Go to page of
Similar user manuals
-
Pacemaker
Emerson Process Management Rosemount 8732em
4 pages 1.1 mb -
Pacemaker
Emerson Process Management 3051
28 pages 3.85 mb -
Pacemaker
Emerson Process Management 3051CF
28 pages 3.85 mb -
Pacemaker
Emerson Process Management 00809-0200-4088
8 pages 0.45 mb -
Pacemaker
Emerson Process Management Rev AA
8 pages 0.45 mb -
Pacemaker
Emerson Process Management Model 2700
204 pages 4.69 mb -
Pacemaker
Emerson Process Management 2400S
208 pages 2.33 mb -
Pacemaker
Emerson Process Management MSP900SH
16 pages 0.47 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Emerson Process Management 3051CF, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Emerson Process Management 3051CF one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Emerson Process Management 3051CF. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Emerson Process Management 3051CF should contain:
- informations concerning technical data of Emerson Process Management 3051CF
- name of the manufacturer and a year of construction of the Emerson Process Management 3051CF item
- rules of operation, control and maintenance of the Emerson Process Management 3051CF item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Emerson Process Management 3051CF alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Emerson Process Management 3051CF, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Emerson Process Management service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Emerson Process Management 3051CF.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Emerson Process Management 3051CF item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
Quick Start Guide 00825-0100-4007, Rev CB February 2015 Note Bef ore installin g the transmitt er , con firm the c orrect Devic e Drive r is loaded on the host systems. See page 3 for Syst em R eadine ss. R osemount 3051 Pressure T ransmitt er and R osemount 3051CF Series Flowmet ers with 4-20 mA HART ® Re vision 5 and 7 prot ocol[...]
-
Page 2
February 2015 2 Quick Start Guide NO TICE This guide provi des basic guide lines f or Rose mount 305 1 T ransmitters. It doe s not provide instructions for con figuration, diagnostics, m ainte nance , service , troublesh ooting, Explo sion-proof , Flameproof , or intrinsically sa fe (I.S.) inst alla tions. Ref er to the R osemount 3051 HA RT 7 Re f[...]
-
Page 3
Quick Start Guide 3 February 2015 System re adiness Confirm HART R evision capability If using HART based control or asset management systems, please confirm the HART capability of those systems prior to transmitte r instal lation. Not all systems are capa ble of communicating with HART Revision 7 pro tocol. This transmitter can be configured f[...]
-
Page 4
February 2015 4 Quick Start Guide T ransmitt er installation St ep 1: Mount the transmitter Liquid applications Coplanar In-line 1. Plac e taps t o the side o f the line . 2. Mount besid e or below th e taps. 3. Mount the transmitter so that the drain/vent valves are oriented up ward. Ga s applications 1. Plac e taps in the top or side of the line.[...]
-
Page 5
Quick Start Guide 5 February 2015 Figure 1. Panel and P ipe Mounting Panel m ount (1) 1. 1. 5 / 16 ⫻ 1 1 / 2 Panel Bolts are cu stomer supp lied. Pipe mount Coplanar fl ange T raditional f lange Rosemount 3051T[...]
-
Page 6
February 2015 6 Quick Start Guide Bolting consider ations If the transmi tter installation re quires assembly of th e process flanges, ma nifolds, or flange adapt ers, follow the assembly guide lines to ensure a tight seal for optimal performa nce characteris tics of the transmit ters. Use only bolts su pplied with the transm itter or sold by Emers[...]
-
Page 7
Quick Start Guide 7 February 2015 In-line gage transmitt er orientation The low side pressure port (atmospher ic refere nce) on the in-line gage transmitter is located in the neck of t he transmitter, behind the housing. The vent path is 360° arou nd the transmitter bet ween the housi ng and sensor. (See Figur e 3 .) Keep the vent pa th free of an[...]
-
Page 8
February 2015 8 Quick Start Guide St ep 2: Consider housing rotation To improve field ac cess to wiring or to better view the optional L CD display: 1. Loosen the housing rotati on set scre w using a 5/64-in. hex wre nch. 2. T ur n the housing lef t or right maximum up to 18 0° from its o riginal position (1) . Please note that over rot ati ng c a[...]
-
Page 9
Quick Start Guide 9 February 2015 Figure 5. T ransmitter Electronics Board A. A l ar m B. Security St ep 4: Connec t the wiring and power up Figure 6. T ransmitter Wiring Diagrams (4–20 mA) A. 24 Vdc supply B. R L ≥ 250 C. Current Meter (Optional) Shielded twiste d pair cable should be used for best resu lts. Use 24 AWG or larger wire that does[...]
-
Page 10
February 2015 10 Quick Start Guide 3. Ground hou sing t o fulfill local grounding regu lation s. 4. Ensure prope r grounding . It is important that the instrume nt cable shield : a. Be trimmed close and insulated from touching the transmitter hou sing b. Be c onnec ted to the next shield if cable is routed through a junction box c. Be connec ted to[...]
-
Page 11
Quick Start Guide 11 February 2015 St ep 5: V erif y configur ation Verify the config uration using any HA RT capable c onfiguration tool or Local Operator Interface ( LOI) - option code M4. Confi guration instructions for a Field Communicator and LOI are incl uded in this step. See Rosemount 3051 reference manual (008 09-0100-4007) for con figurat[...]
-
Page 12
February 2015 12 Quick Start Guide V erif ying co nfigura tion with Local Ope rat or Int erface (L OI) The optional LO I can be used for commission ing the device. The LOI is a two button design with internal and external bu ttons. The internal buttons a re located on the display o f the transmitter, while the extern al buttons are loca ted underne[...]
-
Page 13
Quick Start Guide 13 February 2015 Note See Figure 10 on page 15 to confirm E xternal Bu tton F unctionality . Figure 9. LOI Menu Swit ch HAR T revision mode If the HART configurat ion tool is not capa ble of communic ating with HART Revision 7, the 305 1 will load a generic men u with limited cap ability. The following procedures will switch the H[...]
-
Page 14
February 2015 14 Quick Start Guide St ep 6: T rim the transmitter Devices are calibra ted by the factory. Once in stalled, it is recommended to perform a zero trim on g age and differentia l pressure transmitters to el iminate error due to mounting position or static pressure effe cts. A zero trim can be performed using e ither a Field Commu nicato[...]
-
Page 15
Quick Start Guide 15 February 2015 T rimming with configuration buttons A zero trim is to be perform ed using one of the three possib le sets of external configuration butto ns located under the top tag. To access the con figuration butt ons, loosen the screw a nd slide the ta g on the top of the transmitter. Confirm the fun ctionality using Figure[...]
-
Page 16
February 2015 16 Quick Start Guide Safet y instrum ented systems installation For Safety Certified in stallations, re fer to product manua l (00809-0100- 4007) for installation procedure a nd system requirements.[...]
-
Page 17
Quick Start Guide 17 February 2015 Produc t Cer tific ations European Direc tive Information A copy of the EC Declarat ion of Conformity can be fou nd at the end of the Quick Start Guide. The most recent revision of the EC Declar ation of Conformity can be found at www.rosemount.com. O rd in ary Lo ca ti on Ce rti fi c ation from FM Approvals As st[...]
-
Page 18
February 2015 18 Quick Start Guide Europe E8 A TE X Flameproof and Du st Certificate: KEMA00A TE X2013X; Baseefa11A TE X0275X Standar ds: EN60079-0:2012, E N60079-1:2007, EN6007 9-26:2007, EN60079-31:2009 Marking s: II 1/2 G Ex d IIC T6/T5 Ga /Gb, T6(- 50 °C ≤ T a ≤ +65 °C), T5(-50 °C ≤ T a ≤ +80 °C); II 1 D Ex ta IIIC T95 °C T 500 105[...]
-
Page 19
Quick Start Guide 19 February 2015 N1 AT E X Ty p e n a n d D u s t Certificate: BAS00A TE X3105X; Baseefa11A TE X0275X Standards : EN60079-0:2012, EN60079 -15:2010, EN60079-31:20 09 Markings : II 3 G Ex nA IIC T5 Gc (–40 °C ≤ T a ≤ +70 °C); II 1 D Ex ta IIIC T95 °C T 500 105 °C Da (-20 °C ≤ T a ≤ +85 °C) Special Condition s for Saf[...]
-
Page 20
February 2015 20 Quick Start Guide Special Condition s for Safe Use (X ): 1. If the apparatus is fitted with op tional 90 V transient suppressor , it is not capable of withstanding the 500 V insulation te st required by IEC60079-11. This must be take n into acc ount when installin g the apparatus. 2. The enclosure m ay be made of aluminum alloy and[...]
-
Page 21
Quick Start Guide 21 February 2015 2. In case of re pair , contact the manufac turer for inf ormation on the dimensions o f the flameproof joints. 3. The capacitance of the wrap around label, be ing 1.6 nF , exceeds the limit in T able 9 of ABNT NBR IE C 60079-0. The user sh all dete rmine suitabilit y for the specific application. I2 INMETRO Intri[...]
-
Page 22
February 2015 22 Quick Start Guide Japan E4 Japan Flameproo f Certificate: T C20577, T C20578, T C20583, TC20584 Marking s: Ex d IIC T5 T echnical Re gulations C ustoms Union (EAC) EM EAC Flameproof Certificate: R U C-US.Gb05.B.00400 Markings : Ga/Gb Ex d I IC T5/T6 X, T5(-60 °C ≤ T a ≤ +80 °C), T6(-60 °C ≤ T a ≤ +65 °C ) Special Condit[...]
-
Page 23
Quick Start Guide 23 February 2015 Special Condition s for Safe Use (X): 1. When the thread ad apte r is used with an enc losure in t ype of protection increased saf et y “e” the e ntry thread shall be suitably s ealed in orde r to main tain the ingress protection rating (IP) of the enclosure . 2. The blanking plug shall not be u sed with an ad[...]
-
Page 24
February 2015 24 Quick Start Guide Figure 11. Rosemount 3051 EC Declaration of Conformity[...]
-
Page 25
Quick Start Guide 25 February 2015[...]
-
Page 26
February 2015 26 Quick Start Guide[...]
-
Page 27
Quick Start Guide 27 February 2015[...]
-
Page 28
Rosemount W orld Headquarters Emerson Process Management 6021 Innovation Blvd Shakopee, MN 553 79, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com North America Regional Offic e Emerson Process Management 8200 Market Blvd. Chanhassen, MN 553 17, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCR[...]