Go to page of
Similar user manuals
-
Ventilation Hood
Lifebreath RNC155
36 pages 2.93 mb -
Ventilation Hood
Lifebreath 300DCS
10 pages 1.2 mb -
Ventilation Hood
Lifebreath 300TRV
2 pages 0.33 mb -
Ventilation Hood
Lifebreath Clean Air Furnace CAF-02-
44 pages 4.24 mb -
Ventilation Hood
Lifebreath 195TRV
2 pages 0.33 mb -
Ventilation Hood
Lifebreath 94-EXCHANGER
24 pages 5.27 mb -
Ventilation Hood
Lifebreath 2500EFD
20 pages 0.3 mb -
Ventilation Hood
Lifebreath CAF-02-MB
44 pages 4.05 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Lifebreath RNC10, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Lifebreath RNC10 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Lifebreath RNC10. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Lifebreath RNC10 should contain:
- informations concerning technical data of Lifebreath RNC10
- name of the manufacturer and a year of construction of the Lifebreath RNC10 item
- rules of operation, control and maintenance of the Lifebreath RNC10 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Lifebreath RNC10 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Lifebreath RNC10, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Lifebreath service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Lifebreath RNC10.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Lifebreath RNC10 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
TI-RNC 0108 Residential Heat Reco very V entilators (HR V) Manufactured with 2 Speed RNC Electr onics Installation Instructions for Heat Reco very V entilators with 2 Speed RNC Electronics RNC Series Models RNC95 RNC155 RNC200 RNC10 RNC20 RNC120D RNC5-TPD[...]
-
Page 2
Introduction.........................................................................2 Engineering Data - RNC95 .............................................3-4 Engineering Data - RNC155 ...............................................5 Engineering Data - RNC200 ...............................................6 Engineering Data - RNC10 ..............[...]
-
Page 3
3 Removab le Heat Recovery Core Drain P an Drain spout FRONT TOP knockout f or side mounting of EXHA UST return port 6" round collar converted to oval minimum 18 inches (459 mm) required for service access Threaded inserts (4) at corners SUPPL Y Fresh air from outside 5" round collar SUPPL Y Fresh air to building 6" round (conv . to [...]
-
Page 4
4 RNC95 Specifications The RNC95 HRV (Heat Recovery Ventilator) has been designed to allow the installer to choose between two possible positions on the cabinet for the Stale Air Exhaust (from building) port. Illustrations in this manual show standard (side mounted) port location. The same specifications apply to both RNC95 setups, regardless of wh[...]
-
Page 5
5 Engineering Data - HRV Model RNC155 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters[...]
-
Page 6
6 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. [...]
-
Page 7
7 All units conform to CSA and UL standards Engineering Data - HRV Model RNC10 Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: ________________________________________[...]
-
Page 8
8 All units conform to CSA and UL standards Engineering Data - HRV Model RNC20 Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: ________________________________________[...]
-
Page 9
9 All units conform to CSA and UL standards Engineering Data - HRV Model RNC5-TPD Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: _____________________________________[...]
-
Page 10
10 All units conform to CSA and UL standards Engineering Data - HRV Model RNC120D Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: _____________________________________[...]
-
Page 11
11 Engineering Data - HRV Model RNC120D FRESH AIR FROM OUTSIDE ST ALE AIR TO OUTSIDE ST ALE AIR FROM BUILDING FRESH AIR TO B UILDING BOTT OM VIEW FOR HORIZONT AL MOUNT SER VICE CLEARANCE FROM BO TTOM OF UNIT IS MINIMUM 3’0” SIDE VIEW FOR HORIZONT AL MOUNT ALL DUCT COLLARS ARE 5” DIAMETER Connect drain hose to spout located in door . 9-1/8” [...]
-
Page 12
Ventilation Dehumidistat PART NO. 99-116 The High/Low Speed Switch initiates High or Low speed ventilation. This control also has an ON/OFF Switch and a Dehumidistat Dial. 20/40 ON/OFF Dehumidistat PART NO. 99-2040 The 20/40 Switch will toggle from continuous low speed ventilation to an intermittent mode of 20 minutes fan ON (in low speed) and 40 m[...]
-
Page 13
13 Location Selection The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted. If a basement area is not convenient or does not exist, a utility or laundry room may be u[...]
-
Page 14
14 Suspending the RNC120D STRAPS AND SCREWS (supplied) JOIST F ASTENERS (not supplied) DET AIL Using full length hanger straps is recommended for vibration contr ol, but can be shorter if required. Horizontal Installation W all Mounting the HR V V er tical Installation The unit must be mounted le vel for pr oper drainage of the condensate pans. A T[...]
-
Page 15
15 Drain Connection (HRV Only) During a defrost cycle, the HRV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The HRV cabinet has prepunched holes for the drain (see below). Insert the drain spout through the hole in the drain pan. Do not forget the “O ring” which seals each spo[...]
-
Page 16
16 The Three Methods of Installation The three methods of installation for the HRV system are the Simplified, Partially Dedicated and Fully Dedicated Installations. Refer to the installation illustrations in this manual. Simplified Installations The Simplified Installation draws stale air from the cold air return duct of the air handler/furnace and[...]
-
Page 17
17 The Simplified Installation (Return/Return Method) Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc. W ARNING Air Handler [...]
-
Page 18
18 The Partially Dedicated Installation Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc. W ARNING FIVE PORT MODELS - P ar ti[...]
-
Page 19
19 The Fully Dedicated Installation Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc. W ARNING FIVE PORT MODELS - Full y Dedi[...]
-
Page 20
Intake Weatherhood Requirements • Should be located upstream (if there are prevailing winds) from the exhaust outlet. • At least 6' (2m) from the exhaust weatherhood. • At least 6' (2m) away from dryer vents and air handler exhaust. • A minimum of 6' (2m) from driveways, oil fill pipes, gas meters, swimming pools or garbage c[...]
-
Page 21
21 Electrical The HRV unit should be plugged into a standard designated (120VAC) electrical outlet with a ground. The outlet should be serviced by a separate 15 amp/120V circuit. An extension cord should not be used with this appliance. A qualified service technician should make any required electrical connections. Remote Control Connections Prior [...]
-
Page 22
22 Red to Red Black to Black Green LED Drive to Green DEH UMI DISTA T Red to Red Orange to Orange Black to Black Dehumidistat Ventilation Control Part No. 99-116 20 Minute Timer (shown in a Decora cover plate)* Red to Red Black to Black Remote Dehumidistat Part No. 99-130W Remove factory installed jumper when installing this control Factory install[...]
-
Page 23
23 Recirculating Damper Defrost (4 port models) The recirculating damper defrost HRV has an electronically controlled damper defrost mechanism. The defrost timer is activated when the outside temperature drops below 27°F (- 3°C). A motor driven damper door mechanism closes off the supply air from outside allowing the exhaust air to recirculate th[...]
-
Page 24
24 It is necessary to have balanced air flow in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flow is not properly balanced, then: • The HRV may not operate at its maximum efficiency • A negative or positive air pressure may occur in the house • The unit may not defrost pr[...]
-
Page 25
25 Air Flow Balancing Place pitot tube a minimum of 18" from blower or elbows Note: Duct connections may vary , depending on model. Outdoors MAGNEHELIC Pitot tube Magnehelic gauge M A GN E HELIC Magnehelic gauge Pitot tube Additional dampers may be required Placement of Pitot Tube HRV M AG NEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Lo[...]
-
Page 26
26 AccuFlow Gauge Kit 1 - Accu-Flow Balancing Gauge 2 - Connection Hoses 4 - Rubber Fittings 1 - Instruction Page Lifebreath Accu-Flow is designed to quickly and accurately balance the airflows on units equipped with balancing ports. Normally the HRV/ERV would be balanced on high speed. If the HRV/ERV is connected to a forced air system, both syste[...]
-
Page 27
27 Air Flow Balancing using the Door Ports Models RNC155 and RNC200 Only The door ports ( MODELS RNC155 & RNC 200) are designed to quickly and measure the airflows for balancing. Normally the HRV would be balanced on high speed. If the HRV is connected to a forced air system, both systems should be set to run at the highest operational speed wh[...]
-
Page 28
28 When using the Interface relay contacts to initiate b lower operation on a furnace, cer tain thermostats will initiate the outdoor cooling condenser when R and G are closed. Use this wiring configur ation to pre vent the Interf ace rela y contacts from initializing the condenser unit. This problem can occur at the thermostat because the Y ter mi[...]
-
Page 29
29 Wiring Diagrams Model RNC5-TPD DEFROST DET AILS P1 12 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SP ARE PCB PLUG - IN RED BLACK PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MO TOR ORANGE RED BLACK ORANGE Model RNC5 (Only) TO MO TORS BLUE RED INTERF ACE RELA Y CONT A CTS[...]
-
Page 30
30 Wiring Diagrams RNC120D HRV Control Box DEFROST DET AILS P1 12 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SP ARE PCB PLUG - IN RED BLACK PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MO TOR ORANGE RED BLACK ORANGE TO MO TORS INTERF ACE RELA Y CONT A CTS BLUE 60-120D-WIRING[...]
-
Page 31
31 RNC3WIRINGDIAGRAM HIGHVOLTAGE 12VLOWVOLTAGE FIELDINSTALLED LEGEND 12VLOWVOLTAGE FANMOTORDETAILS CAPACITOR ORANGE WHITE BLACK GREEN DIRECTMOUNTEDCAPACITOR T6 T9 RED YELLOW P1 12 3 4 PIN1-BLACK PIN2-ORANGE PIN3-RED PIN4-SPARE PCBPLUG-IN RED BLACK PLUGIN CONNECTO[...]
-
Page 32
32 Troubleshooting Poor Air Flow Supply air feels cold Dehumidistat is not Operating Humidity Levels are too High in Winter Condensation is appearing on the windows Humidity Levels are too Low HRV and / or Ducts Frosting up Condensation or Ice Build Up in Insulated Duct to the Outside Water in the bottom of the HRV 20 Minute Timer Not Working • 1[...]
-
Page 33
33 1. Inspect Exterior Hoods at least once a month. Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen). WARNING: Blockage of hoods may cause an imbalance. [...]
-
Page 34
34[...]
-
Page 35
35[...]
-
Page 36