Go to page of
Similar user manuals
-
Heat Pump
Bard CH4S1
28 pages 0.72 mb -
Heat Pump
Bard W36H1
27 pages 0.53 mb -
Heat Pump
Bard S**H
19 pages 0.29 mb -
Heat Pump
Bard QW3S1
46 pages 1.23 mb -
Heat Pump
Bard T**H*D
19 pages 0.29 mb -
Heat Pump
Bard GSVS241-A
38 pages 0.43 mb -
Heat Pump
Bard I42H1D
59 pages 1.91 mb -
Heat Pump
Bard I42H1
59 pages 1.91 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Bard WH361, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Bard WH361 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Bard WH361. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Bard WH361 should contain:
- informations concerning technical data of Bard WH361
- name of the manufacturer and a year of construction of the Bard WH361 item
- rules of operation, control and maintenance of the Bard WH361 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Bard WH361 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Bard WH361, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Bard service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Bard WH361.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Bard WH361 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
Manual 2100-193O Page 1 of 26 Models: WH301, WH361 W ALL MOUNTED P ACKAGED HEA T PUMP INST ALLA TION INSTRUCTIONS Manual No.: 2100-193O Supersedes: 2100-193N File: V olume III, T ab 17 Date: 05-04-07 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914. . .Moving ahead just as planned. © Copyright 2003[...]
-
Page 2
Manual 2100-193O Page 2 of 26 CONTENTS St art Up Important I nst aller Note ........................................ 20 Crankcase Heaters .............................................. 20 Service Hints ........................................................ 20 Sequence of Operation ........................................ 20 Pressure Service Port [...]
-
Page 3
Manual 2100-193O Page 3 of 26 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National E lectrical Code ....................... ANSI/[...]
-
Page 4
Manual 2100-193O Page 4 of 26 WALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE WH 36 1 A 10 X X X X X A VOL TS & PHASE A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3 MODEL NUMBER REVISIONS CAP ACITY 30 - 2 ½ To n 36 - 3 T on KW VENTI LA TION OPTIONS X - Barometric Fresh Air Damper (S tandard) B - Blank-off Plate M - Moto[...]
-
Page 5
Manual 2100-193O Page 5 of 26 TABLE 1 ELECTRIC HEAT TABLE s l e d o MA - 1 0 3 H WB - 1 0 3 H WC - 1 0 3 H WA - 1 6 3 H WB - 1 6 3 H WC - 1 6 3 H W 1 - 0 4 21 - 8 0 23 - 0 4 23 - 8 0 23 - 0 6 41 - 0 4 21 - 8 0 23 - 0 4 23 - 8 0 23 - 0 6 4 W KA U T BA U T BA U T BA U T BA U T BA U T BA U T BA U T BA U T BA U T B 58 . 0 25 6 0 7 11 . 8 10 0 8 2 18 . [...]
-
Page 6
Manual 2100-193O Page 6 of 26 FIGURE 1 UNIT DIMENSIONS * OPTIONAL TOP OUTLET (FACTORY INSTALLED ONLY) FOR WH30 AND WH36 MODELS ONLY. TABLE 2 DIMENSIONS OF BASIC UNIT (NOMINAL) l e d o M h t d i W ) W ( h t p e D ) D ( t h g i e H ) H ( y l p p u Sn r u t e R EF G I J K L M N O P Q R S T A BCB 0 3 H W 6 3 H W 0 0 2 . 8 35 2 1 . 7 13 6 5 . 0 78 8 . 7[...]
-
Page 7
Manual 2100-193O Page 7 of 26 TABLE 3 ELECTRICAL SPECIFICATIONS l e d o M d e t a R d n A s t l o V e s a h P . o N d l e i F r e w o P s t i u c r i C 4 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F t i u c r i C r e k a e r B 2 d l e i F r e w o P e r i W e z i S 2 d n u o r G e r i W e z i S 4 m u m i n [...]
-
Page 8
Manual 2100-193O Page 8 of 26 Any grille that meets the 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG-2 through RG-5 or RFG-2 through RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient[...]
-
Page 9
Manual 2100-193O Page 9 of 26 INST ALLA TION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3. 2. On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. 3. Concret[...]
-
Page 10
Manual 2100-193O Page 10 of 26 FIGURE 3 MOUNTING INSTRUCTIONS[...]
-
Page 11
Manual 2100-193O Page 11 of 26 Side section view of supply air duct for wall mounted unit showing 1/4" clearance to combustible surfaces. FIGURE 4 ELECTRIC HEAT CLEARANCE W ARNING A minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the fist three (3) feet of ducting. I[...]
-
Page 12
Manual 2100-193O Page 12 of 26 FIGURE 5 ATTACHING TOP OUTLET AIRFRAMES TO UNIT FIGURE 6 UNIT WITH TOP OUTLET MOUNTED UNDER OVERHANG[...]
-
Page 13
Manual 2100-193O Page 13 of 26 FIGURE 7 WALL-MOUNTING INSTRUCTIONS FIGURE 8 WALL-MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS[...]
-
Page 14
Manual 2100-193O Page 14 of 26 FIGURE 9 COMMON WALL-MOUNTING INSTALLATIONS[...]
-
Page 15
Manual 2100-193O Page 15 of 26 WIRING — MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed K[...]
-
Page 16
Manual 2100-193O Page 16 of 26 FIGURE 10 LOW VOLTAGE WIRING TABLE 5 THERMOSTAT WIRE SIZE r e m r o f s n a r T A VA L Fe g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 53 . 2 e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2[...]
-
Page 17
Manual 2100-193O Page 17 of 26 OPTIONAL OUTDOOR THERMOSTAT APPLICATIONS Since most equipment at the time of manufacture is not designated for any specific destination of the country and are installed in areas not approaching the lower outdoor temperature range, outdoor thermostats are not factory installed as standard equipment, but are offered as [...]
-
Page 18
Manual 2100-193O Page 18 of 26 ELECTRIC HEAT HOLD-OFF ( See Figures 13 and 14) In other applications, it is desirable to disable the operation of the electric heat until outdoor temperatures have reached a certain design point. This won't allow the electric heat to come on as second stage heating unless the outdoor temperature is below the set[...]
-
Page 19
Manual 2100-193O Page 19 of 26 TABLE 6 WALL THERMOSTAT t a t s o m r e h Ts e r u t a e F e t a n i m o d e r P 8 5 0 - 3 0 4 8 ) 1 5 1 1 D 0 2 2 5 H T ( t a e h e g a t s 2 , l o o c e g a t s 2 e l b a m m a r g o r P - n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 0 6 0 - 3 0 4 8 ) 5 4 4 - 0 2 1 1 ( t a e h e g a t s 3 , [...]
-
Page 20
Manual 2100-193O Page 20 of 26 IMPORTANT INSTALLER NOTE For improved start-up performance, wash the indoor coil with a dishwashing detergent. CRANKCASE HEATERS All units are provided with some form of compressor crankcase heat. All single and three phase models have an insertion well-type heater located in the lower section of the compressor housin[...]
-
Page 21
Manual 2100-193O Page 21 of 26 PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found on Page 25 covering all models. It is imperative to match the correct pressure table to the unit by model number. DEFROST CYCLE The defrost cycle is[...]
-
Page 22
Manual 2100-193O Page 22 of 26 TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. Turn on AC power supply to indoor and outdoor units. 2. Turn thermostat blower switch to “Fan On” – the indoor blower should start. (If it doesn't, troubleshoot indoor unit and correct problem). 3. Turn thermostat blower switch to ?[...]
-
Page 23
Manual 2100-193O Page 23 of 26 CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open. 3. Check resistance reading to chart of resistance use sensor ambient temperature. (Tolerance of[...]
-
Page 24
Manual 2100-193O Page 24 of 26 REFRIGERANT CHARGE The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6 inches from compressor) as shown in Table 9. TABLE 10 INDOOR BLOWER PERFORMANCE CFM AT 230 VOLTS . P . S . E H n I 2 O 1 6 3 H W [...]
-
Page 25
Manual 2100-193O Page 25 of 26 Low side pressure ± 2 psig High side pressure ± 5 psig Tables are based upon rated CFM (airflow) across the evaporator coil and should be found under section titled “Refrigerant Charge” on Page 24 in manual. If there is any doubt as to correct charge being in the system, the charge should be removed, system evac[...]
-
Page 26
Manual 2100-193O Page 26 of 26 WH301-A WH301-B WH301-C WH361-A WH361-B WH361-C TABLE 15 OPTIONAL ACCESSORIES L E D O MN O I T P I R C S E D 5 0 A - 0 3 H W H Es e g a k c a P r e t a e H 1 X 0 1 A - 0 3 H W H Es e g a k c a P r e t a e H 1 X 5 0 A - 6 3 H W H Es e g a k c a P r e t a e H 1 X 0 1 A - 6 3 H W H Es e g a k c a P r e t a e H 1 X 5 1 A [...]