Go to page of
Similar user manuals
-
Heat Pump
Bryant 541A
28 pages 1.22 mb -
Heat Pump
Bryant PREFERRED 265A
32 pages 4.73 mb -
Heat Pump
Bryant 575C
28 pages 1.22 mb -
Heat Pump
Bryant 542E
16 pages 2.75 mb -
Heat Pump
Bryant 548J
76 pages 3.33 mb -
Heat Pump
Bryant 604D
4 pages 0.23 mb -
Heat Pump
Bryant 607C-A
50 pages 8.19 mb -
Heat Pump
Bryant 224A
8 pages 0.31 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Bryant 698B, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Bryant 698B one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Bryant 698B. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Bryant 698B should contain:
- informations concerning technical data of Bryant 698B
- name of the manufacturer and a year of construction of the Bryant 698B item
- rules of operation, control and maintenance of the Bryant 698B item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Bryant 698B alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Bryant 698B, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Bryant service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Bryant 698B.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Bryant 698B item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
Form No. PDS 698B.24.1 TWO-SPEED PURON® PLUS™ ELECTRIC HEAT PUMP 698B (60 HZ) Sizes 024, 036, 048, and 060 • T W O - S P E E D • ™ Model 698B Heat Pumps incor porate innov ativ e 2-speed com- pressor technology with Puron ® , the refrigerant of the future, to provide quiet, ef fi cient cooling perf ormance. Built into these units are f e[...]
-
Page 2
— 2 — DIMENSIONS A01063 DIMENSIONS (IN.) SOUND PO WER (dBA) *Sound lev els are equivalent at high and low speeds. UNIT SIZE SERIES A B C D E F G H K L M N MINIMUM MOUNTING P AD DIMENSIONS 024 A 33-13/16 22-1/2 26-3/16 4-1/8 7-1/8 21-15/16 28-3/8 5/8 12 13-3/4 12 2-3/8 20 x 27 036 A 27-13/16 30 33 5-1/16 9-11/16 15-15/16 22-3/8 3/4 16-1/4 14 13-[...]
-
Page 3
— 3 — RECOMMENDED TUBE DIAMETERS NO TE: Maximum long-line tube length of 50 ft liquid and v apor line sets indicated abov e must be f ollowed on all applications . Over 50 ft or 20 ft vertical differential, refer to Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. UNIT SIZE TUBE LENGTH (Ft[...]
-
Page 4
— 4 — SPECIFICA TIONS * P ermissible limits of the voltage r ange at which the unit will operate satisf actorily . Oper ation outside these limits ma y result in unit failure . † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab le (NM), tra[...]
-
Page 5
— 5 — OPTIONAL EQUIPMENT DESCRIPTION AND USA GE (Listed Alphabetically) 1. Coastal Filter A mesh screen inser ted under the top cov er and inside the base pan to protect the condenser coil from salt damage without restricting air fl ow . SUGGESTED USE:In geographic areas where salt damage could occur . 2. Snow Stand Coated wire rac k which sup[...]
-
Page 6
— 6 — COMBINA TION RA TINGS UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Lo w High Low High Lo w High Low High Low High Low 024-A FV4ANF002* 735 440 24,000 12,000 14.0 11.0 21,000 10,600 3.38 3.40 12,400 4400 2.34 1.52 7.8 CC5A/CD5AA024 750 450 22,000 11,800 11.5 9.5 20,400 1[...]
-
Page 7
— 7 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A FK4CNF001 1100 660 33,600 17,200 14.0 10.7 32,600 15,400 3.12 3.50 18,500 7300 2.32 1.78 8.1 FK4CNF002 1100 660 34,000 17,400 14.5 10.8 33,400 15,600 3.26 3.56 18,800 730[...]
-
Page 8
— 8 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CK5A/CK5BA048 1100 700 34,800 17,600 15.0 11.6 32,400 15,800 3.32 3.66 18,400 7300 2.46 1.82 8.7 CK5A/CK5BT042 1100 700 34,400 17,600 15.0 11.5 32,000 15,600 3.26 3.62 18[...]
-
Page 9
— 9 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CC5A/CD5AB042 1200 800 34,600 17,600 14.5 11.2 32,800 15,800 3.20 3.58 18,700 7500 2.38 1.80 8.3 CC5A/CD5A C048 1200 800 34,200 17,400 14.5 11.1 32,000 15,600 3.08 3.52 1[...]
-
Page 10
— 10 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 048-A CK5A/CK5BN060 1470 910 45,500 24,000 14.5 11.0 42,500 24,000 3.06 3.62 27,800 14,000 2.58 2.22 9.0 CK5A/CK5BT048 1470 910 44,000 24,000 14.0 10.6 42,000 24,000 3.02 3.52[...]
-
Page 11
— 11 — * Ratings are net values re fl ecting the eff ects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80 ° F (27 ° C) db 67 ° F (19 ° C) wb indoor entering air temperature and 95 ° F (35 ° C) db air entering outdoor unit. High-T emp Heating Standard: 70 ° F (21 ° C) db in[...]
-
Page 12
— 12 — 698BNX BALANCE POINT WORKSHEET BUILDING H EAT LO SS, 1000 BTU / HR UN I T I NTEGRATED HEATING C APACITY, 1000 BTU/HR P rinte d in U .S.A . OUTDOOR TEMPERATURE, ° F -10 0 10 20 30 40 50 60 70 80 2.9 5.9 8.8 11.7 14.7 17.6 20.5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT. AIR AT 70 ∞ F AND AT RATED CFM 23. 4 80 A - 698BNX024 / FV4ANF002[...]
-
Page 13
— 13 — DET AILED COOLING CAP A CITIES* See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacit[...]
-
Page 14
— 14 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 15
— 15 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 16
— 16 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 17
— 17 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 18
— 18 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 19
— 19 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 20
— 20 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 21
— 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 22
— 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 23
— 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 24
— 24 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 25
— 25 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 26
— 26 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW[...]
-
Page 27
— 27 — DET AILED COOLING CAP A CITIES* continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length is used and/or indoor unit is located abov e outdoor unit, a slight v ariation in capacity may occur . † T otal and sensible capacities are net capa[...]
-
Page 28
— 28 — HEA T PUMP HEA TING PERFORMANCE See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh [...]
-
Page 29
— 29 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K[...]
-
Page 30
— 30 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac[...]
-
Page 31
— 31 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac[...]
-
Page 32
— 32 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac[...]
-
Page 33
— 33 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K[...]
-
Page 34
— 34 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K[...]
-
Page 35
— 35 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K[...]
-
Page 36
— 36 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac[...]
-
Page 37
— 37 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac[...]
-
Page 38
— 38 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K[...]
-
Page 39
— 39 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K[...]
-
Page 40
— 40 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac[...]
-
Page 41
— 41 — HEA T PUMP HEA TING PERFORMANCE continued * The Btuh heating capacity values sho wn are net “ integrated ” values from which the defrost eff ect has been subtracted. The Btuh heating from supplement heaters should be added to those v alues to obtain total system capacity . † The kW values include the compressor , outdoor f an motor[...]
-
Page 42
— 42 —[...]
-
Page 43
— 43 —[...]
-
Page 44
— 44 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5269-803 4-01[...]