Go to page of
Similar user manuals
-
Furnace
Lennox International Inc. O23V-70
24 pages 2.62 mb -
Furnace
Lennox International Inc. Gas Furnace
7 pages 0.54 mb -
Furnace
Lennox International Inc. GHR26
5 pages 0.65 mb -
Furnace
Lennox International Inc. LB-93422A
4 pages 0.21 mb -
Furnace
Lennox International Inc. GSR21Q
6 pages 0.56 mb -
Furnace
Lennox International Inc. EL280DF
7 pages 0.45 mb -
Furnace
Lennox International Inc. R/LUF
4 pages 0.06 mb -
Furnace
Lennox International Inc. R/LBR
4 pages 0.06 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Lennox International Inc. O23V-140, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Lennox International Inc. O23V-140 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Lennox International Inc. O23V-140. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Lennox International Inc. O23V-140 should contain:
- informations concerning technical data of Lennox International Inc. O23V-140
- name of the manufacturer and a year of construction of the Lennox International Inc. O23V-140 item
- rules of operation, control and maintenance of the Lennox International Inc. O23V-140 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Lennox International Inc. O23V-140 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Lennox International Inc. O23V-140, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Lennox International Inc. service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Lennox International Inc. O23V-140.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Lennox International Inc. O23V-140 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
,t_ 2005 Lennox industries Inc, Dallas, Texas, USA INSTALLATION INSTRUCTIONS O23V Series Units OIL UNITS _ Technical 505,082M LL.L[ Publications 10/05 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE A IMPORTANT O23V SERIES UNITS ARE NOT FOR USE IN ZONING APPLICATIONS! These instructions are intended as a general guide and do not superse[...]
-
Page 2
3/4 (19) 3/4_19) 4 D-------_ c==_ CZ222ZD C SUPPLY O AIR czz_ OPENING _ SIDE FLUE OUTLET CENTERING HOLE_ (Field Fabricate Either Side) ELECTRICAL INLET (Right Side Only) OIL PIPING INLET (Left Side Only)_ OPT. OUTDOOR COMBUSTION AIR INLET CENTERING HOLE (Field Fabricate Right Side only) RETURN AIR OPENING (Either Side) 1-1/2 (38)--IP, 1-1/4 (32)--I[...]
-
Page 3
HEATEXCHANGER FLUE OPENING CLEAN-OUT PORT LIMIT SWITCH CONTROL BOX WITH FAN CONTROL BOARD CLEAN-OUT PORT OBSERVATION PORT BECKETT@ AFIIBURNER COMBUSTION AIR INTAKE VARIABLE SPEED BLOWER MOTOR CAPACITOR Figure 2 CONNECTOR TUBE ELECTRONIC PRIMARY 4X4 AIR FLANGE GASKET IGNITION REAR ACCESS CONTROL BOX ADJUST AIR TUBE TRANSFORMER DOOR GASKET IGNITOR DI[...]
-
Page 4
A CAUTION A CAUTION Model No. O23V-70/90/105/120 O23V-140/154 Installation of Lennox oil-fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA-B139 (in Canada), Installation Cod[...]
-
Page 5
Neither the nozzle setting nor the airadjustments are fac- tory set. The furnace is firetested andthe limit control is checked to make sure it functions properly; no factory set- tings are made. During installation, the furnace must be "set up." The installing dealer/contractor must have and use proper test equipment in order to correctly[...]
-
Page 6
A, WARNING I A WARNING CAUTION NOTE - Oil burning equipment may be vented into an ap- proved masonry chimney or type L vent. (Type L vent is similar in construction to type B gas vent. Type L vent car- ties a higher temperature rating and is constructed with an inner liner of stainless steel, rather than aluminum.) Prior to installation of unit, ma[...]
-
Page 7
16. Where condensation of vent gas is apparent, the vent should be repaired or replaced, Accumulation of con- densation in the vent is unacceptable. 17. Vent connectors serving this appliance shall not be connected into any portion of mechanical draft sys- tems operating under positive pressure, 18. Keep the area around the vent terminal free of sn[...]
-
Page 8
Air from an Adjacent Space If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by provid- ing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all fuel-fi[...]
-
Page 9
Equipment in Confined Space All Air From Outside OR_ _ OIL VENT _ WATER II II II II HEATER II II OIL FURNACE INLET AIR NOTE - Each air duct opening shall have a free area of at least one square inch (6A square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located ag[...]
-
Page 10
Locate the barometric draft control within 18 inches of the furnace flue outlet, See figure 13 for barometric draft con- trol location. Horizontal Venting BAROMETRIC CONTROL* HORIZONTAL VENT- -- ING CONTROL CC3 *Barometric control must be installed in the horizontal venting system and located within 18" of flue outlet of furnace. Q U Figure 13[...]
-
Page 11
Oil Piping - One-Pipe System -- AIR VENT -- FILL PIPE _o_1 II TANK I v_l 8ft(2.4m) ol II 111S"UT'OFF I "Maximam IL VALVE I One Pipe Lift _o Oo °°8° _o °o °o_o °o o_ Figure 15 To determine the correct tubing size for piping, refer to table 3 Table 3 One-Pipe Oil Sizing Line Length Pipe Diameter (OD Tubing) 0-50' (15 m) 3/8&[...]
-
Page 12
One-Pipe Systems CAUTION The burner is shipped with fuel pump set for one-pipe op- eration. For one-pipe systems, the oil supply pipe is con- nected to the inlet tap on the pump. A one-pipe system should only be used where there is gravity oil flow to the pump and the pipe is not run at any point above the oil level in the tank. 1. Connect the inle[...]
-
Page 13
IMPORTANT 2, Install the room thermostat and make wire connec- tions to the fan control board. Avoid installing thermo- stat on an outside wall or where it can be affected by radiant heat, Set the adjustable heat anticipator on thermostat according to the wiring diagram sticker pro- vided on unit, 3, Install a separate fused disconnect switch near [...]
-
Page 14
ADJUST The ADJUST pins allow the motor to run at normal speed, approximately 15% higher than normal speed, or 15% low- er than normal speed. Table 6 gives three rows--NORM, (+), and (-) with their respective CFM volumes. Notice that the normal <'NORM" adjustment setting for cool speed position C in table 6 is 800 CFM The "(+)"[...]
-
Page 15
Continuous Fan When the thermostat is set for "Continuous Fan" operation and there is no demand for heating or cooling, the blower control will provide 50% of the COOL CFM selected. G l 50% &_ / G - Fan switch ON CALL g - Fan switch OFF OFF NOTE - With the proper thermostat and subbase, continu- ous blower operation is possible by clo[...]
-
Page 16
023V Wiring Diagram $2, _ ? THERMOSTAT " I _ ' L J LLL: - FACTORY *IRINE co&_____.NsiNG LINE VOLTAGE - -- - LOW VOLTAGE FIELD WIRING DENOTES OPTIONAL COMPONENTS /X 1F ANY WIRE IN THIS APPLIANCE IS REPLACED, IT MUST BE REPLACED WITH LIKE SIZE,RATINE AND INSULATION THICKNESS. REATINO SPEED SELECTOR IF H(_RIZONTAL APPLICATIUN -- IS USED,[...]
-
Page 17
Before starting unit, make sure the oil tank is adequately filled with clean No, 1 or No, 2 furnace oil, NOTE - Water, rust or other contaminants in oil supply sys- tem will cause malfunction and failure of the internal parts of the fuel pump. CAUTION 1, Set thermostat for heating demand and turn on electri- cal supply to unit, 2, Check initial air[...]
-
Page 18
causing the unit to start sooting/smoking, Things which might affect combustion include a nozzle going bad, draft that changes during different climatic condi- tions, dirty oil, dirt obstructing the air inlet, etc. To build in a "window of operation," set up the burner to be 2% less in CO2, For example, if you find a reading of 12% CO2, a[...]
-
Page 19
4, Action: Established flame fails Response: • Burner motor is de-energized and oil primary con- trol goes into recycle mode, • If the fan off delay is longer than the recycle timing, the heat fan continues to run through the next trial for ignition. 5. Action: Limit Switch Opens Response: • Oil primary control shut off the burner. • Circul[...]
-
Page 20
Source Procedure Causes Correction Burner Blown fuse Replace the fuse. Place the trouble light between the black and white leads to the burner motor. No light indicates that no power is getting to the motor. Place trouble light between the black and white leads to the blower motor. Light indicates power to the motor and burner fault. Binding burner[...]
-
Page 21
Source Procedure Causes Correction Burner Motor Low line voltage Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for binding or excessive drag. Check voltage at power source. Correct cause of voltage drop or the call power company. Pump or blower overloading motor Correct cause of o[...]
-
Page 22
Source Procedure Correction Power Locate and secure connection. If voltage fluctuates, fault is in the power source. Recheck voltage at the power source. Causes Loose wiring connection Low or fluctuating line voltage Call power company. Source Poor Fire Flame Detector Oil Supply Procedure After burner fires, immediately jumper across flame detector[...]
-
Page 23
Source Procedure Thermostat Disconnect thermostat wires at the primary control. • Burner turns off: ther- mostat circuit faulty. Primary • Burner not turning off: control primary control faulty. Combus- tion Oil Pres- sure Check burner combustion for CO2, stack temperature, and smoke • Low CO2 less than 10%. • High smoke reading more than a[...]
-
Page 24
Customer Name Street Address City State/Zip Code Furnace Model # Serial # Input Rate Nozzle Used New Construction Replacement Installation Data Furnace Location: A Basement- Open Enclosed* B Utility Room - Open Enclosed* C Closet- Open Enclosed* D Crawl Space- Open Enclosed* *Provisions must be made for adequate air for combustion. See Combustion a[...]