Bryant 3-PHASE 601A manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Bryant 3-PHASE 601A, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Bryant 3-PHASE 601A one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Bryant 3-PHASE 601A. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Bryant 3-PHASE 601A should contain:
- informations concerning technical data of Bryant 3-PHASE 601A
- name of the manufacturer and a year of construction of the Bryant 3-PHASE 601A item
- rules of operation, control and maintenance of the Bryant 3-PHASE 601A item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Bryant 3-PHASE 601A alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Bryant 3-PHASE 601A, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Bryant service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Bryant 3-PHASE 601A.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Bryant 3-PHASE 601A item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 INTRODUCTION ..........................................................................2 RECEIVING AND INSTALLATION ..........................................2 Check Equipment ....[...]

  • Page 2

    WARNING: Improper installation, adjustment, alter- ation, service, maintenance, or use can cause explosion, fire, electric shock, or other occurrences, which could cause serious injury or death or damage your property. Consult a qualified installer or service agency for infor- mation or assistance. The qualified installer or agency must use only fa[...]

  • Page 3

    Fig. 2—601A030-042/602A030-036 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A030 208/230-3-60 287 130.2 39.02 (991.1) 19.5 (495.3) 13.7 (348.0) 15.0 (381.0) 601A036 208/230-3-60, 460-3-60 291 132.0 37.02 (940.3) 19.5 (495.3) 13.7 (348.0) 13.0 (330.2) 601A042 208[...]

  • Page 4

    Fig. 3—601A048-060/602A042-060 Unit Dimensions UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) ”A” CENTER OF GRAVITY IN. (MM) Lb Kg X Y Z 601A048 208/230-3-60, 460-3-60 353 160.1 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 601A060 208/230-3-60, 460-3-60 418 189.6 38.98 (990.2) 19.9 (505.5) 15.7 (398.8) 17.0 (431.8) 6[...]

  • Page 5

    3. Place each of the 4 metal lifting brackets into the rigging holds in the composite pan. 4. Thread lifting bracket strapping around bottom perimeter of unit as follows: a. Open lever of tension buckle (ratchet type). b. Feed strapping through tension buckle as shown in Fig. 8. c. Pull strapping through tension buckle unit taut. d. Snap lever down[...]

  • Page 6

    Fig. 5—Roof Curb Dimensions UNIT SIZE ODS CATALOG NUMBER A IN. (MM) B IN. (MM) C IN. (MM) D IN. (MM) 601A030-042 602A030-036 CPRFCURB006A00 8 (203) 11(279) 161/2 (419) 28-3/4 (730) CPRFCURB007A00 14 (356) 11(279) 161/2 (419) 28-3/4 (730) 601A048, 060 602A042-060 CPRFCURB008A00 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022) CPRFCURB009A00 14 (35[...]

  • Page 7

    3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Tables 3 and 4. Heater limit switches may trip at air quantities below those recommended. 4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through co[...]

  • Page 8

    TABLE 1—PHYSICAL DATA UNIT SIZE 601A030 601A036 601A042 601A048 601A060 NOMINAL CAPACITY (ton) 2-1/2 3 3-1/2 4 5 OPERATING WEIGHT (lb.) 287 291 323 353 418 COMPRESSOR QUANTITY 1 TYPE RECIPROCATING COMPRESSOR SCROLL COMPRESSOR REFRIGERANT R-22 REFRIGERANT METERING DEVICE AccuRater® Refrigerant (R-22) Quantity (lb.) 5.6 7.6 8.0 7.85 9.3 ORIFICE ID[...]

  • Page 9

    VII. INSTALL ELECTRICAL CONNECTIONS WARNING: The unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compart- ment, or conduit approved for electrical g[...]

  • Page 10

    Fig. 12—Wiring Schematics (208/230-3-60) C00134 —10—[...]

  • Page 11

    Fig. 13—Wiring Schematics (460-3-60) C00135 —11—[...]

  • Page 12

    TABLE 5—ELECTRICAL DATA—601A UNIT 601A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 9.9 78 0.9 2.0 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12 .0 20.8/24.1 31.3/36.1 15.3/15.3 28.3/30.3 41.3/45.3 54.4/60.4 20/20 [...]

  • Page 13

    TABLE 6—ELECTRICAL DATA—602A UNIT 602A SIZE V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal kW* FLA MCA FUSE OR CKT BKR MOCP 030 208/230–3–60 187 253 10.4 63 0.9 2.1 -/- 3.8/5.0 7.5/10.0 11.3/15.0 -/- 10.4/12.0 20.8/24.1 31.3/36.1 16.0/16.0 29.0/31.0 42.1/46.1 55.1/61.1 20/20 [...]

  • Page 14

    leads are inside the unit, run leads up the high-voltage raceway to the line wiring splice box (See Fig. 12–17). On all 3-phase units, connect the leads to the black, yellow, and blue wires (See Fig. 16). C. CONNECTING GROUND LEAD TO GROUND LUG Connect the ground lead to the chassis using the ground lug in the wiring splice box (See Fig. 16). D. [...]

  • Page 15

    PRE-START-UP WARNING: Failure to observe the following warnings could result in serious personal injury or death: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured[...]

  • Page 16

    IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minute, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressor[...]

  • Page 17

    E. LOW CHARGE COOLING Use Cooling Charging Charts (Fig. 24-33). Vary refrigerant until the conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging the units to correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing devices are req[...]

  • Page 18

    MAINTENANCE To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This heat pump unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 11. NOTE TO EQUIPMENT OWNER: Consult your loc[...]

  • Page 19

    For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually. WARNING: Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel. Failure to adhere to this warning could cause serious injury or death. III. OUTDOOR COIL, INDO[...]

  • Page 20

    5. Ensure that setscrew engages the flat area on the motor shaft when tightening. 6. Replace grille. V. ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag. Remove access panel to locate all the electrical controls and wiring. Chec[...]

  • Page 21

    Fig. 24—Cooling Charging Chart, 601A030 Units C00028 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) -7 -1 4 10 16 21 27 SUCTION LINE TEMPERA TURE ( ° F) SUCTION LINE TEMPERA TURE ( ° C) 689 620 551 483 414 345 276 207 100 90 80 70 60 50 40 30 (030) 60HZ CHARGING CHART 20.0 30.0 40.0 50.0 60.0 70.0 80.0 OUTDOOR TEMP ° F ° C [...]

  • Page 22

    IX. LIQUID LINE STRAINERS The liquid line strainers (to protect metering devices) are made of wire mesh and are located in the liquid lines on the inlet side of the metering devices. X. HIGH FLOW VALVES High flow valves are located on the compressor hot gas and suction tubes. Large black plastic caps distinguish these valves with O-rings located in[...]

  • Page 23

    689 100.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 207 276 345 414 483 551 620 SUCTION LINE PRESSURE (KILOP ASCALS) SUCTION LINE PRESSURE (PSIG) 20.0 -7 27 21 16 10 4 -1 80.0 70.0 60.0 50.0 40.0 30.0 50JX500221 (036) 60 Hz CHARGING CHART OUTDOOR TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 SUCTION LINE TEMPERA TURE (DEG. C) SUCTION LI[...]

  • Page 24

    TABLE 9—FILTER PRESSURE DROP (IN. WG) FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2 0 X 2 0 X 1 0 . 0 5 0 . 0 7 0 . 0 8 0 . 1 0 0 . 1 2 0 . 1 3 0 . 1 4 0 . 1 5 ——————————— 2 0 X 2 4 X 1 ———— 0 . 0 9 0 . 1 0 0 . 1 1 0 . 1 3 0 . 1 4 0 . 1 5 0 . 1 6 ———[...]

  • Page 25

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start Power Failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective thermostat, contractor, transformer, control relay or defrost board Replace component Insufficient line voltage Det[...]

  • Page 26

    TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART (CONT’D) SYMPTOM CAUSE REMEDY Suction pressure too low (Cool) Dirty air filter Replace filter (Heat) Outdoor coil frosted Move timer on control board to 30 minute between defrost cycles Low refrigerant charge Check for leaks, repair and recharge Metering device or low side restricted Remove sou[...]