Go to page of
Similar user manuals
-
Air Conditioner
York YWC
12 pages 0.79 mb -
Air Conditioner
York DJ 240
40 pages 2.57 mb -
Air Conditioner
York YPHBC
16 pages 0.89 mb -
Air Conditioner
York AFFINITY 360101-XTG-A-0108
24 pages 0.59 mb -
Air Conditioner
York 035-09319
4 pages 0.17 mb -
Air Conditioner
York AFFINITY BHP024
28 pages 2.2 mb -
Air Conditioner
York DHG 240
2 pages 0.08 mb -
Air Conditioner
York TCGF60
22 pages 0.4 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of York ECO R-22, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of York ECO R-22 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of York ECO R-22. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of York ECO R-22 should contain:
- informations concerning technical data of York ECO R-22
- name of the manufacturer and a year of construction of the York ECO R-22 item
- rules of operation, control and maintenance of the York ECO R-22 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of York ECO R-22 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of York ECO R-22, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the York service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of York ECO R-22.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the York ECO R-22 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
Packaged Roof top Air Conditioning Unit s 50 THROUGH 100 T ONS R-407C and R-22 400V AC/3PH/50Hz FORM 100.50-EG3 (802) 00566VIP TM Meet s ASHRAE 90.1 - 2001 Efficiency Requirement s ASHRAE 90.1 COMPLIANT[...]
-
Page 2
YORK INTERNA TIONAL 2 Introduction The eco 2 packaged rooftop – Designed to meet the de- mands of the market for today and tomorrow . Better Economy ... Reduce Energy Consumption • High-efficiency eco 2 rooftop units are optimized for both R-22 and HFC-407C refrigerant, and are the first environmentally responsible rooftop unit s that meet the [...]
-
Page 3
FORM 100.50-EG3 (802) 3 YORK INTERNA TIONAL TABLE OF CONTENTS Introduction ............................................................. 2 Features and Benefit s ............................................ 4 Nomenclature ......................................................... 7 Application Data ...................................................[...]
-
Page 4
YORK INTERNA TIONAL 4 Features and Benefits QUALITY ROOFT OP UNIT DESIGNED T O TODA Y’S ST ANDARDS Ecological and Economical Design • First packaged RTU that meet s ASHRAE 90.1-2001 with both R-22 and R-407C Refrigerants. • Cooling and Heating – Superior operating perfor- mance provides lower operating costs. Smaller steps of cooling capaci[...]
-
Page 5
FORM 100.50-EG3 (802) 5 YORK INTERNA TIONAL Reliable Cooling and Heating T echnology • Reliable, efficient, trouble-free operation is the true measure of a packaged roof top’s value. That’ s why YORK eco 2 Packaged Rooftop Air Conditioners use established scroll-compressor technology to deliver dependable, economical performance in a wide ran[...]
-
Page 6
YORK INTERNA TIONAL 6 Features and Benefits (continued) • Fan Spring Isolators – One-inch spring isolation is used to prevent vibration transmission from the rooftop unit’ s supply fan to the building. T wo-inch spring isolation is also available. • Harsh Environment s – A variety of coil coating and materials are available as well as hai[...]
-
Page 7
FORM 100.50-EG3 (802) 7 YORK INTERNA TIONAL 1 2 3 4 5 6 7 8 9 10 1 1 12 13 14 15 16 BASE PRODUCT TYPE NOMINAL CAP ACITY APPLICA TION REFRIGERANT VOL T AGE DUCT LOCA TIONS DESIGN SPECIAL Y 0 5 0 B 45 B A P0 5 5 C L X 06 0 RS A0 6 5 B 07 0 R L0 7 5 C S 08 0 N 08 5 G 09 0 E 09 5 C V F NOMENCLA TURE BASIC MODEL NUMBER : YORK : Packaged Rooftop : Air-Co[...]
-
Page 8
YORK INTERNA TIONAL 8 Application Data LOCA TION Of the many factors that can affect the acoustical char- acteristics of a rooftop inst allation, one of the most im- portant is the unit location. Ideally , the rooftop unit should be installed away from sound-sensitive areas, such as conference rooms, auditoriums and executive offices. Possible loca[...]
-
Page 9
FORM 100.50-EG3 (802) 9 YORK INTERNA TIONAL For V A V applications, the YORK eco 2 unit uses a VFD to modulate fan speed and maintain a constant duct static pressure. VFDs of fer superior control over the operation of the unit at part load, and of fer the addi- tional benefits of quieter and more ef ficient operation when compared to IGV . HARSH EN[...]
-
Page 10
YORK INTERNA TIONAL 10 The curb should be located according to the location recommendations above, and properly sealed to pre- vent moisture and air leakage into and out of the duct system. Flexible collars should be used when connect- ing the duct work to prevent unit noise transmission and vibration into the building. Duct work should be supporte[...]
-
Page 11
FORM 100.50-EG3 (802) 11 YORK INTERNA TIONAL 6. Required total and sensible capacities are 991 mbh and 681 mbh, respectively . The tot al cap acity is 82.6 tons, therefore a model YP AL085 is selected. Use the Cooling Performance Data in T able 9. Locate the table with the correct ambient air temperature. Next, trace the 80°F entering air dry bulb[...]
-
Page 12
YORK INTERNA TIONAL 12 Physical Data T ABLE 1 – PHYSICAL DA T A – MODELS 50-70 MODEL SIZE 050 055 060 065 070 GENERAL DA T A Length (cm) w/o Hood 874 874 874 874 1 140 Width (cm) w/o Hood 234 234 234 234 234 Height (cm) 208 208 208 208 208 Operating Weights (Kg) (Base Unit, No Options) Cooling Only (Rigging & R407C) 3701 3797 3934 4029 5799[...]
-
Page 13
FORM 100.50-EG3 (802) 13 YORK INTERNA TIONAL MODEL SIZE 050 055 060 065 070 Evaporator Coil Size (Square Meters) 5 5 5 5 5 Number of Rows/Fins per cm 1 1 1 1 1 T ube Diameter (cm) /Surface 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced Condenser Coil (Aluminum Fins) Size (Square Meters) 1 1 1 1 1 1 1 1 182 Number of Rows/Fins[...]
-
Page 14
YORK INTERNA TIONAL 14 Physical Data (continued) T ABLE 1 – PHYSICAL DA T A – MODELS 75-95 MODEL SIZE 075 080 085 090 095 GENERAL DA T A Length (cm) w/o Hood 1 140 1 140 1 140 1240 1240 Width (cm) w/o Hood 234 234 234 234 234 Height (cm) 208 208 208 234 234 Operating Weights (Kg) (Base Unit, No Options) Cooling Only (Rigging & R407C) 5897 5[...]
-
Page 15
FORM 100.50-EG3 (802) 15 YORK INTERNA TIONAL MODEL SIZE 075 080 085 090 095 Evaporator Coil Size (Square Meters) 5 5 5 5 5 Number of Rows/Fins per cm 1 1 1 1 1 T ube Diameter (cm) /Surface 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced Condenser Coil (Aluminum Fins) Size (Square Meters) 17 17 17 17 17 Number of Rows/Fins per [...]
-
Page 16
YORK INTERNA TIONAL 16 Cooling Performance Data – 50 T on Model T ABLE 2 – COOLING PERFORMANCE DA T A* – 50 TON MODEL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 29.4°C AIR ON CONDENSER COI[...]
-
Page 17
FORM 100.50-EG3 (802) 17 YORK INTERNA TIONAL T ABLE 2 – COOLING PERFORMANCE DA T A* – 50 TON MODEL (CONT’D) 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP AC[...]
-
Page 18
YORK INTERNA TIONAL 18 T ABLE 3 – COOLING PERFORMANCE DA T A* – 55 TON MODEL Cooling Performance Data – 55 T on Model * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 29.4°C AIR ON CONDENSER COI[...]
-
Page 19
FORM 100.50-EG3 (802) 19 YORK INTERNA TIONAL T ABLE 3 – COOLING PERFORMANCE DA T A* – 55 TON MODEL (CONT’D) 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP AC[...]
-
Page 20
YORK INTERNA TIONAL 20 T ABLE 4 – COOLING PERFORMANCE DA T A* – 60 TON MODEL Cooling Performance Data – 60 T on Model 29.4°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity [...]
-
Page 21
FORM 100.50-EG3 (802) 21 YORK INTERNA TIONAL T ABLE 4 – COOLING PERFORMANCE DA T A* – 60 TON MODEL (CONT’D) 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP AC[...]
-
Page 22
YORK INTERNA TIONAL 22 T ABLE 5 – COOLING PERFORMANCE DA T A* – 65 TON MODEL Cooling Performance Data – 65 T on Model 29.4°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity [...]
-
Page 23
FORM 100.50-EG3 (802) 23 YORK INTERNA TIONAL T ABLE 5 – COOLING PERFORMANCE DA T A* – 65 TON MODEL (CONT’D) 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP AC[...]
-
Page 24
YORK INTERNA TIONAL 24 T ABLE 6 – COOLING PERFORMANCE DA T A* – 70 TON MODEL Cooling Performance Data – 70 T on Model 29.4°C AIR ON CONDENSER COIL 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . * Rated performance is at sea level. Cooling capacities are gross cooling capacity [...]
-
Page 25
FORM 100.50-EG3 (802) 25 YORK INTERNA TIONAL T ABLE 6 – COOLING PERFORMANCE DA T A* – 70 TON MODEL (CONT’D) 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP AC[...]
-
Page 26
YORK INTERNA TIONAL 26 T ABLE 7 – COOLING PERFORMANCE DA T A* – 75 TON MODEL Cooling Performance Data – 75 T on Model * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 29.4°C AIR ON CONDENSER COI[...]
-
Page 27
FORM 100.50-EG3 (802) 27 YORK INTERNA TIONAL T ABLE 7 – COOLING PERFORMANCE DA T A* – 75 TON MODEL (CONT’D) 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP AC[...]
-
Page 28
YORK INTERNA TIONAL 28 Cooling Performance Data – 80 T on Model T ABLE 8 – COOLING PERFORMANCE DA T A* – 80 TON MODEL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 29.4°C AIR ON CONDENSER COI[...]
-
Page 29
FORM 100.50-EG3 (802) 29 YORK INTERNA TIONAL T ABLE 8 – COOLING PERFORMANCE DA T A* – 80 TON MODEL 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP ACITY (kW) A [...]
-
Page 30
YORK INTERNA TIONAL 30 Cooling Performance Data – 85 T on Model T ABLE 9 – COOLING PERFORMANCE DA T A* – 85 TON MODEL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 29.4°C AIR ON CONDENSER COI[...]
-
Page 31
FORM 100.50-EG3 (802) 31 YORK INTERNA TIONAL T ABLE 9 – COOLING PERFORMANCE DA T A* – 85 TON MODEL 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP ACITY (kW) A [...]
-
Page 32
YORK INTERNA TIONAL 32 T ABLE 10 – COOLING PERFORMANCE DA T A* – 90 TON MODEL Cooling Performance Data – 90 T on Model * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 29.4°C AIR ON CONDENSER CO[...]
-
Page 33
FORM 100.50-EG3 (802) 33 YORK INTERNA TIONAL T ABLE 10 – COOLING PERFORMANCE DA T A* – 90 TON MODEL (CONT’D) 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP A[...]
-
Page 34
YORK INTERNA TIONAL 34 T ABLE 1 1 – COOLING PERFORMANCE DA T A* – 95 TON MODEL Cooling Performance Data – 95 T on Model * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 35°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 29.4°C AIR ON CONDENSER C[...]
-
Page 35
FORM 100.50-EG3 (802) 35 YORK INTERNA TIONAL T ABLE 1 1 – COOLING PERFORMANCE DA T A* – 95 TON MODEL (CONT’D) 46.1°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . 40.5°C AIR ON CONDENSER COIL * Rated performance is at sea level. Cooling capacities are gross cooling capacity . CAP [...]
-
Page 36
YORK INTERNA TIONAL 36 Heating Performance Data – Gas/Electric Heat GAS HEA TING ELECTRIC HEA TING T ABLE 13 – ELECTRIC HEA T PERFORMANCE DA T A UNIT SIZE (kW) NOMINAL HEA T CAP ACITY AIR FLOW MIN MAX TEMP RISE HEA TER SIZE (kW) (kW ) ( m3/hr) (°C) 40 40 40037 13,592 16 50-65 T on 80 80 80075 16,990 25 108 108 108101 20,388 28 150 150 150140 2[...]
-
Page 37
FORM 100.50-EG3 (802) 37 YORK INTERNA TIONAL Supply Fan Data T ABLE 14 – 50 THROUGH 65 TON SUPPL Y F AN DA T A (CONT’D) TOT AL ST A TIC PRESSURE (Pascals of water column) m3/hr 871 995 1 120 1244 1369 STD. AIR kW RPM kW RPM kW RPM kW RPM kW RPM 16990 20388 23786 10.4 802 27184 1 1.8 789 13.5 851 15.2 908 29733 12.9 779 14.5 836 16.3 892 18.3 94[...]
-
Page 38
YORK INTERNA TIONAL 38 Supply Fan Data (continued) T ABLE 15 – 70 THROUGH 85 TON SUPPL Y F AN DA T A TOT AL ST A TIC PRESSURE (Pascals of water column) m3/hr 245 373 498 622 747 STD. AIR kW RPM kW RPM kW RPM kW RPM kW RPM 27184 4.2 397 5.5 467 30582 5.3 41 1 6.7 478 8.2 538 9.8 596 1 1.4 646 33980 6.4 425 7.9 488 9.5 547 1 1.2 599 13.0 648 37378 [...]
-
Page 39
FORM 100.50-EG3 (802) 39 YORK INTERNA TIONAL T ABLE 16 – 90 THROUGH 95 TON SUPPL Y F AN DA T A (CONT’D) TOT AL ST A TIC PRESSURE (Pascals of water column) m3/hr 871 995 1 120 1244 1369 STD. AIR kW RPM kW RPM kW RPM kW RPM kW RPM 30582 15.4 739 17.6 795 33980 16.6 717 18.7 776 22.2 841 24.5 899 37378 16.8 695 19.8 756 23.3 821 26.7 880 29.6 930 [...]
-
Page 40
YORK INTERNA TIONAL 40 Component S tatic Pressure Drops T ABLE 17 – COMPONENT ST A TIC PRESSURE DROPS NOTES: * Includes 2" pleated filters. ** Power exhaust pressure drops are for sizing supply fan. EV APORA TOR RETURN AIR OPENING FIL TERS SIZE AIR FLOW COILS 50.1 cm 50.1 cm 50.1 cm 50.1 cm m3/hr STD. AIR WE T DR Y BOTTOM FRONT SIDE THROWA W[...]
-
Page 41
FORM 100.50-EG3 (802) 41 YORK INTERNA TIONAL FIL TERS ECONOMIZER ECONOMIZER RIGID FIL TER RACK, 30.5 cm 30.5 cm FRESH AIR MANUAL OR 0-100% POWERED NO MEDIA RIGID, 65%* RIGID, 95%* OPENINGS 2-POSITION MODULA TION EXHAUST 22.28 52.86 73.78 18.15 6.66 28.17 2.47 29.1 1 68.66 93.86 26.65 9.59 38.99 3.56 36.51 85.68 1 15.12 36.90 13.05 51.33 4.85 44.41 [...]
-
Page 42
YORK INTERNA TIONAL 42 Component S tatic Pressure Drops (continued) NOTES: * Includes 2" pleated filters. ** Power exhaust pressure drops are for sizing supply fan. T ABLE 17 – COMPONENT ST A TIC PRESSURE DROPS EV APORA TOR RETURN AIR OPENING FIL TERS SIZE AIR FLOW COILS 50.1 cm 50.1 cm 50.1 cm 50.1 cm m3/hr STD. AIR W ET DR Y BOTT OM FRONT [...]
-
Page 43
FORM 100.50-EG3 (802) 43 YORK INTERNA TIONAL FIL TERS ECONOMIZER ECONOMIZER RIGID FIL TER RACK, 30.5 cm 30.5 cm FRESH AIR MANUAL OR 0-100% POWERED NO MEDIA RIGID, 65%* RIGID, 95%* OPENINGS 2-POSITION MODULA TION EXHAUST** 30.29 71.37 97.27 26.65 17.04 37.78 3.00 36.00 84.53 1 13.68 34.17 21.57 46.61 3.80 42.02 98.35 130.74 42.68 26.63 56.24 4.69 48[...]
-
Page 44
YORK INTERNA TIONAL 44 T ABLE 18 – GAS HEA T PRESSURE DROPS SIZE (mbh) SIZE AIR FLOW 375 750 1125 m3/hr STD. AIR 16990 29.86 62.21 – 20388 37.33 74.65 – 23786 42.30 87.09 – 27184 49.77 99.54 – 50 29733 54.74 109.49 – 30582 54.74 1 1 1.98 – 33980 62.21 124.42 – 37378 67.19 136.86 – 38228 69.68 139.35 – 20388 37.33 74.65 – 23786[...]
-
Page 45
FORM 100.50-EG3 (802) 45 YORK INTERNA TIONAL 00566VIP[...]
-
Page 46
YORK INTERNA TIONAL 46 Electric Heat Pressure Drops SIZE (kW) 4 0 80 108 150 250 VOL T/PHASE/HZ 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 SIZE AIR FLOW m3/hr STD. AIR 16990 3.50 5.09 5.09 20388 5.04 7.34 7.34 23786 6.87 9.99 9.99 27184 8.97 13.04 13.04 50 29733 10.73 15.60 15.60 30582 1 1.35 16.51 16.51 33980 14.01 20.38 20.38 37378 16.95 24.66 [...]
-
Page 47
FORM 100.50-EG3 (802) 47 YORK INTERNA TIONAL T ABLE 19 – ELECTRIC HEA T PRESSURE DROPS (CONT’D) SIZE (kW) 4 0 80 108 150 250 VOL T/PHASE/HZ 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 SIZE AIR FLOW m3/hr STD. AIR 27184 10.95 10.95 21.22 30582 13.86 13.86 26.86 33980 17.12 17.12 33.16 37378 20.71 20.71 40.12 75 40776 24.65 24.65 47.75 44174 28.[...]
-
Page 48
YORK INTERNA TIONAL 48 TOT AL ST A TIC PRESSURE (Pascals of water column) m3/hr 31 1 373 435 478 STD. AIR kW RPM kW RPM kW RPM kW RPM 13592 2.6 810 3.0 873 3.4 933 3.9 992 20388 5.6 924 6.1 976 6.6 1025 7.2 1072 27184 1.4 1055 1 1.2 1 104 12.0 1 150 12.7 1 196 33980 TOT AL ST A TIC PRESSURE (Pascals of water column) m3/hr 62 124 187 249 STD. AIR kW[...]
-
Page 49
FORM 100.50-EG3 (802) 49 YORK INTERNA TIONAL T ABLE 22 – 90 THROUGH 95 TON EXHAUST F AN DA T A (CONT’D) TOT AL ST A TIC PRESSURE (Pascals of water column) m3/hr 31 1 373 435 478 STD. AIR kW RPM kW RPM kW RPM kW RPM 23786 4.3 728 4.8 776 5.3 821 5.8 865 30582 7.8 800 7.8 844 8.3 886 8.9 925 37378 1.9 875 1 1.7 919 12.5 959 13.3 997 44174 15.6 95[...]
-
Page 50
YORK INTERNA TIONAL 50 Component S tatic Pressure Drops T ABLE 23 – COMPONENT ST A TIC PRESSURE DROPS (P ASCALS OF W A TER COLUMN) 2-POSITION OR VFD MODULA TING EXHAUST SIZE AIR FLOW POWERED EXHAUST (CONTROL DAMPER) m3/hr STD. AIR (BAROMETRIC DAMPER) 13592 4.98 4.98 16990 7.47 7.47 20388 9.95 9.95 23786 12.44 12.44 50 27184 17.42 17.42 30582 19.9[...]
-
Page 51
FORM 100.50-EG3 (802) 51 YORK INTERNA TIONAL T ABLE 23 – COMPONENT ST A TIC PRESSURE DROPS (P ASCALS OF W A TER COLUMN) (CONT’D) 2-POSITION OR VFD MODULA TING EXHAUST SIZE AIR FLOW POWERED EXHAUST (CONTROL DAMPER) m3/hr STD. AIR (BAROMETRIC DAMPER) 20388 24.88 24.88 23786 34.84 34.84 27184 44.79 44.79 75 30582 59.72 59.72 33980 74.65 74.65 3737[...]
-
Page 52
YORK INTERNA TIONAL 52 Electrical Data ELECTRICAL SER VICE SIZING In order to use the electrical service required for the cool- ing only eco 2 rooftop, use the appropriate calculations listed below from U.L. 1995. Based on the configuration of the rooftop, the calculations will yield dif ferent MCA (minimum circuit ampacity), and MOP (maximum overc[...]
-
Page 53
FORM 100.50-EG3 (802) 53 YORK INTERNA TIONAL T ABLE 25 – SUPPL Y AND EXHAUST F AN MOTOR (ODP OR TEFC) T ABLE 27 – CONTROL TRANSFORMER T ABLE 26 – CONDENSER F AN MOT ORS / TOT AL T ABLE 28 – ELECTRIC HEA T NOMINAL VOL T AGE MOTOR 400/3/50 HP FLA 5 8.5 7.5 12.7 10 15.6 15 25.0 20 32.0 25 42.0 30 46.0 40 62.0 50 74.0 60 91.0 NOMINAL VOL T AGE [...]
-
Page 54
YORK INTERNA TIONAL 54 Controls CONTROL SEQUENCES COMMON T O ALL UNITS GENERAL The control system for the YORK eco² Packaged Roof- top Unit is fully self-contained and based around an OptiLogic ™ rooftop unit controller . T o aid in unit setup, maintenance, and operation, the OptiLogic ™ rooftop unit controller is equipped with a user interfac[...]
-
Page 55
FORM 100.50-EG3 (802) 55 YORK INTERNA TIONAL ELECTRIC HEA TING OPERA TION For units equipped with electric heaters, the unit can control up to six stages of electric heat which are st aged on based on heating demand calculates by the OptiLogic controller . ECONOMIZER OPERA TION The unit can be equipped with one of three types of optional economizer[...]
-
Page 56
YORK INTERNA TIONAL 56 Controls (continued) through the Air Measurement S tation. The unit control- ler shall control the Outside Air damper to this flow rate as long as the unit is in the Occupied mode, and the economizer is not suitable for cooling. Demand V entilation If an optional CO 2 sensor is connected to the unit, the unit controller can r[...]
-
Page 57
FORM 100.50-EG3 (802) 57 YORK INTERNA TIONAL For these applications, the unit must be equipped with optional Low Ambient controls. For optional Low Ambi- ent operation, the OptiLogic ™ controller monitors the refrigeration system discharge pressure and controls the speed of the condenser fans. If the discharge pres- sure falls, the speeds of the [...]
-
Page 58
YORK INTERNA TIONAL 58 Controls (continued) mine if conditions are suitable for economizing and modulate the outside air damper and/or stage up com- pressors as required to maintain the V A V High Supply Air T emperature Setpoint. This setpoint is user select- able at the OptiLogic ™ User Interface. The OptiLogic ™ controller will control to th[...]
-
Page 59
FORM 100.50-EG3 (802) 59 YORK INTERNA TIONAL S tage 1 (“Y1”) Call If Y1 is called and the unit is equipped with an economizer , the control will check to see if the Outside Air is suitable for economizing. If conditions are suitable for economizing, the control will control the economizer and stage up compres- sors, as required, to maintain the[...]
-
Page 60
YORK INTERNA TIONAL 60 Power Wiring SINGLE-POINT POWER SUPPL Y WIRING FIG . 1 – SINGLE-POINT POWER SUPPL Y WIRING P ower S id e Fi e l d Pow e r S uppl y E a rth G roun d Line 3 Lin e 2 Lin e 1 Wirin g Terminal Blo ck C ontrol S id e 1L1 1L2 1 L 3 G ND Electrical / C ontrols Bo x TB1 NOTES: 1. All field wiring must be provided through a field-sup[...]
-
Page 61
FORM 100.50-EG3 (802) 61 YORK INTERNA TIONAL SINGLE-POINT POWER SUPPL Y WIRING WITH NON-FUSED DISCONNECT FIG . 2 – SINGLE-POINT POWER SUPPL Y WIRING WITH NON-FUSED DISCONNECT Power S id e Fi e l d Pow e r Suppl y E a rth G roun d Line 3 Lin e 2 Lin e 1 Wirin g Terminal Blo ck C ontrol S id e 1L1 1L2 1 L 3 G ND Electrical / C ontrols Bo x Mol ded [...]
-
Page 62
YORK INTERNA TIONAL 62 DUAL-POINT POWER SUPPL Y WIRING FIG . 3 – DUAL-POINT POWER SUPPL Y WIRING NOTES: 1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded disconnect switch). 2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requiremen[...]
-
Page 63
FORM 100.50-EG3 (802) 63 YORK INTERNA TIONAL * U se S hielded Wir e * Use Shielded Wir e * U se S hielded Wir e 3. Maximum p ower available from the 24 VAC 1. Wirin g shown indicates typical wirin g . Closed = Smoke Purge C losed = S hutdow n Open = Unoccupied Closed = Occupied O 1.5K Ad j ust Si g na l cause equipment damage. power source external[...]
-
Page 64
YORK INTERNA TIONAL 64 A L H B C D E F G J K R Y T S M N P U V BB AA CC DD W 3.175 FPT COUPLING DRAIN CONNECTION T OP VIEW LEFT SIDE VIEW FRONT REAR General Arrangement Drawing – 50-65 T on Models LD07880 BOTTOM SUPPL Y / BOTTOM RETURN FIG . 5 – GENERAL ARRANGEMENT DRA WING – 50-65 TON MODEL NOTES: 1. S t andard configuration. 2. Center of gr[...]
-
Page 65
FORM 100.50-EG3 (802) 65 YORK INTERNA TIONAL LD07881 SIDE SUPPL Y / FRONT RETURN FIG . 6 – GENERAL ARRANGEMENT DRA WING – 70-95 TON MODEL L H C D E F G J R Y T S M N P DD CC BB AA K EE W 3.175 FPT COUPLING DRAIN CONNECTION T OP VIEW LEFT SIDE VIEW FRONT REAR T ABLE 30 – SIDE SUPPL Y / FRONT RETURN (ALL DIMENSIONS ARE IN CM) NOTES: 1. Left and[...]
-
Page 66
YORK INTERNA TIONAL 66 A L H B C D E F G J K R T S WY P M N U V BB AA CC DD 3.175 FPT COUPLING DRAIN CONNECTION T OP VIEW LEFT SIDE VIEW FRONT REAR General Arrangement Drawing – 70-95 T on Models BOTTOM SUPPL Y / BOTTOM RETURN LD07882 FIG . 7 – GENERAL ARRANGEMENT DRA WING – 70-95 TON MODEL T ABLE 31 – BOTTOM SUPPL Y / BOTT OM RETURN (ALL D[...]
-
Page 67
FORM 100.50-EG3 (802) 67 YORK INTERNA TIONAL L H C D E F G J R T S P M N WY BB AA DD CC K EE 3.175 FPT COUPLING DRAIN CONNECTION T OP VIEW LEFT SIDE VIEW FRONT REAR SIDE SUPPL Y / REAR RETURN LD07883 NOTES: 1. Left and right hand side openings are the same size. 2. Right supply available with cooling only unit s. 3. Left supply available with cooli[...]
-
Page 68
YORK INTERNA TIONAL 68 General Arrangement Drawing – 70-95 T on Models (ONL Y) OPTIONAL SIDE RETURN FIG . 9 – GENERAL ARRANGEMENT DRA WING – 70-95 TON MODEL (ONL Y) TABLE 33 – OPTIONAL SIDE RETURN (CM) NOTE: 1. Left side shown, RH side available (mirror image). B A C D LD07313 MODEL A B C D 70-85 157.80 147.32 101.6 128.91 90-95 174.62 164.[...]
-
Page 69
FORM 100.50-EG3 (802) 69 YORK INTERNA TIONAL Curb Layout Drawing FIG . 10 – CURB LA YOUT DRA WING 3.81 6.67 5.08 11.75 3.17 LD07884 UNIT BASERAIL PROFILE W L D C B A E Supply Opening Return Opening Condenser Section 6.35 Gas Outlet 3.81 MPT Connection G H LD07885 MODEL A B C D E G H L W 50-65 5.08 95.89 495.3 596.9 181.77 40.64 26.03 861.06 220.9[...]
-
Page 70
YORK INTERNA TIONAL 70 Power/Control Entry Drawing FIG . 1 1 – POWER/CONTROL ENTR Y DRA WING – 50 - 95 TON MODELS MODEL 208V 230V 460V 575V 50 AAB B 55 AAB B 60 AAB B 65 AAB B 70 AAB B 75 AAB B 80 AAB B 85 AAB B 90 AAA A 95 AAA A TABLE 35 – POWER/CONTROL ENTRY DIMENSIONS ARE IN CM . .. ..... . . . . . . . . 49.21 137.16 15.875 90.17 77.47 31.[...]
-
Page 71
FORM 100.50-EG3 (802) 71 YORK INTERNA TIONAL Guide Specifications GENERAL Units shall be designed for outdoor roof top inst allation on a roof curb (optional). Units shall be cap able of pro- viding mechanical cooling down to 7.2°C (-17.7°C with a low ambient kit). Unit shall be capable of st arting and running at 48.8°C. Unit electric and gas c[...]
-
Page 72
YORK INTERNA TIONAL 72 Guide Specifications (continued) Fan motors shall be NEMA designed, St andard ef fi- ciency ball bearing type with electrical characteristics and horsepower as specified. Motors shall be 1750 RPM, open drip proof type. The motor shall be located within the unit on an adjustable, heavy steel base. All fan motor drives shall be[...]
-
Page 73
FORM 100.50-EG3 (802) 73 YORK INTERNA TIONAL POWER SUPPL Y Unit power supply shall be 460V 3-phase 60 Hz (208, 230 and 575V optional) single-point power connections with terminal block connections. GAS-FIRED HEA TING SECTION One or two (or three for the YP AL070-095) gas-fired heating modules shall be installed to provide the heat- ing requirements[...]
-
Page 74
YORK INTERNA TIONAL 74 • High and low pressure cutouts (one each refriger- ant circuit) • Minimum on time for compressors • Delay between compressor stages • Anti-short cycle delays (minimum off time) for com- pressors and supply fan • Cooling lockout at 7.2°C; -17.7°C if equipped for low ambient operation • Air flow proving switch wh[...]
-
Page 75
FORM 100.50-EG3 (802) 75 YORK INTERNA TIONAL BACNet IP Communications Card – for BAS com- munications, a BACNet card is available for ethernet connection. BACNet MSTP Communications Card – for BAS com- munications, a BACNet MSTP card is available for an RS-485 connection. IAQ OPTIONS Filter Options – two-inch throwaway , cleanable, car- bon o[...]
-
Page 76
ROOF CURBS Full Perimeter Roof Curbs – 14" high roof curb with wood nailer . Roof curb supports the entire perimeter of the unit. Partial perimeter roof curbs – 14" high roof curb with wood nailer . Roof curb supports the air handling sec- tion with a separate support under the condenser end. ACCESSORIES Compressor Sound Blanket s –[...]