Go to page of
Similar user manuals
-
Power Supply
Toshiba RS485
73 pages 0.53 mb -
Power Supply
Toshiba 1600XP
90 pages 2.72 mb -
Power Supply
Toshiba QX7 Series
6 pages 2.41 mb -
Power Supply
Toshiba Adjustable Speed Drive H3
122 pages 1.49 mb -
Power Supply
Toshiba JK Series
23 pages 2.6 mb -
Power Supply
Toshiba 1000
64 pages 1.62 mb -
Power Supply
Toshiba 1600EP
1 pages 0.03 mb -
Power Supply
Toshiba LQ500
9 pages 0.26 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Toshiba G8000, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Toshiba G8000 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Toshiba G8000. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Toshiba G8000 should contain:
- informations concerning technical data of Toshiba G8000
- name of the manufacturer and a year of construction of the Toshiba G8000 item
- rules of operation, control and maintenance of the Toshiba G8000 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Toshiba G8000 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Toshiba G8000, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Toshiba service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Toshiba G8000.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Toshiba G8000 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
© Copyright 2007 T oshiba International Corporation All rights reserved. Document: 59942-001 November 2007 UNINTERRUPTIBLE POWER SYSTEM (UPS) G8000 SERIES with Isolated Output INST ALLA TION and OPERA TION MANUAL[...]
-
Page 2
[...]
-
Page 3
G8000 Series with Isolated Output Installation and Operation Manual Document: 59942-001 November 2007 UNINTERRUPTIBLE POWER SYSTEM (UPS) G8000 SERIES with Isolated Output INST ALLA TION and OPERA TION MANUAL[...]
-
Page 4
G8000 Series with Isolated Output Installation and Operation Manual The T oshiba products listed in this document are intended for usage in general electronics applications (computer , personal equipment, ofce equipment, measuring equipment, industrial robotics, domestic appliances, etc.). These T oshiba products are neither intended nor warrant[...]
-
Page 5
G8000 Series with Isolated Output Installation and Operation Manual UNINTERRUPTIBLE POWER SYSTEM (UPS) Please complete the following information and retain for your records. Unless otherwise specied, the warranty period for the UPS or UPS part is 12 months from the shipment date (see T oshiba International Corporation bill of lading). Unless oth[...]
-
Page 6
G8000 Series with Isolated Output Installation and Operation Manual Purpose This manual provides information on how to safely operate your T oshiba International Corporation power electronics product. This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual. Read[...]
-
Page 7
i G8000 Series with Isolated Output Installation and Operation Manual T able of Contents 1 Introduction .......................................................................................................................... 1 2 General Safety Instructions ...........................................................................................[...]
-
Page 8
ii G8000 Series with Isolated Output Installation and Operation Manual 1 1.1 T erminal Blocks, T erminal Bus, and Power Cables .................................................... 3 0 1 1.3 Grounding Wire .......................................................................................................... 33 1 1.4 Control Wires................[...]
-
Page 9
1 G8000 Series with Isolated Output Installation and Operation Manual 1 Introduction This manual provides information on how to safely operate your G8000 Series Uninterruptible Power System (UPS). This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual. Read the[...]
-
Page 10
2 G8000 Series with Isolated Output Installation and Operation Manual 2 General Safety Instructions DO NOT attempt to transport, install, operate, maintain or dispose of this equipment until you have read and understood all of the product safety information provided in this manual. 2.1 Symbols The symbols listed below are used throughout this manua[...]
-
Page 11
3 G8000 Series with Isolated Output Installation and Operation Manual 2.2 Signal Words The signal words listed below are used throughout this manual. When the words DANGER, W ARNING, CAUTION and A TTENTION are used in this manual they will include important safety information that must be carefully followed. 2.3 Qualied Personnel Installation, o[...]
-
Page 12
4 G8000 Series with Isolated Output Installation and Operation Manual Be trained and authorized to safely energize, de-energize, ground, lockout/tagout circuits and equipment, and clear faults in accordance with established safety practices. Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats[...]
-
Page 13
5 G8000 Series with Isolated Output Installation and Operation Manual 4 Safety Precautions The T oshiba products listed in this document are intended for usage in general electronics applications (computer , personal equipment, ofce equipment, measuring equipment, industrial robotics, domestic appliances, etc.). These T oshiba products are neith[...]
-
Page 14
6 G8000 Series with Isolated Output Installation and Operation Manual 4.3 T ransporting/Unpacking W ARNING When transporting the UPS by crane, follow the SPECIFIED WORK PROCEDURE. The suspension wire angle should be less than 60°. The UPS falling or overturning may cause crushing, trapping or other personal injuries. See Installation Manual: Chapt[...]
-
Page 15
7 G8000 Series with Isolated Output Installation and Operation Manual Fig. 4.1 Exterior Handling label CAUTION DO NOT transport, move, store, or place the UPS on its side. Forces due to heavy components inside may damage the UPS. A void vibration or shock exceeding 0.5G. Failing to observe this precaution may cause damage to the UPS. DO NOT allow t[...]
-
Page 16
8 G8000 Series with Isolated Output Installation and Operation Manual 4.4 Inspection/Storage Inspection Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material. Unpacking Check the unit for loose, broken, bent or[...]
-
Page 17
9 G8000 Series with Isolated Output Installation and Operation Manual CAUTION Install the UPS in a controlled environment. Improper storage and installation environment may deteriorate insulation, shorten component life and cause malfunctions. See T able 5.1 - UPS Installation Environment Standards DO NOT tilt the UPS more than 10° from upright po[...]
-
Page 18
10 G8000 Series with Isolated Output Installation and Operation Manual DO NOT block air vents. Blocking the vents will increase the internal temperatures and may result in UPS failure or re. DO NOT install the UPS where water may fall on it. W ater may cause electrical shock, personal injury or UPS failure. DO NOT use oor wax that contains si[...]
-
Page 19
1 1 G8000 Series with Isolated Output Installation and Operation Manual T ABLE 5.1 - UPS INST ALLA TION ENVIRONMENT ST ANDARDS Item Environment standard Installation Location Indoors Ambient T emperature Minimum operating temperature: 32 °F (0 ° C) Maximum operating temperature: 104 °F ( 40 ° C) (UPS only) Maximum operating temperature: 95 °F [...]
-
Page 20
12 G8000 Series with Isolated Output Installation and Operation Manual not inuence some sensitive devices that are operating near by . If such interference is experienced, the UPS should be installed further away from the affected equipment and/or powered from a different source than that of the installed equipment. 8) The user should provide ov[...]
-
Page 21
13 G8000 Series with Isolated Output Installation and Operation Manual 5.1 Wiring/Connection W ARNING Perform wiring and connections with correct polarity . Be careful when connecting the UPS to the battery system. A wrong connection may cause damage to the UPS, battery , or charger . Connect ONL Y one (1) ground wire to the earth ground terminal. [...]
-
Page 22
14 G8000 Series with Isolated Output Installation and Operation Manual 6 W arning Labels Below are representative warning labels and their location on the UPS. Exterior Handling labels shown in section 4.3, T ransporting/Unpacking, are in the manual packet, and attached to the UPS shipping covering and shipping pallet. A TTENTION Make sure all the [...]
-
Page 23
15 G8000 Series with Isolated Output Installation and Operation Manual FIGURE 6.1 – G8000 WITH ISOLA TED OUTPUT UPS W ARNING LABELS 6.1 W arning Label Locations FIGURE 6.2 – 100 KV A UPS WARNING LABELS C A U T I O N Do no t t urn o ff while o pera tin g. 8A (control power source switch) Ri sk of elec trica l sho c k. PN 408 31 Heat s ink n ot g[...]
-
Page 24
16 G8000 Series with Isolated Output Installation and Operation Manual FIGURE 6.3 – 150KV A UPS WARNING LABELS[...]
-
Page 25
17 G8000 Series with Isolated Output Installation and Operation Manual 7 W eight and Dimensions T able 7.1 lists the unit and shipping weight(s) for G8000 UPS models illustrated in Figures 7.1 – 7.2. T ABLE 7.1 G8000 UPS UNIT AND SHIPPING WEIGHT(S) Model Unit Shipping 100 kV A 2206 lb (1000 kg) 2296 lb (1041.4 kg) 150 kV A 3200 lb (1451.5 kg) 329[...]
-
Page 26
18 G8000 Series with Isolated Output Installation and Operation Manual FIGURE 7.2 - 150KV A UPS EXTERIOR DIMENSIONS (INCHES) TERMINAL BLOCKS “8A” SWITCH GROUND BUS[...]
-
Page 27
19 G8000 Series with Isolated Output Installation and Operation Manual 8 T ransporting The UPS may be packed in a crate for extra protection during transportation. Avoid impact or vibration against the UPS during transportation. DO NOT expose the UPS directly to water . W ARNING When transporting the UPS by crane, follow the SPECIFIED WORK PROCEDUR[...]
-
Page 28
20 G8000 Series with Isolated Output Installation and Operation Manual G8000 Series Installation Manual 21 8.1 Transporting By Crane Cables should have sufficient ratings and be of the same length. Make sure the suspension cables are hooked at eyebolts. See Fi gure 8.1. Keep the angle less than 60° b etween cables. Refer to Chapter 7 - Weight and [...]
-
Page 29
21 G8000 Series with Isolated Output Installation and Operation Manual 8.2 T ransporting By Forklift Refer to Chapter 7 - Weight and Dimensions. V erify forklift maximum load capacity and ensure that the forks are long enough to properly support the UPS. Insert the forks into the space shown in Figure 8.6. Spaces for the forks are provided undernea[...]
-
Page 30
22 G8000 Series with Isolated Output Installation and Operation Manual 9 Storage/Operating Environment Observe the following when storing the UPS. Store UPS indoors. Maximum storage time for the UPS between powered operation cycles is three years. If the UPS has been stored for a period exceeding 36 months, contact your factory authorized represnet[...]
-
Page 31
23 G8000 Series with Isolated Output Installation and Operation Manual W ARNING Whi le oper ati ng in the inv ert er mode , placi ng the inpu t break er in the “OF F” pos iti on wil l swi tch the UPS to the batt ery backu p mod e. The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the time that[...]
-
Page 32
24 G8000 Series with Isolated Output Installation and Operation Manual 9.2 Maintenance Precautions All internal maintenance sould be performed by factory authorized personnel. 1) T urn of f, lockout, and tagout ALL power sources before connecting the power wiring to the equipment or when performing maintenance. 2) Hardwire type UPS units are not eq[...]
-
Page 33
25 G8000 Series with Isolated Output Installation and Operation Manual CAUTION DO NOT di spose of the bat terie s i n a re. The batteries may explode. DO NOT op en or mutil ate t he ba tte rie s. Released electrolyte is harmful to the eyes and skin and could also be toxic. DANGER A bat ter y can prese nt a risk of elec tri cal shoc k and high sh[...]
-
Page 34
26 G8000 Series with Isolated Output Installation and Operation Manual 10 Installation W ARNING Keep the SPECIFIED CLEARANCE around the UPS. Inadequate space around the UPS makes it difcult to perform maintenance/inspections, lead to insufcient ventilation, and/or will cause malfunctions. See Figure 10.1 - UPS Clearance DO NOT tilt the UPS mo[...]
-
Page 35
27 G8000 Series with Isolated Output Installation and Operation Manual 10.1 Unpacking Unpack the UPS indoors on a paved oor . The UPS should be as close as possible to its nal storage location. Overhead traveling cranes should be used to unpack any G8000 Series UPS. If an overhead traveling crane is not available, allow enough space for forkl[...]
-
Page 36
28 G8000 Series with Isolated Output Installation and Operation Manual 10.3 Anchor Bolts Install the anchor bolts to secure the UPS on the oor . See Figure 10.2 for anchor bolt installation detail. Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base. See Figure 10.3 for the hole locations and [...]
-
Page 37
29 G8000 Series with Isolated Output Installation and Operation Manual 1 1 UPS Wiring Note: Always consult your local and NEC electrical codes for wiring, cabling, and circuit protection devices. requirements. Figure 1 1.1 illustrates the external wiring of the G8000 UPS. See corresponding section to each wiring term. Power cable connection at term[...]
-
Page 38
30 G8000 Series with Isolated Output Installation and Operation Manual 1 1.1 T erminal Blocks, T erminal Bus, and Power Cables Note: Always consult your site specic, local, state, and NEC electrical codes for wiring, cabling, and circuit protection device requirements. The terminal blocks for the 100/150 kV A UPS are shown in Figure 1 1.2. The t[...]
-
Page 39
31 G8000 Series with Isolated Output Installation and Operation Manual T ABLE 1 1.1 RECOMMENDED CRIMP TYPE COMPRESSION LUGS Wire Size Wire Strand Class Recommendation Crimp tool Required Burndy type Y35 or Y46 V endor Cat. No. Color Key Die Index 1/0 B I B Burndy Ilsco Burndy Y A25 CRA-1/OL Y A25-LB Pink Pink Black 12 / 348 12 / 348 13 2/0 B I B Bu[...]
-
Page 40
32 G8000 Series with Isolated Output Installation and Operation Manual Cable knockout plates are provided at the bottom of the 100 kV A UPS, and at the bottom and top of the 150 kV A UPS. The recommended hole locations are illustrated in Figure 1 1.4 - 1 1.6 The ve (5) holes must be punched during installation. The dashed rectangle indicates the[...]
-
Page 41
33 G8000 Series with Isolated Output Installation and Operation Manual 1 1.3 Grounding Wire W ARNING Be sure to ground the UPS as specied. Using the UPS without a proper ground will deteriorate the insulation, cause leakage of currents and electric shock.The resistance to ground should be less than or equal to 10 ohms. The 100/150 kV A earth gro[...]
-
Page 42
34 G8000 Series with Isolated Output Installation and Operation Manual 1 1.4 Control Wires The control wires terminal layouts at TB1 (terminal bus 1) are shown below in T able 1 1.4. T ABLE 1 1.4 EXTERNAL CONNECTIONS No. I/O Signal Name Operation 1 Output Low Battery Closed at Low Battery 2 Output Backup Operation Closed during Backup Operation 3 O[...]
-
Page 43
35 G8000 Series with Isolated Output Installation and Operation Manual The UPS battery cabinet and bypass breaker should be wired as shown below in Figure 1 1.8. FIGURE 1 1.8 - CONNECTION BETWEEN UPS, BA TTERY CABINET & BYP ASS BREAKER 10 1 1 12 13 14 15 16 17 18 19 20 21 22 TC TB1 Battery Cabinet Overheat B-Contact Bypass Breaker Ext. EPO (Cus[...]
-
Page 44
36 G8000 Series with Isolated Output Installation and Operation Manual 1 1.5 Grounding Conguration T h i s se ct io n de sc ri be s th e gr ou nd in g co n gu ra ti on t o b e u se d wi th t hi s UP S. A 2 AWG (or 38 mm 2 ) factory-installeded jumper cable is provided between the neutral terminal and ground bus in the UPS cabinet. The jumper [...]
-
Page 45
37 G8000 Series with Isolated Output Installation and Operation Manual 12 UPS Specications 12.1 General Specication T erms Specication Remarks Conforming Standard UL1778-2001 UL, cUL, IEC Ambient T emperature 32 – 104 ° F (0 – 40 ° C) Relative Humidity 30% – 90% Non-condensing Altitude < 3,280 ft (< 1,000 m) Contact T oshiba [...]
-
Page 46
38 G8000 Series with Isolated Output Installation and Operation Manual 12.2 Mechanical Specication (cont.) Rated Capacity 150kV A Cabinet Protection Conformity IEC298 IP20* Exterior Paint Sherwin Williams, HHT2-7055, 079 Beige T exture Panel Thickness FRONT : 1/16 in. (1.6 mm) BACK/SIDE/TOP: 3/64 in. (1.2 mm) BOTTOM: 1/8 in. (3.2 mm) Input/Outpu[...]
-
Page 47
39 G8000 Series with Isolated Output Installation and Operation Manual 12.3 Electrical Specication AC Input Rated Capacity 100 kV A (80 kW) 150 kV A (120 kW) Input V oltage 480 V ( +10% – -15% ), 3-Phase 3-Wire Input Frequency 60 Hz ±5% Input Power Factor 1.00 – 0.95 Lagging ( at 100% Load ) Current Harmonic Distortion 5% Maximum ( at 100% [...]
-
Page 48
40 G8000 Series with Isolated Output Installation and Operation Manual 13 Operator Interface T able 13.1 shows the functions of the operating buttons on the graphic display panel. A TTENTION Press an operating button for at least 0.5 seconds to change UPS modes. Press the reset button for for at least 5 seconds to reset the UPS. The UPS may not res[...]
-
Page 49
41 G8000 Series with Isolated Output Installation and Operation Manual 13.1 Key-Switch and Buttons The key-switch and operating buttons on the graphic display panel are shown in Figure 13.1. See the sections titled “Key-switch” and “Operating buttons” for each function. FIGURE 13.1 – GRAPHIC DISPLA Y P ANEL KEY -SWITCH/OPERA TING BUTTONS [...]
-
Page 50
42 G8000 Series with Isolated Output Installation and Operation Manual 13.2 LCD/LED Indicators FIGURE 13.2 – GRAPHIC DISPLA Y P ANEL LCD/LED INDICA TORS 23 1 1 21 20 19 18 17 16 15 14 13 22 24 25 12[...]
-
Page 51
43 G8000 Series with Isolated Output Installation and Operation Manual 13.3 LCD Indicators The operator can scroll through the following LCD display screens using the scroll buttons. T ABLE 13.1 - LCD DISPLA Y SCREENS Name Description Normal Display Displays operational status, operational guidance, and measured data. Fault Display Displays detaile[...]
-
Page 52
44 G8000 Series with Isolated Output Installation and Operation Manual 13.4 Normal Display The Normal Display screen indicates the UPS operational status and provides various screens: an operation guidance screens, mode screens and measured data screens. T able 13.2 shows these screens page by page and illustrates the UPS Normal Display operational[...]
-
Page 53
45 G8000 Series with Isolated Output Installation and Operation Manual T ABLE 13.2 - CONTINUED MEASUREMENT SCREENS O/P CURRENT (PEAK) Shows the peak output current peak (%) for each phase. U 50[%] V 50[%] W 50[%] Peak value of output current x 100 [%] RMS value for rated current x 1.41 AC INPUT Shows the AC Input V oltage (line-to-line) and frequen[...]
-
Page 54
46 G8000 Series with Isolated Output Installation and Operation Manual 13.5 Fault Display The Fault Display screen displays the fault records until they are reset. The W arning Display screen displays the warning records until they are reset. The fault records will remain in memory until the reset button is pressed and held for at least 5 seconds, [...]
-
Page 55
47 G8000 Series with Isolated Output Installation and Operation Manual 13.6 LCD Scroll Scroll through the LCD display screens (see Figure 10.4), in sequence, using the “SCROLL UP” and “SCROLL DOWN” buttons on the graphic display panel. • SCROLL UP - Moves back to the previous screen • SCROLL DOWN - Moves forward to the next screen T ABL[...]
-
Page 56
48 G8000 Series with Isolated Output Installation and Operation Manual 14 Operating the UPS This section describes the basic procedures to operate the UPS. Figure 1 1.1 shows the location and functions of the operating switches to operate the UPS. FIGURE 14.1 - EPO AND CONTROL POWER SUPPL Y OPERA TING SWITCHES W ARNING If the UPS produces smoke or [...]
-
Page 57
49 G8000 Series with Isolated Output Installation and Operation Manual 14.1 Operation T ypes The operation types are summarized below . T ABLE 1 1.1 OPERA TION TYPES Operation Description Startup Starting up and operating the UPS. Switch Power Supply Switching power supply source between UPS and Bypass. Stop Stop the inverter and chopper/charger . [...]
-
Page 58
50 G8000 Series with Isolated Output Installation and Operation Manual SYSTEM INITIALIZE BATTERIES AC SWITCH UPS BYPASS DISCHARGE FLO AT CHAR GE EQUAL CHARGE 㨪 AC INPUT ` CONVERTE R ` INVERTER 㨪 AC OUTPUT BYPASS INPUT 㨪 14.3 Startup Procedures The procedure to start the UPS is shown in Steps 1-5. STEP 1 T urn on the control[...]
-
Page 59
51 G8000 Series with Isolated Output Installation and Operation Manual Step 4-5 continues the procedure to start the UPS. STEP 4 T urn on the DC Input Breaker (72B) on the external battery cabinet. BA TTERIES LED is “ON”. STEP 5 *Press the “UPS” button for at least 0.5 seconds.This completes UPS startup procedure BYP ASS LED is “OFF”. U[...]
-
Page 60
52 G8000 Series with Isolated Output Installation and Operation Manual 14.4 Switch Power Supply (UPS→Bypass) The procedure to transfer between the UPS supply and the bypass supply is shown in Steps 1-3 STEP 1 Check AC INPUT LED and BYP ASS LED are on to make sure power is being delivered to the UPS. STEP 2 Press the “BYP ASS” button for at le[...]
-
Page 61
53 G8000 Series with Isolated Output Installation and Operation Manual 14.5 Stop The procedure to stop the UPS is shown in Steps 1-3. STEP 1 T ransfer to Bypass supply as described in Switch Power Supply . UPS LED is “OFF”. BYP ASS LED is “ON”. STEP 2 T urn off the DC Input Breaker (72B) on the external battery cabinet, and, press the G8000[...]
-
Page 62
54 G8000 Series with Isolated Output Installation and Operation Manual 14.6 Complete Shutdown The procedure to turn off the control power and shut down the UPS completely is shown in Steps 1-6. STEP 1 T ransfer to Bypass supply as described in Switch Power Supply . UPS LED is “OFF”. BYP ASS LED is “ON”. STEP 2 T urn off the DC Input Breaker[...]
-
Page 63
55 G8000 Series with Isolated Output Installation and Operation Manual 14.7 Changing Between Float Charge and Equalize Charge The procedure to change the recharge mode between oat charge and equalize charge is shown in Steps 1-3. See the Note below for an explanation of Flaot and Equalize charge modes. STEP 1 Make sure that the FLOA T CHARGE LED[...]
-
Page 64
56 G8000 Series with Isolated Output Installation and Operation Manual 14.8 Changing to Float Charge from Protection Charge (If applicable) The manual procedure to change from protection charge to oat charge is shown in Step 1-3.This operation applies to batteries after they have experienced over temperature condition. See the Note below for an [...]
-
Page 65
57 G8000 Series with Isolated Output Installation and Operation Manual 14.9 Emergency Power Off (EPO) Press the EPO switch for immediate shutdown of all power through the UPS. The signal from the EPO is processed as a “hard fault” by the UPS and results in gate-blocks on the transistors and opens all the internal contactors. T o Reset the UPS a[...]
-
Page 66
58 G8000 Series with Isolated Output Installation and Operation Manual 15.2 Faults and W arnings Data Screen This screen appears when a trip error is detected. Up to 10 screens of fault data can be displayed. Figure 15.1 and T able 15.2 show a sample screen and describe the data shown in the screen. F AUL TS & WARNINGS 1 UPS OVERLOAD 09-09-06 0[...]
-
Page 67
59 G8000 Series with Isolated Output Installation and Operation Manual 15.3 LCD Fault & W arning Displays When a fault occurs, a screen is shown as in Figure 15.2. When a warning occurs, a screen is shown as in Figure 15.3. Select the desired fault or warning data to be displayed using the scroll buttons. BYP ASS F AUL T STOP F AUL TS & WAR[...]
-
Page 68
60 G8000 Series with Isolated Output Installation and Operation Manual 15.4 Fault Messages Figure 15.4 show the corresponding circuit locations for fault detection codes. T ables 15.3 through 15.7 gives details for the fault and warning messages referred to in section 15.3. The “item” code assoiated with each fault or warning message may be use[...]
-
Page 69
61 G8000 Series with Isolated Output Installation and Operation Manual T ABLE 15.5 - W ARNING - 2 (STOP AND REST ART) Item LCD Message Indication Description 27 I AC O/P UV AC output voltage is low . 30U UNIT F AUL T IGBT Stack Failure. 45 DC OV Over-voltage in DC circuit. 49 AC O/P OL Output overload 51 I INV . OC Inverter over-current. 59 I AC O/[...]
-
Page 70
62 G8000 Series with Isolated Output Installation and Operation Manual 15.5 LCD Scroll (w/ faults or warnings) This section describes how to scroll through the LCD screens when a fault has occurred (when Fault Data screens exist). Figure 15.5 shows the locations of the buttons to scroll the LCD screens. See T able 15.8 for detail of the scroll butt[...]
-
Page 71
63 G8000 Series with Isolated Output Installation and Operation Manual 15.6 Restoring UPS Operation The procedure to restore UPS operation is shown in Steps 1-2. The example shows the UPS restored after a trip fault occurred on inverter over current with the message “INV . OC.” STEP 1 Check the LCD screen. Also check other fault data screens wi[...]
-
Page 72
64 G8000 Series with Isolated Output Installation and Operation Manual[...]
-
Page 73
[...]
-
Page 74
INDUSTRIAL DIVISION 13131 West Little Y ork Road, Houston, T exas 77041 T el (713) 466-0277 Fax. (713) 466-8773 US (877) 867-8773 Canada (800) 872-2192 Mexico 01/800/527-1204 www .T oshiba.com/ind Printed in the U.S.A.[...]