Go to page of
Similar user manuals
-
Air Conditioner
Panasonic CU-KE18NKU
69 pages 1.58 mb -
Air Conditioner
Panasonic CU-PC18JKF
8 pages 1.84 mb -
Air Conditioner
Panasonic CU-E18GKR
8 pages 2.15 mb -
Air Conditioner
Panasonic CS-XE9EKE
20 pages 4.11 mb -
Air Conditioner
Panasonic CW-A170KR
8 pages 3.04 mb -
Air conditioner
Panasonic CS-MV12EKE
12 pages 1.47 mb -
Air Conditioner
Panasonic CU-2S18NBU-1
43 pages 4.22 mb -
Air conditioner
Panasonic CU-J43DBE8
64 pages 2.3 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Panasonic CS-ME7QKUA, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Panasonic CS-ME7QKUA one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Panasonic CS-ME7QKUA. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Panasonic CS-ME7QKUA should contain:
- informations concerning technical data of Panasonic CS-ME7QKUA
- name of the manufacturer and a year of construction of the Panasonic CS-ME7QKUA item
- rules of operation, control and maintenance of the Panasonic CS-ME7QKUA item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Panasonic CS-ME7QKUA alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Panasonic CS-ME7QKUA, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Panasonic service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Panasonic CS-ME7QKUA.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Panasonic CS-ME7QKUA item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
© Panasonic Corporation 2013 Order No: PAPAMY1312045CE Indoor Unit CS-ME7QKUA Destination U.S.A. Canada Please file and use this manual together with the service manual for Model No. CU-5E36QBU, Order No. PAPAMY 1312037CE. PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite, be assured of no refrigerant leak age during the installation or r [...]
-
Page 2
2 TABLE OF CONTENTS 1. Safety Pr ecautions ............................................. 3 2. Specification ....................................................... 5 3. Features ............................................................... 7 4. Location of Controls and Components ............ 8 4.1 Indoor Un it ...................................[...]
-
Page 3
3 CA UTION WA RNIN G WA RNIN G 1. Safety Precautions Read the following “SAFET Y PRECAUTIONS” carefully bef ore perform any servicing. Electrical work must be installed or serviced by a licens ed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installe d. The caution items stated here [...]
-
Page 4
4 CA UTION 19. During installation, install the refrigerant piping properly before run the compress or. (Operation of compressor without fi xing ref rigeration piping and valves at opened condition will c ause suck-in of air, abnormal high pressure in refrigeration cycle and result in exp losion, injury etc.). 20. During pump down operation, stop t[...]
-
Page 5
5 2. Specification Model Indoor CS-ME7QKUA Outdoor CU-5E36QBU Performance Test Condition ARI Power Supply Phase, Hz Single, 60 V 208 230 Min. Mid. Max. Min. Mid. Max. Cooling Capacity kW 1.80 2.01 2.90 1.80 2.01 2.90 BTU/h 6100 6900 9900 6100 6900 9900 Running Current A - 2.8 - - 2.5 - Input Power W 340 500 810 340 500 810 EER W/W 5.29 4.02 3.58 5.[...]
-
Page 6
6 Model Indoor CS-ME7QKUA Outdoor CU-5E36QBU Drain Hose Inner Diameter mm (inch) 16.7 (5/8) Length mm (inch) 650 (25 -5/8) Indoor Heat Exchanger Fin Material Aluminium (Pre Coat) Fin Type Slit Fin Row x Stage x FPI 2 x 15 x 21 Size (W x H x L) mm (inch) 25.4 x 315 x 610 (1 x 1 2-3/8 x 24) Air Filter Material Polypropelene Type One-touch Power Suppl[...]
-
Page 7
7 3. Features Inverter Technology o Wider output power range o Energy saving o Quick Cooling o More precise temperature control Environment Protection o Non-ozone depletion sub stances refrigerant (R410A) Long Installation Piping o Long piping up to 82 ft (25 meters) for 1 room Easy to use remote control Quality Improvement o Ra[...]
-
Page 8
8 4. Location of Controls and Components 4.1 Indoor Unit 4.2 Outdoor Unit 4.3 Remote Control[...]
-
Page 9
9 5. Dimensions 5.1 Indoor Unit[...]
-
Page 10
10 6. Refrigeration Cycle Diagram[...]
-
Page 11
11 7. Block Diagram[...]
-
Page 12
12 8. Wiring Connection Diagram 8.1 Indoor Unit[...]
-
Page 13
13 9. Electronic Circuit Diagram 9.1 Indoor Unit[...]
-
Page 14
14 10. Printed Circuit Board 10.1 Indoor Unit 10.1.1 Main Printed Circuit Board[...]
-
Page 15
15 10.1.2 Power Printed Circuit Board 10.1.3 Indicator Prin ted Circuit Board[...]
-
Page 16
16 11. Installation Instruction 11.1 Select the Best Location 11.1.1 Indoor Unit Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. There should not be any heat source or steam near the unit. There should not be any ob stacles bl ocking the air circulation. A place where air circulation in the roo [...]
-
Page 17
17 11.2 Indoor Unit 11.2.1 How to Fix In stallation Plate The mounting wall shall be stron g and solid enough to prevent it from the vibratio n. The center of installation plate sho uld be at more than at right and left of the wall. The distance from installation plate edge to ceiling sho uld more than . From installation plate left edge to[...]
-
Page 18
18 11.2.3 Indoor Unit Installation 11.2.3.1 For the right rear piping 11.2.3.2 For the right bottom piping 11.2.3.3 For the embedded piping (This can be used for left rear pipi ng and bottom piping also.)[...]
-
Page 19
19 11.2.4 Connect the Cable to the Indoor Unit 1. The insi de and outside connectio n cable can be connected without remo ving the front grille. 2. Unscre w the conduit cover and fix the conduit connector to conduit cover with lock nut, then secure it against chassi s. 3. Conne c tion cable between indoor u nit and outdoor unit should be UL listed [...]
-
Page 20
20 11.2.5 Wiring Stripping and connecting requirement 11.2.5.1 Cutting and flaring the piping 1 Please cut using pipe cutter and then remove the burrs. 2 Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe . 3 Please make flare after inserting th[...]
-
Page 21
21 12. Operation Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as time passes, automatically adjusts output power fo r maximum comfort always. In order to achieve the suitable operation mode, the microcomputer maintains the set temperatur e by measuring the temperat[...]
-
Page 22
22 12.1.4.2 Automatic Operation This mode can be set using remote cont rol and the operation is decided by remote control setting temperature, remote control operation mode and indoor inta ke air temperature. During operation mode ju dgment, indoor fan motor (with spee d of Lo-) is running for 30 second s to detect the indoor intake air tem[...]
-
Page 23
23 [Heating] o According to indoor pipe temperature, a u tomati c heating fan speed is determi ned as follows. Feedback control o Immediately after the fan motor started, f eedback control is performed on ce every second. o During fan motor on, if fan motor feedba ck ≥ 2550 rpm or < 50 rpm continue for 10 second s, then fan motor error cou[...]
-
Page 24
24 12.4.2 Horizontal Airflow The horizontal airflow direction l ouvers can be adj usted manually by hand. 12.5 Quiet Operation (Cooling Mode /Cooling Area of Dry Mode) Purpose o To provide quiet cooling operation compare to normal operation. Control condition o Quiet operation start condition When “Quiet” button at remote cont rol i[...]
-
Page 25
25 Control contents o Fan speed auto Indoor FM RPM depends on pipe temperature sensor of indoor he at exchanger. Auto fan speed is changed from normal settin g to quiet setting of respective fan speed. This is to reduce sound o f Hi, Me, Lo for 3dB. o Fan speed manual Manual fan speed for quiet operation is -1 step from setting fan spee[...]
-
Page 26
26 12.10 Indication Panel Note: If POWER LED is blinking, the possible operation of t he unit are Hot Start, during Dei c e operation, operation mode judgment, or ON timer sampling. If Timer LED is blinking, there is an abnormality operati on occurs.[...]
-
Page 27
27 13. Operation Control (For Multi Split Connection) During multi split connection, indoor unit’s ope ration controls are same with single split conne ction unless specified in this chapter. 13.1 Cooling operation 13.1.1 Thermostat control Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperatur e — Inter[...]
-
Page 28
28 For the 2nd judgment onwards o If indoor intake temperature - remote control setting temperature 5.4°F, if previous o perate in DRY mode, then continue in DRY mode, otherwise COOL mode is decided. o If -3.6°F ≤ indoor intake temperature - remote control setti ng temperature < 5.4°F, maintain with previous mode. o If indoor intake[...]
-
Page 29
29 14. Servicing Mode 14.1 Auto Off/On Button 1 AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to operate air conditioner wi th limited func tion if remote control is misplace d or malfunction. 2 TEST RUN OPERATION (FOR PU MP DOWN/SERVICING PURPOSE) The Test Ru[...]
-
Page 30
30 4 REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiv ing Sound OFF/ON Mode will be activated if the Auto OFF/ON butt on is pressed continuously for more than 16 seco nds (4 “beep” sounds will occur at 16 th seconds to identify the Remote Control Receiving Sound OFF/ON Mo de is in standby co ndition) and pre ss “AC Reset?[...]
-
Page 31
31 15. T roubleshooting Guide 15.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspectin g the refrigeration cycle. Such problems include in sufficient insulation, problem with the power source, malfunction of a compressor a nd a fan. The normal outlet air temperature and p r [...]
-
Page 32
32 15.1.1 Relationship between the condition of the air conditioner and pressure and electric current Carry out the measurements of pressure, electric cu rrent, and tempe rature fifteen minutes after an operation is started.[...]
-
Page 33
33 15.2 Breakdown Self Diagnosis Function 15.2.1 Self Diagnosis Function (Thr ee Digits Alphanumeric Code) Once error occurred during operatio n, the uni t will stop its operation, and Timer LED blinks. Although Timer LED goes off when power supply is turn ed off, if the unit is ope rated under a breakdown condition, the LED will ON again. [...]
-
Page 34
34 15.3 Error Code Table[...]
-
Page 35
35 Note: “ ○ ” – Frequency measured and fan spee d fixed The memory data of error code is erased when the powe r supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the CHECK button at remote control. Although operation forced to stop when abnormality d e tected, emergency operation is possible for[...]
-
Page 36
36 15.4 Self-diagnosis Method 15.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions During startup and operati on of cooling and heating, t he data received from outdoor unit in indoor unit signa l transmission is checked whether it is no rmal. Malfunction Caused Faulty indoor unit PCB. Faulty outdoor unit P[...]
-
Page 37
37 15.4.2 H12 (Indoor/Outdoor Cap acity Rank Mismatched) Malfunction Decision Conditions During startup, error code appears when different ty pes of indoor a nd outdoor units are interconnected. Malfunction Caused Wrong models interconnected. Wrong indoor unit or outdoor unit PCBs mounted. Indoor unit or outdoor unit PCBs defective.[...]
-
Page 38
38 15.4.3 H14 (Indoor Intake Air Temp erature Sensor Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, t he temperatures detected by the indoor intake air temperature sensor are used to determine sensor e r rors. Malfunction Caused Faulty connector connecti on. Faulty sensor. Faulty P[...]
-
Page 39
39 15.4.4 H15 (Compressor Temper ature Sensor Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, t he temperatures detected by the outdoor compresso r temperature sensor are used to determine sensor e r rors. Malfunction Caused Faulty connector connecti on. Faulty sensor. Faulty PCB. T[...]
-
Page 40
40 15.4.5 H16 (Outdoor Current Transformer Open Circuit) Malfunction Decision Conditions A current transformer (CT) is detected by checking the comp ressor running frequency ( ≥ rated frequency ) and CT detected input current (less than 0.65A) for continuou sly 20 seconds. Malfunction Caused CT defective Outdoor PCB defective Comp[...]
-
Page 41
41 15.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operati on is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm) Malfunction Caused Operation stops due to short circuit insid e the fan motor winding.[...]
-
Page 42
42 15.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, t he temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor e r rors. Malfunction Caused Faulty connector connecti on. Faulty sensor. Faulty PCB.[...]
-
Page 43
43 15.4.8 H27 (Outdoor Air Temper ature Sensor Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connecti on. Faulty sensor. Faulty PCB. Troubleshoo[...]
-
Page 44
44 15.4.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connecti on. Faulty sensor. Faulty PCB. Troublesho[...]
-
Page 45
45 15.4.10 H30 (Compressor Discharge T emperature Sensor Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, t he temperatures detected by the outdoor discharge pi pe temperature sensor are used to determine sensor e r rors. Malfunction Caused Faulty connector connecti on. Faulty sensor. ?[...]
-
Page 46
46 15.4.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, t he temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor e r rors. Malfunction Caused Faulty connector connecti on. Faulty sensor. [...]
-
Page 47
47 15.4.12 H33 (Unspecified Voltag e between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detec ted for its requir ement by the indoor/out door transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCB s used. Indoor unit or outdoor unit PCB defective. Troubleshoo[...]
-
Page 48
48 15.4.13 H36 (Outdoor Gas Pipe Sensor Abnormalit y) Malfunction Decision Conditions During startup and operati on of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor e r rors. Malfunction Caused Faulty connector connecti on. Faulty sensor. Faulty PCB. Troublesho[...]
-
Page 49
49 15.4.14 H37 (Outdoor Liquid Pipe Te mperature Sensor Abnormality) Malfunction Decision Conditions During startup and operati on of cooling and heating, t he temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor e r rors. Malfunction Caused Faulty connector connecti on. Faulty sensor. Fau[...]
-
Page 50
50 15.4.15 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operati on is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit insid e the fan motor winding. Operation stops due to breaking of wire i [...]
-
Page 51
51 15.4.16 H98 (Indoor High Pressure Pr otection) Error Code will not display (no Time r LED blinking) but store in EEPROM Malfunction Decision Conditions During heating operation, the temperature dete cted by the indoor pipe temperature sensor i s above 140°F. Malfunction Caused Clogged air filter of the indoor unit Dust accumulation [...]
-
Page 52
52 15.4.17 H99 (Indoor Freeze Prevention Pr otection: Cooling or Soft Dry) Malfunction Decision Conditions Freeze prevention control take s place (when in door pipe temperature is lo wer than 35.6°F) Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit he at exchanger Air short circu it [...]
-
Page 53
53 15.4.18 F11 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions When cooling operation, when ind oor pipe temperature or indoor heat excha nger temperature sensor is ab ove 113°F. Malfunction Caused Faulty connector connecti on. Faulty indoor pipe temperature sensor. Faulty indoor main PCB. Troubleshooti[...]
-
Page 54
54 15.4.19 F17 (Indoor Standby Un its Freezing Abnormality) Malfunction Decision Conditions When the different between indoor intake air tempe r ature and indoor pipe tem perature is above 50°F or indoor pipe temperature is below 30.2°F Remark: When the indoor standby unit is free zing, the outdoor unit transfers F17 error code to the corresp[...]
-
Page 55
55 15.4.20 F90 (Pow er Factor Correction Protection) Malfunction Decision Conditions During startup and operati on of cooling and heating, when Power Factor Correction (P FC) protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level. Malfunction Caused DC voltage peak due to power supply surge. DC voltage p[...]
-
Page 56
56 15.4.21 F91 (Refrigeration Cycle Ab normality) Malfunction Decision Conditions During cooling, compresso r frequency = Fcmax. During cooling and heating operatio n, running current: 0.65A < I < 1.65A. During cooling, indoor intake - indoo r pipe < 39.2°F. Malfunction Caused Refrigerant shortage (refrigerant leakage) [...]
-
Page 57
57 15.4.22 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checkin g the compressor running condition thro ugh the position detection circuit. Malfunction Caused Compressor termin al disconnect Outdoor PCB malfunction Troubleshooting[...]
-
Page 58
58 15.4.23 F95 (Cooling High Pressure Ab normality) Malfunction Decision Conditions During operation of cooli ng, when outdoor unit heat exchanger high temperature data (141.8°F) is detecte d by the outdoor pipe temperature sensor. Malfunction Caused Outdoor pipe temperature rise due to sh ort circuit of hot discharge air flow. Outdoor pip[...]
-
Page 59
59 15.4.24 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooli n g and heating, when IPM temper ature da ta (212°F) is detected by the IPM temperature sensor . Malfunction Caused IPM overheats due to short circuit of hot discharge ai r flow. IPM overheats due to defective of outdoor fan motor. IPM overheats [...]
-
Page 60
60 15.4.25 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooli n g and heating, when com pressor tank temperature data (233.6°F) i s detected by the compressor tank temperature sen s or. Malfunction Caused Refrigerant shortage (refrigerant leakag e). 2/3 way valve closed. Detection error due to faulty[...]
-
Page 61
61 15.4.26 F98 (Input Over Current Detection) Malfunction Decision Conditions During cooling and heating operatio n, when an input over-curr ent (16.8A) is detected by checking the input current value being detected by current tran sformer (CT) with the compressor running. Malfunction Caused Over-current due to compressor failure. Over-curr[...]
-
Page 62
62 15.4.27 F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooli n g and heating, when an outp ut over-cur rent (18.5A) is detected by checking the current that flows in the inverter DC peak sensing circuitry. Malfunction Caused DC peak due to compre ssor failure. DC peak due to defective powe r trans[...]
-
Page 63
63 WA RNIN G 16. Disassembly and Assembly Instructions High Voltage is generated in the electrical parts area by the capacitor. Ensure that t he capac itor has discharged sufficiently before proceeding with repair work. Failure to heed this cauti on may result in electric shocks. 16.1 Indoor Electronic Controllers, Cro ss Flow Fan and Indoor Fan Mo[...]
-
Page 64
64 16.1.1.2 To remove discharge grille[...]
-
Page 65
65 16.1.1.3 To remove control board 16.1.1.4 To remove cross flow fan and indoor fan motor[...]
-
Page 66
66[...]
-
Page 67
67 17. Exploded V iew and Replacement Parts List 17.1 Indoor Unit Note The above exploded view is for the purp os e of parts disassembly and repl acement. The non-numbered pa rts are not kept as standard service parts.[...]
-
Page 68
68 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-ME7QKUA REMARK 1 CHASSIS COMPLETE 1 CWD50C1633 2 FAN MOTOR 1 L6CBYYY L0055 O 3 CROSS-FLOW FAN COMPLE TE 1 CWH02C1076 4 BEARING ASSY 1 CWH64K007 5 SCREW - CROSS-FL OW FAN 1 CWH551146 7 EVAPORATOR 1 CWB30C3504 8 FLARE NUT (LIQUID) 1 CWT251030 9 FLARE NUT (GAS) 1 CWT251031 12 CONTROL BOARD CASING [...]