Go to page of
Similar user manuals
-
Air Conditioner
Carrier 38GXQ
12 pages 0.76 mb -
Air conditioner
Carrier 42ADF025
45 pages 2.74 mb -
Air Conditioner
Carrier SINGLE PACKAGED ELECTRIC COOLING UNITS 50GS
28 pages 1.11 mb -
Air conditioner
Carrier 38NYV035
14 pages 5.33 mb -
Air Conditioner
Carrier COMFORT SERIES 25HCR
10 pages 0.44 mb -
Air Conditioner
Carrier 48GP (N) 024-060
30 pages 0.81 mb -
Air Conditioner
Carrier 48SS036
8 pages 0.59 mb -
Air Conditioner
Carrier 90MU
22 pages 0.4 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Carrier ZONEKIT2ZCAR, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Carrier ZONEKIT2ZCAR one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Carrier ZONEKIT2ZCAR. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Carrier ZONEKIT2ZCAR should contain:
- informations concerning technical data of Carrier ZONEKIT2ZCAR
- name of the manufacturer and a year of construction of the Carrier ZONEKIT2ZCAR item
- rules of operation, control and maintenance of the Carrier ZONEKIT2ZCAR item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Carrier ZONEKIT2ZCAR alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Carrier ZONEKIT2ZCAR, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Carrier service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Carrier ZONEKIT2ZCAR.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Carrier ZONEKIT2ZCAR item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
ZONEKIT2ZCAR WeatherMaker® Two-Zone Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. TABLE OF CONTENTS PAGE Safety Considerations .....................................................................1 Installation Consideration[...]
-
Page 2
Step 2—Wiring To prevent personal injury or possible equipment damage, disconnect the power supply before routing wire. All wiring must comply with local, state, and national codes. NOTE: Use No. 18 AWG color-coded, insulated (35°C min) wire. If thermostats are to be located more than 100 ft from the WeatherMaker Two-Zone Center as measured alon[...]
-
Page 3
2. Properly seal joint using duct tape, mastic, or other approved method. Do not allow mastic to come in contact with actuator. 3. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check your local codes.) (See Fig. 7.) NOTE: All zone dampers and ductwork must be properly sup- ported according to local codes or SMACNA standards. NOTE: There sho[...]
-
Page 4
Step 5—Install Barometric Bypass Damper NOTE: The barometric bypass damper is a critical part of the WeatherMaker Two-Zone System for control of minimum airflow and noise reduction. It is recommended that the bypass be installed. The bypass should be installed according to local codes and SMACNA standards. Be sure the bypass is properly supported[...]
-
Page 5
In automatic changeover, the zoning system works on a first come first serve basis. If 1 zone is calling for heating and the other for cooling, the zone which sent its demand to the I/O center first will operate the equipment in that mode until that zone is satisfied. Step 5—Duct Temperature Optimizer (DTO) For Monitoring Leaving Air Temperature [...]
-
Page 6
Fig. 12—WeatherMaker Two-Zone Circuit Board with Standard Thermostat Wiring A97293 3 Thermostat Zone 2 Y 2 Y 1 R W 1 W 2 C G Thermostat Zone 1 Y 2 Y 1 R W 1 W 2 C Sensors HP Duct Equipment R c B O Y 2 Y 1 W 1 W 2 G R h 24 VAC Power 24 v CL OP C Zone 1 Damper Zone 2 Damper CL OP C G B D 4 F A E C K J I H L M N 2 3 1 ZONE 1?[...]
-
Page 7
NOTE: An HP temperature sensor must be used with a heat pump application using electric strip heat. This is necessary in case the DTO is set to the Off position. Timeguard The WeatherMaker Two-Zone provides equipment protection with an internal 5-minute timeguard delay. This delay is present upon initial power up. There is also a 5-minute timeguard[...]
-
Page 8
timer will start counting down 15, 14, 13...0 minutes. Once the timer expires the control will allow a new mode to restart the equipment. The internal time, as well as the cooling 5-minute timeguard can be cleared by using the comprotec override feature. CARE AND MAINTENANCE For continuing optimum performance and to minimize possible equipment fail[...]
-
Page 9
TROUBLESHOOTING This section contains information to assist you in troubleshooting problems and errors associated with the WeatherMaker Two-Zone system. See Table 2. Step 1—System Diagram, Jumpers, and Switches NOTE: For correct control board operation, it must have either a sensor attached or a 10k resistor in place at the duct and HP inputs. 1 [...]
-
Page 10
I Red LED—Displays ON when fan is energized. J Red LED—Displays ON when first-stage cooling is energized. K Red LED—Displays ON when second-stage cooling is energized. L Red LED—Displays ON when reversing valve is ener- gized. M Red LED—Displays ON when first-stage heat is energized. N Red LED—Displays ON when second-stage heat is energ[...]
-
Page 11
Table 3 shows a temperature/ohm/voltage relationship to help aid in troubleshooting the WeatherMaker Two-Zone System. This table will evaluate both the Duct/HP temperature sensor operation. Use a digital multimeter to perform the following: To verify a sensor is good, disconnect both leads from the I/O board and measure the resistance through the s[...]
-
Page 12
→ Fig. 17—Typical Fan Coil With Single-Speed Air Conditioner A97298 SINGLE-SPEED AIR CONDITIONER TYPICAL FAN COIL C Y G W2 W3 C R Y/Y2 O L E RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1 and 3 * * * * * Y1 * * → Fig. 15—Single-Stage Furnace With Single-Speed Air Conditioner A97296 SINGLE-SPEED AIR COND[...]
-
Page 13
→ Fig. 21—Typical Fan Coil With 2-Speed Air Conditioner A97302 2-SPEED AIR CONDITIONER TYPICAL FAN COIL R G R C W2 Y/Y2 E W3 L O Y1 C Y2 Y1 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1, 2, and 3 * * * * * → Fig. 19—Single-Stage Furnace With 2-Speed Air Conditioner A97300 2-SPEED AIR CONDITIONER SINGLE[...]
-
Page 14
→ Fig. 23—Single-Stage Furnace With Single-Speed Heat Pump A97304 SINGLE-STAGE FURNACE TWO-ZONE SYSTEM INTERFACE CONTROL R GF RF WF R GT E HP O HP OT Y HP C W2 Y O RH G W2 W1 Y1 Y2 O B RC G R W C SINGLE-SPEED HEAT PUMP YT E T C Y 2 1 3 OUTDOOR THERMOST A T (KHAO T0301FST) See notes 4, 5, 6, a[...]
-
Page 15
→ Fig. 27—Single-Stage Furnace With 2-Speed Heat Pump A97308 2-SPEED HEAT PUMP SINGLE-STAGE FURNACE R G R C W Y C Y2 W3 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM W2 Y1 O See notes 2, 5, 6, 7, 9, 10, and 11 → Fig. 25—Typical Fan Coil With Single-Speed Heat Pump A97306 SINGLE-SPEED HEAT PUMP TWO-ZONE SYSTEM TYPI[...]
-
Page 16
→ Fig. 29—Typical Fan Coil With 2-Speed Heat Pump A97310 RH G W2 W1 Y1 Y2 O B RC 2-SPEED HEAT PUMP TYPICAL FAN COIL C G W2 Y/Y2 R C W3 L E Y1 R W2 O W3 Y1 Y2 O TWO-ZONE SYSTEM See notes 1, 2, 3, 9, and 11 * * * * * → Fig. 30—FK4C Fan Coil With 2-Speed Heat Pump A97311 FK4C FAN COIL R R G W1 C DH W2 Y1 Y/Y2 O[...]