Go to page of
Similar user manuals
-
Furnace
Trane DX1D120A9601A
40 pages 1.37 mb -
Furnace
Trane TUH2D120A9V5VA
30 pages 1.74 mb -
Furnace
Trane UD1B100A9H31B
24 pages 0.71 mb -
Furnace
Trane TUH2C100A9V5VA
30 pages 1.74 mb -
Furnace
Trane TUD2D120A9V5VB
26 pages 1.36 mb -
Furnace
Trane 100
16 pages 0.67 mb -
Furnace
Trane TUD2C100A9V5VB
26 pages 1.36 mb -
Furnace
Trane DX1B060A9361A
40 pages 1.37 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Trane DD1D120A9H51B, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Trane DD1D120A9H51B one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Trane DD1D120A9H51B. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Trane DD1D120A9H51B should contain:
- informations concerning technical data of Trane DD1D120A9H51B
- name of the manufacturer and a year of construction of the Trane DD1D120A9H51B item
- rules of operation, control and maintenance of the Trane DD1D120A9H51B item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Trane DD1D120A9H51B alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Trane DD1D120A9H51B, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Trane service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Trane DD1D120A9H51B.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Trane DD1D120A9H51B item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
*Horizontal Conversion for these furnaces may be left or right side rotation. *UD1A040A9H21B *UD1B060A9H31B *UD1B080A9H31B *UD1C080A9H41B High Efficiency Single Stage Upflow/ Horizontal and Downflow/ Horizontal Gas-Fired Furnaces, “Fan Assisted Combustion System” ALL phases of this installation must comply with NA TIONAL, ST A TE AND LOCAL CODE[...]
-
Page 2
© 2008 Trane All Rights Reserved 18-CD21D1-5 Installer’ s Guide The following safety practices and precautions must be followed during the installation, servicing, and opera- tion of this furnace. 1. Use only with the type of gas approved for this fur- nace. Refer to the furnace rating plate. 2. Install this furnace only in a location and positi[...]
-
Page 3
Installer’ s Guide 18-CD21D1-5 3 Installation Instructions 3 General Installation Instructions 4 Location and Clearances 4 Outline Drawing 5 Upflow Installation 7 Downflow Installation 7 Air For Combustion and Ventilation 8 Duct Connections 1 0 Return Air Filters 1 1 Typical Upflow Return Air Filter Installations 1 1 Alternate Upflow Filter Clip [...]
-
Page 4
4 18-CD21D1-5 Installer’ s Guide LOCA TION AND CLEARANCES The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements: 1. Is the location selected as near the chimney or vent and as centralized for heat distributio[...]
-
Page 5
Installer’ s Guide 18-CD21D1-5 5 From Dwg. 21C341699 Sh. 1 Rev. 4 *UD1-H OUT LINE DRA WING (ALL DIMENSIONS ARE IN INCHES)[...]
-
Page 6
6 18-CD21D1-5 Installer’ s Guide From Dwg. 21C341700 Sh. 1 Rev. 0 *DD1-HF OUT LINE DRA WING (ALL DIMENSIONS ARE IN INCHES)[...]
-
Page 7
Installer’ s Guide 18-CD21D1-5 7 UPFLOW INST ALLA TION Standoffs and screws (See Figure 1 on page 6) are in- cluded with the cased coils for attachment to the fur- nace. There are clearance alignment holes near the bot- tom of the coil wrapper and drill screws are used to en- gage the furnace top flange. The standoff is inserted into the cabinet [...]
-
Page 8
8 18-CD21D1-5 Installer’ s Guide If the furnace is suspended using perforated steel strap (plumber’s strap), it must be supported at all four cor- ners and in the middle at the front of the furnace. The forward most screw on the side of the furnace may be used to connect the strapping (See Figure 6). Line contact is only permissible between lin[...]
-
Page 9
Installer’ s Guide 18-CD21D1-5 9 1. All air from inside the building as in Figure 9: The confined space shall be provided with two perma- nent openings communicating directly with an addi- tional room(s) of sufficient volume so that the com- bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utiliza-[...]
-
Page 10
10 18-CD21D1-5 Installer’ s Guide DUCT CONNECTIONS Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or which- ever is applicable. Check on controls to make certain they are correct for the elec[...]
-
Page 11
Installer’ s Guide 18-CD21D1-5 11 When the upflow furnace is installed in the horizon- tal right or left application and a return duct is at- tached to the top side as shown in Figure 1 1, re- move the filter from the furnace and install in a re- mote location. Do not install the filter in the return duct directly above the furnace in horizontal [...]
-
Page 12
12 18-CD21D1-5 Installer’ s Guide UPFLO W FURNA CE RETURN AIR FIL TERS CABINET WIDTH QTY* CABINET BO TT OM FIL TER CABINET SIDE FIL TER 14-1/2" 1 14" X 25" X 1" 17-1/2" X 25" X 1" 17-1/2" 1 17" X 25" X 1" 17-1/2" X 25" X 1" 21" 1 20" X 25" X 1" 17-1/2" [...]
-
Page 13
Installer’ s Guide 18-CD21D1-5 13 Bottom P anel Filter Rack Furnace Cabinet Side Filter Rack Retaining Screw/Pin Engagement Hole For Bottom Return Filter Rack Installation With Filter Rack Furnace Cabinet Side Filter Rack Retaining Screw/Pin Engagement Hole For Bottom Return Filter Rack Installation With BLOWER DECK Filter Rack Assembly Furnace B[...]
-
Page 14
14 18-CD21D1-5 Installer’ s Guide T ABLE 5 T ABLE 6 CABINET WIDTH RETURN DUCT WIDTH FIL TER A CCESS OPENING - DIMENSION "A" FIL TER A CCESS OPENING - DIMENSION "B" 14-1/2" 13-1/4" 12" 14" 17-1/2" 16-1/4" 15" 14" 21" 19-3/4" 19-1/2" 14" 24-1/2" 23-1/4" 22&quo[...]
-
Page 15
Installer’ s Guide 18-CD21D1-5 15 NOTE: The following section does not apply if BA YVENT800B (Masonry Chimney Vent Kit) is used. All instructions with the kit must be followed. T ABLE 7 MASONR Y CHIMNEY VENTING Tile Lined Chimney Chimne y Lining T ype Fur nace Internal External “B” V ent Fle xible Metal Liner Single F an Assist No No Y es *Y [...]
-
Page 16
16 18-CD21D1-5 Installer’ s Guide T ABLE 8 π π π π π (D*) 2 4 = X 7 8. Where long periods of airflow are desired for com- fort, use long fan cycles instead of continuous air- flow. 9. Apply other good venting practices as stated in the venting section of the National Fuel Gas Code ANSI Z223.1 “latest edition”. 10. Vent connectors serving[...]
-
Page 17
Installer’ s Guide 18-CD21D1-5 17 SEE NO TE 6 F rom Dwg. B341437 Rev . 1 FURNACE TWIN SEE NO TE 7 B/C B/C T O 115 V 1 PH., 60 HZ., POWER SUPPL Y PER LOCAL CODES HUM SEE NO TE 5 EAC SEE NO TE 5 FIELD WIRING DIAGRAM FOR 1 ST AGE FURNA CE 1 ST AGE HEA TING USING A 1 ST AGE HEA TING THERMOST A T NO COOLING From Dwg. 21B341437 P01 OUTDOOR UNIT (NO TRA[...]
-
Page 18
18 18-CD21D1-5 Installer’ s Guide TWINNING These furnaces may be twinned. Twinning requires that two furnaces with the same configuration, capacity, and airflow must be used. They shall have common returns with equal pressure drops or ducts with equivalent lengths and sizes. See Field Wiring Diagrams below for proper hookup. TWIN TWIN R1 R1 TWINN[...]
-
Page 19
Installer’ s Guide 18-CD21D1-5 19 ▲ WARNING ! FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could re- sult in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commer- cially available soap solution made specifically for the detection of leaks to check all connections. A fire o[...]
-
Page 20
20 18-CD21D1-5 Installer’ s Guide When the thermostat is satisfied, R and W thermostat contacts open, the gas valve will close, the flames will extinguish, and the induced draft blower will be de-en- ergized. The indoor blower motor will continue to run for the fan off period (fixed at 100 seconds), then will be de-energized by the control module[...]
-
Page 21
Installer’ s Guide 18-CD21D1-5 21 ▲ CAUTION ! Replace and/ or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, ex- plosion, or property damage. For LP gases, the final manifold pressure setting shall be[...]
-
Page 22
22 18-CD21D1-5 Installer’ s Guide TABLE 13 Orifice T wist Drill Size I f Installed At Sea Level AL TITUDE ABO VE SEA LEVEL and Orifice Re quired At Other E lev ations 2000 3000 4000 5000 6000 7000 80 00 9000 10000 42 43 44 45 46 47 42 44 45 46 47 48 43 44 45 47 47 48 43 44 45 47 47 49 43 45 46 47 48 49 44 45 47 48 48 49 44 46 47 48 49 50 45 47 48[...]
-
Page 23
Installer’ s Guide 18-CD21D1-5 23 INSTRUCTIONS TO THE OWNERS In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the burner compartment (See Figure 24). Also turn off electrical power to the furnace and contact the service agency designated by y[...]
-
Page 24
24 18-CD21D1-5 Installer’ s Guide File Number 18-CD21D1-5 Supersedes 18-CD21D1-4 Date 05/08 INTEGRATED FURNACE CONTROL ERR OR FLASH CODES Flashing Slow --- Normal - No call f or Heat Flashing F ast --- Nor mal - Call f or Heat Continuous ON --- Replace IFC Continuous OFF --- Chec k P ow er 2 Flashes --- System Loc k out (Retries or Recycles e xce[...]