Go to page of
Similar user manuals
-
Water Heater
Lochinvar 1
52 pages 6.29 mb -
Water Heater
Lochinvar CF-0401
1 pages 0.11 mb -
Water Heater
Lochinvar ARM3072PAB
1 pages 0.18 mb -
Water Heater
Lochinvar SNA400-125
72 pages 8.61 mb -
Water Heater
Lochinvar SSB-i & s--01
12 pages 2.58 mb -
Water Heater
Lochinvar 150
8 pages 0.24 mb -
Water Heater
Lochinvar LT(S)L 030
2 pages 1.34 mb -
Water Heater
Lochinvar CW-360
1 pages 0.12 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Lochinvar RPV-I&S, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Lochinvar RPV-I&S one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Lochinvar RPV-I&S. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Lochinvar RPV-I&S should contain:
- informations concerning technical data of Lochinvar RPV-I&S
- name of the manufacturer and a year of construction of the Lochinvar RPV-I&S item
- rules of operation, control and maintenance of the Lochinvar RPV-I&S item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Lochinvar RPV-I&S alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Lochinvar RPV-I&S, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Lochinvar service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Lochinvar RPV-I&S.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Lochinvar RPV-I&S item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
1 RPV-I&S POWERED VENT GAS WATER HEATER For your family’s comfort, safety and convenience we recommend water heaters to be installed and serviced by a plumbing professional. T ABLE OF CONTENTS GENERAL INFORMATION ............................................................ 1 INSTALLATION .......................................................[...]
-
Page 2
2 RPV-I&S INSTALLATION Locating The Water Heater DO NOT install the water heater in any location where gasoline or flammable vapors are likely to be present. Water Heaters in residential garages must be installed so that all burner(s) and burner ignition device(s) are located not less than 18 inches (46 cm) above the floor and must be located o[...]
-
Page 3
3 RPV-I&S 76,000 BTU (283.9 L - 22.3 kW/Hr) models. Part II will cover venting specifications for 40 Gal - 40,000 BTU (151.4 L - 11.7 kW/ Hr) and 48 gal - 40,000 BTU (181.7 L - 11.7 kW/Hr) models. Refer to the rating plate located on the water heater for correct model identification. The National Fuel Gas Code ANSI Z223.1-(Latest Edition), CGA/[...]
-
Page 4
4 RPV-I&S diameter PVC pipe. When venting with 4" (10.2 cm) PVC, use a 4" (10.2 cm) to 3" (7.6 cm) reducer to exit through the building wall with 3" (7.6 cm) PVC. Use the 3" (7.6 cm) vent terminal supplied with the water heater to terminate on the outside of the building. If the length of 3" (7.6 cm) PVC needed to [...]
-
Page 5
5 RPV-I&S NOTE: For installations requiring both horizontal and vertical runs, the following rule must be followed: Total number of feet of straight pipe (both horizontally and vertically) must not exceed the allowable length listed in the “Through The Wall” section of the table for total number of elbows used. Also: Total number of vertica[...]
-
Page 6
6 RPV-I&S NOTE: When using 3" (7.6 cm) PVC, use a 3" (7.6 cm) to 2" (5.1 cm) reducer and exit the building wall with 2" (5.1 cm) PVC using the 2" (5.1 cm) 45° vent terminal supplied. Two 45° elbows are equivalent to one 90° elbow. Each 90° elbow is equivalent to 5 feet (1.5 m) of straight vent pipe. NOTE: ABS or CPV[...]
-
Page 7
7 RPV-I&S NOTE: For installations requiring both horizontal and vertical runs, the following rule must be followed: Total number of feet of straight pipe (both horizontally and vertically) must not exceed the allowable length listed in the “Through The Wall” section of the table for total number of elbows used. Also: Total number of vertica[...]
-
Page 8
8 RPV-I&S 1. When directly communicating with the outdoors, each opening must have a minimum free area of 1 square inch per 4000 BTU (6.5 cm 2 /1.2 kw) per hour of total input rating of all equipment in the enclosure. 2. When communicating with the outdoors through vertical ducts, each opening must have a minimum free area of 1 square inch per [...]
-
Page 9
9 RPV-I&S GAS CONNECTIONS The gas supply lines must meet all requirements of the National Fuel Gas Code ANSI Z223.1-(Latest Edition) and/or in Canada CAN/CGA B149 Installation Codes - (Latest Editions). The minimum permissible gas supply pressure for the purpose of input adjustment is 1.5" water column (.37 kPa) above the operating manifol[...]
-
Page 10
10 RPV-I&S Figure 11[...]
-
Page 11
11 RPV-I&S Figure 12[...]
-
Page 12
12 RPV-I&S THERMOST A T ADJUSTMENT The thermostat dial is adjusted to approximately 120°F when shipped from the factory. When adjusting the thermostat, it should be remembered that lower temperature settings are more energy efficient. The thermostat cover, on the right side of the gas valve, must be removed when the thermostat is adjusted. To [...]
-
Page 13
13 RPV-I&S MAINTENANCE The following maintenance should be performed by a qualified service technician at the minimum periodic intervals suggested below. In some installations, the maintenance interval may be more frequent depending on the amount of use and the operating conditions of the water heater. Regular inspection and maintenance of the [...]
-
Page 14
14 RPV-I&S THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF: GAS WATER HEATERS SUITABLE FOR WATER (POTABLE) HEATING AND SPACE HEATING 1. All piping components connected to this water heater for space heating applications must be suitable for use with potable water. 2. Toxic chemicals, such as those used for boiler treatment, must not be intro[...]
-
Page 15
15 RPV-I&S VENT PIPE PREPARATION AND JOINING Most failures in PVC, CPVC or ABS systems result from improper preparation and joining of pipe and fittings. The guidelines below must be followed when installing the venting system. If you have any question about the application or installation of the PVC, CPVC or ABS venting system, contact the man[...]
-
Page 16
16 RPV-I&S Printed in USA[...]