York H*RD018 THRU 060 manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of York H*RD018 THRU 060, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of York H*RD018 THRU 060 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of York H*RD018 THRU 060. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of York H*RD018 THRU 060 should contain:
- informations concerning technical data of York H*RD018 THRU 060
- name of the manufacturer and a year of construction of the York H*RD018 THRU 060 item
- rules of operation, control and maintenance of the York H*RD018 THRU 060 item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of York H*RD018 THRU 060 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of York H*RD018 THRU 060, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the York service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of York H*RD018 THRU 060.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the York H*RD018 THRU 060 item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-22 MODELS: H*RD018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) H*RD036 THRU 060 (2.5 THRU 5 NOMINAL TONS, 3 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be f[...]

  • Page 2

    254892-YTG-C-0606 2 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A - 1 PHASE MODEL H2RD018S06 H2RD024S06 H2RD030S06 H 2RD036S06 H2RD042S06 H2RD048S06 H 2RD060S06 Unit Supply V olt age 208-230V , 1 φ, 60Hz Normal [...]

  • Page 3

    254892-YTG-C-0606 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 1 Phase Outdoor Unit H2RD018S06 H2RD024S06 H2RD030S06 H2RD036S06 H2RD042S06 H2RD048S06 H2RD060S06 Required TXV 1 TVM2A1 1 TVM2(A,B)1 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory R-22 Charge, lbs-oz 4 - 9 6 - 3 5 - 13 6 - 0 8 - 13[...]

  • Page 4

    254892-YTG-C-0606 4 Unitary Products Group H C 1 8 A 3 X 0 2 B + 1 ––––– H C 3 0 A 3 X – 2 A + 0 0 –––– HC36B3X – – 0 0 – – – H C 4 2 C 3 X ––––0 0 – H C 6 0 C 3 X –––––0 0 H D 2 4 A 3 X 0 2 A + 0 ––––– HD36B3X – – 0 0 – – – H D 4 8 C 3 X ––––0 0 – H D 6 0 D 3 X ––?[...]

  • Page 5

    254892-YTG-C-0606 Unitary Products Group 5 PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. Addition[...]

  • Page 6

    254892-YTG-C-0606 6 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A - 3 PHASE MODEL H1RD 030S25 H1RD 036S25 H1RD 042S25 H1RD 048S25 H1RD 060S25 H1RD 030S46 H1RD 036S46 H1RD 042S46 H1RD 048S46 H1RD 060S46 Unit Suppl[...]

  • Page 7

    254892-YTG-C-0606 Unitary Products Group 7 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 3 Phase Outdoor Unit H1RD030S(25,46) H1RD036S(25,46) H1RD042S(25,46) H1RD048S(25, 46) H1RD060S(25,46) Required TXV 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory R-22 Charge, lbs-oz 5 - 13 6 - 0 8 - 13 8 - 6 10 - 2 Indoor Coil 1 Ad[...]

  • Page 8

    254892-YTG-C-0606 8 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate include s refr iger ant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. Additi[...]

  • Page 9

    254892-YTG-C-0606 Unitary Products Group 9 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL ELECTRIC HEA T KW 2 W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER AC WITH MA H2RD018S06 MA08B 2,5,8 17 FC/MC18B 600 17.5 1 1.7 13.00 1 1.00 MA08B 2,5,8 17 G*FD024H17 600 17.5 1 1.7 13.00 1 1.00 H2[...]

  • Page 10

    254892-YTG-C-0606 10 Unitary Products Group — = Not applicable. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED H2RD018S06 A V24 2,5,8,10,15 17 – 600 18.0 1 1.7 14.00 1 1.50 H2RD024S06 A V24 2,5,8,10,15 17 – 800 23.2 16.5 14.00 1 1.50 H2RD030S06 A V36 5,8,10,15,18 21 – 1000 30.0 21.2 14.00 1 1.50 H2RD036S06 A V36 5,8,10,15,18 21 – 1200 35[...]

  • Page 11

    254892-YTG-C-0606 Unitary Products Group 11 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL F URNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. H2RD018S06 450 750 14,17 FC/MC/PC/UC18 600 17.5 1 1.7 13.00 1 1.00 14,17 FC/MC/PC/UC24 600 17.7 1 1.9 13.00 1 1.00 14 G*F [...]

  • Page 12

    254892-YTG-C-0606 12 Unitary Products Group H2RD042S06 1200 1600 17,21 FC/MC/PC/UC42 1400 40.5 29.6 13.00 1 1.00 21,24 FC/MC/PC/UC48 1400 41.0 30.2 13.00 1 1.00 17 G*F A042S17 1400 40.5 29.6 13.00 1 1.00 21 G*F A048S21 1400 41.0 29.6 13.00 1 1.00 21 G*FD042H21 1400 40.5 29.6 13.00 1 1.00 17 G*FD046H17 1400 40.5 29.6 13.00 1 1.00 21,24 G*FD048H21,24[...]

  • Page 13

    254892-YTG-C-0606 Unitary Products Group 13 COOLING CAP ACITY - With V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 H2RD018S06 PV8*A12 FC/MC/PC18A 14 600 17.8 1 1.9 14 .00 1 1.50 PV9*A12 FC/MC/PC18A 14 600 17.8 1 1.8 14[...]

  • Page 14

    254892-YTG-C-0606 14 Unitary Products Group H2RD036S06 PV8*A12 FC/MC/PC36A 14 1200 35.0 25.4 13.00 1 1.00 PV8*B16 FC/MC/PC36B 17 1200 35.2 25.6 13.75 1 1.00 PV8*C16 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV8*C20 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV9*A12 FC/MC/PC36A 14 1200 34.8 25.4 13.00 1 1.00 P(C,V)9*B12 FC/MC/PC36B 17 1200 35.0 25.[...]

  • Page 15

    254892-YTG-C-0606 Unitary Products Group 15 H2RD048S06 PV8*C16 FC/MC/PC48C 21 1500 46.5 34.2 13.00 1 1.00 PV8*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C16 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*D20 FC/MC/PC48D 24 1600 47.0 35.2 13.25 1 1.00 PV8*C16 HC48 21 1500 46.5 33[...]

  • Page 16

    254892-YTG-C-0606 16 Unitary Products Group ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Provides increased starting torque for areas with low voltage. COMPRESSOR BLANKET - Designed to furth er reduce the normal compressor operating sound. Refer to price pages for specific match-ups. OFF CYCLE TIMER DELA Y - Provi[...]

  • Page 17

    254892-YTG-C-0606 Unitary Products Group 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel[...]

  • Page 18

    254892-YTG-C-0606 18 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree[...]

  • Page 19

    254892-YTG-C-0606 Unitary Products Group 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel[...]

  • Page 20

    254892-YTG-C-0606 20 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree[...]

  • Page 21

    254892-YTG-C-0606 Unitary Products Group 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel[...]

  • Page 22

    254892-YTG-C-0606 22 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree[...]

  • Page 23

    254892-YTG-C-0606 Unitary Products Group 23 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel[...]

  • Page 24

    Subject to change without notice. Printe d in U .S.A. 254892-YTG-C-0606 Copyright © by York International Corp. 2006. All right s reserved. Supersedes: 254892 / 036-21339-002 Rev. B (020 6) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 NOTES[...]