Carrier OMNIZONE 50XJ064-104 manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Carrier OMNIZONE 50XJ064-104, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Carrier OMNIZONE 50XJ064-104 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Carrier OMNIZONE 50XJ064-104. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Carrier OMNIZONE 50XJ064-104 should contain:
- informations concerning technical data of Carrier OMNIZONE 50XJ064-104
- name of the manufacturer and a year of construction of the Carrier OMNIZONE 50XJ064-104 item
- rules of operation, control and maintenance of the Carrier OMNIZONE 50XJ064-104 item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Carrier OMNIZONE 50XJ064-104 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Carrier OMNIZONE 50XJ064-104, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Carrier service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Carrier OMNIZONE 50XJ064-104.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Carrier OMNIZONE 50XJ064-104 item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    Manufa cturer res erves the right to discon tinue, or chang e at any time , specificat ions or designs witho ut notic e and wit hout inc urring obligati ons. PC 111 Catalog No. 535-00 137 Printe d in U.S.A. Form 50 BV ,XJ-2T Pg 1 2-04 Replace s: 50B V ,XJ-1T Book 1 1 Ta b 2 a 2 b Controls Oper ation and T roub leshooting CONTENTS SAFETY CONSIDERA T[...]

  • Page 2

    2 Comf or t Contr oller I/O Module (PCB2) — This input/output module is factory installed in the 50XJ unit and allows additional field points (8 inputs and 8 outputs): VFD (variable frequency dri ve) Bypass, V A V T erm inals Control, Building V e ntilation, and Heating Interl ock. Comf or t Contr oller I/O Module (PCB3) — This accessory contro[...]

  • Page 3

    3 Table 1 — Control Inputs and Outputs LEGEN D DESCRIPTION ABBREV . TYPE CONTROLLER I/O NO . DIP SWITCH SETTINGS Water Econ. Units Air Econ.Un its Switch N o. and Position Inpu ts SW2 SW3 SW1 Main Con tr oller (PCB1) Addr = 1-16 Supp ly Ai r Tem perature SA T Analo g; 10K MCI 1 1 1 Up 1 Do w n 1 Up VFD Duc t Stati c Press ure DSP 4-20mA; Internal[...]

  • Page 4

    4 Carrier Comfort Netw ork Interface — The 50BV , XJ units can be connected to the CCN (C arrier Comfort Network) if desired. System el ements are connec ted to the com munica- tion bus in a daisy chain arrangeme nt. The negative pin of each system element’ s communication connector must be wired to the respective negative pins, a nd positive p[...]

  • Page 5

    5 Dependencies — W ater Econom izer option is enabled, and Fan is On, and Inle t W ater T e mperature is below set poi nt; or from “Remote Scheduler,” or from “Remote Linkage.” Economizer mode i s switched to Off or no start if: there is no condenser waterflow , F ire Input is On, Fan is not On, or Un- occupied mode is On. V ariable W ate[...]

  • Page 6

    6 by the freeze condition. Unit reset is automatic when t he contacts on t he freeze protect ion switch c lose again. T he contacts on the freez e protection sw itch open below 37 F . TO WER SUMP TEMPERA TURE SENSOR (50XJ PC B 3) — This sensor is used for moni t oring (only) the tower sump temperat ure. LEA VING W A TER TEMPERA TURE SENSOR (50XJ [...]

  • Page 7

    7 AIR TERMINALS AND FRESH AIR DAMP ER (50XJ PC B 2 ) — The V A V T erminal Open (TRMOP), V entilation Output (VENTR), V A V T erminals Control ( TRMCT), and Heat Interlock Relay (HIR) terminals provide dry contacts to command the V A V terminals open; a ventilation dampe r open; V A V ter minals to control to their cooling set points; and V A V t[...]

  • Page 8

    8 CONTROLS AND FUNCTIONS Usin g the Local In terface Displa y — The Local Interface De vice (LID) is a CCN operator interface tha t gives the user the capability to view and modify all configuration and service data for the C C6400 control system. The LID also allows the user to override all point display and maintenance data. ME N U S T R UC T U[...]

  • Page 9

    9 • Pres sing the appr opriate LID numeri c key (i.e., 2) and the appropriate function key (i .e., ) to directly access an item without having to scroll through all the items in that category . Press to display the first maintenance d ecision. Edit Mode — Be cause the L ID firs t displa ys items in Status mode when it is powered up, the user mu[...]

  • Page 10

    10 Table 6 — Quick Access Chart LEGEND NOT ES: 1. T o ch ange from Edit m ode to S tatus m ode, press o r press again. 2. Not all availab le se lections will have items to select in su ble vels. A utomatic Run T est — The 50BV ,XJ unit controls are programmed with an automat ic run test that checks conne ction and operation of major components.[...]

  • Page 11

    11 2. Press 3 and then . The LID display will show: Controller Password 3. Press . The LID display w ill show: L o gi nt oC o n t r o l l e r Enter Passw ord NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. If the LID display is in Edit mode, then the di splay will onl y show the word “pass- word.” Press the key to to[...]

  • Page 12

    12 22. The control forces CMP4 (compressor 4) on, if config- ured, then waits 5 sec onds. The LID display shows: Factory/F ield T est Sto p The yellow LED will go off, and the red LED will go off. 23. The control forces CMP4 off. 24. The r un tes t is c omplet e. P ower Up the LID Displa y — After completing the automatic run test, perform t he f[...]

  • Page 13

    13 8. Enter the la st two digits of the current year . Press then press . The LID display will show: Update Clock No 9. Press 1 and then to cause the controller to update the clock. The LID display wi ll flash. Press twice to view the default display and the clock should update to the input time and date. Configure Sche dules — Schedul es are one[...]

  • Page 14

    14 Table 7 — Controller S et Points LEGEN D Chec k System P arameter s — T o check s ystem parameters, press the button. The LID display will show: “Hardware Points T abl e 1.” Press to view the hardware points. The user can navigate up and down through the points with the up and down arrows. Press 2 and to display the software points. The [...]

  • Page 15

    15 Table 8 — Controller Hardware Points Table 9 — Software Points Table 10 — Configura tion Parameters LEGEND Set Contr oller Addr ess — T o set the address of the OMNIZONE ™ System Control panel c ontroller , pe rform the following procedur e: 1. Press 7 and then . Press and then . 2. T ype in the CCN element number and press . 3. Press [...]

  • Page 16

    16 OPERA TION Occupancy Determination — The O MNIZONE™ controller can determi ne occupancy in many ways. Local occu- pancy is dete rmined by either a local schedule containe d in the CC6400 controller , the use of the ROCC discrete input point or by sett ing the L ocal/O ff/Remot e switc h to Local . In orde r for the CC6400 schedule or ROCC po[...]

  • Page 17

    17 COMRES triggers the compressor staging routine that controls the number of compressors energized. Units are equipped with 4 compressors piped in s eparate refrigerant circuits, and staged On/Off in a fixed sequenti al manner (compressor no. 1 through compressor no. 4). The compressor control routine uses a PID calculation to determine the percen[...]

  • Page 18

    18 Units not equipped with a water economizer ca n be ordered with the r everse/hea d pressure control valve fact ory install ed and a pressure transduce r located in t he discharge line of compressor no. 1. When the condenser water temperature gets low enough to cause the head pressure to dr op, the valve will be modulated t o control the head pre[...]

  • Page 19

    19 LOW -PRESSURE SWITCH ( LPS) — T h e L o w - P r e s s u re Switch is loca ted i n the sucti on refrige rant line of each compressor , and is set to open a t pressures below 27 psig. It is wired in the 1 15 va c control power line of the compressor contactor (in seri es with the HPS and EFS), and activates the COL board (above) when it opens. E[...]

  • Page 20

    20 S T A T U S M O N I T O R M O D E — In Status M onitor mode, it i s possible to monitor t he VFD status (freque ncy comman d, output voltage, c urrent, ter minal info rmatio n, etc.) . Status monitor mode is en tered by pressi n g the Setu p/Program /Monitor k ey , then select ing MON at the mode selecti on menu and pressing the Read/ W ri te [...]

  • Page 21

    21 T a b l e1 3—V F DT r i pM e s s a g e sf o r5 0 X JU n i t LEGEND LED MES SA GE EXPLA NA TION nErr Displa yed in the trip history in standard monitor mode when no trip has been recorded since the last VFD reset or t rip clear . OC1 Overcurrent during acceleration tr ip OC2 Overcurrent during deceleration tr ip OC3 Overcurrent during nor mal ([...]

  • Page 22

    22 Table 14 — VFD Mode Summary for 50XJ Unit 50BV V ariable F requenc y Drive Contr ol — The variable frequency drive is factory wired and program med for proper operation with the unit controls; no installation or service adjustments are normal ly required. The VFD defaul t conditions at unit power up are: “0.0 Hz ” in the LED display . Wh[...]

  • Page 23

    23 ECN lamp Lights when ene rgy-sa ving m ode is in operation . RUN ke y l a mp Lights w hen the RUN ke y i s enab led. RUN k ey Pressing th i s key whil e the RUN key lam p is lig hted starts operat i ons. RUN l a mp Lights w hen the in verter is operat i ng. Blinks wh en the autom atic accelerati on/dec elerat i on is operat ing MON la mp Lights [...]

  • Page 24

    24 Table 15 — Non-Trip Messa ges for the 50BV VFD NO TES: 1. ST : T er minal of stand by function. 2. When the ON/OFF function is selected f or DC braking (DB), using the input terminal selection par ameter , you can judge the in ver ter to be normal if “db” disappears when opening the circuit betw een the terminal and CC. Table 16 — Trip M[...]

  • Page 25

    25 Table 16 — Tr ip Messages fo r 50BV VFD (cont) ERROR CODE COMMUNICA TION NO . PROB LEM POSSIB LE CAUSES REMEDI ES OP3 C Overvoltage during constant-speed operation • The input voltage fluctuates abnor mally . (1) The power supply has a c apacity of 200kV A or m ore. (2) A power factor improvement capacitor is opened or closed. (3) A system u[...]

  • Page 26

    26 Table 16 — Tr ip Messages fo r 50BV VFD (cont) *With a parameter, y ou c an choose between tr ip-on and -off. NO TES: 1. During operation, the f ollowing alarms may be displa yed, which ha ve the same m eaning as pre v iously defined alarms. • C (ov erc urrent alarm ) — same as OC • P (overvoltage alarm ) — same as O P • L (overload [...]

  • Page 27

    27 TROUBLESHOOTING Refer to T abl es 17-21 for troubleshooting information. Run T est T roub leshooting — The automatic run test is a diagnostic tool used during unit start-up. T able 17 describes troubleshooting specifically for the automated run test . Table 17 — Run Test Troubleshooting Forcing and Clearing an Input or Output — Dur- ing un[...]

  • Page 28

    28 Table 20 — Alarms Displayed at Unit LID NO TES: 1. Unit display will indicate alar m by displa ying “There is 1 Alar m” or “There are X alarms”, for the activ e alar ms in the controller . 2. Red light on, indicating alar m . 3. Y ellow light is on, indicating a warning. Standar d Diagnostic Features, Alar m and W ar ning L ight s SUPP[...]

  • Page 29

    29 Table 21 — Compressor MUX Board Voltages CO N D EN S E R W A T ER F L O W — This is an optional switch tha t can be used with t he OMNIZO NE™ cont roller . A therm al disp ersio n flow s witch d etects wat er flo wing pa st th e sensor element and closes normally open contacts that ener gize a relay with normally open contacts to the unit [...]

  • Page 30

    30 APPENDIX A — WIRING DIA GRAMS 50BVJ,K Low Voltage Schemat ic TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OUT SPEED VIA CC P24 CC S1 R SF 5 3 BYP AS VFD1 SF + - CMP1 CLO1 LOGIC 1 2 3 + - CLO2 LOGIC 2 - 1 3 + CMP2 17 18 S 1 3 2 4 V C EWT DHS 5 3 ROCC 5 CDWF 3[...]

  • Page 31

    31 NOTES: SEE W/D NUMBER CNTL0038A-EM FOR PCB1 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038B FOR PCB2 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038D FOR LEGEND. L1 L2 L3 T3 T2 COMPR2 CLO2 CURRENT LOOP CC2 T1 L3 L2 L1 COMPR 1 CC1 T2 T3 T1 CURRENT LOOP CLO1 TRANS-1 CBR PCB1 (J1-3) COMMON TBLK BM BM T2 L2 L3 T3 BR L1 T1 T2 L2 L3 T3 BR L1 T1 W VFD E U[...]

  • Page 32

    32 TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OUT SPEED SF 5 3 BYP AS SF + - CMP4 + - 2 1 3 CLO4 LOGIC CLO3 LOGIC 2 - 1 3 + CMP3 CMP1 CLO1 LOGIC 1 2 3 + - CLO2 LOGIC 2 - 1 3 + CMP2 17 18 S 1 3 2 4 V C EWT DHS 5 3 ROCC 5 CDWF 3 5 3 FSD 4 6 64 6 4 64 CMP1 CMP2 CM[...]

  • Page 33

    33 NOTES: SEE W/D NUMBER CNTL0038A-MA FOR PCB1 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038B FOR PCB2 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038D FOR LEGEND. L1 T1 L2 T2 L3 T3 CC2 COMPR2 CLO2 CURRENT LOOP L1 L2 L3 T3 T2 COMPR 4 CLO4 CURRENT LOOP CC4 T1 L1 L2 L3 T3 T2 COMPR 3 CLO3 CURRENT LOOP CC3 T1 L3 L2 L1 COMPR 1 CC1 T2 T3 T1 CURRENT LOOP CL[...]

  • Page 34

    34 TRANS-2 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 17 18 MA_RA FL TS 3 5 TRMOP COMMON TB 2 31 TO PCB1 (J7) J7 J3 J4 J1 PCB2 12345678 SW1 12345678 SW2 12345678 SW4 12345678 SW3 1234 1234 SW6 SW5 0 1 EXT INT 20MA OTHER OTHER 10VDC AO DO AO DO NOTES: SEE W/D NUMBER CNTL0038A FOR PCB1 LOW VOL T A[...]

  • Page 35

    35 TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OUT SPEED VIA CC P24 CC S1 R SF 5 3 BYP AS VFD1 SF + - CMP1 CLO1 LOGIC 1 2 3 + - CLO2 LOGIC 2 - 1 3 + CMP2 17 18 S 1 3 2 4 V C EWT DHS 5 3 ROCC 5 CDWF 3 5 3 FSD 4 6 64 6 4 64 CMP1 CMP2 CMP3 CMP4 + - DSP TRANS-3 (24V[...]

  • Page 36

    36 TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OUT SPEED VIA CC P24 CC S1 R SF 5 3 BYP AS VFD1 SF + - CMP4 + - 2 1 3 CLO4 LOGIC CLO3 LOGIC 2 - 1 3 + CMP3 CMP1 CLO1 LOGIC 1 2 3 + - CLO2 LOGIC 2 - 1 3 + CMP2 17 18 S 1 3 2 4 V C EWT DHS 5 3 ROCC 5 CDWF 3 5 3 FSD 4 [...]

  • Page 37

    37 LEGEND AND NO TES FOR ALL 5 0BV WIRING DIA GRAMS LEGEND ALARM — Unit Alarm Relay (Critical Faul t) ALM-CM — Alar m/Warning Relay Common AO — Analog Output AQ UA — Aquastat BM — Blower Moto r BPS_S — F an Start/Stop Rela y (VFD Bypass Mod e) BR — Bl ower Relay BYP AS — VFD Bypass C ontrol CBR — Circuit Breaker CC — Com pressor[...]

  • Page 38

    38 3 4 2 1 C V S HIR ROCC ALM-CM - + 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 - IN OUT - + + 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1 2 3 3 LOGIC 1 2 3 LOGIC 1 2 3 LOGIC 1 2 3 LOGIC 1 2 LOW VOL T AGE CONTROL WIRING PCB1 500 ORN T1 CB1 502/RED 503/BRN GRN TB4 N GRN CLO4 VFD SF 515/WHT 517 GRA 518 GRA 530 YEL 531 YEL 533 PNK 534 PNK 613 BLU 535 B[...]

  • Page 39

    39 9 10 T1 T2 M1 M2 OLR2 T1 T2 M1 M2 OLR1 H1 X2 X1 H2 H3 H4 11 5 V T4 300 BLK 302 WHT 301 BLK TB3 N TB2 11 5 V 310 BLK 31 1 BLK CMP1 HRN1 306 BLK 308 WHT 320 WHT HRN1 HRN1 309 WHT 307 BLK 312 BLU LPS1 HPS1 314 BLU 313 BLU 312 BLU 315 BLU HRN1 FU27 1 1 4 2 2 2 A B C1 3 3 6 6 316 BLU 318 BLU FRZ1 321/BLK 322 BLK CMP2 331/WHT HRN1 323 PNK LPS2 HPS2 32[...]

  • Page 40

    40 GND S T R U W V VFD IFM 107 BLK 11 7 BLU 11 2 YEL L2 L3 L1 GND DISC1* USE COPPER SUPPL Y WIRES. TB1 COMP1 COMP2 129 BLK 135 BLU 132 YEL 128 BLK 134 BLU 131 YEL 127 BLK 133 BLU 130 YEL 140 BLK 146 BLU 143 YEL 139 BLK 145 BLU 142 YEL 138 BLK 144 BLU 141 YEL C1 C2 103 BLK 11 3 BLU 108 YEL 104 BLK 11 4 BLU 109 YEL Current Loop of CLO1 Current Loop o[...]

  • Page 41

    41 1 2 3 J7 PCB2 3 2 1 CB GRN 24 V X2 X1 TRAN GRN 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 PCB3 J3 J4 J2 1 2 3 J7 SW1 12345678 1 0 RED WHT BLK T ower Sump T emp 0 1 HEA T 1 Building Pressure Leaving Water T emp Indoor Air Quality - + Indoor Relative Humidity - + - + Outdoor Air T emperature 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 HEA T 2 0 1[...]

  • Page 42

    42 LEGEND AND NO TES FOR ALL 50XJ WIRING DIA GRAMS LEGEND ALARM — Unit Alarm Relay (Critical Faul t) ALM-CM — Alar m/Warning Relay Common BPS_S — F an Start/Stop Rela y (VFD Bypass Mod e) BYP AS — VFD Bypass C ontrol C— Compresso r Contactor CB — Circuit B reaker CDW F — Condenser Waterflow Rela y CDW F S — Condenser Waterflow Switc[...]

  • Page 43

    43 APPENDIX B — C ONTROL SCREENS Displa y Screens DESCRIPTION V ALUE UNITS ST A TUS FORCE NAME OMNIZONE::HWP01-32:Hardware points T able 1 Supply Air T emperature 67 dF SA T Duct Static Press ure 0.2 in H2O DSP Comp. St atus MUX 1.86 V olts CSMUX Fire Alarm /Shut Down Enable FSD Cond. W at er Flow Switch Y es CDWF Remote Occupancy Disable ROCC Du[...]

  • Page 44

    44 Displa y Sc reens (cont) DESCRIPTION V ALUE UNITS ST A T US FORCE NAME OMNIZONE:Custom Configuration Compressor Stages 2 NUM_CMP Reset Ratio 3 dF RSET_RT O CD WF 0 =NO ,1=YES 0 CDFW_SWT ECON 0=NO,1=YES 0 EWT_SN S EWT Reset 0=NO,1=YES 1 EWT_RST MOD .VL V 0=NO,1=YES 0 MO D_ECON 0=CONST .,1=V ARIABLE 0 FLOW_TYP 0=RA T ,1=MA T ,2=NONE 2 MARA_SNS PHA[...]

  • Page 45

    45 Configurati on Screens *Def ault values from factory . NO T E: See CC6400 Com f or t Controller Overview and Configuration Manual for configuation inf o rmation. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::CC6400:Controller Identification Description: OMNIZONE VP A C DevDesc Location: T est V ers ion 0.009 Location Software P ar t Number : CEPP-130[...]

  • Page 46

    46 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::DOPI_01: Sup ply Fan Status Discrete Output P oint SFS Name Time Schedule OCCPC01 Name Setpoint Schedule SETPT01 Name Pe r m i s s i v[...]

  • Page 47

    47 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion. DESCRIPTION V ALUE* UNITS N AME OMNIZONE::PRES: Head Pressure (Comp1) Low Input Endpoint 0.6 V olts LowRange High Input Endpoint 4 V olts HighRng Low Conv ersion Endpoint 6.23[...]

  • Page 48

    48 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::HIR: Heat Interlock Rela y Output Logic T ype Norm al LogT ype Minimum Off Time 60 sec MinOff Minimum On Time 60 sec MinOn Delay Time [...]

  • Page 49

    49 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::DSALM02: Phase Protection Monitored Input Point P HASE Name Comparison Point SENS DI00 Name Alarm I nhibit P oint SENSDI00 Name Discre[...]

  • Page 50

    50 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::DSALM05: Fire alar m Monitored Input Point FSD Name Comparison Point SENSDI00 Name Alarm Inhibit P oint SENSDI00 Name Discrete Check A[...]

  • Page 51

    51 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::DSALM08: Compre ssor 1 Alar m Monitored Input P oint C1_ALM Name Comparison Point SENSDI00 Name Alarm Inhibit P oint SENSDI00 Name Dis[...]

  • Page 52

    52 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation. DESCRIPTION V ALUE* UNITS N AME OMNIZONE::DSALM11: Compressor 4 Alar m Monitored Input Point C 4_ALM Name Comparison Point SENSDI00 Name Alarm I nhibit P oint SENS DI00 Name D[...]

  • Page 53

    53 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::EHV A V01: DO - Elec Heat V A V 01 Discrete Output P oint 1 HEA T1 Name Discrete Output P oint 2 HEA T2 Name Discrete Output P oint 3 [...]

  • Page 54

    54 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation. DESCRIPTION V ALUE* U NITS NAME OMNIZONE::INTL K02: Ok to Cool Discrete Output Point COOLOK Name Discrete Input P oint 1 MODE N ame Discrete Input P oint 2 SF_SFS Name Discret[...]

  • Page 55

    55 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion. DESCRIPTION V ALUE* UNITS N AME OMNIZONE::INT LK09: Condenser Pum p Discrete Output Point PUM P Name Discrete Input P oint 1 COOLOK Name Discrete Input P oint 2 SENSDI00 Name [...]

  • Page 56

    56 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::LMALM 02: Entering WaterT emp. Monitored Input Poi nt EWT Name Alarm Inhibit P oint SENSDI 00 Name Limit Check Low Limit 35 dF LowLim [...]

  • Page 57

    57 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::OCCPC01: O ccupancy 01 Time Schedule Manual Override Hours 0 hours Ovrd P eriod 1: Day of W eek 0 DOW1 P eriod 1: Occ upied from 0:00 [...]

  • Page 58

    58 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation. Maintenance Scr eens DESCRIPTION V ALUE* U NITS NA ME OMNIZONE::VPTE STC: Field T est Field T est Reschedule Rate 5 sec R ESCHRA T P ower on Delay 40 s ec R ESCHPO R OMNIZONE:[...]

  • Page 59

    59 Maintenance Screens (cont ) DESCRIPTION V ALUE UNITS ST A TUS FORCE NAM E OMNIZONE::ANCTL01: Supply F an Status Discrete Output P oint Off Control V alue Sensor Group/SPT Sensor 0.17 in H2O V alue Occupied ? No Statu s Analog Low Setpoint 0.3 in H2O Lo wS P Lo Setpoint + Hy st 0 in H2O M odLowSP Hi Setpoint - Hyst 0 in H2O ModHghSP High Setpoint[...]

  • Page 60

    60 Maintenance Screens (cont) DESCRIPTION V ALUE UNITS ST A TUS FORCE NAME OMNIZONE::PRES: Head P ressure(Comp1) System V alue 118.76 PS IG Sysv alue Fo r c e 0F o r c e Status 0 HwStat Alarm Statu s Nor mal AlmStat Sensor V alue 118. 76 PSIG SenV alue Hardware V alue 1.9 V olts HwV alue Channel Number 24 ChanNum Control Algorithm Nam e AD APT02 Al[...]

  • Page 61

    61 Maintenance Screens (cont ) DESCRIPTION V ALUE UNITS S T A TUS FORCE NAME OMNIZONE::DXV A V01: Com pressor Staging Discrete Output P oint 1 Off V alue Discrete Output P oint 2 Off V alue Discrete Output P oint 3 Off V alue Discrete Output P oint 4 Off V alue Discrete Output P oint 5 Off V alue Discrete Output P oint 6 Off V alue F an Status P oi[...]

  • Page 62

    62 Maintenance Screens (cont) DESCRIPTION V ALUE UNITS S T A TUS FORCE NAME OMNI ZONE::HCV A V01: AO - Heating V A V 01 Heating Coil V a lve 0 % V alu e F an Status P oint Off Control V alu e Sensor Group/SPT Sensor 74 dF V alue Occupied ? No S tatus Space Setpoint 55 dF V alu e High Humidity S witch Off V alu e High Humidity S etpoint 99 %RH V alu[...]

  • Page 63

    63 Maintenance Screens (cont ) DESCRIPTION V ALUE UNITS ST A TUS FORCE NAME OMNIZONE::LMALM0 1: Supply air Sensor (T ypical Limit Alar m) Monitored Input P oint 66.97 dF V alue Alarm Inhibit P oint Off V alue Limit Check Alarm S tatus Normal Status Alarm V alue 0 dF AlmV alue Exceeded Limit 0 dF ExcdLim Alarm Pr ocessor Alarm T yp e 2A l m T y p e [...]

  • Page 64

    Manufa cturer reser ves the right to discon tinue, or change at any time, specificat ions or designs w ithout not ice and without incurrin g obligations. PC 111 Cat alo g No . 535-001 37 Printed i n U. S.A. Form 50B V ,XJ-2 T Pg 64 2-0 4 Repla ces: 50 BV ,XJ-1T Book 1 1 Ta b 2 a 2 b Copyright 2 004 Car rier Cor poration Maintenance Screens (cont) D[...]