Go to page of
Similar user manuals
-
Air-conditioning
Mitsubishi KITMSZ-EF35VES
11 pages -
Air-conditioning
Mitsubishi MSZ-GF60VE-E1
42 pages -
Air-conditioning
Mitsubishi MSZ-SF25VE-E2
23 pages -
Air-conditioning
Mitsubishi MSZ-EF35VEB
11 pages -
Air-conditioning
Mitsubishi MSZ-EF22VES
11 pages -
Air-conditioning
Mitsubishi KITMSZ-HJ25VA
88 pages -
Air-conditioning
Mitsubishi MSC-GE35VB
10 pages -
Air-conditioning
Mitsubishi MSZ-GE42VA
12 pages
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Mitsubishi MSZ-HJ35VA, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Mitsubishi MSZ-HJ35VA one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Mitsubishi MSZ-HJ35VA. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Mitsubishi MSZ-HJ35VA should contain:
- informations concerning technical data of Mitsubishi MSZ-HJ35VA
- name of the manufacturer and a year of construction of the Mitsubishi MSZ-HJ35VA item
- rules of operation, control and maintenance of the Mitsubishi MSZ-HJ35VA item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Mitsubishi MSZ-HJ35VA alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Mitsubishi MSZ-HJ35VA, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Mitsubishi service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Mitsubishi MSZ-HJ35VA.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Mitsubishi MSZ-HJ35VA item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. P ART NAMES AND FUNCTIONS ····················· 4 3. SPECIFICA TION ················································ 5 4. NOISE CRITERIA CURVES ···············?[...]
-
Page 2
2 <Preparation before the repair service> Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner , turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts. <Precautions during the rep[...]
-
Page 3
3 1 TECHNICAL CHANGES MSZ-HJ25V A - E1 MSZ-HJ35V A - E1 MSZ-HJ50V A - E1 1. New model OBH647A[...]
-
Page 4
4 Operation indicator lamp Remote control receiving section Emergency operation switch Horizontal vane Air inlet Air fi lter Front panel Air outlet Heat exchanger Emergency operation switch Remote controller ACCESSORIES MSZ-HJ25V A MSZ-HJ35V A MSZ-HJ50V A Installation plate 1 Installation plate fi xing screw 4 × 25 mm 5 Battery (AAA) for remote [...]
-
Page 5
5 3 SPECIFICA TION Indoor model MSZ-HJ25V A MSZ-HJ35V A MSZ-HJ50V A Power supply Single phase 230 V , 50 Hz Breaker Capacity A 10 12 Electrical data Power input 1 (T otal) Cooling W 730 1,040 2,050 Heating 870 995 1,480 Running current 1 (T otal) Cooling A 3.7 4.9 9.0 Heating 4.2 4.8 6.6 Power factor 1 (T otal) Cooling % 85 92 99 Heating 90 90 97 S[...]
-
Page 6
6 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR BAND CENTER FREQUENCIES, Hz COOLING FUNCTION SPL(dB(A)) LINE Super High F AN SPEED HEA TING 43 43 NC-10 MSZ-HJ25V A INDOOR UNIT WA L L MICROPHONE 0.8m 1m 90 80 70 60 50 40 30 20 10 63 125 250[...]
-
Page 7
7 MSZ-HJ25V A MSZ-HJ35V A MSZ-HJ50V A Unit : mm MSZ-HJ25V A MSZ-HJ35V A MSZ-HJ50V A 5 OUTLINES AND DIMENSIONS 6 WIRING DIAGRAM 232 5 69 41 799 785 7 290 120 630 49 57 80 42 43 69 57 42 7 103 130 100 (57°) 225 225 80.5 80.5 61.5 59.5 340 338 41 42 249 248 21.5 3 167 157 207.5 206.5 172 14 140 57 18 46 Air in Installation plate Piping Drain hose Air[...]
-
Page 8
8 MSZ-HJ25V A MSZ-HJ35V A Indoor heat exchanger Flared connection Room temperature thermistor RT1 1 Flared connection Refrigerant flow in cooling Refrigerant flow in heating Refrigerant pipe ø9.52 (with heat insulator) Refrigerant pipe ø6.35 (with heat insulator) Indoor coil thermistor RT1 2 Indoor coil thermistor RT1 3 Unit : mm MSZ-HJ50V A Indo[...]
-
Page 9
9 8-2. P .C. BOARD MODIFICA TION FOR INDIVIDUAL OPERA TION A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller , P .C. boards of remote controller must be modified according to the number of the indoor unit. 8-1. TIMER SHORT MODE For ser[...]
-
Page 10
10 NOTE: • The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller . • If main power is turned OFF or a power failure occurs while AUTO ST ART/ST OP timer is active, the timer setting is cancelled. • If the unit has been of f with the remote controller before power failure[...]
-
Page 11
11 NOT E : Last setting will be stored after the unit is turned OFF with the remote controller . Indoor unit receives the signal of the remote controller with beeps. WIRELESS REMOTE CONTROLLER MSZ-HJ25V A MSZ-HJ35V A MSZ-HJ50V A Time set buttons RESET button V ane control button Signal transmitting section Operation display section T emperature but[...]
-
Page 12
12 9-2. DR Y ( ) OPERA TION (1) Press OPERA TE/STOP (ON/OFF) button. OPERA TION INDICA TOR lamp of the indoor unit turns on with a beep tone. (2) Select DRY mode with OPERA TION SELECT button. (3) The set temperature is determined from the initial room temperature. 1. Coil frost prevention Coil frost prevention is as same as COOL mode. (9-1.1.) 9-3[...]
-
Page 13
13 (5) STOP (operation OFF) and ON TIMER standby In the following cases, the horizontal vane returns to the closed position. (a) When OPERA TE/STOP (ON/OFF) button is pressed (POWER OFF). (b) When the operation is stopped by the emergency operation. (c) When ON TIMER is ON standby . (6) Dew prevention During COOL or DRY operation with the vane angl[...]
-
Page 14
14 EMERGENCY OPERA TION switch 9-6. EMERGENCY/TEST OPERA TION In case of test run operation or emergency operation, use EMERGENCY OPERA TION switch on the right side of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote controller run down. The unit will start and OPERA[...]
-
Page 15
15 3. T roubleshooting procedure 1) Check if the OPERA TION INDICA TOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality . T o make sure, check how many times the OPERA TION INDICA TOR lamp is flashing ON and OFF before starting service work. 2) Before servicing, check that the connector and terminal are connected properly .[...]
-
Page 16
16 10-2. F AILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the a[...]
-
Page 17
17 2. Indoor unit failure mode table Upper lamp of OP- ERA TION INDICA- TOR lamp Abnormal point (Failure mode) Condition Remedy Not lighted Normal — — 1-time fl ash every 0.5-second Room temperature thermistor The room temperature thermistor short or open circuit is detected every 8 seconds dur- ing operation. Refer to the characteristics of t[...]
-
Page 18
18 10-3. INSTRUCTION OF TROUBLESHOOTING Indoor unit oper- ates. Outdoor unit does not operate. If blinking of OPERA TION INDI- CA TOR lamp cannot be checked, it can be checked with failure mode recall function. Indoor unit operates. Outdoor unit does not operate normally . Indoor unit does not receive the signal from remote controller . OPERA TION [...]
-
Page 19
19 10-4. TROUBLESHOOTING CHECK T ABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the power ON), the indoor fan motor turns OFF and OPERA TION INDICA TOR lamp flashes. No. Abnorm[...]
-
Page 20
20 10-5. TROUBLE CRITERION OF MAIN P ARTS MSZ-HJ25V A MSZ-HJ35V A MSZ-HJ50V A Part name Check method and criterion Figure Room temperature thermistor (RT1 1) Measure the resistance with a tester . Refer to 10-7. "T est point diagram and voltage", "2. Indoor electronic control P .C. board", for the chart of thermistor . Indoor co[...]
-
Page 21
21 10-6. TROUBLESHOOTING FLOW A Check of indoor fan motor The indoor fan motor error has occurred, and the indoor fan does not operate. T urn OFF the power supply . Is there any foreign matter that interferes the rotation of the line fl ow fan? Ye s No Remove the foreign matter and adjust the line fl ow fan. Pay enough attention to the high volta[...]
-
Page 22
22 B Check of remote controller and indoor electronic control P .C. board Check if the remote controller is exclusive for this air conditioner . Does the unit operate with the remote controller? OK Ye s No (Not clear) Replace the batteries. (Refer to 10-1.4.) Press OPERA TE/STOP (ON/OFF) button on the remote controller . Is LCD display on the remot[...]
-
Page 23
23 C Check of indoor P .C. board and indoor fan motor T urn OFF the power supply . Remove indoor fan motor connector CN21 1 from indoor power P .C. board and vane motor connector CN151 from the indoor electronic control P .C. board and turn ON the power supply . Does the unit operate with the remote controller? Does OPERA TION INDICA TOR lamp light[...]
-
Page 24
24 D How to check miswiring and serial signal error A Reinstall ei- ther the unit or the light away from each other . Attach a fi lter on remote control receiving section of the indoor unit. • • T urn OFF inverter-controlled lighting equipment. T urn OFF the power supply and then turn ON again. Press the emergency operation switch. • • •[...]
-
Page 25
25 E Electromagnetic noise enters into TV sets or radios Ye s Is the unit earthed? No Earth the unit. Ye s Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m? No Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor [...]
-
Page 26
26 Room temperature thermistor (RT1 1) Indoor coil thermistor (RT12, RT13) T emperature (°C) Resistance (k Ω ) Fuse (F1 1) T3.15AL250V V aristor (NR1 1) Connector to indoor electronic control P .C. board (CN20A) 5 VDC 12 VDC GND Connector to Indoor fan motor (CN21 1) Resistor (R1 1 1) Connector to T erminal block (CN201) Indoor terminal block con[...]
-
Page 27
OPERA TING PROCEDURE PHOTOS 1. Removing the panel (1) Remove the screw caps on the panel and remove the screws of the panel. (2) Pull the panel slightly toward you, and then remove the panel by pushing it upward. 27 MSZ-HJ25V A MSZ-HJ35V A MSZ-HJ50V A NOTE: Turn OFF power supply before disassembly . Photo 1 Screws of the panel (1) Slide the sleeve [...]
-
Page 28
OPERA TING PROCEDURE PHOTOS 2. Removing the indoor power P .C. board and the electrical box (1) Remove the panel. (Refer to 1.) Remove the right corner box. (2) Disconnect the following connectors: <Indoor electronic control P .C. board> CN151 (V ane motor) CN1 12 (Indoor coil thermistor) CN10A (T o the indoor power P .C. board) (3) Unhook th[...]
-
Page 29
OPERA TING PROCEDURE PHOTOS 3. Removing the indoor electronic control P .C. board (1) Remove the panel. (Refer to 1.) Remove the right corner box. (2) Disconnect the following connectors: <Indoor electronic control P .C. board> CN151 (V ane motor) CN1 12 (Indoor coil thermistor) CN10A (T o the indoor power P .C. board) (3) Unhook the catch on[...]
-
Page 30
OPERA TING PROCEDURE PHOTOS 5. Removing the indoor fan motor , the indoor coil thermistor and the line flow fan (1) Remove the panel. (Refer to 1.) Remove the right cor- ner box. (2) Remove the control P .C. board holder , the electrical box and the nozzle assembly . (Refer to 2.) (3) Remove the screws fixing the motor bed. (4) Disengage the hooks [...]
-
Page 31
31 Fixing the indoor coil thermisor There are 2 forms of parts for fixing the indoor coil thermistor . NOTE: T ake care to avoid loss and accidental falling of the clip-shape part inside the unit. Mount the clip-shape part on the marked position. Do not pull the lead wire when removing the indoor coil thermistor . Holder shape Clip shape 1. Set the[...]
-
Page 32
© Copyright 2012 MITSUBISHI ELECTRIC CORPORA TION Distributed in Mar . 2013. No. OBH647 REVISED EDITION-A Distributed in Dec. 2012. No. OBH647 Made in Japan New publication, effective Mar . 2013 Specifications are subject to change without notice. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN[...]