Go to page of
Similar user manuals
-
Air Conditioner
Nordyne B5SM -090
16 pages 1.72 mb -
Air Cleaner
Nordyne AireCare 707831C
4 pages 0.42 mb -
Heat Pump
Nordyne T3BN
16 pages 0.46 mb -
Air Conditioner
Nordyne M1S
40 pages 1.24 mb -
Air Conditioner
Nordyne E3
32 pages 1.46 mb -
Furnace
Nordyne Residential Gas Furnaces
12 pages 0.54 mb -
Furnace
Nordyne G5RC
9 pages 2.82 mb -
Furnace
Nordyne AND M5S
40 pages 3.89 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Nordyne Q4 Series, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Nordyne Q4 Series one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Nordyne Q4 Series. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Nordyne Q4 Series should contain:
- informations concerning technical data of Nordyne Q4 Series
- name of the manufacturer and a year of construction of the Nordyne Q4 Series item
- rules of operation, control and maintenance of the Nordyne Q4 Series item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Nordyne Q4 Series alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Nordyne Q4 Series, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Nordyne service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Nordyne Q4 Series.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Nordyne Q4 Series item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
460 Volt Q4 Series Read these instructions thoroughly before starting the installation. Follow all precautions and warnings contained within these instructions and on the unit. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local co[...]
-
Page 2
2 TABLE OF CONTENTS OWNER INFORMATION .......................................................................................................... 3 SPECIFICATIONS ................................................................................................................. .... 4 SAFETY CONSIDERATIONS .............................................[...]
-
Page 3
3 It is the sole responsibility of the homeowner to make certain that heat pump has been correctly set up and adjusted to operate properly. NORDYNE warrants the heat pump to be free from defects in material or workmanship for a period of one year. A warranty certificate with full details is included with the heat pump. How- ever, NORDYNE will not b[...]
-
Page 4
4 OPERATING INSTRUCTIONS To Operate Your Heat Pump For Cooling — 1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO. (See Figure 1) 2. Set the thermostat temperature selector to the desired cooling temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indo[...]
-
Page 5
5 All models are shipped from the factory with the following: 1. Zero clearance to combustibles 2. Multi-speed direct-drive blower. 3. Blower Speed Relay. 4. Horizontal or Down flow duct connections. The unit dimensions are shown in Figure 3 . Optional field-installed electric heater kits are available in 9 kw and 15 kw heating capacities. A separa[...]
-
Page 6
6 Figure 3. Dimensions 24.9 13.5 16.0 23.5 12.0 13.3 13.5 16.0 12.0 CG A 47.5 3/4" NPT Female Drain Connector B SUPPL Y RETURN Top View Side View Back View C en t e r o f G rav it y Hei g h t ( in in ch es) Mod el No. C w it h b ase rails w it h o u t b ase rails Q 4S A- 036 3 40 28.0 26.0 33.7 31.3 Q 4S A- 048 3 45 28.0 26.0 33.7 31.3 Q 4S A-[...]
-
Page 7
7 Figure 4. Minimum Clearances 36" 36" 6" 72" 36" Condensate Drain Figure 5. Condensate Drain UNIT INSTALLATION Ground Level — When installing the unit at ground level, provide a concrete mounting pad separate from the building foundation. The pad must be level to insure proper condensate disposal and strong enough to sup[...]
-
Page 8
8 Acoustical Duct Work — Certain installations may require the use of acoustical lining inside the supply duct work. Acoustical insulation must be in accordance with the current revision of the Sheet Metal and Air Conditioning Contractors National Association (SMACNA) application standard for duct liners. Duct lining must be UL classified batts o[...]
-
Page 9
9 Use a separate branch electrical circuit for this unit. A means of electrical disconnect must be located within sight of and readily accessibility to the unit. Internally mounted circuit breakers are available as field installed options. These circuit breakers can be used as an electrical disconnect. Provide power supply (or supplies) for the uni[...]
-
Page 10
10 interval settings are available: 30 minutes, 60 minutes, and 90 minutes. Time setting selection is dependent on the climate where the unit is being installed. Example 1. Dry climate of Southern Arizona. A 90 minute setting is recommended. Example 2. Moist climate of Seattle, Washington. A 30 minute setting is recommended. To set the cycle timer,[...]
-
Page 11
11 UNIT MAINTENANCE ! W ARNING: To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply. Refrigerant Charging — The Q4 packaged heat pumps are fully charged at the factory . The system refrigerant charg[...]
-
Page 12
12 Typical Wiring (Field Supplied) for 1-Stage Cool, 1-Stage Heat Typical Wiring (Field Supplied) for 2-Stage Cool, 1-Stage Heat Figure 10. Typical Thermostat Connection E O G R Y1 1 2 3 4 5 6 7 8 9 Blue ECONOMIZER PLUG INDOOR THERMOST A T SUB-BASE Green FROM BLO WER RELA Y (Optional,Check Thermostat Instructions) Y2 W2 W3 X E R W2 O Y C DEFROST BO[...]
-
Page 13
13 Heat Pump in Heating * Note: All pressures are listed in psig. and all temperatures in deg. F. — Shaded Boxes indicate flooded conditions — Rated Design Values. Suction Pressure will be lower than design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design. — Discharge temperatures greater th[...]
-
Page 14
14 Table 2a. Q4SA Heating Charging Charts Heat Pump in Heating * Note: All pressures are listed in psig. and all temperatures in deg. F. — Shaded Boxes indicate flooded conditions — Rated Design Values. Suction Pressure will be lower than design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design[...]
-
Page 15
15 Q4S A-036 OU T D O O R T E M P E R AT URE ( ° F ) 70 75 80 85 90 95 100 105 Suc t. P res. Di sch . P res. Di sch . Te m p. Di sch . Pre s. Di sch . Te m p. Di sch . Pres . Di sch . Te m p. Di sch . P r es. Disch . Tem p . Di s c h . P r es. Di s c h . Tem p. Di s c h . P r es. Di s ch . Tem p. Di s c h. P res. Di sch. Te m p. D i sch . P res. D[...]
-
Page 16
16 Q4S A-060 OU T D O O R T E M P E R AT URE ( ° F ) 70 75 80 85 90 95 100 105 Suc t. P res. Di sch . P res. Di sch . Te m p. Di sch . Pre s. Di sch . Te m p. Di sch . Pres . Di sch . Te m p. Di sch . P r es. Disch . Tem p . Di s c h . P r es. Di s c h . Tem p. Di s c h . P r es. Di s ch . Tem p. Di s c h. P res. Di sch. Te m p. D i sch . P res. D[...]
-
Page 17
17 Q4 A C C E S S OR IE S Descri pti on P art N u m ber Roof Curb (8" ) 547830 Roof Curb (14" ) 547831 M anual F r es h A i r Damper 547832 E c onom i z er, downf l ow 547833 S uppl y/ ret urn trans it i on, 16" 547834 S uppl y/ ret urn trans it i on, 18" 547835 Conc ent ri c di f f us er, f lus h, 16" 547836 Conc ent ri c [...]
-
Page 18
18 Convertible Packaged Heat Pump 460 V olt Three Phase 60Hz N N OTES: 1. Disconnect all power before servicing. 2. For supply connections use copper conductors only . 3. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105 ° C. 4. For supply[...]
-
Page 19
INST ALLER: PLEASE LEA VE THESE INST ALLA TION INSTRUCTIONS WITH THE HOMEOWNER. R ® A S C O M P L Y I I T N G W H T T H N I S U I H A S B I D D A R I S T A N A R 2 1 0 T A I D N F I E D T R E C E E N R - C O I I O N I N G T A I D N R - C O I I O N I N G D I T I O N I N G N O C - R I A R ¢707885W¤ 707885A St. Louis, MO 707885A (Replaces 7078850) [...]