Go to page of
Similar user manuals
-
Power Supply
APC SMX3000RMJ2U
20 pages 0.25 mb -
Power Supply
APC SmartSlot Series
17 pages 1.39 mb -
Power Supply
APC 6000 VA
13 pages 0.09 mb -
Power Supply
APC SURTA2200RMXL2U
18 pages 0.38 mb -
Power Supply
APC PDUM160H-B
36 pages 0.73 mb -
Power Supply
APC VS 50
65 pages 1.07 mb -
Power Supply
APC 2AP9604S
32 pages 2.46 mb -
Power Supply
APC NEMA 5 15R 320J
2 pages 0.32 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of APC 10-40KW 400V UPS, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of APC 10-40KW 400V UPS one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of APC 10-40KW 400V UPS. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of APC 10-40KW 400V UPS should contain:
- informations concerning technical data of APC 10-40KW 400V UPS
- name of the manufacturer and a year of construction of the APC 10-40KW 400V UPS item
- rules of operation, control and maintenance of the APC 10-40KW 400V UPS item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of APC 10-40KW 400V UPS alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of APC 10-40KW 400V UPS, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the APC service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of APC 10-40KW 400V UPS.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the APC 10-40KW 400V UPS item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
APC Silcon 10-40kW 400V UPS Installation Guide Copyright 2000 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor[...]
-
Page 2
2 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Thank You! Thank you for chosing the APC Silcon Series UPS. Please read this Installation Guide thoroughly prior to installing the system. It provides important information on safe and efficient installation. The installation and use of this product must comply with national, federal, state,[...]
-
Page 3
990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 3 Contents 1.0 Introduction 5 1.1 Tools and Equipment 5 2.0 Unpacking 6 3.0 Installation 8 3.1 Requirements on Site 8 3.1.1 Cabinet Dimensions H*xWxD - 1400xWx800 [mm]. Width as in below table: 8 3.2 Footprint 10 3.2.1 600mm UPS Cabinet with 1xBP I or Isolation Transformer 10 3.2.2 800mm UPS C[...]
-
Page 4
4 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 6.1.3 Operating The External Service Bypass Switch 57 6.2 Service Bypass Panel for Parallel Redundant Operation 59 6.2.1 Two Parallel Systems with Service Bypass Panel 60 6.2.2 Parallel/Redundant Operation with Service Bypass Panel and External Battery via MCCB 61 6.2.3 Operating External Se[...]
-
Page 5
Introduction 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 5 1.0 Introduction Power regulation varies from country to country, and information given in this installation guide can therefore only be of a general nature. Electricians should therefore always refer to national and local electrical codes prior to installing the UPS system. 1.1[...]
-
Page 6
6 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Unpacking 2.0 Unpacking 1. To unpack UPS unit, remove top and bottom screws from side plates of packaging and lift up side plates 2. Verify compliance between type label on reverse side of front door and system ordered. Check input and output voltage 3. Copy type label data to label copy bel[...]
-
Page 7
Unpacking 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 7 Copy of type label PLEASE RECYCLE The shipping materials for the APC Silcon UPS are recyclable. Please save them for later use or dispose of them appropriately.[...]
-
Page 8
8 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Installation 3.0 Installation 3.1 Requirements on Site All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1m free space on all sides should be allowed during installation. Once the system is installed it may be placed close to walls as long [...]
-
Page 9
Installation 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 9 Cabinets 600 mm wide 10-20kW with 1xBP l 1400 mm 10-20kW with 2xBP l 800 mm wide 1400 mm 1000 mm wide 10-20kW with 3xBP l 40kW without batteries 600 mm wide 1000 mm wide 1400 mm 40kW with 2xBP l 1400 mm 1400 mm 1400 mm APC Isolation Transformer module 10-80kW 600 mm wide Battery[...]
-
Page 10
10 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Installation 3.2 Footprint 3.2.1 600mm UPS Cabinet with 1xBP I or Isolation Transformer 3.2.2 800mm UPS Cabinet with 1xBP I or Built-in Isolation Transformer, or 2xBP I Rear Front Power cable entry Com. cable entry Rear Front Power cable entry Com. cable entry[...]
-
Page 11
Installation 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 11 3.2.3 1000mm Cabinet for 10-20kW UPS with 3xBP I 3.2.4 600mm Cabinet for 40kW UPS without Batteries Rear Front Power cable entry Com. cable entry Rear Front Power cable entry Com. cable entry[...]
-
Page 12
12 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Installation 3.2.5 1000mm Cabinet for 40kW UPS with 2xBP I 0 195 Rear Front Power cable entry Com. cable entry[...]
-
Page 13
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 13 4.0 External Connection 4.1 Connecting the UPS 4.1.1 Connecting the 10-20kW UPS CAUTION! At a switch mode load of 100% the neutral must be rated for 200% output phase current CAUTION! This UPS unit is an EN 50091-2 product and may cause radio interference in a domestic e[...]
-
Page 14
14 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection * DIN gL types PVC cables isolated to withstand ambient temperature of max. 30oC ** Must be rated as external PE cable if mains system is not supplying PE NOTICE! Check correct phase rotation of mains input voltage!! Max. input/output cables: 35mm 2 . If there is no neut[...]
-
Page 15
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 15 4.1.2 Connecting the 40kW UPS NOTICE! Install gland plate in bottom of unit CAUTION! At a switch mode load of 100% the neutral must be rated for 200% output phase current. CAUTION! This UPS unit is an EN 50091-2 product and may cause radio interference in a domestic envi[...]
-
Page 16
16 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection * DIN gL types PVC cables isolated to withstand ambient temperature of max. 30oC. ** Must be rated as external PE cable if mains system is not supplying PE. NOTICE! Check correct phase rotation of mains input voltage!! Max. input/output cables: 120mm 2 . Battery: 70 mm 2[...]
-
Page 17
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 17 4.2 System Integration Interface System Integration Interface (SII) is the control link between UPS and system main switches as shown in above diagram. The purpose of the SII is to ensure correct operation of switches without losing system output power. Auxiliary contact[...]
-
Page 18
18 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.2.1 Connections Blue Brown[...]
-
Page 19
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 19 Terminal Blocks: X003/X004 (Anxiliary Contacts) When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to “OFF or 0”, the anxiliary contact has to be open BEFORE the corresponding main contacts are opened. When switching Q001, Q002[...]
-
Page 20
20 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection The built-in parallel board connects two or more UPS systems in parallel, either to obtain increased system reliability or to obtain higher output power. The parallel board also ensures correct load-sharing between paralled systems. To prepare the UPS for parallel/redund[...]
-
Page 21
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 21 External Control Cables External multicore cable is equipped with 15-pin SUB-D plug at either end. Connect pin 1 to pin 1, and pin 2 to pin 2 etc. up to pin 15 - with the exception of pin 8, which is not to be connected. Shield is connected to plug cover at both ends. Te[...]
-
Page 22
22 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.4 Communication Interface Board The 3-port ComInterface is used to establish an interaction between UPS and e.g. a computer system. Main purpose: To ensure a controlled computer shut-down in case of a mains supply failure. 4.4.1 Connections . .[...]
-
Page 23
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 23 4.5 Connecting of APC Silcon Tripel Chassis The enclosed Triple Chassis must be connected to the serial port on the Communication Interface Board, and to the 24V supply (cables included). Terminal locations shown below. 23.62 inch/600mm Cabinet APC Silcon Triple Chassis [...]
-
Page 24
24 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.6 APC Silcon Triple Chassis The APC Silcon Triple Chassis (AP9604S) is an American Power Conversion (APC) external management peripheral that allows you to use monitoring and control management peripherals with your APC Silcon series UPS. The retrofit model (AP9604SR) [...]
-
Page 25
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 25 4.6.2.3LEDs The APC Silcon Triple Chassis status LED provides important information concerning operation of the chassis. Refer to the table below for a description of the conditions indicated by the LED. 4.6.2.4Optional Power Input With the Optional Power input, you can [...]
-
Page 26
26 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.6.3.1Order of Management Peripheral Cards Because UPS signals are passed between management peripherals, you must install management peripheral cards in the correct order for them to work together properly. The card slots are numbered 1 to 3, from left to right, as vie[...]
-
Page 27
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 27 To add card slots, you can daisy-chain the APC Silcon Triple Chassis with the standard Triple Chassis (AP9604) management peripheral, installing the APC Silcon Triple Chassis closer to the UPS. 4.6.4 Powering the APC Silcon Triple Chassis The APC Silcon Triple Chassis su[...]
-
Page 28
28 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.6.5 Troubleshooting The following table shows the solution to common problems with the operation of the Triple Chassis 4.6.5.1If Problems Persist For problems not covered in the troubleshooting chart or for persistent problems, follow this procedure: 1) Note the serial[...]
-
Page 29
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 29 4) Pack the APC Silcon Triple Chassis carefully in its original packaging, if possible. Do not use polystyrene beads for packing. Damage sustained in transit is not covered under the warranty. Enclose a letter in the package with your name, address, RMA number, a copy of[...]
-
Page 30
30 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection UPS Shut Down RS-232 Input or Advanced Mode RS-232 Data RX In Line Fail RS-232 Output or Advanced Mode RS-232 Data TX Out Unregulated +24 VDC Output Normally Open Line Fail Signal Normally Open Low Battery Signal Normally Closed Line Fail Signal Common Chassis[...]
-
Page 31
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 31 4.6.6.2Power, Physical, and Environmental Specifications. Item Specification Power Turn on voltage: > 22 VDC Turn off voltage: < 16 VDC Current draw (normal operation): 90 mADC Current draw (voltage < 16 VDC ): < 1 mADC Physical Size (H xW x D): 1.75 x 17.0 x[...]
-
Page 32
32 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.7 APC Silcon Battery Cabinets Installation and use of this product must comply with all national, federal, state, municipal or local codes. If you need assistance, please have your UPS model and serial number ready and call APC, see “How to Contact APC” in this gui[...]
-
Page 33
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 33 4.7.1 Cabinets UPS with Built-in Batteries 4.7.2 Preparing Batteries CAUTION! Battery drawer weighs approx. 22 kg with batteries. The 12V, 7.2 Ah batteries are glued to drawer plate. Battery drawers present a risk of electric shocks. Prior to installation of battery draw[...]
-
Page 34
34 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection Battery drawers are wrapped in cardboard and delivered on pallets. Unpack battery drawers, checking that type, number and size comply with the order. Connect wire as shown below:[...]
-
Page 35
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 35 800mm Battery Cabinet 1000mm Battery Cabine 4.7.3 Mounting Batteries Unscrew front frame of UPS and slide frame down as shown above. Battery drawers may be installed after removal of front cover. WARNING! Open front door of UPS and unscrew front cover. Do not install bat[...]
-
Page 36
36 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection Check all battery connections to ensure that proper contact is established. Insert battery drawers in the APC Silcon UPS Connect all battery drawers to the terminal on the left side of the column[...]
-
Page 37
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 37 4.7.4 Final Checks CAUTION! Follow the “ start-up procedure ” in APC Silcon User Guide. IMPORTANT SAFETY INSTRUCTIONS a) The servicing of batteries requires battery knowledge and should be carried out or supervised by qualified personnel only. Keep unauthorized perso[...]
-
Page 38
38 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.7.5 APC Silcon Battery Cabinets Installation and use of this product must comply with all national, federal, state, municipal or local codes. If you need assistance, please have your UPS model and serial number ready and call APC, see the section “How to contact APC?[...]
-
Page 39
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 39 4.7.5.1Installation of Batteries See Installation Guide for Battery Cabinet for: • Preparing Batteries and UPS • Dimensions and Weight • Connecting Batteries WARNING! The entire system contains HAZARDOUS AC/DC VOLTAGES from several power sources. Some terminals and[...]
-
Page 40
40 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.8 Battery Breaker Box/Fuse-box Battery Breaker Box/Fuse-box provides overcurrent and short-circuit protection for UPS installations with external batteries. CAUTION! Batteries connected to a UPS out of service for a period exceeding 8 days may be damaged. Refer to Sect[...]
-
Page 41
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 41 4.8.1 Battery Breaker Box UPS Ampere Rating [A] Connection Cable [mm2] Max. short- circuit current [kA] Dimensions HxWxD [mm] Weight [kg] 10 kW 20 kW 40 kW 25 50 63 4 10 16 10 10 10 540x540x183 504x540x183 540x540x183 20 20 20[...]
-
Page 42
42 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.8.2 Battery Breaker Box Connection Diagram X009 LED signal from UPS “OK to operate corresponding MCCB” X010 MCCB position signals for UPS X011 Trip for emergency stop (220-240V AC) Battery 1 Battery 2 Battery 1 Battery 2 UPS UPS Main cables are connected directly t[...]
-
Page 43
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 43 4.8.3 Fuse-box UPS Ampere Rating [A] Connection Cable [mm 2 ] Max. short-circuit current [kA] Dimensions HxWxD [mm] Weight [kg] 10 kW 20 kW 40 kW 25 50 63 4 10 16 10 10 10 540x540x183 504x540x183 540x540x183 20 20 20[...]
-
Page 44
44 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 External Connection 4.8.4 Fuse-box Connection Diagram X009 LED signal from UPS “ OK to operate corresponding fuse. ” X010 Released fuse signal for UPS Battery 1 Battery 2 Battery 1 Battery 2 UPS UPS[...]
-
Page 45
External Connection 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 45 4.8.5 UPS with External Battery in Battery Breaker Box/Fuse-box Configuration[...]
-
Page 46
46 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Programming Parameters 5.0 Programming Parameters Below table shows operating parameters programmable from keyboard. Only qualified users should re-set programming parameters. 5.1 Parameters * Factory settings in bold ** Only for systems with Battery Monitor active *** Do not leave system r[...]
-
Page 47
Programming Parameters 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 47 5.1.1 Programming Keys NOTICE! Display accuracy is + 1%, + digit. Scrolls up through list Scrolls down through list Stores parameters/ enter parameter stack Silences the audible alarm Chooses parameters Displays time Exits a mode Accesses alarm stack[...]
-
Page 48
48 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Programming Parameters 5.1.2 Programming Example - Switch to Bypass Operation Return to normal operation Follow same procedure to program other parameters. 5.2 System Configuration System configuration parameters are vital for correct system operation and are password- protected. NOTICE! Do[...]
-
Page 49
Programming Parameters 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 49 System Configuration Parameters (password protected) * Bold text refers to factory standard setting **Advanced Battery Monitor Parameter Setting* Comments Isolation Transformer Input YES, NO YES if optional input isolation transformer is available IsolationTransformer[...]
-
Page 50
50 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Programming Parameters 5.2.1 Programming Example - Change Charge Voltage to 446 NOTICE! Change charge voltages, battery warning limit, shut down voltage and high battery temperature limit by entering the actual value. See example above.[...]
-
Page 51
Programming Parameters 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 51 5.2.2 Programming Example - Change to Output Isolation Transformer available NOTICE! Change parameters by pressing the key once or several times. See example above.[...]
-
Page 52
52 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Programming Parameters 5.3 Programming Parameters for Advanced Parallel Operation To use the advanced parallel functions, the following parameters must be programmed: 1. “Station number” 2. “Highest station address” 3. “Advanced power management” 4. “APM test mode active” 5.[...]
-
Page 53
Programming Parameters 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 53 5.3.2 Programming example Example with four systems in parallel with separate batteries. • Programme the station addresses 1-4: 1 for UPS 1, 2 for UPS 2, 3 for UPS 3, and 4 for UPS 4. • All UPS systems have to be programmed to “Highest station address”:4. • [...]
-
Page 54
54 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.0 Options/Accessories Please contact your local APC representative for information on options/accessories available in your region. See “How to Contact APC” in this guide. 6.1 Service Bypass Panel for Single Operation UPS Exter- nal System Input Fuse [A] Max. Pro- [...]
-
Page 55
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 55 *** If no external System Output fuses are available or if it has a higher value than indicated above, System Output and UPS Output cables should be dimensioned as System Input and UPS Input cables. ** Sizes according to IEC 364-5-532 for PVC insulated copper cables (max[...]
-
Page 56
56 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.1.1 Wiring up UPS with SBP in TN-C-S Network 6.1.2 Wiring up UPS with SBP in TN-S Network[...]
-
Page 57
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 57 6.1.3 Operating The External Service Bypass Switch Action 1. Press on the k e yboard 2. Press or on the k e yboard until 3. Press on the k e yboard 4. Press on the k e yboard 5. Chec k lamp indication on the Service Bypass Panel 6. T urn the external bypass switch (Q003)[...]
-
Page 58
58 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.1.3.1Switching from External Bypass to Normal UPS Operation Action 1. T urn the input switch (Q002) to position ” 0 “ 2. Open the UPS front door and press the green "ON ” key 3. Press on the keyboard 4. Press or on the keyboard until 5. Press on the keyboard[...]
-
Page 59
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 59 6.2 Service Bypass Panel for Parallel Redundant Operation Service Bypass Panel (SBP) Mains Supply System Output Control cables Q003 Q004 Q001b Q001a Q002b Q002a APC Silcon 400V UPS X020 X021 X020 X021 APC Silcon 400V UPS Battery Battery Breaker/ Fuse Box[...]
-
Page 60
60 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.2.1 Two Parallel Systems with Service Bypass Panel[...]
-
Page 61
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 61 6.2.2 Parallel/Redundant Operation with Service Bypass Panel and External Battery via MCCB[...]
-
Page 62
62 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.2.3 Operating External Service Bypass Switch for Parallel Systems 6.2.3.1Bypassing Parallel UPS Systems CAUTION! Batteries connected to a UPS out of service for a period exceeding 8 days may be damaged. H002a[...]
-
Page 63
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 63 Step 1-4 can be carried out with any of the parallel systems, ho we ver this will s witch all systems into bypass operation. 1. Press on the keyboard 2. Press or on the keyboard until 3. Press on the keyboard 4. Press on the keyboard All systems will transf er to bypass [...]
-
Page 64
64 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.2.3.2 Switching Parallel System from External Bypass into Normal UPS Operation H002a[...]
-
Page 65
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 65 Action 1. Check that output s witch (Q004) is in position “ 0 ” 2. Check that all output s witches (Q002) are in position “ 0 ” 3. T ur n input s witches (Q001) to position “ 1 ” 4. Open the UPS front door and press the green “ ON ” push-botton 5. Press o[...]
-
Page 66
66 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.2.4 Isolating One UPS for Service/Maintenance In a redundant system, one UPS may be isolated for service/maintenance without affecting other UPSs. 1. Check that remaining UPS(s) is capable of carrying the load in the event that one UPS is isolated 2. Switch off system [...]
-
Page 67
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 67 6.2.5 Switching Back to Normal Parallel/Redundant Operation 1. Turn input switch (Q001) and output switch (Q002) to position “ 1 ” 2. Charge capacitor, connect battery and start up UPS UPS will automatically switch to normal operation and start load-sharing with othe[...]
-
Page 68
68 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.3 Intersystem Synchronization Unit Intersystem Synchronization Unit System (ISU System) The ISU system consists of inter-connected ISUs. One ISU system may consist of up to 5 ISUs, regardles of ISU configuration. The ISU system synchronizes the voltage of parallel oper[...]
-
Page 69
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 69 6.4 Relay Board Relays All relays are “fail safe”: In alarm modes, relay coil will be de-energized. Maximum load: 8.0A – 250VAC Minimum load: 0.05A – 6VAC 1 2 3 0.3A – 60VDC 0.05A – 6VDC[...]
-
Page 70
70 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.4.1 Relay Board/Relay Functions NOTICE! If alarm mode “ Communication to controller lost ” is active, ALL relays will indicate failure. Relay Number Message Alarm-trigging Events 1 ## (X002) Mains outside limits Mains voltage RMS outside limits Mains wave form (fas[...]
-
Page 71
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 71 ## Delay programmable in configuration stack: “ Common fault delay ” . Settings 0,10,20,30 seconds. See section 5.2 in this guide for System configuration NOTICE! Alarm Trigging Events 1-2- 3-9-10-11-13 activates the corresponding alarm relay after the delay. Alarm T[...]
-
Page 72
72 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.5 Weight Equalizer Footprint - 600mm and 8 30 30 30 30 75 277.5 755 277.5 75 R6 19 Rear Front 490 - 600mm cabinet 690 - 800mm cabinet 550 - 600mm cabinet 750 - 600mm cabinet[...]
-
Page 73
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 73 Footprint - 1000mm Cabinet 465 - 1000 mm cabinet 395 - 1000 mm cabinet 30 30 950 - 1000 mm cabinet 30 75 75 R6 277.5 277.5 755 Rear Front[...]
-
Page 74
74 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.6 Remote Display With the remote display unit data may be displayed at distances of up to 25 m from UPS. For extended communication distance, see section below. Remote display may easily be connected to UPS via one of the two serial communication ports on the communica[...]
-
Page 75
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 75 6.6.1.1Connections Without Converter Connect a 25-pin female Sub-D and a 9-pin male Sub-D connector with a 3-wire shielded cable, as shown in the table below. Connect shield at one end only. Pin Connection for Interconnection Cable (without converter): 6.6.1.2Connections[...]
-
Page 76
76 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.6.2 Remote Display Installation 6.6.2.1Connecting RS232C and Mains Adapter 6.6.2.2Remote Display Power Supply The remote display is supplied by normal AC power with no battery back-up. For UPS data transmission to remote display to remain unaffected during power failur[...]
-
Page 77
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 77 6.6.3 Remote Display Use The remote display is an inactive unit unable to influence the operation of the UPS: Some of the alarms visible on the internal display are also available on the remote display (See the Alarm section in the APC Silcon User Guide). 6.6.3.1Initiati[...]
-
Page 78
78 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.7 Isolation Transformer UPS Height [mm] Width [mm] Depth [mm] Weight [kg] 10 kW 20 kW 40 kW 1400 1400 1400 600 600 600 800 800 800 185 245 405 NOTICE! APC isolation transformers are available in various configuration. Contact your local APC representative for further i[...]
-
Page 79
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 79 6.7.1 Connecting Isolation Transformer *DIN gL types PVC cables isolated to withstand a maximum ambient temperature of 30 o C. NOTICE! If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn (nominal current) for minimum 10 ms. Isolation [...]
-
Page 80
80 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories NOTICE! Check correct phase rotation of mains input voltage! Maximum input/output cables: 35mm 2 . If in- put neutral is not available, an optional Dzn0 or Dyn11 input isolation transformer must be used. NOTICE! All external cable dimensions are recommended sizes only. R[...]
-
Page 81
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 81 6.7.2 Wiring up UPS with External Yyn0 Isolation Transformer at Output WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed NOTICE! Refer to local legal regulatio[...]
-
Page 82
82 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.7.3 Wiring up UPS with External Yyn0 Isolation Transformer at Input WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed. NOTICE! Refer to local legal regulatio[...]
-
Page 83
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 83 6.7.4 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Input WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed. NOTICE! Refer to local legal [...]
-
Page 84
84 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Options/Accessories 6.7.5 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Output WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Do not bypass isolation transformer in order to avoid damaging circulation currents and to prevent lo[...]
-
Page 85
Options/Accessories 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 85 6.7.6 Wiring up UPS with External Optional Dyn11 Isolation Transformer at Input WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Do not bypass isolation transformer in order to avoid damaging circulation currents and to prevent lo[...]
-
Page 86
86 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 System Specifications 7.0 System Specifications 7.1 Technical Data 7.2 Back-up Time / Dimensions / Weigh Voltage 3x380/400/415V Input Voltage tolerance Normal operation Bypass operation +15% +10% (standard) +4, 6, 8% (programmable) Frequency 50Hz/60Hz +6 standard +0.5-8% (programmable) Inpu[...]
-
Page 87
Warranty 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 87 8.0 Warranty 8.1 APC Silcon Series Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installatio[...]
-
Page 88
88 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 Appendix 9.0 Appendix 9.1 Table 1. Installation Planning Data Main Input Breaker Field Wiring* Battery Bank** UPS Module Service Bypass Panel Field Wiring Output Breaker * ** Internal Batteries available for 40kW units and smaller * * Q1 Q2 Q3 * Not supplied by APC Installation Planning Dat[...]
-
Page 89
Appendix 990-4050 Installation Guide APC Silcon 10-40kW 400V UPS 89 Notes: 1. Nominal input current based on rated load. 2. Maximum input current based on rated load + full battery recharge. Full battery recharge assumed to increase input current with 10%. 3. Nominal power consumption (column 1c) based on nominal input current (1e) and the correspo[...]
-
Page 90
90 Installation Guide APC Silcon 10-40kW 400V UPS 990-4050 How to Contact APC 10.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: 401 789-5735 Fax: 401 789-3710 PowerFax™: 800 347-FAXX Pre-sales Technical Support 877-474-5266 (1-877-4Silcon) Post-sales Technical Support 877-287-7835 (1-877-2UPS-TEK) W[...]