Lennox International Inc. 4HP18LT manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Lennox International Inc. 4HP18LT, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Lennox International Inc. 4HP18LT one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Lennox International Inc. 4HP18LT. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Lennox International Inc. 4HP18LT should contain:
- informations concerning technical data of Lennox International Inc. 4HP18LT
- name of the manufacturer and a year of construction of the Lennox International Inc. 4HP18LT item
- rules of operation, control and maintenance of the Lennox International Inc. 4HP18LT item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Lennox International Inc. 4HP18LT alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Lennox International Inc. 4HP18LT, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Lennox International Inc. service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Lennox International Inc. 4HP18LT.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Lennox International Inc. 4HP18LT item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    506470-01 Issue 1007 Save these instructions for future reference INST ALLA TION AND MAINTENANCE INSTRUCTIONS 4HP18L T Series S plit System Heat Pump Manufactured By Allied Air Enterprises, Inc. A Lennox International Inc. Company 215 Metropolitan Drive West Columbia, SC 29170 T ABLE OF CONTENTS INST ALLA TION ......................................[...]

  • Page 2

    506470-01 Issue 1007 INST ALLA TION Inspection of Shipment Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier ’s freight bill. T ake special care to examine the unit inside the carton if the carton is damaged. Any concealed damage discovered should be reported to the[...]

  • Page 3

    506470-01 Issue 1007 Roof Mounting Install unit at a minimum of 6” above surface of the roof to avoid ice buildup around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications. • Install the unit high enough above the ground or roof to allow adeq[...]

  • Page 4

    506470-01 Issue 1007 1. Install line volt age power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring. 2. Ground unit at unit disconnect switch or to an earth ground. T o facilitate conduit, a hole is in the bottom of the control box. Conn[...]

  • Page 5

    506470-01 Issue 1007 Placement Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neighbor ’ s home, not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a bedroom window . Glass has a verry high level of[...]

  • Page 6

    506470-01 Issue 1007 6. Braze the line set to the service valve. Quench the joints with water or a wet cloth to prevent heat damage to the valve core and opening port. The tube end must sta y bottomed in the fitting during final assembly to ensure proper seating, sealing, and rigidity . 7. Install the thermal exp ansion valve which is sold separate[...]

  • Page 7

    506470-01 Issue 1007 Figure 8 Page 7 Figure 7 Anchored Heavy Nylon Wire Tie Wa l l Stud Metal Slee v e V apor Line Wrapped in Ar mafle x – Liquid Line Wa l l Stud A utomotiv e Muffler-T ype Hanger Strap Liquid Line to V apor Line Metal Slee v e V apor Line Wrapped in Ar mafle x – Liquid Line Strap Liquid Line to V apor Line Refrigerant Line Set[...]

  • Page 8

    506470-01 Issue 1007 Flushing Existing Line Set and Indoor Coil This procedure should not be performed on systems which contain cont aminants, such as compressor burn out. Required Euipment The following equipment is needed to flush the existing line set and indoor coil (See Figure 9). T wo clean R-22 recovery bottles, an oil-less recovery machine [...]

  • Page 9

    506470-01 Issue 1007 4. Remover the existing R-22 refrigerant flow control orifice or thermal expansion valve before continuing with flushing procedures. R-22 flow control devices are not approved for use with R410A refrigerant and may prevent proper flushing. Use a field-provided fitting to reconnect the lines. 5. Remove the pressure tap valve cor[...]

  • Page 10

    506470-01 Issue 1007 3. Connect the external equalizer line to the equalizer port on the suction line and tighten to 8 ft.lbs. 4. S trap the superheat sensing bulb to the suction header . If installing an exp ansion valve on an indoor coil that previously used a fixed orifice, be sure to remove the existing fixed orifice. Failure to remove a fixed [...]

  • Page 11

    506470-01 Issue 1007 Using an Electronic Leak Detector 1. Connect the high pressure hose of the manifold gauge set to the suction valve service port. (Normally the high pressure hose is connected to the liquid line port; however , connecting it to the suction ports helps to protect the manifold gauge set from damage caused by high pressure.) 2. Wit[...]

  • Page 12

    506470-01 Issue 1007 4. Open both manifold valves and start vacuum pump. 5. Evacuate the line set and indoor unit to a minimum of 500 microns or lower . During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in pressure. A rapid rise in pressure indicates a relati[...]

  • Page 13

    506470-01 Issue 1007 ST ART -UP 1. Rotate fan to check for frozen bearings or binding. 2. Inspect all factory and field-installed wiring for loose connections. 3. After evacuation is complete, open liquid line and suction line service valves to release refrigerant charge (contained in outdoor unit) into system. 4. Replace the stem caps and secure f[...]

  • Page 14

    506470-01 Issue 1007 1. Connect the manifold gauge set to the service valve ports as follows (See Figure 13 above): • Low pressure gauge to suction line service valve • High pressure gauge to liquid line service valve 2. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of R410A. 3. If room temperature is [...]

  • Page 15

    506470-01 Issue 1007 5. Compare the subcooling value with those shown in T able 7. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant. Charge Using Approach Method (TXV System) - Outdoor T emperatures 65°F or Above The following procedure is intended as a general guide and is for u[...]

  • Page 16

    506470-01 Issue 1007 = _ Outdoor Ambient T emperature °F Liquid Line T emperature °F Approach T emperature °F ° ° ° 6. Compare the approach value with those shown in T able 9. If the values do not agree with those provided in T able 8, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the app[...]

  • Page 17

    506470-01 Issue 1007 Page 17 T able 8 L - Liquid S- Suction V alues provided above are typical pressures. Indoor unit matchup, indoor air quality equipment, and indoor load will case pressures to vary .[...]

  • Page 18

    506470-01 Issue 1007 OPERA TION Outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is moved to the ON position, the indoor blower operates continuously . Filter Drier The unit is equipped with a large capacity bi-flow filter which keeps the system clean and dry . If replacement is necessary , [...]

  • Page 19

    506470-01 Issue 1007 Defrost Control T iming Pins Each timing pin selection provides a different accumulated compressor run time period during one thermostat run cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes. The defrost timing jumper is factory i[...]

  • Page 20

    506470-01 Issue 1007 System Diagnostic Module 4HP18L T units cont ain a diagnostic module for troubleshouting heat pump system failures. By monitoring and analyzing data from the compressor and thermost a t demand, the module can accurately detect the cause of electrical and system related failure without any sensors. If a system problem occurs, a [...]

  • Page 21

    506470-01 Issue 1007 Every time the module powers up, the last ALERT LED flash code that occurred prior to shutdown is displayed for 60 seconds. The module will continue to display the previous flash code until the condition returns to normal or 21V AC is removed from the module. TRIP and ALERT LEDs flashing at the same time means control circuit v[...]

  • Page 22

    506470-01 Issue 1007 Thermost at Demand W iring The diagnostic module requires a thermostat demand signal to operate properly . The thermostat demand signal input, labeled Y on the module, should always be connected to the compressor contactor coil so that when the coil is energized, the demand signal input is 24V AC. When the coil is not energized[...]

  • Page 23

    506470-01 Issue 1007 MAINTENANCE Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician. Inspect and clean outdoor and indoor coils. The outdoor coil may be flushed with a water hose. NOTE: It may be necessary to flush the outdoor coil more frequently if it is exposed [...]

  • Page 24

    506470-01 Issue 1007 HOMEOWNER INFORMA TION In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most ef ficient level. Ask your dealer to show you where the indoor unit’s filter is located. It will be either at the indoor unit (installed internal[...]

  • Page 25

    506470-01 Issue 1007 Fan Switch In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority . The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. T[...]

  • Page 26

    506470-01 Issue 1007 St art-Up and Performance Checklist Job Name _____________________________ Job No. ____________ Date ___________ Job Location ___________________________ City _______________ S tate ___________ Installer _______________________________ City _______________ S tate ___________ Unit Model No. _________________________ Serial No.__[...]

  • Page 27

    506470-01 Issue 1007 Page 27 Wire Diagram DESCRIPTION KEY COMPONENT A132 DIAGNOSTIC MODULE B1 COMPRESSOR B4 MOT OR - OUTDOOR FAN C12 CAP ACITOR - DU AL CMC1 CONTROL-DEFROST HR1 HEA TER - COMPRESSOR K1-1 CONT ACT OR - COMPRESSOR L1 V AL VE - REVERSING S4 SWITCH - HIGH PRESSURE S6 SWIT CH - DEFROST S40 THERMOST A T - CRANKCASE S87 SWITCH - L OW PRESS[...]

  • Page 28