Carrier 09RH manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Carrier 09RH, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Carrier 09RH one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Carrier 09RH. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Carrier 09RH should contain:
- informations concerning technical data of Carrier 09RH
- name of the manufacturer and a year of construction of the Carrier 09RH item
- rules of operation, control and maintenance of the Carrier 09RH item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Carrier 09RH alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Carrier 09RH, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Carrier service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Carrier 09RH.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Carrier 09RH item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificat ions or des igns without notice an d withou t inc urring obligations. New PC 802 Catalo g No. 510-509 Printe d in U.S.A. Form 5F ,H/09RH-2 XA Pg 1 8-02 Replace s: 5F ,H/09RH-1XA B o o k 2244 T a b 2 a4 a3 a4 b Book 3 Ta b D E 1 Application Data CO NTEN TS Page[...]

  • Page 2

    2 OPEN-DRIVE COMPRESSORS These compressors are desi gned to operate with Refriger- ants 12, 22, 134a, 502, or 507/404A. See T able 1. Operating Requireme nts — Satis factory op eration of a reciprocatin g compres sor depen ds on 3 fundamental requiremen ts: 1. Prevention of excess discharge temperature. 2. Adequate compressor lubric ation. 3. A c[...]

  • Page 3

    3 During compressor shutdown, gr avity , thermal act ion and refrigerant absorption can result in a re frigerant and oil mixture in compressor crankcase. Gr avity flow can be preve nted by the use of recommende d loops, but therm al action a nd t he absorp- tion of refrigerant by lubricating oil cannot be prevented by piping design. For the above r[...]

  • Page 4

    4 Compressor Capacity Notes 1. Compressor capacities are based on 1750 rpm and 15 F subcooling for all unit sizes and refrigera nts. 2. Multiplying factors for other rpm: See Multiplying Factors chart on pa ge 31. 3. Liquid subcooling greater than (less than) 15 F incorpo- rated in ra tings increases (decre ases) system capaci ty by 1 / 2 of 1% for[...]

  • Page 5

    5 Table 6 — R ating Basi s and Ca pacity Multiplier s for R-1 2 and R-1 34a* LEGEND *R-134a capacity multipliers star t at 0 ° F SST and abov e. SST (F) SDT (F) RETURN GAS TEMPERA TURE (F) –30 –2 0 –10 0 10 20 30 40 50 60 65 –30 90 0.963 0.966 0.970 0.973 0.977 0.981 0.985 0.989 0.993 0.998 1.000 100 0.951 0.956 0.960 0.965 0.970 0.976 0[...]

  • Page 6

    6 Table 7 — Rat ing Basis an d Capaci ty Mult ipliers fo r R-502 and R-507 /404A LEGEND SST (F) SDT (F) RETURN GAS TEMPERA TURE (F) –30 –2 0 –10 0 10 20 30 40 50 60 65 –30 90 0.913 0.922 0.931 0.941 0.950 0.959 0.968 0.977 0.986 0.995 1.000 100 0.893 0.905 0.916 0.928 0.939 0.956 0.962 0.973 0.984 0.995 1.000 110 0.870 0.884 0.899 0.913 0[...]

  • Page 7

    7 Table 8 — Compre ssor Ratin gs; R-12 LEGEND NO TES: 1. Shaded ratings require an oil cooler when using a liquid- suction interchanger , or when 50 degrees of superheat is exceeded. 2. Ref er to T able 5 f or T otal Heat Rejection. U N I T 5 F 2 05 F 3 05 F 4 05 F 6 0 SST SDT Cap. Bhp Cap. Bhp Cap. Bhp Cap. Bhp –40 80 0.6 1. 7 1.0 2.7 1.3 3.4 [...]

  • Page 8

    8 Table 8 — Compressor Ratings; R-12 (cont) LEGEND NO TES: 1. Shaded ratings require an oil cooler when using a liquid- suction interchanger , or when 50 degrees of superheat is exceeded. 2. An oil cooler is recommended for all long stroke compressors (5H46,66,86 and 126). 3. Ref er to T able 5 f or T otal Heat Rejection. UNIT 5H40 5H46 5H60 5H66[...]

  • Page 9

    9 Table 8 — Compressor Ratings; R-12 (cont) LEGEND NO TES: 1. Shaded ratings require an oil cooler when using a liquid- suction interchanger , or when 50 degrees of superheat is exceeded. 2. An oil cooler is recommended for all long stroke compressors (5H46,66,86 and 126). 3. Ref er to T able 5 f or T otal Heat Rejection. UNIT 5H80 5H86 5H120 5H1[...]

  • Page 10

    10 Table 9 — Compre ssor Ratin gs; R-22 LEGEND NO TES: 1. Shaded ratings require an oil cooler an d water-cooled heads. 2. Ref er to T able 5 f or T otal Heat Rejection. U N I T 5 F 2 05 F 3 05 F 4 05 F 6 0 SST SDT Cap. Bhp Cap. Bhp Cap. Bhp Cap. Bhp –40 80 1.0 2.6 1.5 4.0 2.1 5.3 3.0 7.9 –30 80 1.5 3.4 2.3 5.1 3.1 6.7 4.6 10.0 90 1.3 3.3 2.0[...]

  • Page 11

    11 Table 9 — Compressor Ratings; R-22 (cont) LEGEND NO TES: 1. Shaded ratings require an oil cooler an d water-cooled heads. 2. An oil cooler is recommended for all long stroke compressors (5H46,66,86 and 126). 3. Ref er to T able 5 f or T otal Heat Rejection. UNIT 5H40 5H46 5H60 5H66 SST SDT Cap. Bhp Cap. Bhp Cap. Bhp Cap. Bhp –40 80 5.0 12.8 [...]

  • Page 12

    12 Table 9 — Compressor Ratings; R-22 (cont) LEGEND NO TES: 1. Shaded ratings require an oil cooler an d water-cooled heads. 2. An oil cooler is recommended for all long stroke compressors (5H46,66,86 and 126). 3. Ref er to T able 5 f or T otal Heat Rejection. UNIT 5H80 5H86 5H120 5H126 SST SDT Cap. Bhp Cap. Bhp Cap. Bhp Cap. Bhp –40 80 10.2 24[...]

  • Page 13

    13 Table 10 — Compre ssor Ratin gs; R-502 LEGEND NO TES: 1. Shaded ratings require water-cooled heads, if the dis- charge temperature exceeds 275 F . 2. An oil cooler is required when SST is belo w – 20 F . 3. Ref er to T able 5 f or T otal Heat Rejection. U N I T 5 F 2 05 F 3 05 F 4 05 F 6 0 SST SDT Cap. Bhp Cap. Bhp Cap. Bhp Cap. Bhp –60 80[...]

  • Page 14

    14 Table 10 — Compressor Ratings; R-502 (cont) LEGEND NO TES: 1. Shaded ratings require water-cooled heads, if the dis- charge temperature exceeds 275 F . 2. An oil cooler is recommended for all long stroke compressors (5H46,66,86 and 126). 3. An oil cooler is required when SST is belo w – 20 F . 4. Ref er to T able 5 f or T otal Heat Rejection[...]

  • Page 15

    15 Table 10 — Compressor Ratings; R-502 (cont) LEGEND NO TES: 1. Shaded ratings require water-cooled heads, if the dis- charge temperature exceeds 275 F . 2. An oil cooler is recommended for all long stroke compressors (5H46,66,86 and 126). 3. An oil cooler is required when SST is belo w – 20 F . 4. Ref er to T able 5 f or T otal Heat Rejection[...]

  • Page 16

    16 Table 11 — Compressor Ratings; R-134a LEGEND NO TES: 1. An oil cooler is recom mended for all long strok e compressor s (5H46, 66, 86, 126). 2. Ref er to T able 5 f or T otal Heat Rejection. U N I T 5 F 2 05 F 3 05 F 4 05 F 6 0 SST SDT C ap. Bhp Cap. Bhp Cap. Bhp Cap. Bhp 10 90 2.9 4.0 4.4 6. 0 5.8 7.9 8.7 11.7 100 2.7 4.2 4.0 6. 3 5.3 8.3 8.0[...]

  • Page 17

    17 Table 12 — Compre ssor Rat ings; R-507/4 04A LEGEND NO TES: 1. Shaded ratings require w ater-cooled heads, if the dis- charge temperature exceeds 275 F . 2. An oil cooler is recom mended for all long strok e compressor s (5H46, 66, 86, 126). 3. Oil cooler required when SST is belo w – 20 F . 4. Ref er to T able 5 f or T otal Heat Rejection. [...]

  • Page 18

    18 Table 13 — Minimum Gpm Required for Water-Cooled Heads and/or Oil Cooler (Based on 3 0° F R ise) SAFETY RELIEF V AL VES — A l l 5 H c o m p r e s s o r s a r e equipped with built-in safety rel ief valves that are factory set to relieve from discharge to suction side of the compressor at a pressure differential of 350 psi. Safety relief val[...]

  • Page 19

    19 Table 15 — Weigh t Distribut ion, Compr essor Units (See drawing , Table 14 ) LEGEN D NEMA — Natio nal Electr ical Manufacturers A ssociation *Oversize frame. Capa city Co ntrol — For all 5F ,H compressors, a pressure-type cylinder unloader is used. O n 5F20 and 5F30 compressors, the capacity control valve is external and on 5F40 through 5[...]

  • Page 20

    20 Table 16 — Capacity Control Reduction Steps *T wo contro lled c ylinde rs (to 33 1 / 3 %) available on request for 5F30. Principle of Operation of the System — An i ncrease in s uc- tion gas pressure, which requires increased compressor capacity , ca uses the needle valve to close. There fore, lubric a- tion oil pressure in power element inc[...]

  • Page 21

    21 Table 17 — Initial and Final Unlo ading Oil Press ures — 5F20 , 5F 30 5F40 THROUGH 5H86 (Fig. 7) Major Elements of Capacity Control Systems : 1. Capacity Contr ol V alve: Function is to raise or lower the control oil pressure to the hydraulic relay piston in response to refrigerant suction pressure. Increase i n suction pressure increases c [...]

  • Page 22

    22 5H120, 5H126 C AP ACITY CO NTROL (Fig. 8) — T h is c a- pacity co ntr ol syst em is sl ight ly differe nt fr om the s ystem o n 5F40 through 5H86 compressors. Unloaded starting and capac- ity reduction is obtained by holding open the suction valves of a number of cylinders. For capaci ty control purposes, a suction-pressure-actuated capaci ty [...]

  • Page 23

    23 Control Pressurestats — Dual pressurestats are furnis hed with all 5F ,H compress ors. They ar e often referre d to as high- and low-pressure cutouts. Their function is to cut the ci rcuit to the holding coil of the compressor motor start er when pressure setting l imits a re exceede d. The high pressurestat has an operating range from 50 t o [...]

  • Page 24

    24 2 2R* 1R 1 1L 3 2L 4 B D C E A * PUMP OIL PRESS. DUMP T O CRANKCASE OIL TO UNLOADER POWER ELEMENTS *STEP 2R DOES NOT EXIST ON A 5F40 COMPRESSOR. NO HOLE IS REQUIRED A T POINT A FRONT VIEW BOTTOM VIEW HANDHOLE COVER (ALL PIPE PLUGS 1/8 NPT) FROM UNLOADER CONNECTIONS WHEN UNLOADING DESIRED, SOLENOID V AL VE SHOULD ALLOW OIL FROM UNLOADERS T O DUMP[...]

  • Page 25

    25 CAP ACITY CONTROL MODIFICA TIONS F OR HEA T PU M P A PP L I CA T ION — Where 5F40, 5F60, and 5H com- pressors are used in refrigerant cycle r eversing heat pump applications, it is usually necessary to modi fy the standard capacity control arrangement to satisfy unloading requir e- ments. On summer cycle, the compressor is requi red to unload [...]

  • Page 26

    26 Appli cation Requi ring 50 % Capacit y Reduct ions — This is the usual specification f or heat pump applications and should cover majority of cases. The necessary modifications to com- pressor capacity control can be accomplished by ordering the compressor with factory modifications and then completing modification at the jobsite with fi eld-s[...]

  • Page 27

    27 The variety of systems using 5F ,H c ompressors make it impractical to cover all a spects of hot gas bypass operation. The following guidelines will aid in determining the proper application. The hot gas bypass valve is basically a press ure regulating valve installed to hold a constant compressor suct ion pressure. It should operate over as sma[...]

  • Page 28

    28 Table 20 — Belt Driv e Pack ages LEGEN D NO TE: Compr essor sh aft diam eter bef ore taper begins: 5F20 , 30 = 1.0 in. 5F40 , 60 = 1.5 in. All 5H = 2.0 DRIVE P A CKA G E P ART NUMBER COMPR SIZE HP FRAME SHAFT DIAM (in.) COMPR RPM CENTER TO CENTER (in.) FL YWHEEL PULLEY BEL TS Pkg No. OD Pkg No. PD Pkg No. No. of Belts 5F20-A181 5F2 0 3 182T 1 [...]

  • Page 29

    29 Table 21 — Flywheel Data *Ref er to Fig. 17. Table 22 — Flywheel — Compressor Dimensions *Ref er to Fig. 17. BOOSTER COMPRESSO RS FOR REFRIGERANT 12, 22, 502, AND 507/404A Booster Applicat ion Data — The following data sup- plements the single-stage compressor applicat ion data, and adds information pertaining to booster application only[...]

  • Page 30

    30 When a c apacity safet y factor i s used, the compressor is selected at its maximum speed t o handle design load pl us safe- ty factor . Multiplying factors for non-standard speeds ar e shown in Fig. 20. Whether or not added c apacity offered by the safety fac tor is incorporated at once is a matte r of judgment. If it is , then the compressor w[...]

  • Page 31

    31 Table 23 — Booster “ R ” Factors Air-cool ed (R -12 a nd R-22 ) W ater-coo led (R -22 o nly) Determining Inte rmediate Pressure — In applic a- tion of commercial compressors t o staged syst ems, the lowest total bhp per ton and most economical equipment selection results when using approximately equal compression ratios for each stage. I[...]

  • Page 32

    32 Contr ol Pre ssurestat f or Booster Applica- tion — The standard dual pressure switch furnished with the 5F ,H compressor cannot be used for booster application. Replace it w ith an appropriate low temperature dual pressurestat that can operate at val ues shown in T able 24. Any commercial pressure swi tch is accept able; for exa mple, an Alle[...]

  • Page 33

    33 Dischar g e V alve Sprin gs — When 5H compre ssors are used for booster applications where di scharge pressure i s below 10 psig, the standard dischar ge valve springs furnished with the machine should be replace d with an equal number of lighter weight springs, Part Number 5H41-1801. No change in discharge valve spring s is recommended for 5F[...]

  • Page 34

    34 Table 25 — 5F,H Booster Ratings; R-12 LEGEND *Also re ferred to as Sa turated Inter medi ate T emp erature. SST SDT* 5F20 5F 30 5F 40 5F 60 Cap. Bhp Cap. Bhp Cap. Bhp Cap . Bhp – 85 – 50 0.28 0. 93 0. 42 1.30 0 .57 1.67 0 .85 2 .42 – 40 0.27 0. 94 0. 40 1.31 0 .54 1.68 0 .80 2 .43 – 30 0.25 0. 94 0. 38 1.31 0 .50 1.69 0 .76 2 .45 – 2[...]

  • Page 35

    35 Table 26 — 5F,H Booster Ratings; R-22 LEGEND *Also ref erred to as Satura ted Intermediate T emper ature . † Requires wat er-cooled heads . SST SDT* 5F20 5F30 5F40 5F60 Cap. Bhp Cap. Bh p Cap. Bhp Cap. B hp – 100 – 50 0.27 0.95 0 .40 1.35 0.54 1.75 0.80 2.25 – 40 0.22 † 1.00 0.3 3 † 1.36 0.43 † 1.7 5 0.6 5 † 2.45 – 30 0.18 ?[...]

  • Page 36

    36 Table 27 — 5F,H Booster Ratings; R-502 LEG END *Also ref erred to as Satura ted Intermediate T emper ature . SST SDT* 5F20 5F30 5F40 5F60 Cap. Bhp Cap. Bhp Cap. Bh p Cap. Bhp – 90 – 30 0.6 1.0 0.9 1.6 1.1 1.7 1.7 3.2 – 20 0.5 1.0 0.7 1.7 1.0 1.8 1.5 3.3 – 10 0.4 1.1 0.6 1.7 0.9 1.9 1.3 3.3 0 0.3 1.0 0.5 1.7 0.7 1 .9 1.1 3.3 10 0.3 1.0 [...]

  • Page 37

    37 Table 28 — Booster Compressor Starting Data *Based on 1750 r pm with 5F ,H c ompressors. W ill v ary directly with r pm at other speeds. CONDENSERS Condenser Ph ysical Data — Refer to T able 29. Re - fer to 5F ,H Product Data for in formation on the cu rrent P701 water-cooled conden sers used with the 5F ,H water- cooled co ndensing un its. [...]

  • Page 38

    38 Table 29 — Conde nser Physical Data LEGEND NO TES: 1. Based on R-22 at 105 F conden sing , 85 F en ter ing water t emperat ure, 10 F rise. Th e 09R H097 is rated a t 10.6 F r ise i n order t o sta y withi n the recomme nded water velocity range. 2. 90 F liquid, 80% fill ed. 3. Purge a nd liquid test cocks fur nish ed on all conde nsers. 4. 5F4[...]

  • Page 39

    39 W ater Cir cuiti ng Arrangements — The water ci r- cuiting arrangement selected for 5F and 09RH condensers depends on available condenser water pressure, t emperature, quantity and source. Refer to T able 32. Refer to the Carr ier System Design Manual for specifi c information and recommenda tions for refri gerant and water piping. Economics ?[...]

  • Page 40

    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d wit hout inc urring obligations. New PC 802 Catalo g No. 510-509 Pri nted in U .S.A. Form 5F ,H/0 9RH-2 XA Pg 40 8- 02 Replace s: 5F ,H/09RH-1X A Copyright 20 02 Car rier Cor po ration Book 3 Ta b D E 1 B o o k 2244 T a b 2[...]