Go to page of
Similar user manuals
-
Heat Pump
Bryant 604D----A
4 pages 0.28 mb -
Heat Pump
Bryant 549B
122 pages 3.03 mb -
Heat Pump
Bryant 650A
20 pages 0.17 mb -
Heat Pump
Bryant 3-PHASE 601A
26 pages 3.56 mb -
Heat Pump
Bryant PREFERRED 265A
32 pages 4.73 mb -
Heat Pump
Bryant Puron Refrigerant Two-Speed
8 pages 0.16 mb -
Heat Pump
Bryant 548J*14D
36 pages 8.38 mb -
Heat Pump
Bryant 280ANV
18 pages 2.1 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Bryant 697C, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Bryant 697C one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Bryant 697C. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Bryant 697C should contain:
- informations concerning technical data of Bryant 697C
- name of the manufacturer and a year of construction of the Bryant 697C item
- rules of operation, control and maintenance of the Bryant 697C item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Bryant 697C alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Bryant 697C, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Bryant service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Bryant 697C.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Bryant 697C item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
Form No. PDS 697C.18.3B SPLIT-SYSTEM HEAT PUMP UNITS 697C (60 HZ) Sizes 018 thru 060 The AeroQuiet System (AQS) consists of 4 design features to achieve ultra-low sound ratings. Aerocoustic Design featuring the Aeromax opening and wire dome top results in quieter and more efficient operation. Energy-Efficient Fan and Fan Motor provide a slower fan [...]
-
Page 2
—2— DIMENSIONS A94148 ACCESS PANEL 1 1 / 4 " 1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low ambient control is used) max 125 ° F. 2. Maximum o[...]
-
Page 3
—3— RECOMMENDED TUBE DIAMETERS * For tube set over 50 ft, consult Long-Line Application Guideline. METERING DEVICE * TXV must be installed when indoor coil is not equipped with a TXV. TXV listed is for any approved coil combination. All TXVs are bi-flow, hard shutoff. UNIT SIZE TUBE LENGTH (Ft)* LIQUID TUBE DIAMETER (In.) VAPOR TUBE DIAMETER (I[...]
-
Page 4
—4— SPECIFICATIONS See notes on page 5. UNIT SIZE-SERIES 018-B 024-B 030-B 036-B 042-B Operating Weight (Lb) 198 198 221 211 231 ELECTRICAL Unit Volts-Hertz-Phase 208/230-60-1 Operating Voltage Range 187—253 Unit Ampacity for Wire Sizing 16.1 17.5 18.7 21.0 32.0 Min Wire Size (60 ° C/75 ° C Copper) (AWG)* 14/14 14/14 14/14 12/12 8/10 Maximu[...]
-
Page 5
—5— SPECIFICATIONS Continued * If wire is applied at ambient greater than 30 ° C (86 ° F), consult T ab le 310-16 of the NEC (ANSI/NFP A 70). If other than uncoated (non-plated), 60 ° or 75 ° C (140 ° or 167 ° F) insulation, copper wire (solid wire f or 10 A WG and smaller , str anded wire f or larger than 10 AWG) is used, consult applica[...]
-
Page 6
—6— ACCESSORY USAGE GUIDELINE * For tubing line sets between 50 and 175 ft, refer to Residential’s Split System Long-Line Application Guidelines. † For buried line applications, refer to Residential’s Split Systems Buried Line Application Guidelines. ‡ Only when low-pressure switch is used. ACCESSORY DESCRIPTION AND USAGE (Listed Alphab[...]
-
Page 7
—7— ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued 1 3. Secondary Outdoor Thermostat An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second- stage set point. SUGGESTED USE: Heat pump installations where 3-stage operation of suppleme[...]
-
Page 8
—8— COMBINA TION RA TINGS* See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP 018-B 72 FC4[...]
-
Page 9
—9— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP 02[...]
-
Page 10
—1 0— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP [...]
-
Page 11
—1 1— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP [...]
-
Page 12
—1 2— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP [...]
-
Page 13
—1 3— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP [...]
-
Page 14
—1 4— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP [...]
-
Page 15
—1 5— COMBINA TION RA TINGS* Continued * Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80 ° F (27 ° C) db 67 ° F (19 ° C) wb indoor entering air temperature and 95 ° F (35 ° C) db air entering outdoor unit. High-Temp Heating Standa[...]
-
Page 16
—1 6— 697C BALANCE POINT WORKSHEET BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR Printed in U.S.A. 11-95 838-756 OUTDOOR TEMPERATURE, °F -10 0 10 20 30 40 50 60 70 80 2.9 5.9 8.8 11.7 14.7 17.6 20.5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT. AIR AT 70°F AND AT RATED CFM 23.4 80 697CN024-A/B FC4BNF030 697CN030[...]
-
Page 17
—1 7— DET AILED COOLING CAP ACITIES* See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw*[...]
-
Page 18
—1 8— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Tota[...]
-
Page 19
—1 9— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡[...]
-
Page 20
—2 0— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡[...]
-
Page 21
—2 1— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System KW** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡[...]
-
Page 22
—2 2— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡[...]
-
Page 23
—2 3— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡[...]
-
Page 24
—2 4— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡[...]
-
Page 25
—2 5— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡[...]
-
Page 26
—2 6— DET AILED COOLING CAP ACITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-89. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower [...]
-
Page 27
—2 7— HEA T PUMP HEA TING PERFORMANCE See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacit[...]
-
Page 28
—2 8— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total P[...]
-
Page 29
—2 9— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr [...]
-
Page 30
—3 0— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr [...]
-
Page 31
—3 1— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr [...]
-
Page 32
—3 2— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr [...]
-
Page 33
—3 3— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr [...]
-
Page 34
—3 4— HEA T PUMP HEA TING PERFORMANCE Continued * The Btuh heating capacity values shown are net “integrated’’ values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity. † The kw values include the compressor, outdoor fan motor, and [...]
-
Page 35
—3 5— System Design 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55 ° F (12.8 ° C). 3. Maximum outdoor operating air temperature for cooling m[...]
-
Page 36
—3 6— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 697C.18.2B ©1997 Bryant Heating & Cooling Systems, 7310 W. Morris Street, Indianapolis, IN 46231 PRINTED IN U.S.A. Catalog No. BY-3269-711 3-97 SERVICE TRAINING Packaged Service Training programs are an exc[...]