Mitsubishi Electronics MUZ-A09/12/15/17/24NA manual
- Read online or download the manual
- 40 pages
- 0.36 mb
Go to page of
Similar user manuals
-
Air Conditioner
Mitsubishi Electronics PCA-A24GA
36 pages 1.34 mb -
Air Conditioner
Mitsubishi Electronics PUZ-ANHA3
36 pages 0.79 mb -
Air Conditioner
Mitsubishi Electronics PDFY-P06NMU-E
25 pages 1.79 mb -
Air Conditioner
Mitsubishi Electronics PAC-YU25HT
4 pages 0.16 mb -
Air Conditioner
Mitsubishi Electronics LGH-150RX4-E
4 pages 1.45 mb -
Air Conditioner
Mitsubishi Electronics PEH-8MYA
115 pages 2.7 mb -
Air Conditioner
Mitsubishi Electronics MSZ-GB50VA
15 pages 1.38 mb -
Air Conditioner
Mitsubishi Electronics 36FL3
12 pages 0.86 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Mitsubishi Electronics MUZ-A09/12/15/17/24NA, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Mitsubishi Electronics MUZ-A09/12/15/17/24NA one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Mitsubishi Electronics MUZ-A09/12/15/17/24NA. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Mitsubishi Electronics MUZ-A09/12/15/17/24NA should contain:
- informations concerning technical data of Mitsubishi Electronics MUZ-A09/12/15/17/24NA
- name of the manufacturer and a year of construction of the Mitsubishi Electronics MUZ-A09/12/15/17/24NA item
- rules of operation, control and maintenance of the Mitsubishi Electronics MUZ-A09/12/15/17/24NA item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Mitsubishi Electronics MUZ-A09/12/15/17/24NA alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Mitsubishi Electronics MUZ-A09/12/15/17/24NA, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Mitsubishi Electronics service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Mitsubishi Electronics MUZ-A09/12/15/17/24NA.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Mitsubishi Electronics MUZ-A09/12/15/17/24NA item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
SER VICE TECHNICAL GUIDE CONTENTS 1. MS MICROPROCESSOR CONTROL ·················· 4 2. MSZ, MSY MICROPROCESSOR CONTROL ······ 7 3. MXZ MICROPROCESSOR CONTROL ·············· 21 4. MFZ MICROPROCESSOR CONTROL ·············· 35 SPLIT -TYPE AIR CONDITIONERS No. OBT16 REVISED EDITION-G Please void OBT16[...]
-
Page 2
2 Revision A: • MXZ-3A30NA- 1 has been added. Revision B: • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD, MSZ-D and MSY -D have been added. Revision C: • MXZ-2A20NA- 2 has been added. Revision D: • MSZ-GA•NA and MSY -GA•NA have been added. Revision E: • MSZ-FE•NA, MSZ-GE•NA, MSY -GE•NA and MXZ-B•NA have been added. Revision F: • MXZ-2[...]
-
Page 3
3 1. MS MICROPROCESSOR CONTROL ·································································································· ················· 4 Indoor unit models Outdoor unit models MS-A09/12W A MU-A09/12W A 1-1. COOL OPERA TION[...]
-
Page 4
4 1-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 1-2. DR Y ( ) OPERA T[...]
-
Page 5
5 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 2. Indoor fan speed control Indoor fan operates at the set speed by F AN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes V ery Low . In AUTO the fan speed is as follows. 4. Coil frost prevention Coil frost[...]
-
Page 6
6 1-3. AUTO V ANE OPERA TION 1. Horizontal vane ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F (2°C) higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil thermist[...]
-
Page 7
7 2-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. ON -1.8°F(-1°C) or [...]
-
Page 8
8 2-2. DR Y ( ) OPERA TION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature d[...]
-
Page 9
9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GE When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66°F (19°C), the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or more and ( ) if the temperature of indoor coil thermistor is le[...]
-
Page 10
10 set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V . coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane V ery Low (temperature of indoor coil thermistor > 64 °F) 30 seconds 30 seconds 30 seconds 40 seconds 5 seconds 5 seconds 40 seconds OFF (39°C) (18°C) OFF OFF ON (HEA T) ON ON [...]
-
Page 11
11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEA T mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) below the set temperature. HEA T mode changes to COOL mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) above the set temperatur[...]
-
Page 12
12 <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided[...]
-
Page 13
13 MUZ-A24 MUY -A24 MUZ-D MUY -D MUZ-FE18 MUZ-GA MUY -GA MUZ-GE24 MUY -GE24 POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies 3-phase AC power to compressor . SMOOTHING CAP ACI[...]
-
Page 14
14 3. Purpose of P AM adoption P AM (Pulse Amplitude Modulation) has been adopted for the ef fi ciency improvement and the adaptation to IEC harmonic cur- rent emission standard Outline of simple partial switching method In conventional inverter models, DIODE MODULE recti fi es AC voltage to DC voltage, SMOOTHING CAP ACITOR makes its DC waveform [...]
-
Page 15
15 4. Intelligent power module IPM consists of the following components · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from overcurrent. Since the above components are all integrated in IPM, IPM has a merit to make the control circuit simpli[...]
-
Page 16
16 2-7-4. Characteristics of sine wave control in case of brushless DC motor ● Although ordinary 3-phase induction motor requires energy to excite the magnetic fi eld of rotor , brushless DC motor does not need it. So, higher ef fi ciency and torque are provided. ● This control provides the most ef fi cient waveform corresponding to the rota[...]
-
Page 17
17 2-8. OPERA TIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tempera- ture. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protectio[...]
-
Page 18
18 (2) T ime chart OFF T ime Ti m e ON Operational frequency of the compressor Commanded to open Standard opening degree Opening degree is corrected according to discharge temperature. (Refer to (3)) Positioning Air conditioner ON Air conditioner OFF (thermostat off) LEV opening degree About 15 minutes 2-9. EXP ANSION V AL VE CONTROL (LEV CONTROL) [...]
-
Page 19
19 (3) Control data F E D C B A T arget discharge temperature Operational frequency of the compressor 30 50 70 90 1 10 130 23 38 53 69 84 99 (Hz) (Hz) ( Other models ) ( MUZ-FE18 MUZ-GE24 MUY -GE24 ) (a) Reference value of target discharge temperature COOL / HEA T ( MUZ ) °F/°C Applied model A B C D E F MUZ-A09/12 COOL 122/50 127/53 140/60 151/66[...]
-
Page 20
20 2. Pre-heat control ON condition (1) Pre-heat control is turned ON for 15 or 30 minutes after the breaker is turned ON. (2) 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF . When the defrost thermistor reads[...]
-
Page 21
21 3-1. INVERTER SYSTEM CONTROL POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + 3-1-1. Inverter main power supply circuit Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies 3-phase AC power to compressor . SMOOTHING CAP ACIT [...]
-
Page 22
22 3. Power factor improvement Booster coil reactor and PFC rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi- lize the voltage of DC supplied to inverter circuit and make its waveform smooth. 4. Intelligent power module IPM consists of[...]
-
Page 23
23 3-2. EXP ANSION V AL VE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit. Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulses in 15 minutes When outdoor unit is operating, some indoor units stop and some operate. COOL: 5 pulses (full closed[...]
-
Page 24
24 In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger , and when temperature difference develops, the indoor coil thermistors adjust LEV opening to diminish the super heat. This action is called Evaporation T emperature Protection. Indoor heat exchanger (MXZ-3A30NA)[...]
-
Page 25
25 23 54 69 84 100 1 15 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A/2B MXZ-3A/4A 23 Compressor operating frequency (Hz) 4Hz 01 02 03 04 05 06 07 08 09 10 LEV Opening (code) Determination of LEV standard opening in each indoor unit • The standard opening is on the straight line, which connects an each standard point in the section where divided into[...]
-
Page 26
26 MXZ-3A30NA- 1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA Exclusive LEV Standard opening (pulse) LEV Opening (code) 123456789 1 0 COOL 126 130 134 138 150 160 170 180 190 200 HEA T 248 248 258 266 274 280 286 292 300 306 Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code1 1,12 Code13,14 Code15or above 23 [...]
-
Page 27
27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor . <Correction> COOL DRY HEA T Discharge temperature ● 2 ● 2 ● Each correction • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermist[...]
-
Page 28
28 Correct the LEV opening according to the difference between target discharge temperature and discharge temperature. (2) Separate correction (COOL,DRY) (Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all. Calculate each super [...]
-
Page 29
29 3-3. OPERA TIONAL FREQUENCY RANGE b) Correct the LEV separately by temperature difference “ ∆ R T” between main/sub indoor coil thermistor . ∆ RT LEV opening correction (pulse) 10.8 ∆ RT 2 7.2 ∆ RT < 10.8 1 ∆ RT < 7.2 1 In addition, decrease the target discharge temperature corresponding ∆ RT . ∆ RT T emperature to be dec[...]
-
Page 30
30 MXZ-3A30NA- 1 MXZ-4A36NA Number of operating unit Capacity code COOL (Hz) DRY (Hz) HEA T (Hz) Min. Max. Min. Max. Defrost 1 4 2 55 82 52 07 05 8 7 2 55 82 52 07 05 8 9,10 25 71 25 20 80 58 12 25 80 35 20 80 58 2 8 ~ 10 25 80 31 20 80 58 1 1 ~ 13 25 80 31 20 80 58 14 ~ 16 25 80 42 20 80 58 17 ~ 25 80 42 20 80 58 3 ( MXZ-3A ) 12 ~ 25 80 52 20 80 5[...]
-
Page 31
31 3-4. HEA T DEFROSTING CONTROL (1) Starting conditions of defrosting When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads 26.6°F or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min- utes). c) More than 5 minutes have pas[...]
-
Page 32
32 COOL Fan speed changes so that the condensing temperature stays within the target range. Fan speed Revolution per minutes (rpm) MXZ-2B20NA- 1 MXZ-3B MXZ-4B 1 100 100 2 150 150 3 200 200 4 250 250 5 300 300 6 350 350 7 400 400 8 450 450 9 500 500 10 550 550 1 1 600 600 12 650 650 13 700 700 14 750 750 HEA T Fan speed is switched according to the [...]
-
Page 33
33 1. Pre-heat control is turned ON for 15 or 30 minutes, after the breaker is turned ON. 2. 30 minutes after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF . When the defrost thermistor reads less than 69.8°F , pre-heat c[...]
-
Page 34
34 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 3-9. DR Y OPERA TION 3-10. HEA T OPERA TION 2. High pressure protection In HEA T operation the indoor coil thermistor detects the temperature of the indoor heat exchanger . The compressor opera- tional frequency is controlled to preve[...]
-
Page 35
35 4 MFZ MICROPROCESSOR CONTROL 3. Coil frost prevention Refer to MXZ MICROPROCESSOR CONTROL, COOL OPERA TION (3-8.2.). 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Refer to MXZ MICROP[...]
-
Page 36
36 1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, HEA T OPERA TION (3-10.1.). 4-3. HEA T ( ) OPERA TION 2. Indoor fan speed control (1) Indoor fan operates at the set speed by F AN SPEED CONTROL button. In Auto the fan speed is as follows. 3. High pressure protection In HEA T operation, the indoor coil thermistor detects the temperature[...]
-
Page 37
37 4-5. INDOOR F AN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor , and outputs signal to the microprocessor to feed- back the rotational frequency . Comparing the current rotational frequency with the target rotational frequency (Super High, High, Med., Low), the micropr[...]
-
Page 38
38 4-6. AUTO V ANE OPERA TION Horizontal vane (1) Cold air prevention in HEA T operation When any of the following conditions occurs in HEA T operation, the vane angle changes to V ertical position automati- cally to prevent cold air blowing on users. Compressor is not operating. Defrosting is performed. Indoor coil thermistor reads 75.2°F or belo[...]
-
Page 39
39[...]
-
Page 40
New publication, effective Sep. 2010. Specifications subject to change without notice. HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2006 MITSUBISHI ELECTRIC CO.,L TD Distributed in Sep. 2010. No. OBT16 REVISED EDITION-G 6 Distributed in Mar . 2010. No. OBT16 REVISED EDITION-F 6 Distributed in Sep. 2009[...]