 will operate simultaneously i n the mode y ou have selected. i .e. If you switch t he ADAM- 5 08 0 to Cou[...]

  • Page 49

    Analog Input m odule 4- 26 ADAM 5000 IO modules Use r ’s Man ual Figure 4 - 3 0 : Wiring for Up/ Down Counting Note : If you need only on e type of counting , connect C0A+ and C0A- for Up C ounting onl y; or co nnect C0B+ and C0B- for Down Counting on ly . Bi-direction Counting For implem enting Bi-direct ion Counting, you need t o connect C0B+/D[...]

  • Page 50

    Chapter 4 4- 27 Features -- Frequenc y Mode If users want to select frequency mode, they can only utilize Up Counting typ e, and can only connect to C0A+ and C0A-. Figure 4 - 3 2: Wiring for Frequency Mode Features -- Alarm Setting According to your application pu rposes, you can run the utility pro gram to set different lim it va lues for High/Low[...]

  • Page 51

    Analog Input m odule 4- 28 ADAM 5000 IO modules Use r ’s Man ual Setting Initial Counter V alue In order to utilize the alarm function, users have to set a high-alarm limit value an d/or a low alarm limit value, and a in itial value to fulfill the requirements for a basic ala rm setting. Figure 4 - 3 4 : Sending Alarm Signal (recommended settings[...]

  • Page 52

    Chapter 4 4- 29 Getting the T otalizer V a lue If users want t o get the actual counter value, a form ula such as follows can facilitate an easy cal culation from the initial counter value, overfl ow value and cu rrent counter value: V tol = {|V ini - V mi n ( or V max ) |+ 1} x |V vf | + | V ini - V cur | V to l : to talizer value V in i : initial[...]

  • Page 53

    Analog Input m odule 4- 30 ADAM 5000 IO modules Use r ’s Man ual Features--Digital Output Map ping If users want to use Digital Output function, ADAM utility is av a i l ab l e for setting sp ecific ally which modu le, chann el or s lot to receive the al arm s i g n a l s . Figure 4 - 3 6 : Dig ital Output Mapping 1 : High Alarm State --Set Alarm[...]

  • Page 54

    Chapter 4 4- 31 TTL/Isolated Inpu t Level According to your need, y ou can sel ect either TTL or Isolated Input Level by setting the configuration fo r the jumpers. Select the proper jumper settings for either TTL or Isolated Input according to Figure 53. Please note that you must confi gure a ll six jumpers to the correct con- figuration for prope[...]

  • Page 55

    Analog Input m odule 4- 32 ADAM 5000 IO modules Use r ’s Man ual AD AM-5080 T e chnical Specification s Channel 4 Input Frequ ency 0.3 ~ 1000 Hz m ax. (Fre quency mode) 5000 Hz m ax. (Counte r mode) Input Level Isolated or TTL level Minim u m Puls e Width 500 µ sec. (Frequency m ode) 100 µ sec. (Counte r mode) Min i mu m In pu t Cu rr en t 2mA [...]

  • Page 56

    S e r i a l Communication M o d u l e 5[...]

  • Page 57

    Serial Communication Module 5- 2 ADAM 5000 IO modules User’ s Manu al Overview Compatible AD AM-5000 Se ries Ma in Un its The ADAM-5090 is a 4-port RS-232 communication module to be im ple mented wit h the followi ng Advant ech ADAM-500 0 series main unit s: ADAM-551 0 ( w it h li b r a ry V er si o n V 1 . 1 0 o r a bove) ADAM-551 1 (w i th l ib[...]

  • Page 58

    Chapter 5 5- 3 Communication Backup Function W ith the ADAM-5090 you can implement dual co mmunication channels between your PC and the ADAM sy stem. Even when one of the two communication channel s is down, your system can still function through the alternative communication channel. Th is dual comm unication channels can be impl emented by applic[...]

  • Page 59

    Serial Communication Module 5- 4 ADAM 5000 IO modules User’ s Manu al PIN Mapping PIN Name RJ-48 DB9 /DCD 1 1 RX 2 2 TX 3 3 /DTR 4 4 GND 5 5 /DSR 6 6 /RTS 7 7 /CTS 8 8 RI or +5V 9 9 GND 10 X T able 5 - 2: Pin Mapping AD AM-5090 T e chnical Specification Function Provides communication ports for the ADAM-5510 to integrate other devices with commun[...]

  • Page 60

    Chapter 5 5- 5 I/O Slots an d I/O P o r ts Numbe ring The ADAM-5090 m odu le provides four RS-232 por ts for communication with target devices. Th e ports are numbered 1 thr ough 4. For programming, the definition of port number de pends on the slot number and port number . For exam ple, the second port on the ADAM-509 0 in slot 1 is de fin ed to p[...]

  • Page 61

    Serial Communication Module 5- 6 ADAM 5000 IO modules User’ s Manu al LED Status of the AD AM-5090 Module There are two LEDs for each port on the front panel of the ADAM-5090 to display specific co mmunication status: a. Gr een LED (RX) : Data Re ceivin g Statu s; the LED indic ator is on wh en the port is receiving data. b. Orange LED (TX): Data[...]

  • Page 62

    Chapter 5 5- 7 port_set_spee d(1,1 15200L); //Enable Por t FIFO. He re we e nable 128 byte FIFO fo r port1. port_enable_fifo(1); //After these above settings are enabled, you can apply any other function lib rary to implement y our progra m. } —A receive-and-tran smit example pr ogram for the ADAM-5090 main() { int e rr_v alue, char c haract er p[...]

  • Page 63

    Analog I/O Modules Calibration 6[...]

  • Page 64

    Analog I/O Modules Calibration 6- 2 ADAM 5000 IO modules User’ s Manu al Analog i nput/output m odules are ca librated when you receive them. However , calibration is so metimes requ ired. No screwdri ver is necessary because calibration is done in software wi th calibration parameters stored in t he ADAM-5000 analog I/O m odule‘s onboard EEPRO[...]

  • Page 65

    Chapter 6 6- 3 Figure 6 - 2 : Zero ca libration 5 . Execute the Span Calibrati on command. This can be done wi th the ADAM utility so ftware. Figure 6 - 3 : Sp an calibration[...]

  • Page 66

    Analog I/O Modules Calibration 6- 4 ADAM 5000 IO modules User’ s Manu al 6 . CJC Cali bration (only for T/C input module) Figure 6 - 4 : Cold junction ca libration * Note: Zero calibration and span calibration must be completed be fo re CJC calibration. T o calibrate CJC, the thermocouple attached to A DA M- 501 8 a nd a s tan da rd th ermo me te[...]

  • Page 67

    Chapter 6 6- 5 Calibration v oltage (AD AM-5 017/5018) Module Input Range Code (Hex) Input Range Span Calibration Voltage 00h ±15 mV +15 mV 01h ±50 mV +50 mV 02h ±100 mV +100 m V 03h ±500 mV +500 m V 04h ±1 mV +1 V 05h ±2.5 V +2.5 V 06h ±20 m V +20 mA (1) 0Eh J thermocouple 0 to 1370°C +50 mV 0Fh K thermocouple 0 to 1370°C +50 mV 10h T the[...]

  • Page 68

    Analog I/O Modules Calibration 6- 6 ADAM 5000 IO modules User’ s Manu al Calibration v oltage (ADAM-5017H) Module Input Range Code (Hex) I nput Range Span Calibration Voltage 00h ±10 V +10 V 01h 0 ~ 10 V +10 V 02h ±5 V +5 V 03h 0 ~ 5 V +5 V 04h ±2.5 V +2.5 V 05h 0 ~ 2.5 V +2.5 V 06h ±1 V +1 V 07h 0 ~ 1 V +1 V 08h ±500 mV +500 mV 09h 0 ~ 500 [...]

  • Page 69

    Chapter 6 6- 7 6. 2 AD AM-5013 RTD Input Resistance Calibration 1 . Apply power to the module and let it warm up for abou t 30 minutes. 2 . Ma ke sure that the module is cor r ectly i nstalled an d is properly con- figured f or the input range you want to calibrate. Y ou can use the ADAM utility software to help in this. 3 . Connect th e correct re[...]

  • Page 70

    Analog I/O Modules Calibration 6- 8 ADAM 5000 IO modules User’ s Manu al Calibration resistances (ADAM-5013) Input Range Code (Hex) Input Range Span Calibration Resistance Zero Calibration Resistance 20 Pt, -100 to 100°C A = 0.00385 140 Ohms 60 Ohm s 21 Pt, 0 to 100°C A = 0.00385 140 Ohms 60 Ohm s 22 Pt, 0 to 200°C A = 0.00385 200 Ohms 60 Ohm [...]

  • Page 71

    Chapter 6 6- 9 6.3 Analog output module cali bration The output current of analo g output module s can be calibrated by using a low calibrati on value and a hi gh calibration val ue. The anal og output modules can be configured for one of two rang es: 0-20 mA and 4-20 mA. Since the low limit of th e 0-20 mA ran ge (0 mA) is in ternally an ab solute[...]

  • Page 72

    Analog I/O Modules Calibration 6- 10 ADAM 5000 IO modules Use r ’s Man ual 4 . Issue the Analog Dat a Out com mand to the m odule with an output va lue of 4 m A. 5 . Check the act u al output value at the m odules terminals. If thi s does not equal 4 mA, use the "Tri m" option i n the "Calibrate" submenu t o change the actual [...]