Go to page of
Similar user manuals
-
Boiler
Kenmore 5EWL.20
41 pages 1.53 mb -
Boiler
Kenmore 4EW1.50
41 pages 1.53 mb -
Boiler
Kenmore 3EW.75
41 pages 1.53 mb -
Boiler
Kenmore KWX - 9V
36 pages 1.39 mb -
Boiler
Kenmore 4EW.90
41 pages 1.53 mb -
Boiler
Kenmore 3E W.65
41 pages 1.53 mb -
Boiler
Kenmore KWX - 7V
36 pages 1.39 mb -
Boiler
Kenmore 5EW2.00
41 pages 1.53 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Kenmore 3EW.75, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Kenmore 3EW.75 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Kenmore 3EW.75. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Kenmore 3EW.75 should contain:
- informations concerning technical data of Kenmore 3EW.75
- name of the manufacturer and a year of construction of the Kenmore 3EW.75 item
- rules of operation, control and maintenance of the Kenmore 3EW.75 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Kenmore 3EW.75 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Kenmore 3EW.75, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Kenmore service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Kenmore 3EW.75.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Kenmore 3EW.75 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
[ Owner's Manual MODEL NO. 3E W. 65 3EW. 75 3EWI';O0 4EW.90 4EWl ;25 4EW1.50 5EWl.20 5EW1.75 5EW2.00 CAUTION Read aft instructions carefully before starting the installation. Save this manual for reference. Off-Fired Hot Water Boiler • Installation • Operation • Repair Parts[...]
-
Page 2
KENNMORE CAST IRON BOILERS FULL ONE YEAR WARRANTY ON HOT WATER AND GAS STEAM CAST IRON BOILERS For one (1) year from the date of installation, when this boiler is installed and maintained in accordance with our instructions. Sears will repair defects in material or workmanship in the boiler, free of charge. LIMITED 12 YEAR WARRANTY ON STEAM CAST IR[...]
-
Page 3
INTRODUCTION The Empire Water boiler is a natural draft oil fired hot water boiler comprised of cast iron sections. The Empire Water boiler is available with 3, 4, or 5 cast iron sections. These sections are held together by cast iron push nipples. The Empire Water boiler is capable of firing #2 fuel oil from 0.65 gph up to 2.00 gph. Boilers may be[...]
-
Page 4
BOILER RATINGS AND CAPACITIES BOIIiR MOI)EI.NO Wlill WIIIIOU I IANK[ISS IANKIESS ('Oil ('OIl niw (_5I ¸ 3[!W65Z - 31,W 751 3EW 75Z 31!WI OttI ¸ 3EWI IRIZ 4[iw 90T 4EW 99Z 41!WI 251 4EWI 25Z 41LWl 501 4EWl 50Z 5EWI 20'I 5EWI 20Z 5EWI.75 I 5EWI 75Z 5[-W2 00"[ SEW200Z NO INPUI **llliA'[ ING Sli(' +M[_II ( APA('IIY [...]
-
Page 5
RULES FOR SAFE INSTALLATION AND OPEIL_TION 1. Read the Owner's Manual for Safe Operation carefidly. Failure to tbllow tile rules tbr sale operation and the instructions can cause a malflmction of the boiler and resuh in death, serious bodily injury, and/or property damage. 2. Check your local codes and utility requirements before installation.[...]
-
Page 6
BEFORE YOU START Complete all of the following prior to installing the boiler. A. Check to be sure you have selected the right size boiler with the proper capacity. The I=B=R rating of the boiler selected should be greater than or equal to the calculated peak heating load (heat loss) for the building or area(s) served by the boiler and associated h[...]
-
Page 7
ALWAYS KEEP TILE NL_NUAL FUEL SUPPLY VALVE SHUT OFF, IF THE BUI_NER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIa_clE. I_NSTALLATION REQUIRELMENTS 1 SHUT OFF VALVE OIL RLTER 2** FI LL PiPE MIN 2" VENT PIPE OIL TANK LINES TO OTHER APPLIANCES TO OUTSIDE ELECTRIC LINE AUTOMATIC FILL VALVE NOSHUTOFF EXPANSION TANK DRAFT REGULATO_ VENT PiPE RELIEF VAI[...]
-
Page 8
FRESH AIR FOR COMBUSTION WARNING I Be sure to provide enough fresh air for combustion. Enough air ensures proper combustion and assures that no hazard will develop due to the lack of oxygen. I NOTE [ If you use a fireplace or a kitchen or a bathroom exhaust fan, you should install an outside air intake. These devices will rob the boiler and water h[...]
-
Page 9
B. All Air from Outdoors: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. 1. When d[...]
-
Page 10
SYSTEM PIPING I. When the installation of the boiler is for a new heating system, first instal! all of the radiation units (panels, radiators, baseboard, or tubing) and the supply and return mains. After all heating system piping and components have been installed, make final connection of the system piping to the boiler. It is recommended to mount[...]
-
Page 11
SYSTEM PIPING ARRANGEMENT ZONING WITH ZONE VALVES > CIRCULATOR ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK > PIPING ARRANGED FOR "POWER P[VRGING" AIR OUT OF SYSTEM PIPING, REFER TO THIS MANUAL'S SECTION ON "FILLING THE SYSTEM _,VITH WATER" OPTION #1 BALANCINGVALVE ZONE VALVE RETURN FROM SYSTEM IT I RAIN VALVE FOR [...]
-
Page 12
SYSTEM PIPING ARRANGEMENT ZONING WITH CIRCULATORS CIRCULATOR ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PIPING ARRANGED FOR "POWER PURGING" AIR OUT OF SYSTEM PIPING, REFER TO THIS MANI_AL'S SECTION ON "FILLING THE SYSTEM WITH WATER" OPTION #1 RETURN FROM SYSTEM [ _ DRAIN VALVE FOR POWER PURGING MAIN SHUTOFF VALVE AUTOM[...]
-
Page 13
SYSTEM PIPING ARRANGEMENT ALTERNATE NEAR BOILER PIPING DIAPHRAGM EXPANSION TANK MOUNTED OFF THE BOILER > CIRCULATOR ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL, USE OPTION #2 IN "FILLING THE SYSTEM WITH VATER" THIS PIPING ARRANGE_IENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS RETURN FROM SYSTEM ISOLATION VAL[...]
-
Page 14
7. Boilers may be factory packaged with a tanMess heater coil see figure below. This coil provides instantaneous heating of water for domestic use - if proper burner and water supply line controls are used. Tankless coils are meant to provide domestic hot water for intermittent draws, no_J continuous flow. IMPORTANT Do not use a tankless coil if yo[...]
-
Page 15
8. Antifreeze addedto boilers must be non-toxic, and must be of a type specifically intended for use in closed b_ydronic heating systems. Under no circumstances should automotive antifreeze be used. Antifreeze used in any boiler may reduce capacity by 10% or more and increase fuel consumption. Tankless coil performance will fall as concentration of[...]
-
Page 16
I or oil-fired boilers for connections to vents or chimneys, vent installations shall be in accordance with applicable provisions of INSTALLATION OF OIL BURNING EQUIPMENT, NFPA-31 - latest revision, and applicable provisions of local building codes. CHIMNEY AND CHIMNEY CONNECTIONS This is a very important part of your heating system. No boiler, how[...]
-
Page 17
TYPICAL CHIMNEY CONNECTION MUST BE AT LEAST 4 INCHES THICK- AND BE TIGHT. MUST SLOPE UP AT LEAST 1/4 INCH PER FOOT OF HORIZONTAL RUN DRAWBAND LAST PIECE INSTALLED TIGHT, SMOOTH, CORRECTLY SIZED. I I ! • SEALED IN THIMBLE .TIGHT CLEAN-OUT DOOR MUST BE REQUIRED MIN- IMUM HEIGHT• MUST RE AT LEAST 3 FT. HIGHER THAN HIGHEST PART QF PASSAGE THROUGH R[...]
-
Page 18
ELECTRICAL CONNECTIONS Thermostat Install a 24-volt thermostat (not provided) in a proper location. The location of the thermostat has an important effect on boiler system operation. BE SURE TO FOLLOW THE INSTRUCTIONS INCLUDED WITH THE THERMOSTAT. Grounding Permanently ground the boiler according to local codes and the National Electrical Code. Run[...]
-
Page 19
SE_/ARS KENNMORE CAST IRON BOILERS FULL ONE YEAR WARRANTY ON HOT WATER AND GAS STEAM CAST IRON BOILERS For one (1} year from the date of installation, when this boiler is installed and maintained in accordance with our instructions Sears will repair defects in material or workmanship in the boiler, free of charge. LIMITED 12 YEAR WARRANTY ON STEAM [...]
-
Page 20
MAIN AIR VENT: for down flow systems or diaphragm type expansion tanks (not provided) Before a system is filled with water, there is air in the pipes and radiation units• Some of the air will be trapped as the system is filled. It is possible to eliminate most of this air through the air vents on the radiation units• A main air vent will speed [...]
-
Page 21
FILLING THE BOILER HOW A HOT WATER SYSTEM OPERATES The entire heating system (boiler, piping, and radiation units) is filled with water. As the water in the boiler is heated, it is circulated from the top of the boiler through the supply main to the radiation units. The cooler water in the radiation units flows back through the return piping throug[...]
-
Page 22
BECKETT OIL BURNER, NOZZLE, AND AIR SETTINGS _BOILER MODEL 3EW 65* 3EW.75 3EW1.00 4EW.90 4EW1.25 4EW1.50 5EW1.20 5EW1.75 5EW2.00 DELEVAN OIL NOZZLE 0.50-80°B 0.65-70°B 0.85-70°B O.75-80OA 1.00-80°A 1.25-80°A 1.00-60°13 1.5045°B 1.65-60°B FIRING RATE (gph) 0.65 0.75 1.00 0.90 1.25 1.50 1.20 1.75 2.00 HEAD-ADJ. OR SETTING F0 - 1 1/8 F3 - 1 1/[...]
-
Page 23
NOZZLES AND ELECTRODES: Use the proper size, spray angle, and spray pattern nozzle. Refer to the recommended nozzle selection charts at the end of this manual. To install a nozzle, remove the nozzle line electrode assembly, if necessary remove the retention ring assembly, and then install and tighten the nozzle. Be careful not to damage the electro[...]
-
Page 24
BECKETT AFG BURaNER ELECTRODE ADJUSTMENTS VARIABLE (VI) HEADS BOILER MODEL 5EW DIMENSION "'N" DIMENSION "H" (electrode to nozzle) (head to nozzle) 1/16" 7/32" to 9/32" lMENSION "}'1" SEE BELOW--_ 5132 ,,. .._.._CTROOE GAP " " _ ..,a LI or VI HEAD _.. _DIMEMBION -N" E B£LOW BECK[...]
-
Page 25
5/32" - 4 mm ,)- 5/64" to 7/64" or 2 to 2.5 m[__ "_ 5/32" or 4 mm 5/32" to 13/64" or 4 to 5 mm _ I _ i -- E E TO 23[...]
-
Page 26
CHECKING AND ADJUSTING CONTROLS A boiler using a tankless coil is configured with a Honeywell L8124C Combination Hi/Low Limit Aquastat Relay (refer back to the SYSTEM PIPING section for more details). A boiler not using a tankless coil is configured with a Honeywell L8148A Hi Limit Aquastat Relay. Instructions for the control provided are included [...]
-
Page 27
MAINTENANCE ANUALLY: To assure trouble-free operation, it is recommended that the flue passages, combustion chamber area (target wall, fire door insulation, durablanket), burner adjustment, operation of the controls, and boiler seals (fire door gasket or silicone seal, cast iron sectional seals, flue collector) be checked once each year by a compet[...]
-
Page 28
OIL BOILER / BURNER CLEANING INSTRUCTIONS OIL BOILER CLEANING: I. Shut off all electrical power to the boiler / burner and shut off fuel oil supply. 2. Remove the vent pipe from the top of the boiler. Inspect the pipe and chimney for signs of corrosion and deterioration. Clean out the base of the chimney. If the vent pipe shows any signs of corrosi[...]
-
Page 29
OIL BURNER CLEANING: These are general instructions for cleaning an oil burner. For speci_'lcs, consult the buruer manufacturer's instructions. 1. Make sure all electrical power to the boiler / burner and the fuel supply to the burner are shut off. 2. With the swing door open, clean any soot accumulations from the end of the burner and if[...]
-
Page 30
SERVICE HINTS You may avoid inconvenience and service calls by checking these points before you call for service. Possible Cause Thermostat is not set correctly Boiler or Burner may be dirty Burner may not be firing at proper rate Burner may be short-cycling No power to boiler Controls out of adjustments Radiators not heating Circulating pump not r[...]
-
Page 31
ELECTRICAL WIRING BOILER WITH TANKLESS COIL AND HONEYWELL L8124C AQUASTAT CONTROL (BECKETT AFG BURNER SHOWN) BOILER WITHOUT TANKLESS COIL HONEYWELL L8 ! 48A AQUASTAT CONTROL (BECKETT AFG BURNER SHOWN) 24 VOLT THERMOSTAT 120V i I SUPPLY ? NEUTRAL I I HOT _ BK W : : PROTECTED OISCONNECT [_ ua12_c _ ® mUASTAT @j().@@ ,.___ W @ IGN. TRANN OIL VALVE CI[...]
-
Page 32
BOILER WITH TANKLESS COIL AND H ONEYWELL L8124C AQUASTAT CONTROL (CARLIN EZ BURNER SHOWN) BOILER WITHOUT TANKLESS COIL HONEYWELL L8148A AQUASTAT CONTROL (CARLIN EZ BURNER SHOWN) 24 VOLT THERMOSTAT 120V _ r _k POWER I i soP.LY _ N_UTRAL i i .oT _ eK w ] I L8124C _--_-'#'-(_@ AQUASTAT @J_'_(_ R W k CIRCULATOR 8K m IGN* TRAN$ OIL VALVE [...]
-
Page 33
BOILERWITH TANKLESS COIL AND HONEYWELL L8124C AQUASTAT CONTROL (RIELLO 40 BURNER SHOWN) BOILERWITHOUTTANKLESS COIL HONEYWELL L8148A AQUASTAT CONTROL (RIELLO 40 BURNER SHOWN) 120V pOWER SUPPLY 120/6O/I OVERCURREHT PROTECTED DISCONN[CT 24 VOLT THERMOSTAT @ COLO_ COOL BK- BLACX R- RED E_ - 8K'G_m B.- 8U_ L8124C AOUASTAT E w BK iI _ _CAPAC[TOR C T[...]
-
Page 34
SEQUENCE OF OPERATION BOILER WITH TANKLESS COIL: Aquastat hiI_h limit controller: The aquastat control's high limit contacts open and rum off the burner when the boiler water temperature reaches the control's high limit set point. The high limit contacts automatically reset alter the boiler water temperature drops past the set point by 10[...]
-
Page 35
SEQUENCE OF OPERATION BOILER LESS TANKLESS COIL: Aquastat high limit controller: The aquastat control's high limit contacts open and turn offthe burner when the boiler water temperature reaches the control's high limit set point. The high limit contacts automatically reset after the boiler water temperature drops past the set point by 10?[...]
-
Page 36
REPAIR PARTS NOTES: _O0-F _CX _IUCQ_C _U88_R _or S_ewH i © ITEM DESCRIPTION 3EW I Water Boiler Back Section (EW-3) ¢03-00-008 2 Water Boiler Mddle Section EW-2) 403-00-007 3 Empire Water Front SeclJon IEW-1) 403`00-006 4 Cast Iron Machined Nipples 2" 433-00-976 5 1/4" Tie Rods 1464354302 6 Tie Rod 1/4"-20 Hex Head Nut 146-95-041 7 [...]
-
Page 37
REPAIR PARTS I I I I BALLOON SYMBOL KEY NO. &NTITY [_ ___1 I ITEM 1 2 3 4 5 6 7 8 9 10 11 12 DESCRIPTION Empire Water Front Section (EW-1 3/8"-16 x 2-1/4" stud 3/8" Whizlock Nut Swing Door Insulation Swing Door Hinge 1/4" x 2" Round Head Rivet 3/8" x 1" Hex Head Serrated Flange Bolt 3/8" x 48" Fiberf[...]
-
Page 38
% REPAIR PARTS BALLOON 5YMBOL KEY //--_TD4 _oI / / ITEM DESCRIPTION 1 Right Side iacket Panel 2 Back Jacket Panel 3 Top Jacket Panel 4 Left Side jacket Panel 5 Upper Front Jacket Panel 6 5/16" Acorn Nut 7 #10 x 1/2" Jacket Screw 8 Stand Off 9 Lower Front Jacket Panel {boiler w/swing door) XX Complete Jacket for Boiler with Swing Door 3EW [...]
-
Page 39
REPAIR PARTS 5a,5b 4 I (Without Tankle_= colt) Tankle== Coil) 8 FRONT VIEW WATER OUTLET 7 RIGHT SIDE VIEW j 3b 3a 3c 5 OPTIONAL TANKLESS COIL WATER HEATER WITH 1/2" NPT CONNECTIONS ITEM DESCRIPTION 1 Beckett AFG F-Head Oil Burner 1 Beckett AFG Variable Head Oil Burner ..... Beckett AFG F-Head Low Fire Kit (0.65 _ph) Beckett AFG F-Head Low Fire[...]
-
Page 40
BECKETT OIL BURNER_ NOZZLE, AND AIR SETTINGS BOILER DELEVAN FIRING HEAD-ADJ, LOW FIRE AIR STATIC OIL MODEL OIL NOZZLE RATE (gph) OR SETTING BAFFLE SHUTTER / BAND PLATE BURNER 3EW.65" 0.50-80°B 0 65 F0 - 1 1/8 YES 10 / 0 3-5/8 AFG F-HEAD 3EW 75 0.65-70°B 0.75 F3 - 1 1/8 YES 10 / 0 3-1/2 AFG F-HEAD 3EW1.00 0.85-70°B 1.00 F3 - 1 II8 NO 10 / 2 [...]
-
Page 41
Owner's Manual MODEL NO. 3EW.65 3EW.7+5 3EWI:00" 4EI/V.-90. 4EW.1_25 4EWI'_50 5EW1.20 5EWi".75 5EW2.00 HOW TO ORDER REPAIR PARTS TELL SEARS YOU WANT IT INSTALLED THEN RELAX F_4-t_9 Oi/-Fired Hot Water Boiler Now that you have purchased your Bo_ler should a need ever exist for repair parts or serwce, simply coHtact an,! Sears Ser[...]