LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO manual
- Read online or download the manual
- 73 pages
- 6.06 mb
Go to page of
Similar user manuals
-
Air Conditioner
LG Electronics PRCKD20E
35 pages 4.33 mb -
Air Conditioner
LG Electronics LSA3ES5M
16 pages 9.01 mb -
Air Conditioner
LG Electronics LT121CSG
39 pages 12.23 mb -
Air Conditioner
LG Electronics L-Maxima Plus
16 pages 9.01 mb -
Air Conditioner
LG Electronics AMNC093D4A0(LMN090CE)
86 pages 6.96 mb -
Air Conditioner
LG Electronics LSA3MP3M
16 pages 9.01 mb -
Air Conditioner
LG Electronics LSA6AP2M
16 pages 9.01 mb -
Air Conditioner
LG Electronics W091CA TSG0
19 pages 5.63 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO should contain:
- informations concerning technical data of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO
- name of the manufacturer and a year of construction of the LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO item
- rules of operation, control and maintenance of the LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the LG Electronics service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the LG Electronics LAN181CNW, LAU181CNW, LA180CPI, LA180CPO item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
LG Room Air Conditioner SERVICE MANUAL LG MODELS: LAN181CNW(ASNC183VML3) LAU181CNW(ASUC183VML3) LA180CPI (ASNC183VML3) LA180CPO (ASUC183VML3) CAUTION website http://www.lgservice.com • BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL. • ONLY FOR AUTHORIZED SERVICE PERSONNEL.[...]
-
Page 2
2 Room Air Conditioner Details of 2006 LG Model Name .................................................................................................... 3 Safety Precautions ......................................................................................................................... 4 Functions .........................................[...]
-
Page 3
Ser vice Manual 3 Details of 2006 LG Model Name 12 Code T ype Code of Model Meaning 1 Producing Center/ A~Z L: ChangW on R22, A: ChangWon R410A, C: ChangW on R407C Refrigerant 2 T ype of Air conditioner A~Z S: Split T ype Air conditioner 3 Cooling/Heating A~Z C: C/O , H: H/P , X: C/O + E/H, Z: H/P + E/H 4,5 Capacity(Btu/h) 1~9 Cooling/Heating Capac[...]
-
Page 4
4 Room Air Conditioner Saf ety Precautions Safety Precautions T o pre v ent injury to the user or other people and proper ty damage, the f ollo wing instructions must be f ollow ed. ■ Incorrect operation due to ignoring instruction will cause har m or damage . The seriousness is classified by the f ollo wing indications. ■ Meanings of symbols u[...]
-
Page 5
Ser vice Manual 5 Saf ety Precautions ■ Operation Be cautious when unpacking and installing the product. • Shape edges could cause injur y . Be especially careful of the shar p edges. For installation, alwa ys contact the dealer or an A uthorized Ser- vice Center . • There is risk of fire, electric shock, e xplosion, or injur y . Do not insta[...]
-
Page 6
6 Room Air Conditioner Saf ety Precautions Do not place a heater or other appliances near the power cable. • There is risk of fire, f ailure of the product, and/or electric shock. Do not let the air conditioner run for a long time when the humidi- ty is very high and a door or a window is left open. • Moisture ma y condense and wet or damage fu[...]
-
Page 7
Ser vice Manual 7 Saf ety Precautions V entilate the product fr om time to time when operating it togeth- er with a stove, etc. • There is risk of fire or electr ical shock. Unplug the appliance before performing c leaning or mainte- nance. • There is risk of electr ic shock. When the product is not be used for a long time disconnect the power [...]
-
Page 8
8 Room Air Conditioner Saf ety Precautions ■ Operation Use two or more people to lift and transport the air conditioner • A void personal injury . Do not install the product where it will be exposed to sea wind (salt spray) directl y . • It ma y cause corrosion in the product. Corrosion, par ticular ly on the condenser and e v aporator fins, [...]
-
Page 9
Ser vice Manual 9 Saf ety Precautions Do not drink the water drained from the unit. • It is not sanitar y and could cause serious health issues. Use a firm stool or ladder when cleaning or maintaining the air conditioner . • Be careful and av oid personal injur y . Replace all the batteries in the remote. • There is risk of fire or explosion.[...]
-
Page 10
10 Room Air Conditioner Functions • Room temperature sensor . (THERMIST OR) • Maintains the room temperature in accordance with the Setting T emp . • Indoor f an is delay ed for 5 sec at the star ting. • Restar ting is inhibited for appro x. 3 minutes. • High, Med, Low , CHA OS • Inter mittent operation of f an at low speed. • The f a[...]
-
Page 11
Ser vice Manual 11 Functions Healthy Dehumidification Operation Mode. ( ) Remote Control Operation ON/OFF Reset Operation Mode Selection Temperature Setting Timer Selection Timer Setting JET COOL Timer Cancel Sleep Operation Airflow Direction Control (Cooling model only) (Heating model only) TEMPERATURE LOW HIGH Cooling Operation Mode.( ) Heating O[...]
-
Page 12
12 Room Air Conditioner Product Ref erences NO TE: Please refer to Label Quality on the product since this specification ma y be changed for impro ving perf or mance Items Unit LA*181CNW(AS-C183VML3)/LA180CP* (AS-C183VML3) P ower Supply ø , V , Hz 1, 208/230, 60 Cooling Capacity BTU/h 17 800/18 000 Input W 2,000/2,000 Running Current A 9.8/8.9 COM[...]
-
Page 13
Ser vice Manual 13 Dimensions 522 928 147 Pipe Hole Fix Hole MODEL DIM Unit W mm(inch) 928(36.5) H mm(inch) 522(20.6) D mm(inch) 147(5.8) Indoor Unit Dimensions Indoor Unit[...]
-
Page 14
14 Room Air Conditioner Dimensions W L6 L5 L7 L8 D L1 L2 L9 L10 L3 L4 H Gas side 3-way valve Liquid side 2-way valve MODEL OUTDOOR UNIT DIM W mm(inch) 870(34.3) H mm(inch) 655(25.8) D mm(inch) 320(12.6) L1 mm(inch) 370(14.6) L2 mm(inch) 25(1.0) L3 mm(inch) 630(24.8) L4 mm(inch) 25(1.0) L5 mm(inch) 546(21.5) L6 mm(inch) 162(6.4) L7 mm(inch) 162(6.4)[...]
-
Page 15
Ser vice Manual 15 Refrigeration Cycle Diagram F or installation ov er rated, *a proper quantity of refr igerant should be added f or each meter . Ex) 18K: When installed at a distance of 30m, 450g of refrigerant should be added. (30-7.5) x 20g = 450g INDOOR UNIT HEA T EXCHANGER (EV APORA T OR) HEA T EXCHANGER (CONDENSER) COMPRESSOR GAS SIDE CAPILL[...]
-
Page 16
16 Room Air Conditioner Wiring Diagram 18K (Cooling Only Models) Wiring Diagram Indoor Unit Outdoor Unit[...]
-
Page 17
Ser vice Manual 17 Operation Details • DISPLA Y 1) C/O Model Operation Indicator • ON while in appliance operation, OFF while in appliance pause . • Flashing while in disconnection or shor t in Ther mistor . (3 sec off / 0.5 sec on) Sleep Timer Indicator • ON while in sleep timer mode, OFF when sleep timer cancel or appliance oper ation pau[...]
-
Page 18
18 Room Air Conditioner Operation Details • While in compressor off , the indoor f an repeats low airflo w speed and pause. • While the intak e air temp is between compressor on temp. and compressor off temp ., 10-min dehumidifica- tion operation and 4-min compressor off repeat. Compressor ON T emp . ➲ Setting T emp+0.5 ° C Compressor OFF T [...]
-
Page 19
Ser vice Manual 19 Operation Details ■ Fuzzy Operation (C/O Model) • According to the temperature set b y Fuzzy rule, when the intake air temp is 0.5 ° C or more belo w the setting temp , the compressor is tur ned off . When 0.5 ° C or more abov e the setting temp, the compressor is turned on. Compressor ON T emp ➲ Setting T emp + 0.5 ° C [...]
-
Page 20
20 Room Air Conditioner Operation Details 2) Fuzzy Operation for Dehumidification • According to the setting temperature selected by Fuzzy rule, when the intak e air temp is 0.5 ° C or more below the setting temp , the compressor is turned off. When 0.5 ° C or more abov e the setting temp, the compressor is tur ned on. Compressor ON T emp ➲ S[...]
-
Page 21
Ser vice Manual 21 Operation Details ■ Off-Timer Operation • When the set time is reached after the time is input by the remote control, the appliance stops oper ating. • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. • If the appliance is on pause at the time set by the timer , the pau[...]
-
Page 22
22 Room Air Conditioner Operation Details ■ Jet Cool Mode Operation (H/P Model) • While in heating mode or Fuzzy operation, the Jet Cool k ey cannot be input. When it is input while in the other mode operation (cooling, dehumidification, v entilation), the Jet Cool mode is operated. • In the Jet Cool mode, the indoor f an is operated at super[...]
-
Page 23
Ser vice Manual 23 Displa y Function 3sec 3sec 3sec (once) Error Code 1 Error Displa y LED (Indoor body operation LED) Error contents • Indoor room temperature thermistor open/shor t • Indoor pipe temperature thermistor open/shor t. • Indoor Thermistor assembly chec k SVC check point 1. Heating Model 2. Cooling Model • Cooling, Soft Dr y , [...]
-
Page 24
24 Room Air Conditioner Intr oduction This symbol alerts you to the risk of electric shoc k. This symbol alerts you to hazar ds that may cause harm to the air conditioner . This symbol indicates special notes. NOTICE Symbols used in this Manual Features Signal Receptor Front Panel Air Inlet Air Discharge Power Cord Air Filter Air Intake Vents Air O[...]
-
Page 25
Ser vice Manual 25 Installation Installation Type "A" screw and plastic anchor Type "B" screw Remote control holder Installation plate Figure Figure Name Screw driver Electric drill Measuring tape, Knife Hole core drill Spanner Torque wrench Ohmmeter Hexagonal wrench Ammeter Gas-leak detector Thermometer, Horizontal meter Flarin[...]
-
Page 26
26 Room Air Conditioner Installation Installation Map Installation parts you should purchase. NOTICE (Left and right are identical) More than 12"(30cm) More than 28"(70cm) More than 24"(60cm) More than 12"(30cm) Sleeve Bushing-Sleeve Putty(Gum Type Sealer) Bend the pipe as closely on the wall as possible, but be careful that it [...]
-
Page 27
Ser vice Manual 27 Installation 1. Check the quality label on the indoor and outdoor unit. 2. Make certain that the refr igerant is R-410A. THIS PRODUCT CONT AINS R-410A REFRIGERANT 1) Diff erent compressor oil - R-410A(P olyol ester) / R-22(Mineral). - Do not mix the e xisting mineral oil. - Do not apply used pipe, tools and gauges co vered with t[...]
-
Page 28
28 Room Air Conditioner Installation Read completely , then follo w step by step . 1) Select the best location 1. Indoor unit ■ Do not hav e any heat or steam near the unit. ■ Select a place where there are no obstacles in front of the unit. ■ Make sure that condensation dr ainage can be con- veniently routed a wa y . ■ Do not install near [...]
-
Page 29
Ser vice Manual 29 Installation 1. Open panel front ■ First,Pull the grille bottom, then remov e screws(2 pieces), and close grille bottom again. ■ The moment of lifting the both low er par ts of panel front, you can hear sound this panel came out, In this time panel front is separated ■ After pull down this panel a bit, and separate con- nec[...]
-
Page 30
30 Room Air Conditioner Installation 4) How to fix installation plate The wall y ou select should be strong and solid enough to pre vent vibr ation Mount the installation plate on the wall with type "A" screws . If mounting the unit on a concrete wall, use anchor bolts . ■ Mount the installation plate horizontally by aligning the center[...]
-
Page 31
Ser vice Manual 31 Installation 1) Flaring work Main cause f or refrigerant leakage is due to defect in the flaring work. Carr y out correct flar ing work using the f ollowing procedure. 1. Cut the pipes and the cable. • Use the piping kit accessor y or pipes purchased locally . • Measure the distance between the indoor and the outdoor unit. ?[...]
-
Page 32
32 Room Air Conditioner Installation 2. T ape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the b undle. Locating at the upper side can cause drain pan to overflo w inside the unit. NO TE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so t[...]
-
Page 33
Ser vice Manual 33 Installation 3) Connection of the pipes-Outdoor 1 . Align the center of the pipings and sufficientl y tighten the flare nut b y hand. 2 . Finally , tighten the flare nut with torque wrenc h until the wrench c licks. • When tightening the flare nut with torque wrench, ensure the direction f or tightening follo ws the arrow on th[...]
-
Page 34
34 Room Air Conditioner Installation 1 Indoor Unit Outdoor Unit 2 3 4 1 2 3 4 5 6 G To branch circuit Ground P ower supply a L1 * L2 Connecting cable(Low v oltage) b T er minal (4P) T er minal (6P) Outdoor unit Wiring Diagram T er minal bloc k Over 5mm (2") Cov er control Conduit panel Connecting cable P ower supply cord * L1 is neutral f or 1[...]
-
Page 35
Ser vice Manual 35 Installation G T er minal bloc k Cap (Remov e) Clamp cord Lock nut Conduit panel Loop Round terminal Screw with special washer Screw with special washer Round terminal T er minal plate Wire Wire Round terminal Insulation Strip 25mm(15/16") Strip 10mm(3/8") Solid wire Cap(Reuse) T aping (f or sealing) Low v oltage line ([...]
-
Page 36
36 Room Air Conditioner Installation After the confir mation of the abov e conditions, prepare the wiring as follo ws: 1) Never fail to ha ve an individual po wer cir cuit specifically for the air conditioner . As for the method of wiring, be guided by the cir cuit diagram posted on the inside of control co ver . 2) The screw whic h fasten the wiri[...]
-
Page 37
Ser vice Manual 37 Installation 2) Form the piping 1. Form the piping by wrapping the connecting por- tion of the indoor unit with insulation material and secure it with two kinds of vin yl tapes. ■ If you w ant to connect an additional drain hose , the end of the drain outlet should be routed abov e the ground. Secure the drain hose appropriatel[...]
-
Page 38
38 Room Air Conditioner Installation CAUTION CAUTION Air Conditioner Circuit Breaker Use a circuit breaker or time dela y fuse. Main pow er source If a pow er plug is not to be used, provide a circuit break er between pow er source and the unit as shown belo w . 3) Connect the cable to the indoor unit 1. Connect the wires to the terminals on the co[...]
-
Page 39
Ser vice Manual 39 Installation T o av oid nitrogen enter ing the refrigerant system in a liquid state, the top of the cylinder m ust be higher than its bottom when you pressurize the system. Usually , the cylinder is used in a v er tical standing position. 1) Air purging Air and moisture remaining in the refrigerant system hav e undesirable eff ec[...]
-
Page 40
40 Room Air Conditioner Installation 3. Evacuation • Connect the charge hose end described in the pre- ceding steps to the vacuum pump to e vacuate the tub- ing and indoor unit. Confirm the "Lo" knob of the manifold v alve is open. Then, run the vacuum pump . The operation time f or ev acuation varies with tubing length and capacity of [...]
-
Page 41
Ser vice Manual 41 Installation 1. First, Check the side co ver assembly exactl y , Fix power cor d in the bottom groo ve of cover side left. 2. Assemble connecting lead wire with controller and first fix the upper part of panel front, then match the lower part of panel front 3. Drive three screws. P anel F ront Connector P anel Front Assemb ly[...]
-
Page 42
42 Room Air Conditioner Installation 1. Chec k that all tubing and wiring have been properly connected. 2. Chec k that the gas and liquid side ser vice valv es are fully open. 1. Prepare remote contr ol 1. Remov e the batter y cover by pulling it according to the arrow direction. 2. Inser t new batteries making sure that the (+) and ( – ) of batt[...]
-
Page 43
Ser vice Manual 43 Operation Operation Remote Contr ol Operations The controls will look like the f ollowing. 1. ST ART/ST OP BUTT ON Operation star ts when this button is pressed and stops when the button is pressed again. 2. OPERA TION MODE SELECTION BUTT ON Used to select the operation mode . 3. ROOM TEMPERA TURE SETTING BUTT ONS Used to select [...]
-
Page 44
44 Room Air Conditioner Disassembly of the parts (Indoor unit) W arning : Disconnect the unit from power supply bef ore making any chec ks. Be sure the power s witch is set to “ OFF ” . 1. T o remove the Grille fr om the Chassis. - Push mark[ ] on the grille bottom then pull it down and remov e 3 secur ing screws . - Lift the both lower parts o[...]
-
Page 45
Ser vice Manual 45 Disassembly of the parts (Indoor unit) 3. T o remove the Ev aporator . - Remo ve 1 scre ws securing the ev aporator . - Pull the e vapor ator out from the chassis carefully . 4. Before remo ving the T urbo Fan. - Remo ve the securing screws from the chassis . - Pull the pipe cov er , top cov er and the air guide. 5. T o remove th[...]
-
Page 46
46 Room Air Conditioner 2-wa y , 3-wa y V alv e 2-way V alve (Liquid Side) 3-way V alve (Gas Side) Shaft position Shaft position Service por t Closed Closed Closed (with valv e cap) (with valv e cap) (with cap) Open Closed Open (counter-clockwise) (clockwise) (push-pin or with vacumm pump) Open Open Closed (with valv e cap) (with valv e cap) (with [...]
-
Page 47
Ser vice Manual 47 2-wa y , 3-wa y V alv e 1. Air purging Required tools : h e xagonal wrench, adjustable wrench, torque wrenches, wrench to hold the joints, and gas leak detec- tor . The additional gas f or air purging has been charged in the outdoor unit. Howe ver , if the flare connections hav e not be done correctly and there gas leaks, a gas c[...]
-
Page 48
48 Room Air Conditioner 2-wa y , 3-wa y V alv e 2. Pumping down • Procedure (1) Confirm that both the 2-way and 3-wa y valves are set to the open position. – Remo ve the v alve stem caps and confirm that the valv e stems are in the raised position. – Be sure to use a he xagonal wrench to operate the valv e stems. (2) Operate the unit for 10 t[...]
-
Page 49
Ser vice Manual 49 2-wa y , 3-wa y V alv e 1) Re-air purging (Re-installation) • Procedure (1) Confirm that both the 2-way v alve and the 3- way v alve are set to the closed position. (2) Connect the charge set and a gas cylinder to the service por t of the 3-way v alve . – Leav e the valv e on the gas cylinder closed. (3) Air purging. – Open[...]
-
Page 50
50 Room Air Conditioner 2-wa y , 3-wa y V alv e 2) Balance refrigerant of the 2-way , 3-way v alves (Gas leakage) • Procedure (1) Confirm that both the 2-way and 3-wa y valves are set to the back seat. (2) Connect the charge set to the 3-wa y valve ’ s port. – Leav e the valv e on the charge set closed. – Connect the charge hose with the pu[...]
-
Page 51
Ser vice Manual 51 2-wa y , 3-wa y V alv e 3. Ev acuation (All amount of refrigerant leaked) • Procedure (1) Connect the vacuum pump to the char g e set ’ s center hose (2) Evacuation f or appro ximately one hour . – Confir m that the gauge needle has mov ed tow ard -76 cmHg (vacuum of 4 mmHg or less). (3 ) Close the valve (Lo side) on the c [...]
-
Page 52
52 Room Air Conditioner 2-wa y , 3-wa y V alv e 4. Gas Charging (After Evacuation) • Procedure ( 1 ) Connect the charge hose to the char ging cylinder . – Connect the charge hose which you dis-con- nected from the vacuum pump to the v alve at the bottom of the cylinder . – If you are using a gas cylinder , also use a scale and re vers the cyl[...]
-
Page 53
Ser vice Manual 53 2-wa y , 3-wa y V alv e Additional gas c harging (Gas leakage) • When refrigerant is insufficient b y leakage, recharge the unit with the refrigerant up to normal oper- ating suction pressure. • Use the gr aph or the equation below to get operating suction pressure according to indoor and out- door temperature . Suction press[...]
-
Page 54
54 Room Air Conditioner Cycle T roubleshooting Guide 1. T rouble anal ysis 1. Check temper ature difference betw een intake and discharge air and oper ating current. T emp . Diff erence Operating Current T emp . diff erence :appro x. 0 ° F Current : less than 80% of rated current T emp . diff erence :appro x. 8 ° C(14 ° F) Current : less than 80[...]
-
Page 55
Ser vice Manual 55 Cycle T roubleshooting Guide 2. Pr oduct does not operate at all. (* Refer to Electr onic Control De vice drawing and Schematic diagram.) T urn off Main Po wer T urn on Main P ower Does "beeping" sound is made from the Indoor Unit? Primar ily , the operating condition of Micom is OK. Check the v oltage of po wer(About A[...]
-
Page 56
56 Room Air Conditioner Cycle T roubleshooting Guide 3. The pr oduct is not operate with the remote controller . T urn on Main Po wer While the compressor has been stopped, the compressor does not operate owing to the dela ying function for 3 min utes after stopped. Caused by other parts except the remote controller Cause by the remote controller W[...]
-
Page 57
Ser vice Manual 57 Cycle T roubleshooting Guide 4. Compressor/Outdoor F an are unable to drive. T urn on Main P ower Operate "Cooling Mode( )" b y setting the desired temperature of the remote controller is less than one of the indoor temperature b y 2 ° F at least. When in F an Mode, Compressor/Outdoor F an is stopped. Check the sensor [...]
-
Page 58
58 Room Air Conditioner Cycle T roubleshooting Guide 5. When Indoor F an does not operate . Check connecting condition of the CN-MO T OR CON- NECT OR Does the v oltage of terminal of CN-DC/DC CONNECT OR in Indoor unit corresponds to the v alues in the tab le of page 63? Do the voltage of terminal of CN-DC/DC CONNECT OR in Outdoor unit corresponds t[...]
-
Page 59
Ser vice Manual 59 Cycle T roubleshooting Guide • Confir m that the V er tical Louver is normally geared with the shaft of Step- ping Motor . • If the regular torque is detected when rotating the V er tical Louver with hands Nor mal • Check the connecting condition of CN-U/D , CN-L/R Connector • Check the soldering condition(on PWB) of CN-U[...]
-
Page 60
60 Room Air Conditioner Cycle T roubleshooting Guide • The operation indicator of Indoor unit b links five times . • The red indicator of Outdoor unit blinks fiv e times. Check the connecting wires betw een Indoor and Outdoor unit for the connecting error and the contacting condition. Check the installation condition of outdoor unit. Check f or[...]
-
Page 61
Ser vice Manual 61 Cycle T roubleshooting Guide 8. The phenomena in case of connecting error INDOOR UNIT Connector T ype Condition Open and connecting error Open Open Open Open Shor t between terminals ( and ) of ROOM-TH. Shor t between terminals ( and ) of PIPE-TH. Shor t between ter minals • The same as the phenomenon of Outdoor Unit. • The u[...]
-
Page 62
62 Room Air Conditioner Cycle T roubleshooting Guide OUTDOOR UNIT Connector T ype Condition OPEN • PWB pattern is damaged when applying the power . Connecting re versely Connecting re versely OPEN OPEN OPEN OPEN Connecting error ( ) Connecting error ( ) Connecting error ( ) Connecting error ( ) Connecting error ( ) Connecting error ( ) • All fu[...]
-
Page 63
Ser vice Manual 63 Cycle T roubleshooting Guide 9. V oltage of Connectors accor ding to Indoor Fan Speed 4 3 2 1 1 1 2 3 4 INDOOR FAN MOTOR INDOOR PWB ASSY Connecting wires between Indoor and Outdoor Indoor Connecting Terminal Outdoor Connecting Terminal Input Power TAB-N RY-COMP-A RY-COMP-B CN-DC/DC BL BK BR RD BL BK BR RD +- 12 32 42 12 32 42 12 [...]
-
Page 64
64 Room Air Conditioner Electronic Control De vice • PWB ASSY SVC P AR T LIST 1 18K Cooling Model 6871A20387J 12K 20K 27K 12K OPEN OPEN NO MODEL P/No. OPTIONAL FUNCTION OR1H OR2H OR3H OR4H OR5H OR6H OJ1H, OJ2H, : SHOR T • T OP VIEW • BO TT OM VIEW Electr onic Control De vice MAIN PWB ASSY(Indoor Unit)[...]
-
Page 65
Electronic Control De vice • T OP VIEW • BO TT OM VIEW MAIN PWB ASSY(Outdoor Unit)[...]
-
Page 66
66 Room Air Conditioner Electronic Control De vice • T OP VIEW • BO TT OM VIEW DISPLA Y PWB ASSEMBL Y[...]
-
Page 67
Ser vice Manual 67 Schematic Diagram OUTDOOR 48 46 47 44 42 43 40 38 39 41 36 35 34 33 37 45 15 1 2 2 1 23 18 16 17 19 20 21 22 28 24 25 26 27 29 30 31. 32 SLEEP TIMER ON/OFF DEFROST LED1 LED3 LED4 LED2 58 7 11 13 14 12 10 9 8 63 3 5 6 4 1 2 64 62 61 60 59 53 57 56 55 54 51 52 50 49 1 CN-HVB(BL) 3 2 HVB ASSY 1 3 2 12V R93 10K RXE250 POLY SW1 CN-MOT[...]
-
Page 68
68 Room Air Conditioner Schematic Diagram Outdoor Unit[...]
-
Page 69
Ser vice Manual 69 Exploded Vie w and Replacement P ar ts List 249951 26871 1-2 14758 1 135311- 2 146811 135500- 2 146811 352380-2 352380-1 131410 14758 1 135311- 1 567480 135500- 1 135311-3 147581 354210 352150 35211B 349490 330870 135500- 3 267110 152302 346810-1 359012-1 346810-2 359012-2 146811 135316 352116 352115 26871 1-1 135313 159830 Explo[...]
-
Page 70
70 Room Air Conditioner Exploded View and Replacement P ar ts List P arts List(indoor) 131410 CHASSIS ASSEMBL Y 3141A20008J R 135311-1 GRILLE ASSEMBL Y ,DISCHARGE(INDOOR) 3531A20124K R 135311-2 GRILLE ASSEMBL Y ,DISCHARGE(INDOOR) 3531A20124J R 135311-3 GRILLE ASSEMBL Y ,DISCHARGE(INDOOR) 3531A20125G R 135316 GRILLE ASSEMBL Y ,FRONT(INDOOR) 3531A103[...]
-
Page 71
Ser vice Manual 71 Exploded View and Replacement P ar ts List 2. Outdoor unit(18K) 435512 437210 559010 546810 55211G 554031 437212 435511 447910 552202 561410 567502-1 552116 566000 430410 649950 263230-1 263230-2 668711 W0CZZ-2 W0CZZ-1 552203-2 552203-1 554160-1 554160-2 567502-2 550140 550140 263230[...]
-
Page 72
72 Room Air Conditioner Exploded View and Replacement P ar ts List P arts List(outdoor) LOCA TION DESCRIPTION PA R T N o . REMARKS No. 552203-1 V AL VE,SER VICE 2H02479B R 552203-2 V AL VE,SER VICE 5220A20006A R 554031 CONDENSER ASSY ,BENT 5403A20058B R 554160-1 COMPRESSOR SET 2520UGJK2AA R 554160-2 COMPRESSOR SET 2520UGAK2AA R 559010 F AN ASSY , P[...]
-
Page 73
P/No.: 3828A20065Y Printed in Korea[...]