Go to page of
Similar user manuals
-
Boiler
Crown Boiler BWC150
26 pages 3.96 mb -
Boiler
Crown Boiler TWI061
42 pages 1 mb -
Boiler
Crown Boiler MWC116ENT
88 pages 9.07 mb -
Boiler
Crown Boiler KSZ065
36 pages 0.31 mb -
Boiler
Crown Boiler XBF-EID
23 pages 1.54 mb -
Boiler
Crown Boiler DTR220
73 pages 1.94 mb -
Boiler
Crown Boiler BSI069
54 pages 1.17 mb -
Boiler
Crown Boiler CWD110
78 pages 2.16 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Crown Boiler BSI207, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Crown Boiler BSI207 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Crown Boiler BSI207. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Crown Boiler BSI207 should contain:
- informations concerning technical data of Crown Boiler BSI207
- name of the manufacturer and a year of construction of the Crown Boiler BSI207 item
- rules of operation, control and maintenance of the Crown Boiler BSI207 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Crown Boiler BSI207 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Crown Boiler BSI207, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Crown Boiler service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Crown Boiler BSI207.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Crown Boiler BSI207 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
1 D E S I G N E D T O L E A D T el: (215) 535-8900 • Fax: (215) 535-9736 • www .crownboiler .com Manufacturer of Hydronic Heating Products P .O. Box 14818 3633 I. S treet Philadelphia, P A 19134 BSI Series Gas-Fired Natural Draf t S team Boilers INST ALLA TION INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler WARNING [...]
-
Page 2
2 T able of Contents I . Product Description .................................................. 1 II. Specifications ............................................................. 2 III. Before Installing ......................................................... 3 IV . Locating the Boiler ...................................................... 3 V . [...]
-
Page 3
3 T ABLE 1: BSI SPECIFICA TIONS 2 II Specifications FIGURE 1: BSI BOILERS - GENERAL CONFIGURA TION INP UT (M B H ) (M B H ) (Sq . ft) (M B H ) (% ) " A " "B " "C " "D " (G al) BS I06 9S 80 .0 BS I06 9E 81 .9 BS I10 3S 80 .0 BS I10 3E 82 .0 BS I13 8S 80 .3 BS I13 8E 82 .0 BS I17 2S 80 .6 BS I17 2E 82 .1 BS I20[...]
-
Page 4
4 3 III Before Installing 1 ) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the requirements of the authority having jurisdiction. • In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the Nati[...]
-
Page 5
5 4 4 ) Do not install this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used. Do not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop. 5 ) The boiler should be located as close to the chimney as possible. 6 ) Do not install this boiler directly on [...]
-
Page 6
6 For Buildings of Other than Unusually Tight Construction 1) Determine whether the boiler is to be installed in a confined space - A confined space is defined by the National Fuel Gas Code as having a volume less than 50 cubic feet per 1000 BTU/hr input of all appliances installed in that space. To determine whether the boiler room is a confined s[...]
-
Page 7
7 6 FIGURE 4: ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC FIGURE 5: ALL AIR FROM OUTDOORS, VIA VENTILATED ATTIC FIGURE 3: BOILER INSTALLED IN CONFINED SPACE, ALL AIR FROM INSIDE[...]
-
Page 8
8 FIGURE 6: ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM FIGURE 7: ALL AIR FROM OUTDOORS, USING HORIZONTAL DUCTS INTO BOILER ROOM 7[...]
-
Page 9
9 8 VI V enting Vent installation must be in accordance with local building codes, or the local authority having jurisdiction, or the National Fuel Gas Code , NFPA 54/ANSI Z 223.1. A typical vent installation is illustrated by Figure 8. The components of vent installation are the vent damper (if used), vent connector and chimney. 1 ) Acceptable Chi[...]
-
Page 10
10 9 1 4 ) Vent damper installation is mandatory on all sizes from the BSI069 to BSI276. The BSI310 through BSI379 may be ordered with or without vent damper. If supplied, install vent damper (see Figure 9) as follows: a ) Open vent damper carton and remove installation instructions. Read the instructions thoroughly before proceeding. Verify that v[...]
-
Page 11
11 10 FIGURE 8: BSI BOILER TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS FIGURE 9: VENT DAMPER INSTALLATION DETAILS RIGHT SIDE VIEW[...]
-
Page 12
12 11 FIGURE 10: GAS CONNECTION TO BOILER * State of Massachusetts Requires Manual Shut-off V alve to be “T” Handle T ype * VII Gas Piping Gas piping to the boiler must be sized to deliver adequate gas for the boiler to fire at the nameplate input at a line pressure between the minimum and maximum values shown on the rating plate. For more info[...]
-
Page 13
13 12 CAUTION • INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED FROM WATER (DRIPPING, SPRAYING, RAIN, ETC.) DURING APPLIANCE OPERATION AND SERVICE (CIRCULATOR REPLACEMENT, ETC.). • OPERATION OF THIS BOILER IN A SYSTEM HAVING SIGNIFICANT AMOUNTS OF DISSOLVED OXYGEN CAN CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE. VIII Sy[...]
-
Page 14
14 Piping Installation 1) Remove parts bag from boiler crate. 2) Install safety valve (spindle must be in vertical position) into tapping on boiler left side (see Figure 1) using the 3/4” NPT nipples and elbow supplied. 3) Pipe the discharge of the safety relief valve to a location where water or steam will not create a hazard or cause property d[...]
-
Page 15
15 14 WRONG - HEADER BULLHEADED INT O T AKE-OFF AND EQUALIZER WRONG - T AKE-OFF BULLHEADED INTO TWO MAINS WRONG - T AKE-OFF BETWEEN RISERS FIGURE 12: COMMON NEAR-BOILER PIPING MIST AKES FIGURE 11: STEAM BOILER PIPING FOR GRAVITY RETURN "A" "B" "C" "D" BSI 069 * 2 1 1/ 2 1 1/ 4 BSI 103 * 2 1 1/ 2 1 1/ 4 BSI 13[...]
-
Page 16
16 IX Indirect W ater Heater Piping All BSI series boilers are equipped with tappings to permit the connection of a Crown Mega-Stor, or other indirect water heater. In this type of system, hot boiler water is drawn from below the water line and passed through the heat exchanger in the indirect water heater. This section describes boiler-side piping[...]
-
Page 17
17 X Wiring 1) 120 V olt W iring - The boiler should be provided with its own 15A branch circuit with fused disconnect. All 120 volt connections are made inside the junction box on the left side of the boiler . Remove the transformer to gain access to this box (also see Figures 16 through 19): • Hot (“black”) - W ire nut to black transformer [...]
-
Page 18
18 Feeder Wiring for Boilers Equipped with McDonnell & Miller #67 Low W ater Cut-offs Figures 14a and 14b show feeder wiring for McDonnell & Miller #101A, McDonnell & Miller WF2-U-24 and Hydrolevel VXT - 24 feeders on boilers equipped with #67 low water cutoffs. The following points apply to all feeder wiring to #67 low water cut-offs: [...]
-
Page 19
19 18 FIGURE 14b: WIRING MCDONNELL & MILLER WF2-U-24 FEEDER OR THREE-WIRE HYDROLEVEL VXT -24 FEEDER T O BOILER EQUIPPED WITH #67 L.W .C.O. CAUTION D O NOT INST ALL JUMPER BETWEEN 2 & 3 ON #67 L.W .C.O. FIGURE 15: WIRING INDIRECT W A TER HEA TER TO BOILER[...]
-
Page 20
20 BSI Control System – Sequence of Operation (Refer to Figures 16 through 19 for ladder and connection diagrams) Sequence of Operation, Standing Pilot 1) When the boiler is ener gized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damper . Assuming that there is no call for heat, and that the damper[...]
-
Page 21
21 20 FIGURE 16: WIRING DIAGRAM, STANDING PILOT AND HYDROLEVEL CG-400A LOW WATER CUTOFF “BURNER” “BURNER” L N V8295A (BSI310-379 ONL Y) FIGURE 17: WIRING DIAGRAM, STANDING PILOT AND McDONNELL & MILLER MODEL 67 LOW WATER CUTOFF L N V8295A (BSI310-379 ONL Y) VENT DAMPER (NOTE 2) NOTE 3 LESS VENT DAMPER 2. VENT DAMPER REQUIRED ON BSI069 - [...]
-
Page 22
22 Safety Control Operation - S tanding Pilot and Intermittent Ignition Hydrolevel CG400A Low W ater Cut-of f - Interrupts burner operation if the water in the boiler drops below a safe level. As the water drops past the cut-off point, the amber lamp on the CG400 will glow . The CG400 will interrupt power to the burners 15 seconds after the water l[...]
-
Page 23
23 FIGURE 19: WIRING DIAGRAM, INTERMITTENT IGNITION AND McDONNELL & MILLER MODEL #67 LOW WATER CUTOFF Blocked Vent (“Spill”) Switch - Automatically interrupts burner operation in the event that flue gas spills from the draft diverter opening. This switch is equipped with a reset button which must be pressed to restore normal burner operatio[...]
-
Page 24
24 XI S tar t-up and Checkout Use the following procedure for initial start-up of the boiler: 1 ) Make sure that the boiler is filled with water to the normal water line (28 3/4 inches above the floor or pad on which the boiler is installed) 2 ) Check all new gas piping for leaks and purge piping sections that are filled with air. See Part 4 of the[...]
-
Page 25
25 24 1 6 ) Check the manifold pressure and adjust if necessary. To do this, use the following procedure: a ) Connect a manometer to the inlet pressure tap on the gas valve (see Figures 23 and 24). b) Check the inlet pressure with all gas appliances on and off. The inlet pressure at the boiler must be within the following limits regardless of what [...]
-
Page 26
26 25 A. This a pplian ce has a pilot wh ich m ust b e l ighted by hand . Whe n lighting th e pilot, f oll ow these in s truc tions exactly. B. BEFO RE LIGHTING smell all a round t he applian ce area fo r gas. B e su re to smell next to t he floor beca use s ome gas is he avier than air and w ill settl e on the floo r . WHA T TO DO IF YOU SMEL L GA[...]
-
Page 27
27 26 A. This a pplian ce has a pilot which m ust b e l ighted by hand . Whe n lighting th e pilot, f ol low these in s truc tions exactly. B. BEFO RE LIGHTING smell all a round t he applian ce area fo r gas. B e su re to smell next to t he floor beca use s ome gas is he avier than air and w ill settl e on the floo r . WHA T TO DO IF YOU SME LL G A[...]
-
Page 28
28 27 A. This applian ce is e quipped w ith an ign ition device whic h automa ti cally lights the pilot. Do try to lig ht the p ilot by han d. B. B E FO RE LIGHTING smell all a round t he applian ce area fo r gas. B e su re to smel l next to t he floor beca use s o me gas is he avier than ai r an d w ill settl e on the fl oor . WHA T TO DO IF YOU S[...]
-
Page 29
29 28 A. This applian ce is e quipped w ith an ign ition device whic h automa ti cally lights the pilot. Do try to lig ht the p ilot by han d. B. B E FO RE LIGHTING smell all a round t he applian ce area fo r gas. B e su re to smel l next to t he floor beca use s ome gas is he avier than ai r an d w ill settl e on the fl oor . WHA T TO DO IF YOU SM[...]
-
Page 30
30 29 FIGURE 22a: MAIN BURNER FLAME - 1” BURNERS FIGURE 22b: MAIN BURNER FLAME - 40mm (“HIGH ALTITUDE”) BURNERS 17) Test thermostat operation while the boiler is running. Turn the thermostat to the lowest setting. For standing pilot boiler models, pilot burner should remain lit but the main burners should stop firing. For intermittent ignitio[...]
-
Page 31
31 30 FIGURE 24a: GAS VALVE DETAIL - HONEYWELL VR8204 AND VR8304 (INTERMITTENT IGNITION) FIGURE 23a: GAS VALVE DETAIL - HONEYWELL VR8200 OR VR8300 (STANDING PILOT) FIGURE 23b: GAS VALVE DETAIL - ROBERTSHAW 7000ERHC AND HONEYWELL V8295 (STANDING PILOT) FIGURE 24b: GAS VALVE DETAIL - ROBERTSHAW 7000DERHC (INTERMITTENT IGNITION)[...]
-
Page 32
32 XII Service and Maintenance On a continuous basis: 1 ) Keep the area around the boiler free and clear from combustible materials, gasoline, and other flammable vapors and liquids. 2 ) Keep the area around the boiler and boiler room ventilation openings clear of objects which might obstruct the flow of combustion and ventilation air . On at least[...]
-
Page 33
33 replace cable. 8 ) Reinstall burners, being careful to put the pilot main burner in its original location. 9 ) Inspect all boiler wiring for loose connections or deterioration. 1 0 ) Inspect the vent system: • Make sure that the vent system is free of obstructions. • Make sure that all vent system supports are intact. • Inspect joints for [...]
-
Page 34
34 disturbed during the inspection process for leaks. Heat Exchanger Cleaning Procedure 1 ) Turn off electrical power and gas supply to the boiler 2 ) Disconnect the damper and vent connector from the boiler . 3) Remove the upper front and top jacket panels. If possible, remove the rear and left side jacket panels 4 ) Remove the burners. 5 ) Remove[...]
-
Page 35
35 XIII T roubleshooting The following pages contain troubleshooting charts for use in diagnosing control problems. T o use these charts, go to the box marked “Start” at the top of the chart on page 35 or 37 and follow the appropriate path though the chart until a box with a list of possible causes is reached. If the problem is known to be with[...]
-
Page 36
36 T roubleshooting Chart for BSI Boilers Equipped with Hydrolevel CG400A Low W ater Cut-offs and V ent Dampers Caution : Read page 34 before attempting to use this chart 35 I s th er e an aud i b le c li c k as R 8225 rel ay pulls in w hen t h e th er m os tat c al l s f or heat ? Do e s r e l a y pull in now ? Ve n t dam per open ? ST A R T Th e [...]
-
Page 37
37 36 24 volts across 1 & 4 (blue&yellow) and 2 & 4 (orange&yellow ) on damper end of harness? N Y Main burners light? 24 volts across red damper lead and yellow transformer lead? * Refer to standing pilot or intermittent ignition troubleshooting chart (page 39 or 40). * Defective damper * Defective or loose damper harness * Obstruc[...]
-
Page 38
38 37 T roubleshooting Chart for BSI Boilers Equipped with McDonnell & Miller #67 Low W ater Cut-offs and V ent Dampers Caution : Read page 34 before attempting to use this chart I s th er e an aud ibl e c lic k as R 82 25 r elay pul ls in w h en the ther m os ta t c alls f or heat ? Do e s r e l a y pul l i n now ? V ent dam per open ? ST AR T[...]
-
Page 39
39 24 volts across 1 & 4 (blue&yellow) and 2 & 4 (orange&yellow ) on damper end of harness? N Y Main burners light? 24 volts across red damper lead and yellow transformer lead? * Refer to standing pilot or intermittent ignition troubleshooting chart (page 39 or 40). * Defective damper * Defective or loose damper harness * Obstructio[...]
-
Page 40
40 S tanding Pilot Ignition System T roubleshooting Chart P ilot li t ? Ma in burners li ght ? Y T urn c o nt rol on gas v al v e t o PIL O T . D e pr ess re d b utt on a nd l i ght pi lot . Hold but t on for at le as t o ne mi nu t e . Does pi l ot light? N * P i l o t t ubi ng bl oc k ed, k ink e d or l eak i ng * P ilo t orif i c e bl oc k ed * [...]
-
Page 41
41 40 Doe s s park s t op w he n p ilot li ght s ? 24 v olt s a cr o ss t ermi nal s 2& 3 at S 8600? Sp a rk ac ros s i g n i t or/ s ens or gap? Y Can y ou hear spa r k in g? * Fau l ty S 860 0 modul e * B reak i n s p ark cab l e in su l ation * B reak i n pi lot p o r c ela in * Inco rrec t p il ot sp a r k g a p * Loos e c onnec t i on i n [...]
-
Page 42
42 41 XIV P AR TS The following parts may be obtained from any Crown distributor . T o find the closest Crown distributor , consult the area Crown representative or the factory at: Crown Boiler Co. Customer Service P .O. Box 14818 Philadelphia P A. 19134 www .crownboiler .com For boilers installed at elevations above 2000 ft, consult the local Crow[...]
-
Page 43
43 42[...]
-
Page 44
44 43 ** These V alves Piped in Series to Provide Redundant Shut-off ***1/4 Pilot T ubing Used with Robertshaw V alves 69 103 138 1 72 207 241 2 76 310 345 3 79 42 1" B URNE R LES S P ILO T B RA CKET 1505 01 2 e a. 4 ea . 6 e a. 8 ea. 11 ea. 1 3 e a. 15 ea . 17 e a. 2 0 e a. 22 ea . 43 MANI FO LD ( 1" B URN ERS ) 1 e a. 7 0015 3 70015 4 7[...]
-
Page 45
45 44[...]
-
Page 46
46 45 69 10 3 138 1 72 207 241 2 76 310 345 3 79 7 5 LEF T SI DE JAC K ET P ANEL 1 e a. 8 50 30 1 85 030 1 85 03 01 8 50 30 1 8 50 3012 85 03 012 8 503 01 2 8 50 30 15 8503 01 5 8 503 01 5 7 6 R IG HT SID E JAC KET PANE L 1 e a. 850 30 0 85 030 0 85 03 00 8 50 30 0 8 50 30 02 8503 002 8503 00 2 8 50 30 05 8503 00 5 8 503 00 5 7 7 R EAR JA C KET PAN[...]
-
Page 47
47 46[...]
-
Page 48
48 A. Before Installing 1 ) Thoroughly inspect the cast iron heat exchanger for any shipping damage, i.e. cracks in the castings, broken lugs or punctures due to mishandling. 2 ) Do not use the heat exchanger if there is any damage to it. 3 ) Inspect the joints between the sections for openings. Reseal any openings with high temperature silicone se[...]
-
Page 49
49 48 FIGURE A1: BASE, HEA T EXCHANGER, FLUE COLLECT OR ASSEMBL Y[...]
-
Page 50
50 5 ) Install the left side panel in the same manner as the right side. 6 ) Attach the front corners of the diverter panel to the side jacket panels using #10 sheet metal screws. 7 ) Install the horizontal (angle) jacket clips in the front edge of the side jacket panels. Slide this clip through the rectangular slot that is about halfway up the fro[...]
-
Page 51
51 50 FIGURE A2: JACKET INST ALLA TION[...]
-
Page 52
52 F . Electrical Wiring Connections (Also refer to wiring diagrams in Part X of the installation manual) 1 ) A pre-wired junction box assembly specific to the control package ordered with the boiler has been provided by the factory . 2 ) Orient the junction box so the black relay , which is mounted to the outside of the junction box, is facing dow[...]
-
Page 53
53 52 FIGURE A3: T APPING LOCA TIONS (SEE TEXT FOR T APPING USES)[...]
-
Page 54
54 T el: (215) 535-8900 • Fax: (215) 535-9736 • www .crownboiler .com Manufacturer of Hydronic Heating Products P .O. Box 14818 3633 I. Street Philadelphia, P A 19134 CROWN Bo iler Co[...]