Go to page of
Similar user manuals
-
Power Supply
MGE UPS Systems EXB RT 3U
24 pages 0.67 mb -
Power Supply
MGE UPS Systems Comet TM 5 - 30 kVA
60 pages 0.34 mb -
Power Supply
MGE UPS Systems 3200RT
28 pages 0.51 mb -
Power Supply
MGE UPS Systems 1100
196 pages 3.81 mb -
Power Supply
MGE UPS Systems Galaxy PW
44 pages 0.23 mb -
Power Supply
MGE UPS Systems 2200C
28 pages 0.84 mb -
Power Supply
MGE UPS Systems 1100 Rack
196 pages 3.81 mb -
Power Supply
MGE UPS Systems 300
6 pages 0.44 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of MGE UPS Systems EX 11 RT 3:1, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of MGE UPS Systems EX 11 RT 3:1 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of MGE UPS Systems EX 11 RT 3:1. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of MGE UPS Systems EX 11 RT 3:1 should contain:
- informations concerning technical data of MGE UPS Systems EX 11 RT 3:1
- name of the manufacturer and a year of construction of the MGE UPS Systems EX 11 RT 3:1 item
- rules of operation, control and maintenance of the MGE UPS Systems EX 11 RT 3:1 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of MGE UPS Systems EX 11 RT 3:1 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of MGE UPS Systems EX 11 RT 3:1, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the MGE UPS Systems service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of MGE UPS Systems EX 11 RT 3:1.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the MGE UPS Systems EX 11 RT 3:1 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
34007724EN/AA - Page 1 T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R www .mgeups.com MGE UPS SYSTEMS Installation and user manual Comet EX 5 R T 3:1 EX 7 R T 3:1 EX 11 R T 3:1[...]
-
Page 2
Page 2 - 34007724EN/AA Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your equipment. The Comet EX RT range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS. Warning: this is a class A UPS product. In a domestic environ[...]
-
Page 3
34007724EN/AA - Page 3 Contents 1. Presentation 1.1 Standard configurations .............................................................................................................. 5 T ower configuration ......................................................................................................................... 5 Rack configurati[...]
-
Page 4
Page 4 - 34007724EN/AA Contents 3. Operation 3.1 Initial start up .............................................................................................................................. 2 6 UPS personalisation ............................................................................................................ ......... 26 Accessing p[...]
-
Page 5
34007724EN/AA - Page 5 1. Presentation 1.1 Standard configurations Rack configuration Tower configuration w w w . m g e u p s . c o m w w w . m g e u p s . c o m E X B R T E X 1 1 R T O F F O N w w w . m g e u p s . c o m E X B R T E X 1 1 R T O F F O N w w w . m g e u p s . c o m Battery module ( Comet EXB 7 RT / EXB 11 RT ) Battery module ( Comet[...]
-
Page 6
Page 6 - 34007724EN/AA BY PASS NORMAL 1. Presentation 1.2 Rear panels Slot for communication cards. Communication port by relays. Remote Emergency Power Off communication port (REPO). Connectors for automatic detection of battery module(s). RS232 communications port. Battery module connectors (to the UPS or to other battery modules). Manual Bypass [...]
-
Page 7
34007724EN/AA - Page 7 OFF ON E X 1 1 R T 3:1 1.3 Display and control panel 1. Presentation Load protected LED. Operation on battery LED. Operation on bypass LED. Fault LED. Alphanumeric display. UPS OFF button. Function buttons (scroll up / scroll down). UPS ON button (or function button in personalisation mode). 13 14 15 16 17 18 19 20 13 14 15 1[...]
-
Page 8
Page 8 - 34007724EN/AA www.mgeups.com E X R T T r a n s f o r m e r BY PASS NORMAL Transformer for galvanic isolation or earthing arrangement change (Part number 68003) Battery module ( Comet EXB RT ) Power module ( Comet EX 5 RT / EX 7 RT / EX 11 RT ) Transformer module ( Comet EX RT ) UPS output to load Normal AC input 1. Presentation Example of [...]
-
Page 9
34007724EN/AA - Page 9 1. Presentation Battery extensions for UPS backup times up to 60 minutes (at full load) Comet EX RT offers a standard backup time of 5/9 minutes at full load. To increase backup time, it is possible to connect Comet EXB 7 RT / EXB 11 RT modules to the UPSs. Battery extensions for Comet EX 5 RT, Comet EX 7 RT or Comet EX 11 RT[...]
-
Page 10
Page 10 - 34007724EN/AA 1. Presentation Modules integration system for extended backup time configurations to conveniently stack and secure up to 8 modules on the same cart (swivel wheels with brakes, leveling feet, seismic side panels, plates to lock modules and screws included). Modules integration system (Part number 68005) Battery module with R[...]
-
Page 11
34007724EN/AA - Page 11 Card Settings RS232 Download 66074 UPS data Reset 100 10 1 2 ON ETHERNET RS232 IP= MAC=00E0D8FF855E E X B R T E X 1 1 R T 2.1 Unpacking and parts check Two sets of tower stands. RS232 communications cable. Product documentation. Telescopic rails for rack enclosure with mounting hardware (optional, or standard with Network Pa[...]
-
Page 12
Page 12 - 34007724EN/AA 2. Installation 2.2 Installation in tower configuration Follow steps 1 to 4 to adjust the tower stands for the upright position. w w w . m g e u p s . c o m w w w . m g e u p s . c o m E X B R T E X 1 1 R T O F F O N 1 3 4 2 1 4 3 2 4 4 Use the tower stand template provided with the battery module.[...]
-
Page 13
34007724EN/AA - Page 13 2.3 Installation in rack configuration 2. Installation Adjustment of the orientation of the logo and control panels 1 2 3 4 5 6 Battery module rack mounting (optional rails required, part number: 68002) We recommend to mount the battery module first, then mount the power module above the battery module. The battery module is[...]
-
Page 14
Page 14 - 34007724EN/AA Follow steps 1 to 4 for rack mounting the UPS onto the rails. The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS. Note for step 1 : it is possible to adjust the position of both front mounting ears. 1 3 3 4 2 1 4 3 3 Power or battery module rack mounting (optional rails required, part number: 68001[...]
-
Page 15
34007724EN/AA - Page 15 2. Installation 1 2 4 Input/output junction box bracket system (included with power module rail kit, part number 68001) This bracket will maintain the Input/Output box at the rear of the rack enclosure when hot-swapping the power module. It will then be easier to slide the replacement module into the connectors of the Input/[...]
-
Page 16
Page 16 - 34007724EN/AA BY PASS NORMAL 2. Installation Connection to the RS 232 communication port 1 - Connect the RS 232 23 communications cable to the serial port on the computer. 2 - Connect the other end of the communications cable 23 to the RS 232 5 communications port on the UPS. The UPS can now communicate with various MGE UPS SYSTEMS power [...]
-
Page 17
34007724EN/AA - Page 17 BY PASS NORMAL Card Settings RS232 Download 66074 UPS data Reset 100 10 1 2 ON ETHERNET RS232 IP= MAC=00E0D8FF855E Installation of communication cards (optional, standard with the Network Pack version) It is not necessary to shut down the UPS to install the communication card: 1 - Remove the slot cover secured by two screws.[...]
-
Page 18
Page 18 - 34007724EN/AA UPS with separate Normal and Bypass AC inputs Main low- voltage switchboard (MLVS) load Bypass AC Normal AC 2. Installation 2.5 Installation depending on the system earthing arrangement (SEA) UPS with common Normal and Bypass AC inputs Change in SEA between upstream and downstream or galvanic isolation required load Bypass A[...]
-
Page 19
34007724EN/AA - Page 19 8 10 11 8 11 10 Frequency converter (without Bypass AC input) Main low- voltage switchboard (MLVS) load Normal AC 2. Installation UPS with separate Normal and Bypass AC inputs, supplied by separate sources Change in SEA between upstream and downstream or galvanic isolation required MLVS 1 MLVS 2 load MLVS 1 MLVS 2 or MLVS 1 [...]
-
Page 20
Page 20 - 34007724EN/AA 2. Installation 2.6 Required protective devices and cable cross-sections Recommended upstream protection Recommended downstream protection The indicated protection ensures discrimination for each output circuit downstream of the UPS, whether supplied by the Normal or the Bypass AC source. If these recommendations are not fol[...]
-
Page 21
34007724EN/AA - Page 21 2. Installation 2.7 Connections of input/output power cables ◗ This type of connection must be carried out by qualified electrical personnel. ◗ Before carrying out any connection, check that the battery circuit breaker 12 and that the upstream protection devices (Normal and Bypass AC sources) are open ("0"). ?[...]
-
Page 22
Page 22 - 34007724EN/AA Card Settings RS232 Download 66074 UPS data Reset 100 10 1 2 ON ETHERNET IP= MAC=00E0D8FF855E N O R M A L φ R e c t i f i e r I n p u t L 2 L 1 L 1 B y p a s s I n p u t N 2 L 2 N 1 L 3 O u t p u t N L R e c t if i e r I n p u t L 2 L 1 L 1 B y p a s s I n p u t N 2 L 2 N 1 L 3 O u t p u t N L R e c t i f i e r I n p u t L [...]
-
Page 23
34007724EN/AA - Page 23 Frequency converter 1 - Remove the terminal block cover (5 screws), 2 - Remove the bridge connected between L2 and L1, 3 - Insert the Normal AC cable through the cable gland, 4 - Connect the 5 wires to the Normal AC terminal block, Always connect the earthing wire first. 5 - Insert the Output cable suppling the load through [...]
-
Page 24
Page 24 - 34007724EN/AA BY PASS NORMAL N L N L OUTPUT INPUT 2. Installation Connection of battery cables 1 - Check that the battery circuit breaker 12 is OFF ("0" position), 2 - Connect the battery power cable 28 to the connectors 6 of the power and battery modules, 3 - Connect the battery detection cable 29 to the connectors 4 of the pow[...]
-
Page 25
34007724EN/AA - Page 25 BY PASS NORMAL _ + N L BATTERY AC INPUT 2. Installation Connection of CLA module AC Input To battery 29 28 ◗ Connect the battery cable 28 (provided with the CLA module) between the power module and the CLA module. ◗ Connect the cable 29 (provided with the CLA module) between the power module and the CLA module. ◗ Conne[...]
-
Page 26
Page 26 - 34007724EN/AA OFF ON 20 UPS SET UP EXIT ENT 19 OFF ON 3. Operation 3.1 Initial start up Check that the manual bypass switch 7 is on Normal position. Set the normal AC source circuit-breaker 9 to the "I" position. Set the battery circuit breaker 12 to the "I" position. The load is powered via the bypass AC source, but n[...]
-
Page 27
34007724EN/AA - Page 27 3. Operation ON/OFF features Factory setting Disabled Enabled Enabled Disabled Enabled Function Cold start Forced reboot Automatic restart Sleep mode UPS ON/OFF by software Options Enabled Disabled Disabled Enabled Disabled Comments Start on battery. Enables automatic restart of the system even if normal AC source is restore[...]
-
Page 28
Page 28 - 34007724EN/AA ECO mode The main advantage of the Eco mode (see glossary) is that it reduces the consumption of electrical power. Three possible choices: 1 - Bypass AC source available: LEDs 13 and 15 are ON. The load is supplied in ECO mode. OFF ON OFF ON OFF ON 13 15 13 13 14 3. Operation OFF ON 13 14 BACKUP TIME 10 minutes 2 - Normal AC[...]
-
Page 29
34007724EN/AA - Page 29 OFF ON 3. Operation After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled via UPS personalisation). 13 14 15 13 14 Threshold for the low-battery warning End of backup time LED 13 is ON. LED 14 flashes. The audio alarm beeps every 3 seconds. Low battery warning on di[...]
-
Page 30
Page 30 - 34007724EN/AA BY PASS NORMAL OFF ON 18 12 9 3.6 Shut down 1 - Press the OFF button 18 more than 3 seconds. The load is no longer protected by the UPS. It is powered via the bypass AC source. If the UPS is set in frequency converter mode, the load will not be powered. If the bypass AC source is out of tolerance, the UPS will generate a 10 [...]
-
Page 31
34007724EN/AA - Page 31 4. Maintenance Indication Leds 15 * and 16 are on and audible alarm is on. The alphanumeric display shows: xxx FAULT www.mgeups.com Led 15 is on* and audible alarm is on. the alphanumeric display shows: BATTERY FAULT Led 15 is on, the alphanumeric display shows: SHUTDOWN STATIC SW FAILED Audible alarm is on, and the alphanum[...]
-
Page 32
Page 32 - 34007724EN/AA C a r d S e t t i n g s 6 6 0 7 4 U P S d a t a R e s e t 1 0 0 1 0 1 2 O N E T H E R N E T R S 2 3 2 IP = M A C = 0 0 E 0 D 8 F F 8 5 5 E B Y P A S S φ R S 2 3 2 D o w n l o a d OFF ON 4.2 Hot-swapping the power module ◗ Stop the UPS with the OFF button 18 (press more than 3 seconds). ◗ Check if UPS is on bypass AC sou[...]
-
Page 33
34007724EN/AA - Page 33 BY PASS NORMAL 4.3 Hot-swapping the battery module Disconnecting the battery module ◗ Switch the battery circuit breaker(s) 12 to the "0" position. ◗ Disconnect the battery cables 28 and 29 from the power module. The battery module can be replaced. The connected equipment is powered by the UPS. It is also possi[...]
-
Page 34
Page 34 - 34007724EN/AA To allow you to use MGE UPS SYSTEMS products effectively and carry out basic maintenance, we offer a complete range of technical training courses in English and French. 50 Hz Training Center: MGE UPS SYSTEMS 140, Avenue Jean Kuntzmann Zirst - Montbonnot St Martin 38334 - St Ismier Cedex - FRANCE Tel: (33) (0)4 76 18 34 14 Fa[...]
-
Page 35
34007724EN/AA - Page 35 10 8 11 9 10 8 11 9 5. Appendices 5.1 T echnical specifications Electrical characteristics I/T network and industrial operating modes Bypass AC Normal AC Bypass AC Normal AC Upstream circuit breaker (not supplied) Downstream circuit breaker (not supplied) Input fuse Output fuse Upstream circuit breaker (not supplied) Downstr[...]
-
Page 36
Page 36 - 34007724EN/AA 5. Appendices Time/current curves for UPS input and output fuses Intput fuses of Comet EX 5 RT : 25 A Comet EX 7 RT : 25 A Output fuses of Comet EX 5 RT : 80 A Comet EX 7 RT : 80 A Output fuses of Comet EX 11 RT : 100 A Intput fuses of Comet EX 11 RT : 30 A Time/current curves for UPS Normal AC source circuit-breaker 10 1 10[...]
-
Page 37
34007724EN/AA - Page 37 Comet EX Transformer Nominal power Nominal current Input voltage V oltage drop Frequency Isolation (EN 61558-1-2-4) Operating temperature Max. operating rel. humidity Derating / altitude Dimensions HxWxD (tower) Dimensions HxWxD (rack 3U) Weight 11 k VA 63 A 160-280 V olts AC 7 V olts at nominal load 50/60 Hz (+/-10%) 3.75 k[...]
-
Page 38
Page 38 - 34007724EN/AA 5. Appendices 5.2 Glossary Backup time Time that the connected loads can operate on battery power. Bypass AC source Source supplying the bypass line. The load can be transferred to the bypass line if an overload occurs on the UPS output, for maintenance or in the event of a malfunction. ECO mode Operating mode by which the l[...]